Inspected By: Phillip O’Keefe Date: 02 / 12/ 2021
Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….
Comments:……………………………………………………………………………………………………………………………………….
Thermograph Inspection At
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
February 12, 2021
Job No.
WO-08391082
Thermo Gram: 02 / 04 /21
Analysis & Recommended Actions:
Object Parameters: Values
Atmos Temperature: 23.0°C
Humidity %: 69%
Reflective Temperature: °C
Reference Temperature: 23.0°C
Emissivity: .95
Image Date: 02 / 04 / 2021
IR Photo No.: 0041
Page No.: 13
Location: VA’s Medical Center (Hou)
Floor Level: Basement Level, Laundry Area
Room No. BC-350, Textile Care
Type Equipment: Panel
FLN: BLLA
Voltage Rating: 208/120A
Current Rating: 225 Amp Max
Brk. / Cir. / Size: Cir. 32, 34, 36 / 60 Amp
Phase(s): B Phase
Actual Cir. Load: 7.2 Amp
Disc. Type: N/A
Fuse Size: N/A
Fuse Type: N/A
Digital Photo No. 0040
Severity: Minor
Possible Causes:
Possible Loose Connection
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings. In need of some preventative maintenance. Cleaning.
Warrants Further investigations into current loads.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 34.7°C Spot 1&2 5.5°C
AØ
2.0A Spot 2 29.2°C
Spot 3 °C °C
BØ
7.2A Spot 4 °C
Spot 5 °C °C
CØ
2.0 Spot 6 °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
February 12, 2021
Job No.
Humidity %: 69%
Reflective Temperature: °C
IR Photo No.: 0041
Page No.: 14
Location: VA’s Medical Center (Hou)
Floor Level: Basement Level, Laundry Area
Room No. BC-350, Textile Care
Type Equipment: Disconnect Switch
FLN: Kings Edge, Century, Sheet Folder
Voltage Rating: 480/277V
Current Rating: 100 Amps Max
Brk. / Cir. / Size: N/A
Phase(s): B Phase
Actual Cir. Load:
Disc. Type: Fused
Fuse Size: ECS-R- 80
Fuse Type: Time Delay
Digital Photo No. 0042
Possible Causes:
Possible Loose Connection
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings. In need of some preventative maintenance. Cleaning.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 31.0°C Spot 1&2 1.8°C
AØ
Spot 2 29.2°C
Spot 3 29.0°C Spot 2&3 2.0°C
BØ
Spot 4 °C
Spot 5 °C °C
Spot 6 °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
February 12, 2021
Job No.
Humidity %: 69%
Reflective Temperature: °C
IR Photo No.: 0044
Page No.: 15
Location: VA’s Medical Center (Hou)
Floor Level: Basement Level, Laundry Area
Room No. BC-300, Soiled Linen
Type Equipment: Disconnect Switch
FLN: QGD-25 Compressor(on the left)
Voltage Rating: 480/277V
Current Rating: 60 Amp Max
Brk. / Cir. / Size: N/A
Phase(s): A Phase
Actual Cir. Load: A: 29.1A / B: 29.2A / C: 5.3A
Disc. Type: Non-Fused
Fuse Size: N/A
Fuse Type: N/A
Digital Photo No. 0043
Possible Causes:
Possible Loose Connection
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings. In need of some preventative maintenance. Cleaning.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 47.4°C Spot 1&2 6.4°C
AØ
29.1A Spot 2 41.0°C
Spot 3 37.5°C Spot 1&3 9.9°C
BØ
29.2A Spot 4 °C
Spot 5 °C °C
5.3A Spot 6 °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
February 12, 2021
Job No.
Humidity %: 69%
Reflective Temperature: °C
IR Photo No.: 0049
Page No.: 16
Location: VA’s Medical Center (Hou)
Floor Level: Basement Level, Laundry Area
Room No. BC-300, Soiled Linen
Type Equipment: Disconnect Switch
FLN: CBW-1
Voltage Rating: 480/277V
Current Rating: 60 Amps
Brk. / Cir. / Size: N/A
Phase(s): B & C Phase
Actual Cir. Load: A: 45.9A / B: 45.6A / C: 7.0A
Disc. Type: Fused
Fuse Size: TRS-R-60
Fuse Type: Time Delay
Digital Photo No. 0050
Possible Causes:
Possible Loose Connections
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 43.9°C Spot 1&2 2.7°C
AØ
Spot 2 41.1°C
Spot 3 36.2°C Spot 1&3 7.7°C
BØ
Spot 4 °C
Spot 5 °C °C
Spot 6 °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
February 12, 2021
Job No.