Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-3 Substation PM
April 22, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-3 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-3 480V Switchboard
USS-3 480V Switchboard Main Breaker trip unit failed to trip during breaker primary injection testing. After troubleshooting was performed, we have found that the trip unit was bad and needed to be replaced. Main Breaker Carriere trip unit was replaced by AC pro trip unit. Time delay curve for the replacement trip unit was set to match the existing trip unit as close as possible since the replacement trip unit and the existing trip unit was not made from the same manufacturer. The trip curve was slightly different from each other. The customer was advised to have a new coordination study to ensure the right protection settings is set to the main Breaker.
USS-3 Spare ME Square D Breaker A-phase and C-Phase contact resistance reading is abnormally higher compare to B-Phase. Loose connection on the breaker will cause a hot spot when energize which can potentially cause a fault that will result to a costly repair to the gear and injury to personnel. It is recommended that the breaker will need to be replaced.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-3_876101-G3_XD
Report Source DryTypeTransformer 4/21/2021 6:50:40 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-G3 Location 2002 Holcombe Blvd Houston, Texas Special ID USS-3 XFMR
77030 Division Houston Circuit Designation USS-3 SUBSTATION Manufacturer Square D Electric Class Year Manufactured Type DryTypeTransformer Mfr Location USA Winding Insulation Open-Wound Coolant Select Coolant Weight 6460 Tank Type Select Tank Type BIL 110 kV Dry Tank Type Ventilated VA Rating 750 kV 12.47,0.48,* Insulation Material Nomex
Administration Test Date 4/21/2021 Test Time: 6:50 PM Weather Indoors Air Temperature 20°C Apparatus * Humidity 35 %
Temperature Tester C.Espartero Work Order Date Last Tested Verified Test Set Type M4000 Date Retested Verification Date 4/21/2021 Set Top Serial # Reason ROUTINE Last Sheet # Set Bottom Serial # Travel Time Purchase Order Ins. Book # Duration Copies Sheet # Crew Size 1
876101-G3 1 - 6
Session Notes
876101-G3 2 - 6
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * * H2 H2 * * * * * * H3 H3 * * * * * *
Overall Tests - 2K
876101-G3 3 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 2.000 8.000 2.000
1.000 0.999 0.999 mA Watts 0.037 0.024 0.008 0.013 0.084 0.066 0.008 0.017
% PF Meas.
0.107 0.306 0.029 0.049 0.131 0.178 0.030 0.065
Cap (pF) 908.515 205.987 702.787 702.529 1691.166 988.605 702.980 702.561
IR Man.
Good Good Good Good Good Good Good Good
3.425 0.777 2.649 2.648 6.376 3.727 2.650 2.649
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.425/3.425, 1/1 mA: 0.777/0.777, 1/1 mA: 2.649/2.649, 1/1 mA: 2.648/2.648, 1/1 mA: 6.376/6.376, 1/1 mA: 3.727/3.727, 1/1 mA: 2.650/2.650, 1/1 mA: 2.649/2.649, 1/1
Watts: 0.037/0.037, 1/1 Watts: 0.024/0.024, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.013/0.013, 1/1 Watts: 0.084/0.084, 1/1 Watts: 0.066/0.066, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.017/0.017, 1/1
Cap (pF): 908.515/908.515, 1/1 Cap (pF): 205.987/205.987, 1/1 Cap (pF): 702.787/702.787, 1/1 Cap (pF): 702.529/702.529, 1/1 Cap (pF): 1691.166/1691.166, 1/1 Cap (pF): 988.605/988.605, 1/1 Cap (pF): 702.980/702.980, 1/1 Cap (pF): 702.561/702.561, 1/1
Δ-
USS-3_876101-G3_XD
Overall Tests - LG
Winding Resistance
Winding Manufacturer Serial Number Configuration Winding Temperature Factory Factory
Temperature Rise Resistance Temperature (Ohms)
Y * * * *
High Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 316.8 milli Ohms * * * * 3 B 318.1 milli Ohms * * * * 3 C 317.5 milli Ohms * * * *
Low Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 618.4 micro Ohms * * * * 3 B 605.3 micro Ohms * * * * 3 C 601.2 micro Ohms * * * *
876101-G3 4 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 10.004 10.005 10.004
1.000 1.000 1.000 mA Watts 0.038 0.023 0.011 0.014 0.083 0.066 0.008 0.017
% PF Meas.
