Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
MSG Circuit B1 Power Distribution Transformers
July 3, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform MSG Circuit B1 Power distribution Transformers PM in accordance with project specification and applicable industry standard located at VA Campus 2002
Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe Ceasar of VA
Medical Center Electrical Power Distribution Department (713)806-7506.
BLDG 125 Distribution Transformer
BLDG 125 Distribution Transformer was not tested because building 125 is still under warranty and was not included on VA 3-year scheduled maintenance.
BLDG 109A, 109B, and 110 Power distribution transformers
We were not able to pull oil samples on the power distribution transformer due to transformer being under vacuum/ negative pressure and transformer is not equipped with a fill port for nitrogen filling. Schneider electric service highly recommends installing nitrogen fill port on all the liquid filled transformer and run an external piping that will allow transformer oil sampling while the transformer is still energized. This will eliminate having a power outage for transformer oil sampling.
BLDG 109A and 108 Transformers
Transformer excitation current did not conform to the known pattern. This may due to the core being magnetized during dienergization. With the limited time, it was not enough to allow the magnetism to dessipate before any electrical testing is performed. However the TTR and winding resistance test results are all acceptable which prove’s that the BLDG 109A and 108 transformers windings are in good, acceptable condtions.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
BLDG 108 XFMR_871049-H1_X2
TwoWindingTransformerReport Source
6/26/2021 9:59:38 AMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 1650009680
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID BLDG 108 XFMR
Division Houston Circuit Designation BLDG 108 XFMR
Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 2016 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class OA
Oil Volume 215 UG BIL 95 kV
Weight 4675 LB kV 12.47, 0.48 VA Rating 500, *, *, *, KVA
Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Cloudy
Air Temperature 30°C Apparatus Temperature
40°C Humidity 77 %
Tester JRojas Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 2
1 - 5871049-H1
Session Notes
2 - 5871049-H1
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 10.043 38.126 4.406 0.743 0.643 10112.47
Good
2 CH 10.083 7.236 0.904 0.803 0.643 1919.261 Good Good
3 CHL(UST) 10.084 30.886 3.512 0.731 0.643 8192.263 Good Good
4 CHL 0 30.890 3.503 0.729 0.643 8193.211 Good
5 CL+CHL 1.000 60.603 7.734 0.821 0.643 16073.97
6 CL 1.000 29.723 4.208 0.910 0.643 7883.672 Good Good
7 CHL(UST) 1.003 30.894 3.539 0.737 0.643 8194.377
8 CHL 0 30.879 3.525 0.734 0.643 8190.304 Good Good
LSR mA: 38.126/38.126, 1/1 Watts: 4.406/4.406, 1/1 Cap (pF): 10112.472/10112.472, 1/1
LSR mA: 7.236/7.236, 1/1 Watts: 0.904/0.904, 1/1 Cap (pF): 1919.261/1919.261, 1/1
LSR mA: 30.886/30.886, 1/1 Watts: 3.512/3.512, 1/1 Cap (pF): 8192.263/8192.263, 1/1
LSR mA: 30.890/30.890, 1/1 Watts: 3.503/3.503, 1/1 Cap (pF): 8193.211/8193.211, 1/1
LSR mA: 60.603/60.603, 1/1 Watts: 7.734/7.734, 1/1 Cap (pF): 16073.976/16073.976, 1/1
LSR mA: 29.723/29.723, 1/1 Watts: 4.208/4.208, 1/1 Cap (pF): 7883.672/7883.672, 1/1
LSR mA: 30.894/30.894, 1/1 Watts: 3.539/3.539, 1/1 Cap (pF): 8194.377/8194.377, 1/1
LSR mA: 30.879/30.879, 1/1 Watts: 3.525/3.525, 1/1 Cap (pF): 8190.304/8190.304, 1/1
FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.
3 (Good) - All values are acceptable.
6 (Good) - All values are acceptable.
8 (Good) - All values are acceptable.
3 - 5871049-H1
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 143 milli Ohms * * * *
3 B 163 milli Ohms * * * *
3 C 145 milli Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 120 micro Ohms * * * *
3 B 136 micro Ohms * * * *
3 C 143 micro Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 7 23.925 224.135 L 5.770 55.867 C 22.438 212.426 L Good
LSR mA: 23.925/23.925, 1/1 Watts: 224.135/224.135, 1/1 Cap (pF): */*, 1/1
LSR mA: 5.770/5.770, 1/1 Watts: 55.867/55.867, 1/1 Cap (pF): */*, 1/1
LSR mA: 22.438/22.438, 1/1 Watts: 212.426/212.426, 1/1 Cap (pF): */*, 1/1
4 - 5871049-H1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections - - -
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 45.016 44.999 44.998 44.772 45.222 Good Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
Exciting Current Plot
5 - 5871049-H1
BLDG 109-9A XFMR_871049-C1_X2
6/26/2021 9:59:38 AMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 871049-C1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID BLDG 109-9A XFMR
Division Houston Circuit Designation BLDG 109-9A XFMR
Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1989 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class OA
Oil Volume 350 UG BIL 95 kV
Weight 7595 LB kV 12.47, 0.48 VA Rating 1000, *, *, *, KVA
Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy
Air Temperature 30°C Apparatus Temperature
28°C Humidity 68 %
Tester Cory Llewellyn Work Order WO-08754081 Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
1 - 5871049-C1
2 - 5871049-C1
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 10.003 24.559 0.663 0.260 0.962 6514.395
2 CH 10.002 5.346 0.196 0.352 0.962 1418.001 Good
3 CHL(UST) 10.002 19.206 0.474 0.237 0.962 5094.381 Good
4 CHL 0 19.213 0.468 0.234 0.962 5096.394
5 CL+CHL 1.000 36.919 1.845 0.481 0.962 9792.787
6 CL 1.000 17.736 1.393 0.756 0.962 4704.523 Good
7 CHL(UST) 1.000 19.186 0.495 0.248 0.962 5089.271
8 CHL 0 19.182 0.452 0.227 0.962 5088.264 Good
LSR mA: 24.559/24.559, 1/1 Watts: 0.663/0.663, 1/1 Cap (pF): 6514.395/6514.395, 1/1
LSR mA: 5.346/5.346, 1/1 Watts: 0.196/0.196, 1/1 Cap (pF): 1418.001/1418.001, 1/1
LSR mA: 19.206/19.206, 1/1 Watts: 0.474/0.474, 1/1 Cap (pF): 5094.381/5094.381, 1/1
LSR mA: 19.213/19.213, 1/1 Watts: 0.468/0.468, 1/1 Cap (pF): 5096.394/5096.394, 1/1
LSR mA: 36.919/36.919, 1/1 Watts: 1.845/1.845, 1/1 Cap (pF): 9792.787/9792.787, 1/1
LSR mA: 17.736/17.736, 1/1 Watts: 1.393/1.393, 1/1 Cap (pF): 4704.523/4704.523, 1/1
LSR mA: 19.186/19.186, 1/1 Watts: 0.495/0.495, 1/1 Cap (pF): 5089.271/5089.271, 1/1
LSR mA: 19.182/19.182, 1/1 Watts: 0.452/0.452, 1/1 Cap (pF): 5088.264/5088.264, 1/1
FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.
3 (Good) - All values are acceptable.
6 (Good) - All values are acceptable.
8 (Good) - All values are acceptable.
3 - 5871049-C1
Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 1.457 Ohms * * * *
3 B 1.457 Ohms * * * *
3 C 1.394 Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 1.07 milli Ohms * * * *
3 B 0.98 milli Ohms * * * *
3 C 1.04 milli Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 7 41.818 359.897 L 27.411 240.211 L 48.463 409.072 L Investigate
LSR mA: 41.818/41.818, 1/1 Watts: 359.897/359.897, 1/1 Cap (pF): */*, 1/1
LSR mA: 27.411/27.411, 1/1 Watts: 240.211/240.211, 1/1 Cap (pF): */*, 1/1
LSR mA: 48.463/48.463, 1/1 Watts: 409.072/409.072, 1/1 Cap (pF): */*, 1/1
4 - 5871049-C1
Delta Wye
Connections - - -
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 45.01 45.015 45.014 44.772 45.222 Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
Exciting Current Plot
5 - 5871049-C1
BLDG 109-9B XFMR_930206-A1_X2
6/26/2021 9:59:38 AMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 930206-A1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID BLDG 109-9B XFMR
Division Houston Circuit Designation BLDG 109-9B XFMR
Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1993 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class OA
Oil Volume 300 UG BIL 95 kV
Weight 7300 LB kV 12.47, 0.48 VA Rating 1000, *, *, *, KVA
Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy
Air Temperature 30°C Apparatus Temperature
28°C Humidity 68 %
Tester Cory Llewellyn Work Order WO-08754081 Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
1 - 5930206-A1
2 - 5930206-A1
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 10.004 17.876 0.537 0.289 0.962 4741.618
2 CH 10.003 5.141 0.188 0.352 0.962 1363.688 Good
3 CHL(UST) 10.003 12.728 0.357 0.270 0.962 3376.283 Good
4 CHL 0 12.735 0.349 0.263 0.962 3377.929
5 CL+CHL 1.000 33.384 1.019 0.294 0.962 8855.185
6 CL 1.000 20.671 0.674 0.314 0.962 5483.130 Good
7 CHL(UST) 1.000 12.718 0.361 0.273 0.962 3373.644
8 CHL 0 12.713 0.345 0.261 0.962 3372.056 Good
LSR mA: 17.876/17.876, 1/1 Watts: 0.537/0.537, 1/1 Cap (pF): 4741.618/4741.618, 1/1
LSR mA: 5.141/5.141, 1/1 Watts: 0.188/0.188, 1/1 Cap (pF): 1363.688/1363.688, 1/1
LSR mA: 12.728/12.728, 1/1 Watts: 0.357/0.357, 1/1 Cap (pF): 3376.283/3376.283, 1/1
LSR mA: 12.735/12.735, 1/1 Watts: 0.349/0.349, 1/1 Cap (pF): 3377.929/3377.929, 1/1
LSR mA: 33.384/33.384, 1/1 Watts: 1.019/1.019, 1/1 Cap (pF): 8855.185/8855.185, 1/1
LSR mA: 20.671/20.671, 1/1 Watts: 0.674/0.674, 1/1 Cap (pF): 5483.130/5483.130, 1/1
LSR mA: 12.718/12.718, 1/1 Watts: 0.361/0.361, 1/1 Cap (pF): 3373.644/3373.644, 1/1
LSR mA: 12.713/12.713, 1/1 Watts: 0.345/0.345, 1/1 Cap (pF): 3372.056/3372.056, 1/1
FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.
3 (Good) - All values are acceptable.
6 (Good) - All values are acceptable.
8 (Good) - All values are acceptable.
3 - 5930206-A1
Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 0.46 Ohms * * * *
3 B 0.47 * * * *
3 C 0.46 * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 0.95 milli Ohms * * * *
3 B 0.97 milli Ohms * * * *
3 C 0.96 milli Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 7 50.487 452.650 L 35.685 289.053 L 54.953 467.438 L Good
LSR mA: 50.487/50.487, 1/1 Watts: 452.650/452.650, 1/1 Cap (pF): */*, 1/1
LSR mA: 35.685/35.685, 1/1 Watts: 289.053/289.053, 1/1 Cap (pF): */*, 1/1
LSR mA: 54.953/54.953, 1/1 Watts: 467.438/467.438, 1/1 Cap (pF): */*, 1/1
4 - 5930206-A1
Delta Wye
Connections - - -
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 45.018 45.021 45.024 44.772 45.222 Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
Exciting Current Plot
5 - 5930206-A1
BLDG 110 XFMR_871049-D1_X2
6/26/2021 9:59:38 AMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 871049-D1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID BLDG 110 XFMR
Division Houston Circuit Designation BLDG 110 XFMR
Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1989 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class OA
Oil Volume 270 UG BIL 95 kV
Weight 5185 LB kV 12.47, 0.208 VA Rating 500, *, *, *, KVA
Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy
Air Temperature 30°C Apparatus Temperature
50°C Humidity 66 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 1
1 - 5871049-D1
2 - 5871049-D1
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 10.005 13.333 0.785 0.303 0.514 3536.520
2 CH 10.004 4.360 0.233 0.274 0.514 1156.463 Good
3 CHL(UST) 10.004 8.971 0.541 0.310 0.514 2379.567 Good
4 CHL 0 8.973 0.552 0.316 0.514 2380.057
5 CL+CHL 0.201 26.293 1.412 0.276 0.514 6974.357
6 CL 0.200 17.312 0.846 0.251 0.514 4592.091 Good
7 CHL(UST) 0.200 8.977 0.551 0.316 0.514 2381.086
8 CHL 0 8.981 0.566 0.324 0.514 2382.266 Good
LSR mA: 13.333/13.333, 1/1 Watts: 0.785/0.785, 1/1 Cap (pF): 3536.520/3536.520, 1/1
LSR mA: 4.360/4.360, 1/1 Watts: 0.233/0.233, 1/1 Cap (pF): 1156.463/1156.463, 1/1
LSR mA: 8.971/8.971, 1/1 Watts: 0.541/0.541, 1/1 Cap (pF): 2379.567/2379.567, 1/1
LSR mA: 8.973/8.973, 1/1 Watts: 0.552/0.552, 1/1 Cap (pF): 2380.057/2380.057, 1/1
LSR mA: 26.293/26.293, 1/1 Watts: 1.412/1.412, 1/1 Cap (pF): 6974.357/6974.357, 1/1
LSR mA: 17.312/17.312, 1/1 Watts: 0.846/0.846, 1/1 Cap (pF): 4592.091/4592.091, 1/1
LSR mA: 8.977/8.977, 1/1 Watts: 0.551/0.551, 1/1 Cap (pF): 2381.086/2381.086, 1/1
LSR mA: 8.981/8.981, 1/1 Watts: 0.566/0.566, 1/1 Cap (pF): 2382.266/2382.266, 1/1
FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.
3 (Good) - All values are acceptable.
6 (Good) - All values are acceptable.
8 (Good) - All values are acceptable.
3 - 5871049-D1
Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 3.63 Ohms * * * *
3 B 3.65 Ohms * * * *
3 C 3.65 Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 0.52 milli Ohms * * * *
3 B 0.49 milli Ohms * * * *
3 C 0.85 milli Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 7 27.346 232.296 L 16.605 147.472 L 29.534 241.767 L Good
LSR mA: 27.346/27.346, 1/1 Watts: 232.296/232.296, 1/1 Cap (pF): */*, 1/1
LSR mA: 16.605/16.605, 1/1 Watts: 147.472/147.472, 1/1 Cap (pF): */*, 1/1
LSR mA: 29.534/29.534, 1/1 Watts: 241.767/241.767, 1/1 Cap (pF): */*, 1/1
4 - 5871049-D1
Delta Wye
Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 208 103.840 103.83 103.84 103.83 103.321 104.359 Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
Exciting Current Plot
5 - 5871049-D1
PARKING GARAGE_17V11579_X2
6/26/2021 9:59:38 AMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 17V11579
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID PARKING GARAGE XFMR
Division Houston Circuit Designation PARKING GARAGE
Manufacturer Vantran Configuration Δ-Y Year Manufactured 2017 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class OA
Oil Volume 149 UG BIL 95 kV
Weight 4082 LB kV 12.47, 0.48 VA Rating 750, *, *, *, KVA
Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy
Air Temperature 27.8°C Apparatus Temperature
40°C Humidity 76 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
1 - 617V11579
2 - 617V11579
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 10.005 18.317 1.095 0.531 0.889 4858.669
2 CH 10.022 4.963 0.736 1.319 0.889 1316.435 Deteriorated
3 CHL(UST) 10.004 13.360 0.366 0.244 0.889 3543.864 Good
4 CHL 0 13.354 0.358 0.239 0.889 3542.234
5 CL+CHL 1.000 23.046 1.627 0.628 0.889 6113.004
6 CL 1.001 9.691 1.281 1.176 0.889 2570.302 Deteriorated
7 CHL(UST) 1.001 13.380 0.386 0.256 0.889 3549.148
8 CHL 0 13.355 0.345 0.230 0.889 3542.701 Good
LSR mA: 18.317/18.317, 1/1 Watts: 1.095/1.095, 1/1 Cap (pF): 4858.669/4858.669, 1/1
LSR mA: 4.963/4.963, 1/1 Watts: 0.736/0.736, 1/1 Cap (pF): 1316.435/1316.435, 1/1
LSR mA: 13.360/13.360, 1/1 Watts: 0.366/0.366, 1/1 Cap (pF): 3543.864/3543.864, 1/1
LSR mA: 13.354/13.354, 1/1 Watts: 0.358/0.358, 1/1 Cap (pF): 3542.234/3542.234, 1/1
LSR mA: 23.046/23.046, 1/1 Watts: 1.627/1.627, 1/1 Cap (pF): 6113.004/6113.004, 1/1
LSR mA: 9.691/9.691, 1/1 Watts: 1.281/1.281, 1/1 Cap (pF): 2570.302/2570.302, 1/1
LSR mA: 13.380/13.380, 1/1 Watts: 0.386/0.386, 1/1 Cap (pF): 3549.148/3549.148, 1/1
LSR mA: 13.355/13.355, 1/1 Watts: 0.345/0.345, 1/1 Cap (pF): 3542.701/3542.701, 1/1
FRANK™ Message 2 (Deteriorated) - The winding insulation power factor is higher than expected for this type of transformer. This may reflect a low level contamination. Advise your supervisor.
For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The humidity is high, equal to or more than 70%. This may cause the watts and power factor to be higher than usual on your tests. If you compare sets of duplicate apparatus (arresters, bushings, live tank breakers) and one alone shows a high power factor, consider it suspect. but if all three duplicates all have high power factors, it may be due to the factor common to them all, the high humidity. Clean and dry, using heat if necessary, for better results.
3 (Good) - All values are acceptable.
6 (Deteriorated) - The winding insulation power factor is higher than expected for this type of transformer. This may reflect a low level contamination. Advise your supervisor.
8 (Good) - All values are acceptable.
