Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
CHP Bldg. Substation PM
June 9, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on CHP Bldg. Substation located at VA Bldg. 102
Power Plant 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
15KV Switchgear 102A-MVPS
Cubicle D9 MVATS-A1 Breaker MULTILIN 350 protection relay did not have any of the protection elements turned on. This relay did not have a test sticker and could have been a unit that was replaced and never had the settings loaded into it. After discussing with the customer, the customer then decides to copy the settings from one of the MVATS breaker protection relays and load the same settings to MVATS-A1 breaker MULTILIN 350 protection relay.
15KV Switchgear 102A-MVPS
Several cubicle breaker position indicators hung up when breaker is racked out. The position indicator was then cleaned and lubed and was exercised multiple times to ensure the breaker position indicator was functioning properly.
3 | P a g e
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 76 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 58
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
21001 - SE Switchboard / Switchgear Inspection
Cuong Ho, Chris Espartero
VA Hospital WO-08391081
12.47KVMANUFACTURER
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
N/A
CONDITION
N/A
Description
N/A
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC Acceptable
FUNCTIONAL CHECKS
BUS INSULATION Acceptable N/A N/A
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
37412-P-MVPS
INSPECTION
N/A
PT'S AND CT'S
Acceptable N/A AcceptablePOWER CABLES
Acceptable N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS
Acceptable N/ADOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
N/AINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
N/A
N/A
N/A
RUSSEL ELECTRIC
RANGE
BARRIERS / SHUTTERS
VOLTAGE (kV)
N/AMeg-OhmsMicro-Amps
387.7698
345.45
316.67
B to Ground
C to Ground
A to Ground
N to Ground
(Note: All phases not under test are grounded)
A / C
DIELECTRIC WITHSTAND TEST
D / C
@1000VMEG-OHMS 20°C
39.0 47.6
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
59.849.0
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
42.0
48.0
44.0
48.0
53.7
51.2
58.6 58.6TEST 3
N-GNDTEST 4
1.22TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
TIE
TIE D1
D13
118 108
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
DEFICIENCIES:
EQUIPMENT TEMPERATURE
NO.
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D1 GENERATOR #1
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.01
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
1 2
0.14
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
1,097,660
55,600.0 789,520.0
24,300.0 345,060.0
99,800.0 1,417,160
101,300.0 1,438,460
65,100.0 924,420.0
99.991
99.992
0.01
0.01
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
77,300.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
MEDIUM VOLTAGE VACUUM CIRCUIT BREAKER
TEMPERATURE 70 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/20/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D1 GENERATOR #1
SUB-ELEMENT
DEVICE
EQUIPMENT USED
03058 - SE MV VACUUM CKT. BKR.
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83571
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 403
COUNTER READING AF 401
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
718.0 757.5
513.0 541.2
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
750.1711.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
587.0
555.0
608.0
501.0
685.0
642.0641.4
619.3
677.3
585.5 528.6
722.7
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
1.8
N/AMEG-OHMSMICRO-AMPSCLOSED
380010
19000
21111.11
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
COMMENTS: BREAKER TEST SASTISFACTORY READY FOR SERVICE
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/20/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D10
SUB-ELEMENT
DEVICE
EQUIPMENT USED
SPARE TOP
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83575
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 117
COUNTER READING AF 115
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
1,670.0 1,761.8
1,650.0 1,740.8
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
2,131.12,020.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
1,850.0
1,890.0
1,980.0
1,900.0
1,450.0
1,520.02,088.9
1,951.7
1,603.6
1,993.9 2,004.5
1,529.8
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
2.3
1.6
N/AMEG-OHMSMICRO-AMPSCLOSED
47508
16521.74
23750
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/08/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D10
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-RA
CUONG HO,JAVIER ROJAS
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83565
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 103
COUNTER READING AF 101
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
172.0 181.5
215.0 226.8
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
234.2222.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
235.0
193.0
211.0
172.0
215.0
211.0222.6
247.9
222.6
203.6 181.5
226.8
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
1.1
2.5
N/AMEG-OHMSMICRO-AMPSCLOSED
34545.451.1
34545.45
15200
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D11 GENERATOR #5
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.111