0.110 0.301 0.040 0.054 0.131 0.178 0.031 0.065
Cap (pF) 908.387 206.024 702.524 702.363 1691.119 988.587 702.954 702.533
Tip UP
-0.005 0.011
-0.001 0.000
FRANK IR Man.
3.425 0.777 2.648 2.648 6.375 3.727 2.650 2.649
Good Investigate
Good
Investigate
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.425/3.425, 1/1 mA: 0.777/0.777, 1/1 mA: 2.648/2.648, 1/1 mA: 2.648/2.648, 1/1 mA: 6.375/6.375, 1/1 mA: 3.727/3.727, 1/1 mA: 2.650/2.650, 1/1 mA: 2.649/2.649, 1/1
Watts: 0.038/0.038, 1/1 Watts: 0.023/0.023, 1/1 Watts: 0.011/0.011, 1/1 Watts: 0.014/0.014, 1/1 Watts: 0.083/0.083, 1/1 Watts: 0.066/0.066, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.017/0.017, 1/1
Cap (pF): 908.387/908.387, 1/1 Cap (pF): 206.024/206.024, 1/1 Cap (pF): 702.524/702.524, 1/1 Cap (pF): 702.363/702.363, 1/1 Cap (pF): 1691.119/1691.119, 1/1 Cap (pF): 988.587/988.587, 1/1 Cap (pF): 702.954/702.954, 1/1 Cap (pF): 702.533/702.533, 1/1
LSR mA: 86.190/86.190, 1/1 Watts: 688.078/688.078, 1/1 Cap (pF): */*, 1/1 LSR mA: 86.610/86.610, 1/1 Watts: 693.720/693.720, 1/1 Cap (pF): */*, 1/1 LSR mA: 43.176/43.176, 1/1 Watts: 348.345/348.345, 1/1 Cap (pF): */*, 1/1
USS-3_876101-G3_XD
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK Manual
3 12470 3 480 44.997 45.154 44.94 45.152 44.772 45.222 Good Good
876101-G3 5 - 6
DETC
LTC Test kV mA 86.190
H3 H1 Watts
688.078 X L
mA 86.610
H1 H2 Watts
693.720 X L
mA 43.176
H2 H3 Watts X
L FRANK Manual
Good348.345
Exciting Current Plot
876101-G3 6 - 6
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 68 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-3DESIGNATION
SUBSTATION BUILDING 100
4/21/2021 45
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
N/A
N/A
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
Torqued
N/A N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
N/A
N/A
GAUGES
SUPPORT INSULATORS
N/ATorqued
N/A
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
GAUGES
N/A
CONTROLLED
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
35 35
902902902
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,094
TAP POSITION/CONNECTION
12,782 12,158
CLASS
12,470
Phase 3876101-G3SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
YEAR OF MANUF.N/A 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA K FACTOR N/A °CTEMPERATURE RISE
U.S.A
805.8
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
750 / 750
12,470
TOTAL WEIGHT
Dry
Square D
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1
5,000
1,000
5,000
325,000.0 325,000.0 528,000.0 528,000.0
331,000.0331,000.0128,400.0128,400.0
224,000.0 224,000.0 317,000.0 317,000.0
1.62
2.58
1.42
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X2 - X0
H1 - H3 H2 - H1 H3 - H2
X3 - X0
TAP TO
TEST
3 45.154 44.940 45.1520.12 % PASS 0.35 % PASSPASS44.996 0.35 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE N/ADBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 316.800 385.264 318.100 386.845 317.500 386.115 0.618 0.752 0.605 0.736 0.601 0.7311
Primary Secondary
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
DEFICIENCIES: