Exhibit K - MSG Circuit B1 XFMR and Breakers Test Reports.pdf

PDF 493 KB Posted

Attached to
J061--AUTOMATICE TRANSFER SWITCHES AND PARALLELING SWITCHGEAR PREVENITIVE MAINTENANCE, TESTING, AND INSPECTION SERVICES
Solicitation number
36C25623Q0012
Issued by

View the file

Other files

File Type Posted
Exhibit N - PT-12 BLDG 29 Test Report.pdf PDF
Exhibit G - Chiller Water XFMR Test Report.pdf PDF
Exhibit AF - USS-L Test Report.pdf PDF
Exhibit P - SESG Test Report.pdf PDF
Exhibit AA - USS-10 Test Report.pdf PDF
Exhibit V - USS-5 Test Report.pdf PDF
Exhibit D - Building 108 Visor Clininc IR Sheet.pdf PDF
Exhibit C - Bldg. 122, IR Sheets.pdf PDF
Exhibit W - USS-6 Test Report.pdf PDF
Exhibit H - CHP Bldg. Test Report.pdf PDF
Exhibit AC - USS-12 Test Report.pdf PDF
Exhibit AE - USS-14 Test Report.pdf PDF
Exhibit T - USS-3 Test Report.pdf PDF
Exhibit M - PT-1 and PT-14 Oil report.pdf PDF
36C25623Q0012 0001.docx DOCX document
Exhibit R - USS-1 Test Report.pdf PDF
Exhibit X - USS-7 Test Report.pdf PDF
Exhibit AD - USS-13 Test Report.pdf PDF
Exhibit E - Building 109 Lab IR Sheets.pdf PDF
Exhibit L - MSG Test Report.pdf PDF
Exhibit Y - USS-8 Test report.pdf PDF
Exhibit AB - USS-11 Test Report.pdf PDF
Exhibit U - USS-4 Test Report.pdf PDF
Exhibit Z - USS-9 Test Report.pdf PDF
Exhibit Q - USS L Laundry Report.pdf PDF
Exhibit A - Bldg. 104A Test Report.pdf PDF
Exhibit J - MBSG Test Report.pdf PDF
Exhibit F - Building 110 IR Sheets.pdf PDF
Exhibit S - USS-2 Test Report.pdf PDF
Exhibit B - Bldg. 105 IR Sheet (1).pdf PDF
36C25623Q0012.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared By:

Chris Espartero Sr Field Service Representative

North America Service Operations

Houston, TX

MSG Circuit B1 Power Distribution Transformers

July 3, 2021

Work Order: 08391081

2 | P a g e

EXECUTIVE SUMMARY

Schneider Electric Services perform MSG Circuit B1 Power distribution Transformers PM in accordance with project specification and applicable industry standard located at VA Campus 2002

Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe Ceasar of VA

Medical Center Electrical Power Distribution Department (713)806-7506.

BLDG 125 Distribution Transformer

BLDG 125 Distribution Transformer was not tested because building 125 is still under warranty and was not included on VA 3-year scheduled maintenance.

BLDG 109A, 109B, and 110 Power distribution transformers

We were not able to pull oil samples on the power distribution transformer due to transformer being under vacuum/ negative pressure and transformer is not equipped with a fill port for nitrogen filling. Schneider electric service highly recommends installing nitrogen fill port on all the liquid filled transformer and run an external piping that will allow transformer oil sampling while the transformer is still energized. This will eliminate having a power outage for transformer oil sampling.

BLDG 109A and 108 Transformers

Transformer excitation current did not conform to the known pattern. This may due to the core being magnetized during dienergization. With the limited time, it was not enough to allow the magnetism to dessipate before any electrical testing is performed. However the TTR and winding resistance test results are all acceptable which prove’s that the BLDG 109A and 108 transformers windings are in good, acceptable condtions.

If there are any questions or concerns, please contact:

Chris Espartero

832-205-1547

Christopher.Espartero@se.com

BLDG 108 XFMR_871049-H1_X2

TwoWindingTransformerReport Source

6/26/2021 9:59:38 AMSession Test Date

Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 1650009680

Location 2002 Holcombe Blvd Houston, Texas 77030

Special ID BLDG 108 XFMR

Division Houston Circuit Designation BLDG 108 XFMR

Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 2016 Tank Type Sealed

Mfr Location USA Coolant Oil

Phases Three Class OA

Oil Volume 215 UG BIL 95 kV

Weight 4675 LB kV 12.47, 0.48 VA Rating 500, *, *, *, KVA

Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Cloudy

Air Temperature 30°C Apparatus Temperature

40°C Humidity 77 %

Tester JRojas Work Order Date Last Tested

Verified Test Set Type M4000 Date Retested

Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE

Last Sheet # Set Bottom Serial # Travel Time

Purchase Order Ins. Book # Duration

Copies Sheet # Crew Size 2

1 - 5871049-H1

Session Notes

2 - 5871049-H1

Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps

H1 H1 * * * * * *

H2 H2 * * * * * *

H3 H3 * * * * * *

Overall Tests Insulation Test kV mA Watts % PF

Corr.

Corr Fctr Cap (pF) FRANK™ Manual

1 CH+CHL 10.043 38.126 4.406 0.743 0.643 10112.47

Good

2 CH 10.083 7.236 0.904 0.803 0.643 1919.261 Good Good

3 CHL(UST) 10.084 30.886 3.512 0.731 0.643 8192.263 Good Good

4 CHL 0 30.890 3.503 0.729 0.643 8193.211 Good

5 CL+CHL 1.000 60.603 7.734 0.821 0.643 16073.97

6 CL 1.000 29.723 4.208 0.910 0.643 7883.672 Good Good

7 CHL(UST) 1.003 30.894 3.539 0.737 0.643 8194.377

8 CHL 0 30.879 3.525 0.734 0.643 8190.304 Good Good

LSR mA: 38.126/38.126, 1/1 Watts: 4.406/4.406, 1/1 Cap (pF): 10112.472/10112.472, 1/1

LSR mA: 7.236/7.236, 1/1 Watts: 0.904/0.904, 1/1 Cap (pF): 1919.261/1919.261, 1/1

LSR mA: 30.886/30.886, 1/1 Watts: 3.512/3.512, 1/1 Cap (pF): 8192.263/8192.263, 1/1

LSR mA: 30.890/30.890, 1/1 Watts: 3.503/3.503, 1/1 Cap (pF): 8193.211/8193.211, 1/1

LSR mA: 60.603/60.603, 1/1 Watts: 7.734/7.734, 1/1 Cap (pF): 16073.976/16073.976, 1/1

LSR mA: 29.723/29.723, 1/1 Watts: 4.208/4.208, 1/1 Cap (pF): 7883.672/7883.672, 1/1

LSR mA: 30.894/30.894, 1/1 Watts: 3.539/3.539, 1/1 Cap (pF): 8194.377/8194.377, 1/1

LSR mA: 30.879/30.879, 1/1 Watts: 3.525/3.525, 1/1 Cap (pF): 8190.304/8190.304, 1/1

FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5

The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.

3 (Good) - All values are acceptable.

6 (Good) - All values are acceptable.

8 (Good) - All values are acceptable.

3 - 5871049-H1

Winding Resistance

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 143 milli Ohms * * * *

3 B 163 milli Ohms * * * *

3 C 145 milli Ohms * * * *

High Voltage

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 120 micro Ohms * * * *

3 B 136 micro Ohms * * * *

3 C 143 micro Ohms * * * *

Low Voltage

Winding

Manufacturer Serial Number Configuration Winding Temperature

Temperature Rise

Factory Resistance

(Ohms)

Factory Temperature

Δ-Y * * * *

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

H3 H1 H1 H2 H2 H3

DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

3 7 23.925 224.135 L 5.770 55.867 C 22.438 212.426 L Good

LSR mA: 23.925/23.925, 1/1 Watts: 224.135/224.135, 1/1 Cap (pF): */*, 1/1

LSR mA: 5.770/5.770, 1/1 Watts: 55.867/55.867, 1/1 Cap (pF): */*, 1/1

LSR mA: 22.438/22.438, 1/1 Watts: 212.426/212.426, 1/1 Cap (pF): */*, 1/1

4 - 5871049-H1

Turns Ratio Tests Serial Number HV Winding LV Winding

Delta Wye

Connections - - -

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual

3 12470 3 480 44.997 45.016 44.999 44.998 44.772 45.222 Good Good

FRANK™ Message 1 (Good) - Ratio is within expected values.

TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.

Exciting Current Plot

5 - 5871049-H1

BLDG 109-9A XFMR_871049-C1_X2

6/26/2021 9:59:38 AMSession Test Date

Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 871049-C1

Location 2002 Holcombe Blvd Houston, Texas 77030

Special ID BLDG 109-9A XFMR

Division Houston Circuit Designation BLDG 109-9A XFMR

Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1989 Tank Type Sealed

Mfr Location USA Coolant Oil

Phases Three Class OA

Oil Volume 350 UG BIL 95 kV

Weight 7595 LB kV 12.47, 0.48 VA Rating 1000, *, *, *, KVA

Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy

Air Temperature 30°C Apparatus Temperature

28°C Humidity 68 %

Tester Cory Llewellyn Work Order WO-08754081 Date Last Tested

Verified Test Set Type M4000 Date Retested

Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE

Last Sheet # Set Bottom Serial # Travel Time

Purchase Order Ins. Book # Duration

1 - 5871049-C1

2 - 5871049-C1

H1 H1 * * * * * *

H2 H2 * * * * * *

H3 H3 * * * * * *

Overall Tests Insulation Test kV mA Watts % PF

Corr.

