View the file

Other files

File Type Posted
Exhibit N - PT-12 BLDG 29 Test Report.pdf PDF
Exhibit G - Chiller Water XFMR Test Report.pdf PDF
Exhibit AF - USS-L Test Report.pdf PDF
Exhibit P - SESG Test Report.pdf PDF
Exhibit AA - USS-10 Test Report.pdf PDF
Exhibit V - USS-5 Test Report.pdf PDF
Exhibit D - Building 108 Visor Clininc IR Sheet.pdf PDF
Exhibit C - Bldg. 122, IR Sheets.pdf PDF
Exhibit K - MSG Circuit B1 XFMR and Breakers Test Reports.pdf PDF
Exhibit W - USS-6 Test Report.pdf PDF
Exhibit H - CHP Bldg. Test Report.pdf PDF
Exhibit AC - USS-12 Test Report.pdf PDF
Exhibit AE - USS-14 Test Report.pdf PDF
Exhibit M - PT-1 and PT-14 Oil report.pdf PDF
36C25623Q0012 0001.docx DOCX document
Exhibit R - USS-1 Test Report.pdf PDF
Exhibit X - USS-7 Test Report.pdf PDF
Exhibit AD - USS-13 Test Report.pdf PDF
Exhibit E - Building 109 Lab IR Sheets.pdf PDF
Exhibit L - MSG Test Report.pdf PDF
Exhibit Y - USS-8 Test report.pdf PDF
Exhibit AB - USS-11 Test Report.pdf PDF
Exhibit U - USS-4 Test Report.pdf PDF
Exhibit Z - USS-9 Test Report.pdf PDF
Exhibit Q - USS L Laundry Report.pdf PDF
Exhibit A - Bldg. 104A Test Report.pdf PDF
Exhibit J - MBSG Test Report.pdf PDF
Exhibit F - Building 110 IR Sheets.pdf PDF
Exhibit S - USS-2 Test Report.pdf PDF
Exhibit B - Bldg. 105 IR Sheet (1).pdf PDF
36C25623Q0012.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared By:

Chris Espartero Sr Field Service Representative

North America Service Operations

Houston, TX

USS-3 Substation PM

April 22, 2021

Work Order: 08391081

2 | P a g e

EXECUTIVE SUMMARY

Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-3 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe

Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.

USS-3 480V Switchboard

USS-3 480V Switchboard Main Breaker trip unit failed to trip during breaker primary injection testing. After troubleshooting was performed, we have found that the trip unit was bad and needed to be replaced. Main Breaker Carriere trip unit was replaced by AC pro trip unit. Time delay curve for the replacement trip unit was set to match the existing trip unit as close as possible since the replacement trip unit and the existing trip unit was not made from the same manufacturer. The trip curve was slightly different from each other. The customer was advised to have a new coordination study to ensure the right protection settings is set to the main Breaker.

USS-3 Spare ME Square D Breaker A-phase and C-Phase contact resistance reading is abnormally higher compare to B-Phase. Loose connection on the breaker will cause a hot spot when energize which can potentially cause a fault that will result to a costly repair to the gear and injury to personnel. It is recommended that the breaker will need to be replaced.

If there are any questions or concerns, please contact:

Chris Espartero

832-205-1547

Christopher.Espartero@se.com

USS-3_876101-G3_XD

Report Source DryTypeTransformer 4/21/2021 6:50:40 PMSession Test Date

Nameplate Company VA Medical Center Serial Number 876101-G3 Location 2002 Holcombe Blvd Houston, Texas Special ID USS-3 XFMR

77030 Division Houston Circuit Designation USS-3 SUBSTATION Manufacturer Square D Electric Class Year Manufactured Type DryTypeTransformer Mfr Location USA Winding Insulation Open-Wound Coolant Select Coolant Weight 6460 Tank Type Select Tank Type BIL 110 kV Dry Tank Type Ventilated VA Rating 750 kV 12.47,0.48,* Insulation Material Nomex

Administration Test Date 4/21/2021 Test Time: 6:50 PM Weather Indoors Air Temperature 20°C Apparatus * Humidity 35 %

Temperature Tester C.Espartero Work Order Date Last Tested Verified Test Set Type M4000 Date Retested Verification Date 4/21/2021 Set Top Serial # Reason ROUTINE Last Sheet # Set Bottom Serial # Travel Time Purchase Order Ins. Book # Duration Copies Sheet # Crew Size 1

876101-G3 1 - 6

Session Notes

876101-G3 2 - 6

Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps

H1 H1 * * * * * * H2 H2 * * * * * * H3 H3 * * * * * *

Overall Tests - 2K

876101-G3 3 - 6

# Insulation

CH+CHL

CH

CHL(UST)

CHL

CL+CHL

CL

CHL(UST)

CHL

Test kV 2.000 8.000 2.000

1.000 0.999 0.999 mA Watts 0.037 0.024 0.008 0.013 0.084 0.066 0.008 0.017

% PF Meas.

