View the file

Other files

File Type Posted
Exhibit N - PT-12 BLDG 29 Test Report.pdf PDF
Exhibit G - Chiller Water XFMR Test Report.pdf PDF
Exhibit AF - USS-L Test Report.pdf PDF
Exhibit P - SESG Test Report.pdf PDF
Exhibit AA - USS-10 Test Report.pdf PDF
Exhibit V - USS-5 Test Report.pdf PDF
Exhibit D - Building 108 Visor Clininc IR Sheet.pdf PDF
Exhibit K - MSG Circuit B1 XFMR and Breakers Test Reports.pdf PDF
Exhibit W - USS-6 Test Report.pdf PDF
Exhibit H - CHP Bldg. Test Report.pdf PDF
Exhibit AC - USS-12 Test Report.pdf PDF
Exhibit AE - USS-14 Test Report.pdf PDF
Exhibit T - USS-3 Test Report.pdf PDF
Exhibit M - PT-1 and PT-14 Oil report.pdf PDF
36C25623Q0012 0001.docx DOCX document
Exhibit R - USS-1 Test Report.pdf PDF
Exhibit X - USS-7 Test Report.pdf PDF
Exhibit AD - USS-13 Test Report.pdf PDF
Exhibit E - Building 109 Lab IR Sheets.pdf PDF
Exhibit L - MSG Test Report.pdf PDF
Exhibit Y - USS-8 Test report.pdf PDF
Exhibit AB - USS-11 Test Report.pdf PDF
Exhibit U - USS-4 Test Report.pdf PDF
Exhibit Z - USS-9 Test Report.pdf PDF
Exhibit Q - USS L Laundry Report.pdf PDF
Exhibit A - Bldg. 104A Test Report.pdf PDF
Exhibit J - MBSG Test Report.pdf PDF
Exhibit F - Building 110 IR Sheets.pdf PDF
Exhibit S - USS-2 Test Report.pdf PDF
Exhibit B - Bldg. 105 IR Sheet (1).pdf PDF
36C25623Q0012.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspected By: Phillip O’Keefe Date: 03 / 24 / 2021

Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….

Comments:……………………………………………………………………………………………………………………………………….

Thermograph Inspection At

Michael E. DeBakey Veterans Affairs Medical Center

Houston, Texas

Date:

March 24, 2021

Job No.

WO-08391082

Thermo Gram: 03 / 24 / 2021

Analysis & Recommended Actions:

Object Parameters: Values

Atmos Temperature: 23.0°C

Humidity %: 54%

Reflective Temperature: °C

Reference Temperature: 23.0°C

Emissivity: .95

Image Date: 03 /24 / 2021

IR Photo No.: 0345

Page No.: 72

Location: VA’s Medical Center (Hou)

Floor Level: Outside along building

Room No. N/A

Type Equipment: Panel

FLN: G

Voltage Rating: 208/120V

Current Rating: 225 Amp. Max

Brk. / Cir. / Size: Cir. 26 / 20A / #12 AWG

Phase(s): A Phase

Actual Cir. Load: 10.6 Amps

Disc. Type: N/A

Fuse Size: N/A

Fuse Type: N/A

Digital Photo No. 0346

Severity: Minor

Possible Causes:

Possible Loose Connection

Recommended Actions:

Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.

Warrants Further investigations into current loads.

Spot No.

Spot No.

Tan Delta

Phase Loads

Spot 1 29.3°C Spot 1&2 2.1°C

AØ

10.6 Amps. Spot 2 27.2°C

Spot 3 °C °C

BØ

Spot 4 °C

Spot 5 °C °C

CØ

Spot 6 °C

Inspected By: Phillip O’Keefe Date: 03 / 24 / 2021

Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….

Comments:……………………………………………………………………………………………………………………………………….

Thermograph Inspection At

Michael E. DeBakey Veterans Affairs Medical Center

Houston, Texas

Date:

March 24, 2021

Job No.

WO-08391082

File details come from the government source that posted it. Updated .