Corr Fctr Cap (pF) FRANK™ Manual

1 CH+CHL 10.003 24.559 0.663 0.260 0.962 6514.395

2 CH 10.002 5.346 0.196 0.352 0.962 1418.001 Good

3 CHL(UST) 10.002 19.206 0.474 0.237 0.962 5094.381 Good

4 CHL 0 19.213 0.468 0.234 0.962 5096.394

5 CL+CHL 1.000 36.919 1.845 0.481 0.962 9792.787

6 CL 1.000 17.736 1.393 0.756 0.962 4704.523 Good

7 CHL(UST) 1.000 19.186 0.495 0.248 0.962 5089.271

8 CHL 0 19.182 0.452 0.227 0.962 5088.264 Good

LSR mA: 24.559/24.559, 1/1 Watts: 0.663/0.663, 1/1 Cap (pF): 6514.395/6514.395, 1/1

LSR mA: 5.346/5.346, 1/1 Watts: 0.196/0.196, 1/1 Cap (pF): 1418.001/1418.001, 1/1

LSR mA: 19.206/19.206, 1/1 Watts: 0.474/0.474, 1/1 Cap (pF): 5094.381/5094.381, 1/1

LSR mA: 19.213/19.213, 1/1 Watts: 0.468/0.468, 1/1 Cap (pF): 5096.394/5096.394, 1/1

LSR mA: 36.919/36.919, 1/1 Watts: 1.845/1.845, 1/1 Cap (pF): 9792.787/9792.787, 1/1

LSR mA: 17.736/17.736, 1/1 Watts: 1.393/1.393, 1/1 Cap (pF): 4704.523/4704.523, 1/1

LSR mA: 19.186/19.186, 1/1 Watts: 0.495/0.495, 1/1 Cap (pF): 5089.271/5089.271, 1/1

LSR mA: 19.182/19.182, 1/1 Watts: 0.452/0.452, 1/1 Cap (pF): 5088.264/5088.264, 1/1

FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5

The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.

3 (Good) - All values are acceptable.

6 (Good) - All values are acceptable.

8 (Good) - All values are acceptable.

3 - 5871049-C1

Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 1.457 Ohms * * * *

3 B 1.457 Ohms * * * *

3 C 1.394 Ohms * * * *

High Voltage

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 1.07 milli Ohms * * * *

3 B 0.98 milli Ohms * * * *

3 C 1.04 milli Ohms * * * *

Low Voltage

Winding

Manufacturer Serial Number Configuration Winding Temperature

Temperature Rise

Factory Resistance

(Ohms)

Factory Temperature

Δ-Y * * * *

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

H3 H1 H1 H2 H2 H3

DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

3 7 41.818 359.897 L 27.411 240.211 L 48.463 409.072 L Investigate

LSR mA: 41.818/41.818, 1/1 Watts: 359.897/359.897, 1/1 Cap (pF): */*, 1/1

LSR mA: 27.411/27.411, 1/1 Watts: 240.211/240.211, 1/1 Cap (pF): */*, 1/1

LSR mA: 48.463/48.463, 1/1 Watts: 409.072/409.072, 1/1 Cap (pF): */*, 1/1

4 - 5871049-C1

Delta Wye

Connections - - -

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual

3 12470 3 480 44.997 45.01 45.015 45.014 44.772 45.222 Good

FRANK™ Message 1 (Good) - Ratio is within expected values.

TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.

Exciting Current Plot

5 - 5871049-C1

BLDG 109-9B XFMR_930206-A1_X2

6/26/2021 9:59:38 AMSession Test Date

Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 930206-A1

Location 2002 Holcombe Blvd Houston, Texas 77030

Special ID BLDG 109-9B XFMR

Division Houston Circuit Designation BLDG 109-9B XFMR

Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1993 Tank Type Sealed

Mfr Location USA Coolant Oil

Phases Three Class OA

Oil Volume 300 UG BIL 95 kV

Weight 7300 LB kV 12.47, 0.48 VA Rating 1000, *, *, *, KVA

Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy

Air Temperature 30°C Apparatus Temperature

28°C Humidity 68 %

Tester Cory Llewellyn Work Order WO-08754081 Date Last Tested

Verified Test Set Type M4000 Date Retested

Verification Date 6/26/2021 Set Top Serial # Reason ROUTINE

Last Sheet # Set Bottom Serial # Travel Time

Purchase Order Ins. Book # Duration

1 - 5930206-A1

2 - 5930206-A1

H1 H1 * * * * * *

H2 H2 * * * * * *

H3 H3 * * * * * *

Overall Tests Insulation Test kV mA Watts % PF

Corr.

Corr Fctr Cap (pF) FRANK™ Manual

1 CH+CHL 10.004 17.876 0.537 0.289 0.962 4741.618

2 CH 10.003 5.141 0.188 0.352 0.962 1363.688 Good

3 CHL(UST) 10.003 12.728 0.357 0.270 0.962 3376.283 Good

4 CHL 0 12.735 0.349 0.263 0.962 3377.929

5 CL+CHL 1.000 33.384 1.019 0.294 0.962 8855.185

6 CL 1.000 20.671 0.674 0.314 0.962 5483.130 Good

7 CHL(UST) 1.000 12.718 0.361 0.273 0.962 3373.644

8 CHL 0 12.713 0.345 0.261 0.962 3372.056 Good

LSR mA: 17.876/17.876, 1/1 Watts: 0.537/0.537, 1/1 Cap (pF): 4741.618/4741.618, 1/1

LSR mA: 5.141/5.141, 1/1 Watts: 0.188/0.188, 1/1 Cap (pF): 1363.688/1363.688, 1/1