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
7600747
1 2
0.110
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
2,409,740
110,100.0 1,563,420
98,700.0 1,401,540
135,400.0 1,922,680
156,700.0 2,225,140
99,300.0 1,410,060
99.998
99.997
0.00
0.00
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
7600748
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
169,700.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/20/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D11 GENERATOR #5
SUB-ELEMENT
DEVICE
EQUIPMENT USED
GENERATOR #5
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KA
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83564
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 316
COUNTER READING AF 313
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable Cleaned N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Cleaned
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
800.0 844.0
753.0 794.4
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
1,276.61,210.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
1,020.0
1,460.0
651.0
724.0
725.0
1,256.0686.8
1,076.1
1,325.1
1,540.3 763.8
764.9
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
1.3
N/AMEG-OHMSMICRO-AMPSCLOSED
27142.861.4
29230.77
38000
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/21/2021 52
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D12 GENERATOR #4
SUB-ELEMENT
DEVICE
EQUIPMENT USED
GENERATOR #4
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 63570
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 349
COUNTER READING AF 347
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
3,000.0 3,420.0
2,450.0 2,793.0
TEST 1
TEST 3
1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
3,420.03,000.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
3,000.0
2,460.0
2,290.0
2,100.0
3,000.0
3,000.02,610.6
3,420.0
3,420.0
2,804.4 2,394.0
3,420.0
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
3.4
7.2
N/AMEG-OHMSMICRO-AMPSCLOSED
6551.725.8
11176.47
5277.78
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D12 GENERATOR #4
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.01
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
7600752
1 2
0.14
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
2,431,040
105,900.0 1,503,780
89,060.0 1,264,652
78,900.0 1,120,380
66,100.0 938,620.0
24,000.0 340,800.0
99.991
99.997
0.00
0.01
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
7600754
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
171,200.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/21/2021 52
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D13 GENERATOR #3
SUB-ELEMENT
DEVICE
EQUIPMENT USED
03058 - SE MV VACUUM CKT. BKR.
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83574
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 355
COUNTER READING AF 353
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
2,670.0 3,043.8
2,670.0 3,043.8
TEST 1
TEST 3
1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
3,420.03,000.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
3,000.0
2,630.0
3,000.0
3,000.0
3,000.0
1,670.03,420.0
3,420.0
1,903.8
2,998.2 3,420.0
3,420.0
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
2.2
1.2
N/AMEG-OHMSMICRO-AMPSCLOSED
6551.725.8
17272.73
31666.67
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D13 GENERATOR #3
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.01
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
7600752
1 2
0.14
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
2,431,040
105,900.0 1,503,780
89,060.0 1,264,652
78,900.0 1,120,380
66,100.0 938,620.0
24,000.0 340,800.0
99.991
99.997
0.00
0.01
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
7600754
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
171,200.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/20/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D2 GENERATOR #2
SUB-ELEMENT
DEVICE
EQUIPMENT USED
03058 - SE MV VACUUM CKT. BKR.
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83562
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 379
COUNTER READING AF 377
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable Cleaned N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Torqued
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
1,240.0 1,308.2
1,660.0 1,751.3
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
2,036.11,930.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
2,300.0
1,940.0
1,560.0
1,710.0
1,620.0
1,270.01,645.8
2,426.5
1,339.8
2,046.7 1,804.1
1,709.1
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
1.4
N/AMEG-OHMSMICRO-AMPSCLOSED
76005
27142.86
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D2 GENERATOR #2
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.01
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
1 2
0.14
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
826,440.0
24,600.0 349,320.0
13,300.0 188,860.0
55,800.0 792,360.0
44,200.0 627,640.0
21,600.0 306,720.0
99.971
99.983
0.02
0.03
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
58,200.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/20/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D3 GENERATOR #6
SUB-ELEMENT
DEVICE
EQUIPMENT USED
03058 - SE MV VACUUM CKT. BKR.