0.107 0.306 0.029 0.049 0.131 0.178 0.030 0.065

Cap (pF) 908.515 205.987 702.787 702.529 1691.166 988.605 702.980 702.561

IR Man.

Good Good Good Good Good Good Good Good

3.425 0.777 2.649 2.648 6.376 3.727 2.650 2.649

LSR

LSR

LSR

LSR

LSR

LSR

LSR

LSR

mA: 3.425/3.425, 1/1 mA: 0.777/0.777, 1/1 mA: 2.649/2.649, 1/1 mA: 2.648/2.648, 1/1 mA: 6.376/6.376, 1/1 mA: 3.727/3.727, 1/1 mA: 2.650/2.650, 1/1 mA: 2.649/2.649, 1/1

Watts: 0.037/0.037, 1/1 Watts: 0.024/0.024, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.013/0.013, 1/1 Watts: 0.084/0.084, 1/1 Watts: 0.066/0.066, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.017/0.017, 1/1

Cap (pF): 908.515/908.515, 1/1 Cap (pF): 205.987/205.987, 1/1 Cap (pF): 702.787/702.787, 1/1 Cap (pF): 702.529/702.529, 1/1 Cap (pF): 1691.166/1691.166, 1/1 Cap (pF): 988.605/988.605, 1/1 Cap (pF): 702.980/702.980, 1/1 Cap (pF): 702.561/702.561, 1/1

Δ-

USS-3_876101-G3_XD

Overall Tests - LG

Winding Resistance

Winding Manufacturer Serial Number Configuration Winding Temperature Factory Factory

Temperature Rise Resistance Temperature (Ohms)

Y * * * *

High Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage

Resistance Factor Resistance Deviation 3 A 316.8 milli Ohms * * * * 3 B 318.1 milli Ohms * * * * 3 C 317.5 milli Ohms * * * *

Low Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage

Resistance Factor Resistance Deviation 3 A 618.4 micro Ohms * * * * 3 B 605.3 micro Ohms * * * * 3 C 601.2 micro Ohms * * * *

876101-G3 4 - 6

# Insulation

CH+CHL

CH

CHL(UST)

CHL

CL+CHL

CL

CHL(UST)

CHL

Test kV 10.004 10.005 10.004

1.000 1.000 1.000 mA Watts 0.038 0.023 0.011 0.014 0.083 0.066 0.008 0.017

% PF Meas.

0.110 0.301 0.040 0.054 0.131 0.178 0.031 0.065

Cap (pF) 908.387 206.024 702.524 702.363 1691.119 988.587 702.954 702.533

Tip UP

-0.005 0.011

-0.001 0.000

FRANK IR Man.

3.425 0.777 2.648 2.648 6.375 3.727 2.650 2.649

Good Investigate

Good

Investigate

LSR

LSR

LSR

LSR

LSR

LSR

LSR

LSR

mA: 3.425/3.425, 1/1 mA: 0.777/0.777, 1/1 mA: 2.648/2.648, 1/1 mA: 2.648/2.648, 1/1 mA: 6.375/6.375, 1/1 mA: 3.727/3.727, 1/1 mA: 2.650/2.650, 1/1 mA: 2.649/2.649, 1/1

Watts: 0.038/0.038, 1/1 Watts: 0.023/0.023, 1/1 Watts: 0.011/0.011, 1/1 Watts: 0.014/0.014, 1/1 Watts: 0.083/0.083, 1/1 Watts: 0.066/0.066, 1/1 Watts: 0.008/0.008, 1/1 Watts: 0.017/0.017, 1/1

Cap (pF): 908.387/908.387, 1/1 Cap (pF): 206.024/206.024, 1/1 Cap (pF): 702.524/702.524, 1/1 Cap (pF): 702.363/702.363, 1/1 Cap (pF): 1691.119/1691.119, 1/1 Cap (pF): 988.587/988.587, 1/1 Cap (pF): 702.954/702.954, 1/1 Cap (pF): 702.533/702.533, 1/1

LSR mA: 86.190/86.190, 1/1 Watts: 688.078/688.078, 1/1 Cap (pF): */*, 1/1 LSR mA: 86.610/86.610, 1/1 Watts: 693.720/693.720, 1/1 Cap (pF): */*, 1/1 LSR mA: 43.176/43.176, 1/1 Watts: 348.345/348.345, 1/1 Cap (pF): */*, 1/1