LSR mA: 12.728/12.728, 1/1 Watts: 0.357/0.357, 1/1 Cap (pF): 3376.283/3376.283, 1/1

LSR mA: 12.735/12.735, 1/1 Watts: 0.349/0.349, 1/1 Cap (pF): 3377.929/3377.929, 1/1

LSR mA: 33.384/33.384, 1/1 Watts: 1.019/1.019, 1/1 Cap (pF): 8855.185/8855.185, 1/1

LSR mA: 20.671/20.671, 1/1 Watts: 0.674/0.674, 1/1 Cap (pF): 5483.130/5483.130, 1/1

LSR mA: 12.718/12.718, 1/1 Watts: 0.361/0.361, 1/1 Cap (pF): 3373.644/3373.644, 1/1

LSR mA: 12.713/12.713, 1/1 Watts: 0.345/0.345, 1/1 Cap (pF): 3372.056/3372.056, 1/1

FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5

The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.

3 (Good) - All values are acceptable.

6 (Good) - All values are acceptable.

8 (Good) - All values are acceptable.

3 - 5930206-A1

Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 0.46 Ohms * * * *

3 B 0.47 * * * *

3 C 0.46 * * * *

High Voltage

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 0.95 milli Ohms * * * *

3 B 0.97 milli Ohms * * * *

3 C 0.96 milli Ohms * * * *

Low Voltage

Winding

Manufacturer Serial Number Configuration Winding Temperature

Temperature Rise

Factory Resistance

(Ohms)

Factory Temperature

Δ-Y * * * *

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

H3 H1 H1 H2 H2 H3

DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

3 7 50.487 452.650 L 35.685 289.053 L 54.953 467.438 L Good

LSR mA: 50.487/50.487, 1/1 Watts: 452.650/452.650, 1/1 Cap (pF): */*, 1/1

LSR mA: 35.685/35.685, 1/1 Watts: 289.053/289.053, 1/1 Cap (pF): */*, 1/1

LSR mA: 54.953/54.953, 1/1 Watts: 467.438/467.438, 1/1 Cap (pF): */*, 1/1

4 - 5930206-A1

Delta Wye

Connections - - -

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual

3 12470 3 480 44.997 45.018 45.021 45.024 44.772 45.222 Good

FRANK™ Message 1 (Good) - Ratio is within expected values.

TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.

Exciting Current Plot

5 - 5930206-A1

BLDG 110 XFMR_871049-D1_X2

6/26/2021 9:59:38 AMSession Test Date

Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 871049-D1

Location 2002 Holcombe Blvd Houston, Texas 77030

Special ID BLDG 110 XFMR

Division Houston Circuit Designation BLDG 110 XFMR

Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1989 Tank Type Sealed

Mfr Location USA Coolant Oil

Phases Three Class OA

Oil Volume 270 UG BIL 95 kV

Weight 5185 LB kV 12.47, 0.208 VA Rating 500, *, *, *, KVA

Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy

Air Temperature 30°C Apparatus Temperature

50°C Humidity 66 %

Tester C.Espartero Work Order Date Last Tested

Verified Test Set Type M4000 Date Retested

Verification Date Set Top Serial # Reason ROUTINE

Last Sheet # Set Bottom Serial # Travel Time

Purchase Order Ins. Book # Duration

Copies Sheet # Crew Size 1

1 - 5871049-D1

2 - 5871049-D1

H1 H1 * * * * * *

H2 H2 * * * * * *

H3 H3 * * * * * *

Overall Tests Insulation Test kV mA Watts % PF

Corr.

Corr Fctr Cap (pF) FRANK™ Manual

1 CH+CHL 10.005 13.333 0.785 0.303 0.514 3536.520

2 CH 10.004 4.360 0.233 0.274 0.514 1156.463 Good

3 CHL(UST) 10.004 8.971 0.541 0.310 0.514 2379.567 Good

4 CHL 0 8.973 0.552 0.316 0.514 2380.057

5 CL+CHL 0.201 26.293 1.412 0.276 0.514 6974.357

6 CL 0.200 17.312 0.846 0.251 0.514 4592.091 Good

7 CHL(UST) 0.200 8.977 0.551 0.316 0.514 2381.086

8 CHL 0 8.981 0.566 0.324 0.514 2382.266 Good

LSR mA: 13.333/13.333, 1/1 Watts: 0.785/0.785, 1/1 Cap (pF): 3536.520/3536.520, 1/1

LSR mA: 4.360/4.360, 1/1 Watts: 0.233/0.233, 1/1 Cap (pF): 1156.463/1156.463, 1/1

LSR mA: 8.971/8.971, 1/1 Watts: 0.541/0.541, 1/1 Cap (pF): 2379.567/2379.567, 1/1

LSR mA: 8.973/8.973, 1/1 Watts: 0.552/0.552, 1/1 Cap (pF): 2380.057/2380.057, 1/1

LSR mA: 26.293/26.293, 1/1 Watts: 1.412/1.412, 1/1 Cap (pF): 6974.357/6974.357, 1/1

LSR mA: 17.312/17.312, 1/1 Watts: 0.846/0.846, 1/1 Cap (pF): 4592.091/4592.091, 1/1

LSR mA: 8.977/8.977, 1/1 Watts: 0.551/0.551, 1/1 Cap (pF): 2381.086/2381.086, 1/1

LSR mA: 8.981/8.981, 1/1 Watts: 0.566/0.566, 1/1 Cap (pF): 2382.266/2382.266, 1/1

FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5

The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.

3 (Good) - All values are acceptable.

6 (Good) - All values are acceptable.

8 (Good) - All values are acceptable.

3 - 5871049-D1

Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 3.63 Ohms * * * *

3 B 3.65 Ohms * * * *

3 C 3.65 Ohms * * * *

High Voltage

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 0.52 milli Ohms * * * *

3 B 0.49 milli Ohms * * * *

3 C 0.85 milli Ohms * * * *

Low Voltage

Winding

Manufacturer Serial Number Configuration Winding Temperature

Temperature Rise

Factory Resistance

(Ohms)

Factory Temperature

Δ-Y * * * *

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

H3 H1 H1 H2 H2 H3

DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

3 7 27.346 232.296 L 16.605 147.472 L 29.534 241.767 L Good

LSR mA: 27.346/27.346, 1/1 Watts: 232.296/232.296, 1/1 Cap (pF): */*, 1/1

LSR mA: 16.605/16.605, 1/1 Watts: 147.472/147.472, 1/1 Cap (pF): */*, 1/1

LSR mA: 29.534/29.534, 1/1 Watts: 241.767/241.767, 1/1 Cap (pF): */*, 1/1

4 - 5871049-D1

Delta Wye

Connections H3 - H1 H1 - H2 H2 - H3

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual

3 12470 3 208 103.840 103.83 103.84 103.83 103.321 104.359 Good

FRANK™ Message 1 (Good) - Ratio is within expected values.

TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.

Exciting Current Plot

5 - 5871049-D1

PARKING GARAGE_17V11579_X2

6/26/2021 9:59:38 AMSession Test Date

Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 17V11579

Location 2002 Holcombe Blvd Houston, Texas 77030

Special ID PARKING GARAGE XFMR

Division Houston Circuit Designation PARKING GARAGE

Manufacturer Vantran Configuration Δ-Y Year Manufactured 2017 Tank Type Sealed

Mfr Location USA Coolant Oil

Phases Three Class OA

Oil Volume 149 UG BIL 95 kV

Weight 4082 LB kV 12.47, 0.48 VA Rating 750, *, *, *, KVA

Administration Test Date 6/26/2021 Test Time: 9:59 AM Weather Partly Cloudy

Air Temperature 27.8°C Apparatus Temperature

40°C Humidity 76 %

Tester C.Espartero Work Order Date Last Tested

Verified Test Set Type M4000 Date Retested

Verification Date Set Top Serial # Reason ROUTINE

Last Sheet # Set Bottom Serial # Travel Time

Purchase Order Ins. Book # Duration

1 - 617V11579

2 - 617V11579

H1 H1 * * * * * *

H2 H2 * * * * * *

H3 H3 * * * * * *

Overall Tests Insulation Test kV mA Watts % PF

Corr.

Corr Fctr Cap (pF) FRANK™ Manual

1 CH+CHL 10.005 18.317 1.095 0.531 0.889 4858.669

2 CH 10.022 4.963 0.736 1.319 0.889 1316.435 Deteriorated

3 CHL(UST) 10.004 13.360 0.366 0.244 0.889 3543.864 Good

4 CHL 0 13.354 0.358 0.239 0.889 3542.234

5 CL+CHL 1.000 23.046 1.627 0.628 0.889 6113.004

6 CL 1.001 9.691 1.281 1.176 0.889 2570.302 Deteriorated

7 CHL(UST) 1.001 13.380 0.386 0.256 0.889 3549.148

8 CHL 0 13.355 0.345 0.230 0.889 3542.701 Good

LSR mA: 18.317/18.317, 1/1 Watts: 1.095/1.095, 1/1 Cap (pF): 4858.669/4858.669, 1/1

LSR mA: 4.963/4.963, 1/1 Watts: 0.736/0.736, 1/1 Cap (pF): 1316.435/1316.435, 1/1

LSR mA: 13.360/13.360, 1/1 Watts: 0.366/0.366, 1/1 Cap (pF): 3543.864/3543.864, 1/1

LSR mA: 13.354/13.354, 1/1 Watts: 0.358/0.358, 1/1 Cap (pF): 3542.234/3542.234, 1/1

LSR mA: 23.046/23.046, 1/1 Watts: 1.627/1.627, 1/1 Cap (pF): 6113.004/6113.004, 1/1

LSR mA: 9.691/9.691, 1/1 Watts: 1.281/1.281, 1/1 Cap (pF): 2570.302/2570.302, 1/1

LSR mA: 13.380/13.380, 1/1 Watts: 0.386/0.386, 1/1 Cap (pF): 3549.148/3549.148, 1/1

LSR mA: 13.355/13.355, 1/1 Watts: 0.345/0.345, 1/1 Cap (pF): 3542.701/3542.701, 1/1

FRANK™ Message 2 (Deteriorated) - The winding insulation power factor is higher than expected for this type of transformer. This may reflect a low level contamination. Advise your supervisor.