3 - 617V11579
Insulation Resistance
Connections Volts T1 (Mohms) T2 (Mohms) PI
Hi to Lo/Earth * * * *
Hi to Earth Guard Lo 5000.00 3500.00 5200.00 1.49
Lo to Hi/Earth * * * *
Lo to Earth Guard Hi 1000.00 2210.00 3340.00 1.51
Hi to Lo Guard Earth 5000.00 3700.00 6200.00 1.68
Core to Earth * * * *
Core Ground Test
Manufacturer
Serial #
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 1.292 Ohms * * * *
3 B 1.278 Ohms * * * *
3 C 1.295 Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 0.97 milli Ohms * * * *
3 B 0.91 milli Ohms * * * *
3 C 0.878 milli Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
4 - 617V11579
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H1 H3 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 7 29.703 242.891 L 15.676 136.397 L 28.235 241.100 L Good
LSR mA: 29.703/29.703, 1/1 Watts: 242.891/242.891, 1/1 Cap (pF): */*, 1/1
LSR mA: 15.676/15.676, 1/1 Watts: 136.397/136.397, 1/1 Cap (pF): */*, 1/1
LSR mA: 28.235/28.235, 1/1 Watts: 241.100/241.100, 1/1 Cap (pF): */*, 1/1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 44.964 44.966 44.667 44.772 45.222 Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
5 - 617V11579
Exciting Current Plot
6 - 617V11579
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
109DESIGNATION
SUBSTATION BUILDING 109
6/26/2021 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MSB FDR
Cuong Ho
VA Hospital WO-08391081
1600 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONPE
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. PEF361600LSIG
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
MFR. DATE / CODE N/A
SN / SO NO.Square D micrologic series b N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
4.5
2.5
.2
2.5 5 2.5
.2
.1
.2IN
4.5
2.5
.2
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600RATING PLUG:1600 1600
Overcurrent Settings
CT / SENSOR RATINGS:
.1 .2
.35.2
AS FOUND
RANGE
MINIMUM MAXIMUM
1.037
.162
7,200 1 1.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8.5 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800
7.444
SHORT TIME PICKUP
SHORT TIME DELAY 4.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
5,760 7,040
8,8007,200
504 616
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker
COMMENTS: all tested funtions passed
DEFICIENCIES:
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
109DESIGNATION
SUBSTATION BUILDING 109
6/26/2021 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
Cuong Ho
VA Hospital WO-08391081
480/277
100 KA
MANUFACTURER
1600 AMP
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
N/A
CONDITION
N/A
Description
N/A
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION Acceptable N/A N/A
KEY / MECH. INTERLOCKS
Performed
PLC's / HMI's N/A
CONDITION
Acceptable
Acceptable
N/A
Acceptable
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
08000-75S
INSPECTION
Acceptable
PT'S AND CT'S
N/A N/A AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS
Acceptable N/ADOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
N/AINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
N/A
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
SEC1
SEC 2
SEC 3
SEC 4
SEC 3
SEC 4
SEC 5
SEC 2
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
109DESIGNATION
SUBSTATION BUILDING 109
6/26/2021 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MSA FDR
Cuong Ho
VA Hospital WO-08391081
1600 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONPE
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. PEF361600LSIG
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D micrologic series b N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
4.5
2.5
.2
2.5 5 2.5
.25
.1
.2
.2IN
4.5
2.5
.2
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600RATING PLUG:1600 1600
Overcurrent Settings
CT / SENSOR RATINGS:
.1 .2
.35.25
AS FOUND
RANGE
MINIMUM MAXIMUM
1.046
.162
7,200 1 1.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8.5 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800
7.509
SHORT TIME PICKUP
SHORT TIME DELAY 4.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
5,760 7,040
8,8007,200
504 616
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker
COMMENTS: all tested funtions passed
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
109DESIGNATION
SUBSTATION BUILDING 109
6/26/2021 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
TIE
Cuong Ho
VA Hospital WO-08391081
1600 AMP
Cleaned
N/A Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONPE
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. PEF361600SLIG
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
N/A
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
MFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic Series B N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VMEG-OHMS 20°C
TEST 1
TEST 3
1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
.2
2.5 5 2.5
.2
.1
.2IN
.2
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: RATING PLUG:1600 1600
Overcurrent Settings
CT / SENSOR RATINGS:
.1 .2
.35.2
AS FOUND
RANGE
MINIMUM MAXIMUM
1.036
.161
7,200 1 1.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8.5 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800
7.379
SHORT TIME PICKUP
SHORT TIME DELAY 4.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
5,760 7,040
8,8007,200
504 616
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker
COMMENTS: All results are satisfactory at this time.