Inspected By: Phillip O’Keefe Date: 03 / 24 / 2021
Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….
Comments:……………………………………………………………………………………………………………………………………….
Thermograph Inspection At
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 24, 2021
Job No.
WO-08391082
Thermo Gram: 03 / 24 / 2021
Analysis & Recommended Actions:
Object Parameters: Values
Atmos Temperature: 23.0°C
Humidity %: 54%
Reflective Temperature: °C
Reference Temperature: 23.0°C
Emissivity: .95
Image Date: 03 /24 / 2021
IR Photo No.: 0345
Page No.: 72
Location: VA’s Medical Center (Hou)
Floor Level: Outside along building
Room No. N/A
Type Equipment: Panel
FLN: G
Voltage Rating: 208/120V
Current Rating: 225 Amp. Max
Brk. / Cir. / Size: Cir. 26 / 20A / #12 AWG
Phase(s): A Phase
Actual Cir. Load: 10.6 Amps
Disc. Type: N/A
Fuse Size: N/A
Fuse Type: N/A
Digital Photo No. 0346
Severity: Minor
Possible Causes:
Possible Loose Connection
Recommended Actions:
Remove conductor(s). Clean conductor(s) & termination point(s). Re-install conductor(s) to termination point(s) and tighten to proper torque settings.
Warrants Further investigations into current loads.
Spot No.
Spot No.
Tan Delta
Phase Loads
Spot 1 29.3°C Spot 1&2 2.1°C
AØ
10.6 Amps. Spot 2 27.2°C
Spot 3 °C °C
BØ
Spot 4 °C
Spot 5 °C °C
CØ
Spot 6 °C
Inspected By: Phillip O’Keefe Date: 03 / 24 / 2021
Repaired By: ……………………………………………………….. Date Repaired: ……………………………………….
Comments:……………………………………………………………………………………………………………………………………….
Thermograph Inspection At
Michael E. DeBakey Veterans Affairs Medical Center
Houston, Texas
Date:
March 24, 2021
Job No.
WO-08391082
File details come from the government source that posted it. Updated .