For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5

The humidity is high, equal to or more than 70%. This may cause the watts and power factor to be higher than usual on your tests. If you compare sets of duplicate apparatus (arresters, bushings, live tank breakers) and one alone shows a high power factor, consider it suspect. but if all three duplicates all have high power factors, it may be due to the factor common to them all, the high humidity. Clean and dry, using heat if necessary, for better results.

3 (Good) - All values are acceptable.

6 (Deteriorated) - The winding insulation power factor is higher than expected for this type of transformer. This may reflect a low level contamination. Advise your supervisor.

8 (Good) - All values are acceptable.

3 - 617V11579

Insulation Resistance

Connections Volts T1 (Mohms) T2 (Mohms) PI

Hi to Lo/Earth * * * *

Hi to Earth Guard Lo 5000.00 3500.00 5200.00 1.49

Lo to Hi/Earth * * * *

Lo to Earth Guard Hi 1000.00 2210.00 3340.00 1.51

Hi to Lo Guard Earth 5000.00 3700.00 6200.00 1.68

Core to Earth * * * *

Core Ground Test

Manufacturer

Serial #

Winding Resistance

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 1.292 Ohms * * * *

3 B 1.278 Ohms * * * *

3 C 1.295 Ohms * * * *

High Voltage

DETC LTC Phase Resistance Units Calculated Resistance

Correction Factor

Corrected Resistance

Percentage Deviation

3 A 0.97 milli Ohms * * * *

3 B 0.91 milli Ohms * * * *

3 C 0.878 milli Ohms * * * *

Low Voltage

Winding

Manufacturer Serial Number Configuration Winding Temperature

Temperature Rise

Factory Resistance

(Ohms)

Factory Temperature

Δ-Y * * * *

4 - 617V11579

Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 3 3 *

H1 H3 H1 H2 H2 H3

DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

3 7 29.703 242.891 L 15.676 136.397 L 28.235 241.100 L Good

LSR mA: 29.703/29.703, 1/1 Watts: 242.891/242.891, 1/1 Cap (pF): */*, 1/1

LSR mA: 15.676/15.676, 1/1 Watts: 136.397/136.397, 1/1 Cap (pF): */*, 1/1

LSR mA: 28.235/28.235, 1/1 Watts: 241.100/241.100, 1/1 Cap (pF): */*, 1/1

Turns Ratio Tests Serial Number HV Winding LV Winding

Delta Wye

Connections H3 - H1 H1 - H2 H2 - H3

Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual

3 12470 3 480 44.997 44.964 44.966 44.667 44.772 45.222 Good

FRANK™ Message 1 (Good) - Ratio is within expected values.

TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.

5 - 617V11579

Exciting Current Plot

6 - 617V11579

ZONE INTLK

BREAKER TYPE

TRIP UNIT TYPE

N/A

BKR INT. RATING

MOUNTING

LOW VOLTAGE POWER CIRCUIT BREAKER

TEMPERATURE 75 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

109DESIGNATION

SUBSTATION BUILDING 109

6/26/2021 55

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

MSB FDR

Cuong Ho

VA Hospital WO-08391081

1600 AMP

N/A

N/A N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

ONPE

100KA

MANUFACTURER

FUSE MFR.

BKR CATALOG NO. PEF361600LSIG

N/AFUSE CAT. NO.

1600 AMP Off

B.I.

THERMAL MEMORY

SENSOR TAPS

FRAME SIZE

MAIN / ARCING CONTACTS

BATTERY STATUS

PRIMARY DISCONNECTS

CELL AND RACKING DEV.

CLEAN/LUBE Description CLEAN/LUBECONDITION

N/A

N/A

Acceptable

N/A

N/A

ARC CHUTES

SECONDARY DISCONNECT

CONDITIONDescription CLEAN/LUBE

N/AAcceptable

Description

N/A

N/A

AcceptableOPERATING MECHANISM N/A

PHASE BARRIERS Acceptable N/A

N/AAUXILIARY DEVICES

BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

N/A

Acceptable

N/A

BREAKER NAMEPLATE

INSPECTION

TARGETS

03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

D.O.

N/A

N/A

N/A

MFR. DATE / CODE N/A

SN / SO NO.Square D micrologic series b N/A

COUNTER READING AL N/A

FUSE AMPS N/A

COUNTER READING AF

RANGE

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

CONTACT RESISTANCE - MICRO-OHMS

POLE 1

FUSE 2FUSE 1 FUSE 3

N/A N/A N/A

POLE 3POLE 2

4.5

2.5

.2

2.5 5 2.5

.2

.1

.2IN

4.5

2.5

.2

LONG TIME DELAY

SHORT TIME PICKUP

SHORT TIME DELAY

INSTANTANEOUS PICKUP

GROUND FAULT PICKUP

GROUND FAULT DELAY

LONG TIME PICKUP

AS FOUND

SETTING

AS TESTED

SETTING

AS LEFT

SETTING I2T ON

AS TESTED

SETTING

AS LEFT

SETTING I*2 T ON

AS FOUND

SETTING

CT / SENSOR TAP: 1600RATING PLUG:1600 1600

Overcurrent Settings

CT / SENSOR RATINGS:

