Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
Service Entrance Switchgear
June 16, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform medium voltage HVL switch PM in accordance with project specification and applicable industry standard on SESG located at North West corner of VA CHP
Power Plant building 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
No insulation resistance and dielectric withstand test was performed on the HVL switch due to cable connected on both primary and secondary side of the switch. Switch was cleaned, lubed, exercised and ductor. No issues were found, and contact resistance test were satisfactory at this time.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
A1DESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Carden
10-212760
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
N/A
N/AOPERATING MECHANISM N/A
PHASE BARRIERS N/A N/A
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable N/AINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 30
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
31 25
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.
COMMENTS: Contact resistance test results are satisfactory at this time.
DEFICIENCIES:
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
A2DESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Carden
10-212750
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
N/A
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 28
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
27 26
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
B1DESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Carden
10-212800
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 27
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
26 25
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
B2DESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Carden
10-212790
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 27
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
28 28
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
RADESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Carden
10-212770
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 25
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
30 34
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
RBDESIGNATION
SUBSTATION BUILDING SESG
5/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
Medium Voltage Air Switch
Mike Danford, Billy Cardon
10-212780
VA Hospital WO-08391081
C & L
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES N/A N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
N/A
Acceptable
Acceptable
N/A
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N / A
44035-233-51
15 kv
N / A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone Switch Assembly
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSN / AFUSE MFG. N / A FUSE CAT. NO. N / A
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
15 kv
Square D
61 kA
RANGE
(µ-ohms) 27
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10A
POLE 1
29 28
TECH NOTE(S): Unable to perform insulation resistance test due to cable connected on both side of the switch.