Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
Bldg. 104A
May 13, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on Bldg. 104A Substation located at VA Cooling
Tower 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
Chiller 8 Starting Contactor
Chiller 8 Starting contactor umbilical cord male plug connector was frozen and secondary control wiring needed to be disconnected at the terminal block to be able to pull the contactor out of the cubicle. Medium Voltage contactor umbilical cord male plug is also missing a protective covering and needed to be replaced.
3 | P a g e
MCC 6
We are not able to test 480V MCC 6 main bus due to a potential back feed from the ATS to the last section of MCC 6 gear.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
PT-14_010584-VA1_X2
TwoWindingTransformerReport Source
5/13/2021 1:46:08 PMSession Test Date
Nameplate - Two-winding Transformer Company VA Medical Center Serial Number 010584-VA1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID PT-14 XFMR
Division Houston Circuit Designation BLDG 104-A PT-14
Manufacturer Square D Electric Configuration Δ-Y Year Manufactured 1988 Tank Type Sealed
Mfr Location USA Coolant Oil
Phases Three Class ONAN
Oil Volume 309 UG BIL 95 kV
Weight 7078 LB kV 4.16, 0.48 VA Rating 750, *, *, *, KVA
Administration Test Date 5/13/2021 Test Time: 1:46 PM Weather Partly Cloudy
Air Temperature 27.8°C Apparatus Temperature
35°C Humidity 56 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 5/13/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 1
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
1 - 4010584-VA1
Overall Tests Insulation Test kV mA Watts % PF
Corr.
Corr Fctr Cap (pF) FRANK™ Manual
1 CH+CHL 1.999 40.492 2.146 0.489 0.923 10740.30
2 CH 2.000 5.150 0.142 0.255 0.923 1366.078 Good
3 CHL(UST) 2.000 35.318 2.009 0.525 0.923 9368.289 Good
4 CHL 0 35.342 2.004 0.523 0.923 9374.227
5 CL+CHL 1.000 53.810 2.588 0.444 0.923 14273.20
6 CL 1.000 18.494 0.601 0.300 0.923 4905.680 Good
7 CHL(UST) 1.000 35.321 2.026 0.529 0.923 9368.875
8 CHL 0 35.316 1.987 0.519 0.923 9367.524 Good
LSR mA: 40.492/40.492, 1/1 Watts: 2.146/2.146, 1/1 Cap (pF): 10740.305/10740.305, 1/1
LSR mA: 5.150/5.150, 1/1 Watts: 0.142/0.142, 1/1 Cap (pF): 1366.078/1366.078, 1/1
LSR mA: 35.318/35.318, 1/1 Watts: 2.009/2.009, 1/1 Cap (pF): 9368.289/9368.289, 1/1
LSR mA: 35.342/35.342, 1/1 Watts: 2.004/2.004, 1/1 Cap (pF): 9374.227/9374.227, 1/1
LSR mA: 53.810/53.810, 1/1 Watts: 2.588/2.588, 1/1 Cap (pF): 14273.204/14273.204, 1/1
LSR mA: 18.494/18.494, 1/1 Watts: 0.601/0.601, 1/1 Cap (pF): 4905.680/4905.680, 1/1
LSR mA: 35.321/35.321, 1/1 Watts: 2.026/2.026, 1/1 Cap (pF): 9368.875/9368.875, 1/1
LSR mA: 35.316/35.316, 1/1 Watts: 1.987/1.987, 1/1 Cap (pF): 9367.524/9367.524, 1/1
FRANK™ Message 2 (Good) - For this transformer, the upper % power factor limit for a "G" rating is 1.0 and the upper % power factor limit before an "I" rating is 1.5
The relative humidity is between 45 and 70 percent, a medium amount, which may cause some increases in watts and power factor ratings. Clean and dry the surfaces of bushings arresters, and other apparatus with insulators onto which may condense moisture from the air, before testing, using heat if necessary.
3 (Good) - All values are acceptable.
6 (Good) - All values are acceptable.
8 (Good) - All values are acceptable.