.1 .2

.35.2

AS FOUND

RANGE

MINIMUM MAXIMUM

1.037

.162

7,200 1 1.5

POLE 3

AS FOUNDAS FOUND AS LEFT AS LEFT

NT NT NT

CURRENT

MULTIPLE

TEST

AMPERES

sec 8.5 sec

LONG TIME PICKUP

LONG TIME DELAY

MILLIVOLT DROP

4,800

7.444

SHORT TIME PICKUP

SHORT TIME DELAY 4.5

INSTANTANEOUS PICKUP

INSTANTANEOUS DELAY

GROUND FAULT PICKUP

GROUND FAULT DELAY 1

sec sec sec sec sec sec

AS LEFT

1,440 A A1,760

A A

AA

A A

5,760 7,040

8,8007,200

504 616

POLE 1

FUNCTION

POLE 2TEST RESULTS BY SECONDARY INJECTION

TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker

COMMENTS: all tested funtions passed

DEFICIENCIES:

SE SWITCHBOARD / SWITCHGEAR INSPECTION

TEMPERATURE 75 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

109DESIGNATION

SUBSTATION BUILDING 109

6/26/2021 55

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

480 VOLT SWITCHGEAR

Cuong Ho

VA Hospital WO-08391081

480/277

100 KA

MANUFACTURER

1600 AMP

BUS CONNECTIONS

EXTERIOR CONDITION

CLEAN/LUBE CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

Acceptable

N/A

CONDITION

N/A

Description

N/A

N/A

INDICATORS / LAMPS

N/A

MATCHES DWG OR SPEC N/A

FUNCTIONAL CHECKS

BUS INSULATION Acceptable N/A N/A

KEY / MECH. INTERLOCKS

Performed

PLC's / HMI's N/A

CONDITION

Acceptable

Acceptable

N/A

Acceptable

Acceptable

NAMEPLATE

21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us

WITHSTAND RATING

TYPE / STYLECURRENT RATING QED

SN / SO NO. SYSTEM VOLTAGE

MODEL / CATALOG

N/A

08000-75S

INSPECTION

Acceptable

PT'S AND CT'S

N/A N/A AcceptablePOWER CABLES

N/A N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS

Acceptable N/ADOORS / COVERS / GASKETS

CPT AND CPT XFER CKT. ANCHORAGE

GROUNDING

PHASING CHECK

CONTROL WIRING

SPACE HEATERS

Description

N/A

N/AINTERIOR SECTIONS / CUBICLES

N/A

PHASE BARRIERS

SEQUENCE OF OPERATION

Description

N/A

N/A

N/A

N/A

N/A

Square D

RANGE

BARRIERS / SHUTTERS

SEC1

SEC 2

SEC 3

SEC 4

SEC 3

SEC 4

SEC 5

SEC 2

NBAFROM TO

BUS SECTION TESTED RESISTANCE IN MICRO-OHMS

C

RESISTANCE IN MICRO-OHMS

G

N

BUSWORK CONNECTION RESISTANCE

CBAFROM TO

BUS SECTION TESTED

G

TECH NOTE(S):

COMMENTS: All results are satisfactory at this time.

TRIP UNIT TYPE

N/A

BKR INT. RATING

MOUNTING

LOW VOLTAGE POWER CIRCUIT BREAKER

TEMPERATURE 75 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

109DESIGNATION

SUBSTATION BUILDING 109

6/26/2021 55

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

MSA FDR

Cuong Ho

VA Hospital WO-08391081

1600 AMP

N/A

N/A N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

ONPE

100KA

MANUFACTURER

FUSE MFR.

BKR CATALOG NO. PEF361600LSIG

N/AFUSE CAT. NO.

1600 AMP Off

B.I.

THERMAL MEMORY

SENSOR TAPS

FRAME SIZE

MAIN / ARCING CONTACTS

BATTERY STATUS

PRIMARY DISCONNECTS

CELL AND RACKING DEV.

CLEAN/LUBE Description CLEAN/LUBECONDITION

N/A

N/A

Acceptable

N/A

N/A

ARC CHUTES

SECONDARY DISCONNECT

CONDITIONDescription CLEAN/LUBE

N/AAcceptable

Description

N/A

N/A

AcceptableOPERATING MECHANISM N/A

PHASE BARRIERS Acceptable N/A

N/AAUXILIARY DEVICES

BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

N/A

Acceptable

N/A

BREAKER NAMEPLATE

INSPECTION

TARGETS

03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

D.O.

N/A

N/A

N/A

N/AMFR. DATE / CODE N/A

SN / SO NO.Square D micrologic series b N/A

COUNTER READING AL N/A

FUSE AMPS N/A

COUNTER READING AF

RANGE

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

CONTACT RESISTANCE - MICRO-OHMS

POLE 1

FUSE 2FUSE 1 FUSE 3

N/A N/A N/A

POLE 3POLE 2

4.5

2.5

.2

2.5 5 2.5

.25

.1

.2

.2IN

4.5

2.5

.2

LONG TIME DELAY

SHORT TIME PICKUP

SHORT TIME DELAY

INSTANTANEOUS PICKUP

GROUND FAULT PICKUP

GROUND FAULT DELAY

LONG TIME PICKUP

AS FOUND

SETTING

AS TESTED

SETTING

AS LEFT

SETTING I2T ON

AS TESTED

SETTING

AS LEFT

SETTING I*2 T ON

AS FOUND

SETTING

CT / SENSOR TAP: 1600RATING PLUG:1600 1600

Overcurrent Settings

CT / SENSOR RATINGS:

.1 .2

.35.25

AS FOUND

RANGE

MINIMUM MAXIMUM

1.046

.162

7,200 1 1.5

POLE 3

AS FOUNDAS FOUND AS LEFT AS LEFT

NT NT NT

CURRENT

MULTIPLE

TEST

AMPERES

sec 8.5 sec

LONG TIME PICKUP

LONG TIME DELAY

MILLIVOLT DROP

4,800

7.509

SHORT TIME PICKUP

SHORT TIME DELAY 4.5

INSTANTANEOUS PICKUP

INSTANTANEOUS DELAY

GROUND FAULT PICKUP

GROUND FAULT DELAY 1

sec sec sec sec sec sec

AS LEFT

1,440 A A1,760

A A

AA

A A

5,760 7,040

8,8007,200

504 616

POLE 1

FUNCTION

POLE 2TEST RESULTS BY SECONDARY INJECTION

TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker

COMMENTS: all tested funtions passed

TRIP UNIT TYPE

N/A

BKR INT. RATING

MOUNTING

LOW VOLTAGE POWER CIRCUIT BREAKER

TEMPERATURE 73 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

109DESIGNATION

SUBSTATION BUILDING 109

6/26/2021 55

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

TIE

Cuong Ho

VA Hospital WO-08391081

1600 AMP

Cleaned

N/A Cleaned

MATCHES DWG OR SPEC

GROUND CONNECTION

ONPE

100KA

MANUFACTURER

FUSE MFR.

BKR CATALOG NO. PEF361600SLIG

N/AFUSE CAT. NO.

1600 AMP Off

B.I.

THERMAL MEMORY

SENSOR TAPS

FRAME SIZE

MAIN / ARCING CONTACTS

BATTERY STATUS

PRIMARY DISCONNECTS

CELL AND RACKING DEV.

CLEAN/LUBE Description CLEAN/LUBECONDITION

N/A

N/A

N/A

N/A

N/A

ARC CHUTES

SECONDARY DISCONNECT

CONDITIONDescription CLEAN/LUBE

N/AAcceptable

Description

N/A

N/A

AcceptableOPERATING MECHANISM Cleaned

PHASE BARRIERS Acceptable N/A

N/AAUXILIARY DEVICES

BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

N/A

Acceptable

N/A

BREAKER NAMEPLATE

INSPECTION

TARGETS

03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

D.O.

N/A

N/A

N/A

MFR. DATE / CODE N/A

SN / SO NO.Square D

Micrologic Series B N/A

COUNTER READING AL N/A

FUSE AMPS N/A

COUNTER READING AF

RANGE

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

CONTACT RESISTANCE - MICRO-OHMS

POLE 1

FUSE 2FUSE 1 FUSE 3

N/A N/A N/A

POLE 3POLE 2

.2

2.5 5 2.5

.2

.1

.2IN

.2

LONG TIME DELAY

SHORT TIME PICKUP

SHORT TIME DELAY

INSTANTANEOUS PICKUP

GROUND FAULT PICKUP

GROUND FAULT DELAY

LONG TIME PICKUP

AS FOUND

SETTING

AS TESTED

SETTING

AS LEFT

SETTING I2T ON

AS TESTED

SETTING

AS LEFT

SETTING I*2 T ON

AS FOUND

SETTING

CT / SENSOR TAP: RATING PLUG:1600 1600

Overcurrent Settings

CT / SENSOR RATINGS:

.1 .2

.35.2

AS FOUND

RANGE

MINIMUM MAXIMUM

1.036

.161

7,200 1 1.5

POLE 3

AS FOUNDAS FOUND AS LEFT AS LEFT

NT NT NT

CURRENT

MULTIPLE

TEST

AMPERES

sec 8.5 sec

LONG TIME PICKUP

LONG TIME DELAY

MILLIVOLT DROP

4,800

7.379

SHORT TIME PICKUP

SHORT TIME DELAY 4.5

INSTANTANEOUS PICKUP

INSTANTANEOUS DELAY

GROUND FAULT PICKUP

GROUND FAULT DELAY 1

sec sec sec sec sec sec

AS LEFT

1,440 A A1,760

A A

AA

A A

5,760 7,040

8,8007,200

504 616

POLE 1

FUNCTION

POLE 2TEST RESULTS BY SECONDARY INJECTION

TECH NOTE(S): Insulation resistance test was not performed due cable connected on the breaker

COMMENTS: All results are satisfactory at this time.