Inspected By: Phillip O’Keefe Date: 03 / 17 / 2021
Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….
Comments:……………………………………………………………………………………………………………………………………….
Thermograph Inspection At
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 17, 2021
Job No.
WO-08391082
Thermo Gram: 03 / 16 / 21
Analysis & Recommended Actions:
Object Parameters: Values
Atmos Temperature: 23.0°C
Humidity %: 53%
Reflective Temperature: °C
Reference Temperature: 24.0°C
Emissivity: .95
Image Date: 03 / 16 / 2021
IR Photo No.: 0287
Page No.: 62
Location: VA’s Medical Center, Bldg. 110
Floor Level: 1st. Floor Level
Room No. 151
Type Equipment: Panel
FLN: 1A
Voltage Rating: 208/120V
Current Rating: 225 Amp Max
Brk. / Cir. / Size: Cir. 22 / 20A / #12 AWG
Phase(s): B Phase
Actual Cir. Load: 27.9
Disc. Type: N/A
Fuse Size: N/A
Fuse Type: N/A
Digital Photo No. 0288
Severity: Minor
Possible Causes:
Possible Loose Connection & Possible Overload Issue.
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.
Current exceeds 80% of breaker size.
Warrants Further investigations into current loads.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 37.3°C 5.1 °C
AØ
27.9 Amp Spot 2 32.2°C
Spot 3 °C °C
BØ
Spot 4 °C
Spot 5 °C °C
CØ
Spot 6 °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 17, 2021
Job No.
Thermo Gram: 03 / 16 /21
Humidity %: 23%
Reflective Temperature: °C
Reference Temperature: 23.0°C
Image Date: 03 / 16 / 2021
IR Photo No.: 0289
Page No.: 63
Location: VA’s Medical Center, Bldg. 110
Floor Level: 2nd. Floor Level
Room No. Main Hallway
Type Equipment: Panel
FLN: H
Voltage Rating: 208/120V
Current Rating: Unknown
Brk. / Cir. / Size: Cir. 19 / 20A / #12 AWG
Phase(s): On Right side of panel
Actual Cir. Load: 21.9
Disc. Type: N/A
Digital Photo No. 0290
Possible Causes:
Possible Loose Connection.
Possible Overload Issue.
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.
Current exceeds 80% of breaker size.
Warrants Further investigations into current loads.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 39.7°C Spot 1&2 11.4°C
AØ
21.9 Amps Spot 2 28.3°C
Spot 3 °C °C
BØ
Spot 4 °C
Spot 5 °C °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 17, 2021
Job No.
Thermo Gram: 03 / 17 / 21
Humidity %: 23%
Reflective Temperature: °C
Reference Temperature: 24.0°C
Image Date: 03 / 17 / 2021
IR Photo No.: 0297
Page No.: 64
Location: VA’s Medical Center, Bldg. 110
Floor Level: Basement Floor Level
Room No. Compressor Area @ west end
Type Equipment: Panel
FLN: 110-B Basement
Voltage Rating: 208/120V
Current Rating: Unknown
Brk. / Cir. / Size: Top Right Breaker / 20A / #10 AWG
Phase(s):
Actual Cir. Load: 36- 40.2 Amps
Disc. Type: N/A
Digital Photo No. 0298
Possible Causes:
Possible Loose Connection.
Possible Overload Issue.
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.
Current exceeds 80% of breaker size.
Warrants Further investigations into current loads.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 33.7°C Spot 1&2 4.2°C
AØ
36-40,2 Amps Spot 2 29.5°C
Spot 3 °C °C
BØ
Spot 4 °C
Spot 5 °C °C
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 17, 2021
Job No.