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KA
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83569
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 323
COUNTER READING AF 320
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
C & L N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable Cleaned N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Cleaned
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
890.0 938.9
753.0 794.4
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
809.2767.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
903.0
851.0
741.0
724.0
971.0
959.0781.8
952.7
1,011.7
897.8 763.8
1,024.4
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
2.2
1.7
N/AMEG-OHMSMICRO-AMPSCLOSED
25333.331.5
17272.73
22352.94
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
NO.
SIZE
SIZE
CLASS
NAMEPLATE RATIO
TYPE
TYPE
kVA
TYPE
SECONDARY VOLTAGE
MANUFACTURER
MANUFACTURER
Other
PRIMARY VOLTAGE
MANUFACTURER
Christopher EsparteroTESTED BY:
27200, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
TEST EQUIPMENT USED:
VOLTAGE TRANSFORMER TEST
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/8/2021 72
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D3 GENERATOR #6
SUB-ELEMENT
DEVICE
EQUIPMENT USED
27200 - VOLTAGE TRANSFORMER TEST
Christopher Espartero
VA Hospital WO-08391081
JVM-5
1.5
°C
CONNECTIONS H H x x 1
20°C
1 2
0.01
Error %
CONNECTIONS H H x x
20°C
CONNECTIONS H H x x
20°C
1 2
0.14
2.5
2.5
1 2
VT CONNECTION: 1 PHASE 3 PHASE
77 14.2
1,394,440
87,600.0 1,243,920
50,700.0 719,940.0
82,600.0 1,172,920
77,200.0 1,096,240
38,100.0 541,020.0
99.998
99.994
0.01
0.00
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
PRIMARY FUSE:
PRIMARY: SECONDARY:
NAMEPLATE DATA
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
CALCULATED TURNS RATIO
MEASURED TURNS RATIO
POLARITY
POLARITY
POLARITY
100 1
12,000
DELTAWYEDELTAWYE
Error kVDC kVDC
MEGOHMS
MEGOHMS
MEGOHMS
RDG.
SERIAL NUMBER:
@ 1 kVDC kVDC kVDC
RDG.
MEGOHMS
MEGOHMS
MEGOHMS
INSULATION TEST
INSULATION TEST
INSULATION TEST
SERIAL NUMBER:
MEGOHMS
MEGOHMS
RDG.
kVDC kVDC kVDC
SERIAL NUMBER:VT IDENTIFICATION:
VT IDENTIFICATION:
TURNS RATIO TEST
Error
TURNS RATIO TEST
TURNS RATIO TEST
VT IDENTIFICATION:
SECONDARY FUSE:
2.5
2.5 kVDC
MEGOHMSPRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
PRI - SEC
PRI - GRD
SEC - GRD
98,200.0
765X021029CATALOG NO.General Electric
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D4
SUB-ELEMENT
DEVICE
EQUIPMENT USED
SPARE TOP
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
1783568
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 67
COUNTER READING AF 64
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
Acceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Deficiency N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
48 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
346.0 365.0
522.0 550.7
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
622.4590.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
619.0
1,650.0
639.0
536.0
539.0
738.0674.1
653.0
778.6
1,740.8 565.5
568.6
N / A PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
7.5
N/AMEG-OHMSMICRO-AMPSCLOSED
8444.444.5
5066.67
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D4
SUB-ELEMENT
DEVICE
EQUIPMENT USED
SPARE BOTTOM
Cuong Ho
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83573
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 102
COUNTER READING AF 100
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
1,080.0 1,139.4
703.0 741.7
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
898.9852.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
826.0
520.0
612.0
660.0
449.0548.6
871.4
473.7
1,740.8 645.7
696.3
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
2.6
N/AMEG-OHMSMICRO-AMPSCLOSED
76005
14615.38
12666.67
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D5
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-B2
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83577
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 67
COUNTER READING AF 64
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
138.0 145.6
123.0 129.8
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
148.8141.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
142.0
121.0
139.0
128.0
116.0
162.0146.6
149.8
170.9
127.7 135.0
122.4
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
3.4
1.6
N/AMEG-OHMSMICRO-AMPSCLOSED
21111.111.8
11176.47
23750
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D5
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-B1
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83578
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 77
COUNTER READING AF 74
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
163.0 172.0
168.0 177.2
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
278.5264.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
203.0
256.0
255.0
271.0
260.0
323.0269.0
214.2
340.8
270.1 285.9
274.3
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
1.8
1.4
N/AMEG-OHMSMICRO-AMPSCLOSED
237501.6
21111.11
27142.86
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D6
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-RB
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83563
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 98
COUNTER READING AF 95
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
277.0 292.2
372.0 392.5
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
1,424.31,350.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
520.0
1,260.0
173.0
450.0
257.0
477.0182.5
548.6
503.2
1,329.3 474.8
271.1
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
2.5
N/AMEG-OHMSMICRO-AMPSCLOSED
25333.331.5
15200
19000
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
4/19/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D8
SUB-ELEMENT
DEVICE
EQUIPMENT USED
TIE BREAKER
JONATHAN DERDARI
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83567
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 135
COUNTER READING AF 133
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
Schneider Electric
N/ARANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
192.0 202.6
195.0 205.7
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
285.9271.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
270.0
214.0
255.0
165.0
182.0
233.0269.0
284.8
245.8
225.8 174.1
192.0
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
N/AMEG-OHMSMICRO-AMPSCLOSED
4222.229
4222.22
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/08/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D9
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-A2
CUONG HO,JAVIER ROJAS
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83572
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 71
COUNTER READING AF 69
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Cleaned
ANTI-PUMP
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
AcceptableOPERATING MECHANISM C & L
PHASE BARRIERS N/A N/A
C & LAUXILIARY DEVICES
PUSH / PULL ROD ADJ. Acceptable N/A N/AINTERLOCKS Acceptable C & LINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
INSPECTION
N/A
N/A
Schneider Electric
RANGE
INSULATION RESISTANCE IN:
MEG-OHMS @1000V
ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
125 VDC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
125 VDC
N/A
N/A
125 VDC VoltsVolts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
OPTIONAL
VOLT RANGE
INFORMATIONTRIP COIL INFORMATION
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@5000VGIG-OHMS 20°C
185.0 195.2
201.0 212.1
TEST 1
TEST 3
1.055TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
193.1183.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
233.0
236.0
174.0
204.0
208.0
125.0183.6
245.8
131.9
249.0 215.2
219.4
PASS PASS
POLE 1
PASS
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
DIELECTRIC WITHSTAND TEST
A / C
N/AMEG-OHMSMICRO-AMPSCLOSED
380010
4222.22
B to C, A & GND
C to A, B & GND
A to B, C & GND
D / C
DIELECTRIC WITHSTAND TEST
(Note: All specimens not under test are grounded)
VOLTAGE (kV)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
15KV SWGR 102A-MVPSDESIGNATION
SUBSTATION POWER PLANT BUILDING
6/08/2021 56
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT CUBICLE D9
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MVATS-A1
CUONG HO,JAVIER ROJAS
3228,2701,3230
VA Hospital WO-08391081
25KV
BREAKER NAMEPLATE
MANUFACTURER
INT. RATING
17 83565
V5D6133YJOO
1/15
SN / SO NO.
RATED VOLTAGE MAX. VOLTAGE 15
VR
RATED INT. TIME 3 CYCLE
K FACTOR
N/A
12.47KV
1200RATED CURRENT
TYPE / STYLE
BIL RATING
D.O.
FREQUENCY
MOUNTING
MANUF. DATE
CATALOG NO.
COUNTER READING AL 75
COUNTER READING AF 73
N/A
B.I.
03058, REVISED 9/17/2020(888) 778-2733 www.schneider-electric.us
Cleaned
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTIONCONTACT EROSION
CONTACT WIPE
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Accepta…