2 - 4010584-VA1
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
1 A 230 milli Ohms * * * *
1 B 230 milli Ohms * * * *
1 C 230 milli Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
1 A 1.01 milli Ohms * * * *
1 B 1.18 milli Ohms * * * *
1 C 1.18 milli Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Square D 010584-VA1 Δ-Y 0°C 18.3°C * *
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 2 278.256 2367.550 L 195.095 1676.755 L 269.054 2296.742 L Good Good
LSR mA: 278.256/278.256, 1/1 Watts: 2367.550/2367.550, 1/1 Cap (pF): */*, 1/1
LSR mA: 195.095/195.095, 1/1 Watts: 1676.755/1676.755, 1/1 Cap (pF): */*, 1/1
LSR mA: 269.054/269.054, 1/1 Watts: 2296.742/2296.742, 1/1 Cap (pF): */*, 1/1
3 - 4010584-VA1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 4160 3 480 15.011 15.004 15.014 15.011 14.936 15.086 Good Good
FRANK™ Message 1 (Good) - Ratio is within expected values.
TTR results are considered acceptable if the measured value is within 0.5% of the calculated value. Anything outside this range is cause for further investigation.
Exciting Current Plot
4 - 4010584-VA1
SE Medium Voltage Vacuum Contactor
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-4DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 8 MAIN CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W430
NA
RCY67977-1
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500 A
SERIAL NUMBER
RATED VOLTAGE
CUTLER-HAMMERFUSE MFG. 5SCL-12RFUSE CAT. NO. 230FUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable N/A
N/A N/A
Acceptable C & L
Acceptable N/A
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. Acceptable N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
1245 1240 1235
POLE 3POLE 2
68160
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
68.0 81.3
122.0 145.8
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
444.5372.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
418.0
489.0
113.0
169.0
187.0
267.0135.0
499.5
319.1
584.4 202.0
223.5
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/AN/A
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
120 VOLT RANGE
CLOSE COIL INFORMATION
N/AVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
COMMENTS: All tests proved satisfactory.
DEFICIENCIES:
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-4DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 8 STARTING CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W230
NA
NA
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500
SERIAL NUMBER
RATED VOLTAGE
NAFUSE MFG. NAFUSE CAT. NO. NAFUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable N/A
N/A N/A
Acceptable C & L
N/A N/A
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. N/A N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
N/A N/A N/A
POLE 3POLE 2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
287.0 343.0
329.0 393.2
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
811.4679.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
424.0
763.0
324.0
275.0
309.0
288.0387.2
506.7
344.2
911.8 328.6
369.3
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/A120 VAC
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
VOLT RANGE
CLOSE COIL INFORMATION
120 VACVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
DEFICIENCIES: Controls 120 abilical cord male plug is frozen together with female plug and the male plug covering is broken.
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-4DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 8 RUN CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W430
NA
NA
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500 A
SERIAL NUMBER
RATED VOLTAGE
NAFUSE MFG. NAFUSE CAT. NO. NAFUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable N/A
N/A N/A
Acceptable C & L
N/A N/A
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. N/A N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
N/A N/A N/A
POLE 3POLE 2
130133
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
135.0 161.3
249.0 297.6
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
527.0441.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
564.0
572.0
248.0
336.0
369.0
300.0296.4
674.0
358.5
683.5 401.5
441.0
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/A120 VAC
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
VOLT RANGE
CLOSE COIL INFORMATION
120 VACVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 86 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-4DESIGNATION
SUBSTATION BUILDING 104-A
05/13/2021 80
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH MCC-4
Mike Danford
1509,0115
N/A
VA Hospital WO-08391081
C & L
Cleaned Torqued
MATCHES DWG OR SPEC
GROUND CONNECTION
NA NA
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
Cleaned
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
17-15229802-001
44036-325-50
15 kv
NA
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE HVL
95 kv
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
24 VDC N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