USS-3_876101-G3_XD

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

Turns Ratio Tests Serial Number HV Winding LV Winding

Delta Wye Connections H3 - H1 H1 - H2 H2 - H3

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK Manual

3 12470 3 480 44.997 45.154 44.94 45.152 44.772 45.222 Good Good

876101-G3 5 - 6

DETC

LTC Test kV mA 86.190

H3 H1 Watts

688.078 X L

mA 86.610

H1 H2 Watts

693.720 X L

mA 43.176

H2 H3 Watts X

L FRANK Manual

Good348.345

Exciting Current Plot

876101-G3 6 - 6

TWO-WINDING DRY-TYPE TRANSFORMER

TEMPERATURE 68 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

USS-3DESIGNATION

SUBSTATION BUILDING 100

4/21/2021 45

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

DRY TYPE TRANSFORMER

Chris Espartero

N/A

N/A

VA Hospital WO-08391081

Acceptable

CONDITIONDescription CLEAN/LUBEDescription

N/A

Torqued

N/A N/A

N/A

N/A N/A

FANS

N/AAcceptable

Acceptable

N/A N/A N/A

N/A

N/AVENTILATION / FILTERS

N/A

PAINT Acceptable

INDOOR

CleanedAcceptable

N/A

MATCHES DWG OR SPEC

WEATHER

Cleaned

ENVIRONMENT

N/A

N/A

GAUGES

SUPPORT INSULATORS

N/ATorqued

N/A

Windings

Acceptable

N/A CABINET HEATERS

AUXILIARY DEVICES N/ATorqued

PRIMARY CONNECTIONS

TANK / FRAME GROUND

NEUTRAL GROUND

Description CONDITION

SEC. CONNECTIONS Acceptable

N/A

N/A

Acceptable

N/A Torqued

ARRESTERS

CORE GROUND

ALARMS / ANNUNCIATOR

CONTROLS

BUSHINGS

CLEAN/LUBE CLEAN/LUBECONDITION

TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)

GAUGES

N/A

CONTROLLED

23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us

35 35

902902902

NAMEPLATE DATA

RATED CURRENT

RATED CURRENT

AMPERES

AMPERES/

11,846

3 4 5 kV PRI.

PRIMARY VOLTAGE

SECONDARY VOLTAGE 277 WYE

13,094

TAP POSITION/CONNECTION

12,782 12,158

CLASS

12,470

Phase 3876101-G3SERIAL NO.

kVA/

THERMAL RATINGS

DELTA

kV SEC.

IMPEDANCE

YEAR OF MANUF.N/A 1988

MANUFACTURER

SPECIFICATION NO. MANUF. LOCATION

TYPE AA K FACTOR N/A °CTEMPERATURE RISE

U.S.A

805.8

B.I.L. RATINGWINDING MATERIAL Cu

LB

DELTA480

TAP VOLTAGES

WINDING POLARITY SUBTRACTIVE

WYE

750 / 750

12,470

TOTAL WEIGHT

Dry

Square D

RANGE

INSPECTION

INSULATION RESISTANCE TEST

TESTED

PRIMARY TO

SECONDARY AND GROUND

SECONDARY TO

PRIMARY AND GROUND

VOLTAGE

(VOLTS DC)

(MEGOHMS)

Windings TEST RESISTANCE

PRIMARY TO

SECONDARY

1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C

DIELECTRIC

ABSORPTION

RATIO

TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1

5,000

1,000

5,000

325,000.0 325,000.0 528,000.0 528,000.0

331,000.0331,000.0128,400.0128,400.0

224,000.0 224,000.0 317,000.0 317,000.0

1.62

2.58

1.42

Calculated PASS/FAIL Calculated

PASS/FAIL

TO

% DEVIATIONMeasured

TRANSFORMER TURNS RATIO TESTS

Calculated PASS/FAIL

CALC.

RATIO

Secondary

VOLTAGE

ENTER Primary

VOLTAGE

X1 - X0 X2 - X0

H1 - H3 H2 - H1 H3 - H2

X3 - X0

TAP TO

TEST

3 45.154 44.940 45.1520.12 % PASS 0.35 % PASSPASS44.996 0.35 %12,470 277

TWO-WINDING DRY-TYPE TRANSFORMER

PAGEDRY TYPE TRANSFORMERDEVICE N/ADBID

23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us

H3-H1 X0-X3X0-X1

WINDING RESISTANCE

H2-H3

Meas. Corr.

TAP

POSITION

TEST

# (milliohms)H1-H2 (milliohms) (milliohms)

Corr.Meas. Corr.Meas.

(milliohms)

Corr. Corr.Meas. Corr.Meas.Meas.

X0-X2 (milliohms) (milliohms)

WINDING TESTED

(t = Equipment Temperature)

Values Corrected to: °C75

Aluminum windings

R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings

R(Corr) = R(Meas) * (226 + c) / (226 + t)

(c = Corrected Temperature)

3 316.800 385.264 318.100 386.845 317.500 386.115 0.618 0.752 0.605 0.736 0.601 0.7311

Primary Secondary

TECH NOTE(S):

COMMENTS: All results are satisfactory at this time.

DEFICIENCIES: