Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-11 Substation PM
May 17, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-11 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-11 Main Breaker ground fault pick up is slightly above the expected value. All other results are satisfactory at this time.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-11_876101-C3_XD
Report Source DryTypeTransformer 5/12/2021 7:06:16 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-C3 Location 2002 Holcombe Blvd Houston, Texas Special ID USS-11 XFMR
77030 Division Houston Circuit Designation USS-11 SUBSTATION Manufacturer Square D Electric Class Year Manufactured Type DryTypeTransformer Mfr Location USA Winding Insulation Open-Wound Coolant Select Coolant Weight 11000 Tank Type Select Tank Type BIL 110 kV Dry Tank Type Ventilated VA Rating 750 kV 12.47,0.48,* Insulation Material Epoxy Mica
Administration Test Date 5/12/2021 Test Time: 7:06 PM Weather Indoors Air Temperature 26.1°C Apparatus * Humidity 67 %
Temperature Tester C.Espartero Work Order Date Last Tested Verified Test Set Type M4000 Date Retested Verification Date 5/12/2021 Set Top Serial # Reason ROUTINE Last Sheet # Set Bottom Serial # Travel Time Purchase Order Ins. Book # Duration Copies Sheet # Crew Size 1
876101-C3 1 - 6
Session Notes
876101-C3 2 - 6
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * * H2 H2 * * * * * * H3 H3 * * * * * *
Overall Tests - 2K
876101-C3 3 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 2.000 8.000 2.000
1.000 1.000 1.000 mA Watts 0.021 0.006 0.012 0.015 0.068 0.049 0.009 0.019
% PF Meas.
0.053 0.065 0.041 0.050 0.090 0.107 0.029 0.063
Cap (pF) 1032.606 245.334 787.356 787.271 2003.910 1217.190 787.242 786.721
IR Man.
Good Good Good Good Good Good Good Good
3.893 0.925 2.968 2.968 7.555 4.589 2.968 2.966
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.893/3.893, 1/1 mA: 0.925/0.925, 1/1 mA: 2.968/2.968, 1/1 mA: 2.968/2.968, 1/1 mA: 7.555/7.555, 1/1 mA: 4.589/4.589, 1/1 mA: 2.968/2.968, 1/1 mA: 2.966/2.966, 1/1
Watts: 0.021/0.021, 1/1 Watts: 0.006/0.006, 1/1 Watts: 0.012/0.012, 1/1 Watts: 0.015/0.015, 1/1 Watts: 0.068/0.068, 1/1 Watts: 0.049/0.049, 1/1 Watts: 0.009/0.009, 1/1 Watts: 0.019/0.019, 1/1
Cap (pF): 1032.606/1032.606, 1/1 Cap (pF): 245.334/245.334, 1/1 Cap (pF): 787.356/787.356, 1/1 Cap (pF): 787.271/787.271, 1/1 Cap (pF): 2003.910/2003.910, 1/1 Cap (pF): 1217.190/1217.190, 1/1 Cap (pF): 787.242/787.242, 1/1 Cap (pF): 786.721/786.721, 1/1
Δ-
USS-11_876101-C3_XD
Overall Tests - LG
Winding Resistance
Winding Manufacturer Serial Number Configuration Winding Temperature Factory Factory
Temperature Rise Resistance Temperature (Ohms)
Y * * * *
High Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 199.7 milli Ohms * * * * 3 B 192.6 milli Ohms * * * * 3 C 195.8 milli Ohms * * * *
Low Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 190.3 micro Ohms * * * * 3 B 193 micro Ohms * * * * 3 C 189.1 micro Ohms * * * *
876101-C3 4 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 10.005 10.005 10.004
0.999 1.000 0.999 mA Watts 0.021 0.006 0.016 0.015 0.068 0.048 0.009 0.020
% PF Meas.
0.054 0.064 0.053 0.051 0.090 0.105 0.030 0.067
Cap (pF) 1032.268 245.276 787.076 786.992 2003.836 1217.147 787.206 786.688
Tip UP
-0.001 0.012
-0.002 0.000
FRANK IR Man.
3.892 0.925 2.967 2.967 7.554 4.589 2.968 2.966
Good Investigate
Good
Investigate
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.892/3.892, 1/1 mA: 0.925/0.925, 1/1 mA: 2.967/2.967, 1/1 mA: 2.967/2.967, 1/1 mA: 7.554/7.554, 1/1 mA: 4.589/4.589, 1/1 mA: 2.968/2.968, 1/1 mA: 2.966/2.966, 1/1
Watts: 0.021/0.021, 1/1 Watts: 0.006/0.006, 1/1 Watts: 0.016/0.016, 1/1 Watts: 0.015/0.015, 1/1 Watts: 0.068/0.068, 1/1 Watts: 0.048/0.048, 1/1 Watts: 0.009/0.009, 1/1 Watts: 0.020/0.020, 1/1
Cap (pF): 1032.268/1032.268, 1/1 Cap (pF): 245.276/245.276, 1/1 Cap (pF): 787.076/787.076, 1/1 Cap (pF): 786.992/786.992, 1/1 Cap (pF): 2003.836/2003.836, 1/1 Cap (pF): 1217.147/1217.147, 1/1 Cap (pF): 787.206/787.206, 1/1 Cap (pF): 786.688/786.688, 1/1
LSR mA: 165.218/165.218, 1/1 Watts: 1329.980/1329.980, 1/1 Cap (pF): */*, 1/1 LSR mA: 76.237/76.237, 1/1 Watts: 606.257/606.257, 1/1 Cap (pF): */*, 1/1 LSR mA: 165.933/165.933, 1/1 Watts: 1323.210/1323.210, 1/1 Cap (pF): */*, 1/1
USS-11_876101-C3_XD
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye Connections - - -
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK Manual
3 12470 3 480 44.997 44.975 44.934 44.94 44.772 45.222 Good Good
876101-C3 5 - 6
DETC
LTC Test kV mA 165.218
H3 H1 Watts
1329.980 X L
mA 76.237
H1 H2 Watts
606.257 X L
mA 165.933
H2 H3 Watts X
L FRANK Manual
Good1323.210
Exciting Current Plot
876101-C3 6 - 6
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/12/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT A
Mike Danford
0030, 0248
N/A
N/A
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
10 7 10
.2
1 IN
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 800RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
5,584
1.982
0.544
NT NT NT NT NT
4,200 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
3,200
8.936
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
720 A A880
A A
AA
A A
3,600 4,400
6,1605,040
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
DEFICIENCIES:
TRIP UNIT TYPE
6616C36G04
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
5/12/21 45
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Javier Rojas
3230,3115,01025
VA Hospital WO-08391081
3200 AMP
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 632
65 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
3200 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Comment
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Westinghouse
Carriere N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
2,100.0 2,509.5
1,768.0 2,112.8
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
3,047.32,550.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
2,210.0
2,330.0
1,391.0
774.0
1,544.0
695.01,662.2
2,641.0
830.5
2,784.4 924.9
1,845.1
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1.0
7.5
5.0
.4
2 2 2
.3
.4
1.0
2.5
2.5
.15
1.0
7.5
5.0
.4
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 3200 AMPRATING PLUG:3200 AMP 3200 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.4 .4
.4.3
AS FOUND
RANGE
MINIMUM MAXIMUM
6,645
0.18
0.46
1,460
6,645
0.18
8,040
0.46
1,460
6,525
0.18
8,300
0.46
1,462
6,525
0.18
8,300
0.46
1,427
6,800
0.17
8,320
0.46
1,438
6,800
0.17
8,320
0.46
1,438
12,000 0.08 0.18
1,920 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 9.30 8.25 8.25 9.20 9.20
3,411 3,010 3,010 3,220 3,220
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
9,600 7
3,411
9.30
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
2,880 A A3,520
A A
AA
A A
7,200 8,800
7,0405,760
1,152 1,408
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S): Inst OFF
COMMENTS: Breaker placed back in service.
DEFICIENCIES: Ground fault pick up outside of range
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/12/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
Mike Danford
0248, 0115
N/A
N/A
VA Hospital WO-08391081
480/277
20 KA
MANUFACTURER
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
N/A
Acceptable
Cleaned
CONDITION
N/A
Description
Cleaned
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION N/A N/A N/A
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
N/A
Acceptable
N/A
N/A
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
45-08000-45S
INSPECTION
New
PT'S AND CT'S
Acceptable N/A AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING Not CheckedRACKING / LIFTING MECHANISMS
Acceptable N/ADOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
C & LINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
Cleaned
N/A
N/A
SQUARED
RANGE
BARRIERS / SHUTTERS
@1000VGIG-OHMS 20°C
54.8 68.5
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
158.5126.8
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
122.1
175.9
87.9
114.7
109.9
152.6
219.9 143.4TEST 3
N-GNDTEST 4
1.25TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
SECTION 1
SECTION 2 SECTION 3
SECTION 2
24 25
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 79 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
5/12/2021 67
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
M4K
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
Torqued
Acceptable N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
Acceptable
N/A
GAUGES
SUPPORT INSULATORS
N/ATorqued
Acceptable
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
GAUGES
N/A
CLEAN
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
69 69
1,8041,8041,804
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,094
TAP POSITION/CONNECTION
12,782 12,158
1,500
CLASS
12,470
Phase 3876101-C3SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
11000
YEAR OF MANUF.NA 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA/FA K FACTOR N/A °CTEMPERATURE RISE
USA
305.5
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
1,500 / 1,500
12,470
TOTAL WEIGHT
Dry
Square D
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
Acceptable
Acceptable
Acceptable
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1.3226
5,000
1,000
5,000
179,200.0 237,009.9 204,000.0 269,810.4
1,891,3181,430,0001,341,1161,014,000
344,000.0 454,974.4 424,000.0 560,782.4
1.14
1.41
1.23
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X2 - X0
H3 - H1 H1 - H2 H2 - H3
X3 - X0
TAP TO
TEST
3 44.975 44.934 44.9400.14 % PASS 0.12 % PASSPASS44.996 0.05 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE DBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 199.700 237.172 192.600 228.740 195.800 232.541 0.190 0.226 0.193 0.229 0.189 0.2241
Primary Secondary
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH RB
Steve O'Keefe
VA Hospital WO-08391081
C & L
Cleaned N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
NA NA NA
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
C & L
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
NA
NA
15 kv
NA
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone
95 kV
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE NAVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
NA
NA
NA
CLOSE COIL INFORMATION
NA
NA
NA
N/A
NA
NA
N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
NA
NA
NA
NA
UNDERVOLTAGE COIL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSNAFUSE MFG. NA FUSE CAT. NO. NA
@5000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
Square D
600 Amps
RANGE
(µ-ohms) 0
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at
POLE 1
0 0
10 A 70 6880POLE CONTACT RESISTANCE at (µ-ohms)
TECH NOTE(S): Did not test insulation resistance due to feeder cables connected to the switch.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH B2
Steve O'Keefe
VA Hospital WO-08391081
C & L
Cleaned N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Dirty
Acceptable
Acceptable
N/A
C & L
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
NA
NA
15 kv
NA
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE Power Zone
95 kV
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE NAVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
NA
NA
NA
CLOSE COIL INFORMATION
NA
NA
NA
N/A
NA
NA
N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
125 VDC
NA
NA
NA
NA
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 Amps
FUSE AMPSA1550X100E-1DFUSE MFG. Gould FUSE CAT. NO. 100 Amps
@5000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
Square D
600 Amps
RANGE
(µ-ohms) 64
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
84 66
10 AFUSE RESISTANCE at (µ-ohms)
TECH NOTE(S): Did not test insulation resistance due to feeder cables connected to the switch.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/12/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT B
Mike Danford
0030, 0248
N/A
N/A
VA Hospital WO-08391081
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF436LSIG
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
9 7 9
.2
1 IN
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 400RATING PLUG:400 400
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2,796
1.983
0.543
NT NT NT NT NT
2,100
400 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
1,600
8.937
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
360 A A440
A A
AA
A A
1,600 2,400
3,0802,520
144 176
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-11DESIGNATION
SUBSTATION BUILDING 100
05/12/2021 47
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT C
Mike Danford
0030, 0248
N/A
N/A
VA Hospital WO-08391081
2000 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONPEL
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. PEF36200LIG
N/AFUSE CAT. NO.
2000 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
Cleaned
N/AOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
N/A
N/A
6 5 6
640AMP
.2 OUT
N/A
N/A
N/A
N/A
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 2000RATING PLUG:2000 2000
Overcurrent Settings
CT / SENSOR RATINGS:
.2 OUT .2 OUT
880640AMP
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
10,200
NT
NT
0.161
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
2,000 1.4 2
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8.5 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
6,000
2,200
7.251
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.27
sec sec sec sec sec sec
AS LEFT
1,800 A A2,200
A A
AA
A A
15,40012,600
792 960
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.