FUSE AMPS55GFMSJD200EFUSE MFG. Square D FUSE CAT. NO. 200
@5000VGIG-OHMS 20°C
220.0 347.6
143.0 225.9
TEST 1
TEST 3
1.58TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
301.8191.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
251.0
267.0
139.0
145.0
208.0
255.0219.6
396.6
402.9
421.9 229.1
328.6
15 kv
Square D
61 ka
RANGE
(µ-ohms) 36
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
35 38
10 A 2,111 2,1102,119FUSE RESISTANCE at (m-ohms)
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-5DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 9 MAIN CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W430
NA
NA
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500
SERIAL NUMBER
RATED VOLTAGE
CUTLER-HAMMERFUSE MFG. 5ACLS-12RFUSE CAT. NO. 230FUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable Cleaned
N/A N/A
Acceptable C & L
Acceptable Cleaned
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. Acceptable N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
1220 1234 1235
POLE 3POLE 2
167183
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
120.0 143.4
173.0 206.7
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
490.0410.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
324.0
410.0
163.0
141.0
74.0
211.0194.8
387.2
252.1
490.0 168.5
88.4
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/A120 VAC
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
VOLT RANGE
CLOSE COIL INFORMATION
120 VACVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-5DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 9 RUNNING CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W430
NA
NA
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500
SERIAL NUMBER
RATED VOLTAGE
NAFUSE MFG. NAFUSE CAT. NO. NAFUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable N/A
N/A N/A
Acceptable C & L
N/A N/A
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. N/A N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
N/A N/A N/A
POLE 3POLE 2
155150
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
160.0 191.2
42.0 50.2
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
148.2124.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
119.0
152.0
32.0
71.0
400.0
226.038.2
142.2
270.1
181.6 84.8
478.0
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/A120 VAC
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
VOLT RANGE
CLOSE COIL INFORMATION
120 VACVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
TEMPERATURE 86 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-5DESIGNATION
SUBSTATION BUILDING 104-A
05/13/2021 80
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH MCC-5
Mike Danford
1509, 0115
N/A
N/A
VA Hospital WO-08391081
C & L
Cleaned Torqued
MATCHES DWG OR SPEC
GROUND CONNECTION
NA NA
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
Cleaned
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
17-15229802-001
44036-325-50
15 kv
NA
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE HVL
95 kv
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
48 VDC
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
FUSE AMPS55GFMSJD200EFUSE MFG. Square D FUSE CAT. NO. 200
@5000VGIG-OHMS 20°C
524.0 827.9
44.1 69.7
TEST 1
TEST 3
1.58TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
270.2171.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
208.0
170.0
34.7
54.1
573.0
516.054.8
328.6
815.3
268.6 85.5
905.3
15 kv
Square D
61 ka
RANGE
(µ-ohms) 42
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
34 58
10 A 2,159 2,1702,116FUSE RESISTANCE at (m-ohms)
TECH NOTE(S):
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-5DESIGNATION
SUBSTATION BUILDING 104-A
5/14/2021 60
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
CHILLER 9 STARTING CONTACTOR
Javier Rojas
VA Hospital WO-08391081
CONTACTOR NAMEPLATE DATA
MANUFACTURER
TYPE or STYLE
CATALOG NUMBER
SL50W230
NA
NA
BIL kV RATING
NADATE MANUFACTURED RATED CURRENT
RATED SHORT CIRC. 8500
SERIAL NUMBER
RATED VOLTAGE
NAFUSE MFG. NAFUSE CAT. NO. NAFUSE AMPS
NANA COUNTER READING ALCOUNTER READING AF
Cutler-Hammer
INSPECTION
Description CONDITION CLEAN/LUBE
N/A N/A
PHY. & MECH. CONDITION Acceptable
Acceptable N/A
N/A N/A
Acceptable C & L
N/A N/A
CONDITIONDescription CLEAN/LUBE
OPERATING MECHANISM Acceptable N/A
FUSE HOLDERS ADEQ. SUPP. N/A N/A
EXT. & INT. CUBICLE CONDITION Acceptable C & L
IND. & CTRL. DEVICE OPER. N/A N/A
OPER. COIL CONDITION Acceptable N/A
C & LAcceptableDISCONN. FINGER CONDITION
MATCHES DWG OR SPEC
C & L
TIGHTNESS OF BOLTED CONN.
ANCH. & REQ. CLEARANCES
LUBRICATION
FUSES SIZED PROPERLY
CONDITION CLEAN/LUBEDescription
PHASE BARRIERS Acceptable Cleaned
TEST RESULTS
N/A N/A N/A
POLE 3POLE 2
108116
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
@1000VGIG-OHMS 20°C
90.0 107.6
15.0 17.9
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
33.528.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
32.0
40.0
9.0
25.0
50.0
114.010.8
38.2
136.2
47.8 29.9
59.8
XX
POLE 1
TEST KV
VACUUM INTEGRITY (as per Manufacturer)
POLE 3 POLE 2
A.C. D.C.
INSULATION RESISTANCE IN:
N/AN/A
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
MAX CLOSING VOLTAGE
MIN CLOSING VOLTAGE
VOLT RANGE
Volts
ADDITIONAL INFORMATIONCONTACTOR OPERATING VOLTAGE
VOLT RANGE
CLOSE COIL INFORMATION
N/AVolts
ADDITIONAL INFO
PICKUP VOLTS
CONTROL WIRING
MEG-OHMS @500V 20°C
TECH NOTE(S):
TEMPERATURE 86 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-6DESIGNATION
SUBSTATION BUILDING 104-A
05/13/2021 80
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH MCC-6
Mike Danford
1509, 0115
N/A
N/A
VA Hospital WO-08391081
C & L
Cleaned Torqued
MATCHES DWG OR SPEC
GROUND CONNECTION
NA NA
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
Cleaned
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
17-15229802-001
44036-325-50
15 kv
NA
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE HVL
95 kv
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
48 VDC
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
FUSE AMPS55GFMSJD200EFUSE MFG. Square D FUSE CAT. NO. 200
@5000VGIG-OHMS 20°C
471.0 744.2
251.0 396.6
TEST 1
TEST 3
1.58TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
301.8191.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
251.0
267.0
139.0
267.0
406.0
503.0219.6
396.6
794.7
421.9 421.9
641.5
15 kv
Square D
61 ka
RANGE
(µ-ohms) 41
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
39 38
10 A 2,117 2,2212,118FUSE RESISTANCE at (m-ohms)
TECH NOTE(S):
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 80 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
MCC-6DESIGNATION
SUBSTATION BUILDING 104-A
05/13/2021 85
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Mike Danford
0030, 1509
N/A
N/A
VA Hospital WO-08391081
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONPXL
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. PXF361000G
N/AFUSE CAT. NO.
1200 Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
N/A
N/AOPERATING MECHANISM N/A
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1.0
.1 OUT
2.5 5 2.5
.2
.1 ON
1.0
.2 OUT
1.0
.1 OUT
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1000RATING PLUG:1200 1200
Overcurrent Settings
CT / SENSOR RATINGS:
.1 ON .2 ON
.35.2
AS FOUND
RANGE
MINIMUM MAXIMUM
5,016
1.047
0.160
5,000 0.75 1.25
1,000 0.14 0.2
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
2.5
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
5,000
1,092
7.379
SHORT TIME PICKUP
SHORT TIME DELAY 5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
900 A A1,100
A A
AA
A A
3,600 4,400
5,5004,500
360 440
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
5.5
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
0 104
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
3,950
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
4,370
TAP POSITION/CONNECTION
4,260 4,060
CLASS
4,160
Phase 3010584-VA1SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
COOLANT TYPE 7078
YEAR OF MANUF.N/A N/A
MANUFACTURER
SEALED
SPECIFICATION NO. MANUF. LOCATION
TYPE ONAN K FACTOR N/A °CTEMPERATURE RISE
U.S.A
655.5
B.I.L. RATING
MAIN TANK VOLUME
WINDING MATERIAL Cu
OIL UG LBTOTAL WEIGHTOLTC VOLUME GAL
DELTA480
TAP VOLTAGES
DETC OLTC
WINDING POLARITY SUBTRACTIVE
WYE
/TAP CHANGER:
4,160
Square D
RANGE
LIQUID FILLED TRANSFORMER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
PT-14DESIGNATION
SUBSTATION BUILDING 104-A
5/13/2021 63
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
PT-14 XFMR
Chris Espartero
M4K, 2988, 1388, 3115
N/A
N/A
VA Hospital WO-08391081
N/A
CONDITIONDescription CLEAN/LUBEDescription
Cleaned
Acceptable N/A
N/A N/A
FANS
Acceptable
N/A
INSPECTION
N/A
N/A
N/A
N/A
PAINT Acceptable
CLOUDY
Cleaned
MATCHES DWG OR SPEC
WEATHER
N/A
ENVIRONMENT
N/A
N/A
GAUGES
SUPPORT INSULATORS
N/A
Torqued
N/A
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
N/A
Torqued
ARRESTERSCORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
Acceptable
OUTSIDE
23230, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
N/A
N/A
N/A
N/A
GAUGES
OIL TEMPERATURE 35
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X2 - X0
H1 - H3 H2 - H1 H3 - H2
X3 - X0
TAP TO
TEST
3 15.004 15.014 15.0110.02 % PASS 0.00 % PASSPASS15.011 0.04 %4,160 277
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 230.000 271.388 230.000 271.388 230.000 271.388 1.010 1.192 1.000 1.180 1.000 1.1801
Primary Secondary
TECH NOTE(S):
LIQUID FILLED TRANSFORMER
PAGEPT-14 XFMRDEVICE N/ADBID
23230, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
COMMENTS: