Laboratory Analysis Report
253131
Schneider Electric
REPORT AUTHORIZATIONORDER INFORMATIONCUSTOMER INFORMATION
Address:
Date Report Issued:
Authorization Signature:
Email:
Authorized By:
Report Revision:
Date Received:
Submitter Ref:
Purchase Order:
Thank you for using Doble Engineering analytical laboratory services, we greatly appreciate the opportunity to serve you and value your business. In accordance with your request, we have performed testing on the sample(s) provided. If the sampling date is not provided, the sample receipt date is used to provide chronological information. Should you have any comments, suggestions or questions please feel free to contact us at the Email listed above.
Primary Email:
Primary Contact:
NEEDSPO
05/20/2021
06/02/2021
Terry Bowden
Terry.Bowden@se.com
Schneider Electric
8501 Joor Rd
PO Box 78032
Baton Rouge, LA 70837
Vernon Glover
VGlover@doble.com
Samples Requiring Immediate Attention
Sample Id Apparatus Type Serial No Miscellaneous Id
Doble Engineering and Morgan Schaffer Laboratories are ISO/IEC 17025 Accredited
The analyses contained in this report are based upon material and information supplied by the customer. Doble Engineering/ Morgan Schaffer do not imply that the contents of the sample received are the same as all such material in the environment from which the sample was taken. Our test results only relate to the sample(s) tested. Doble Engineering/ Morgan Schaffer assume no responsibility and makes no warranty or representation as provided in the Doble Terms and Conditions Revision 030232020. This report must not be reproduced, unless in its entirety, without the written consent of Doble Engineering.
(^Accredited Tests (from the start date of each lab's accreditation), Ŧ Subcontracted Tests, *Non-Doble/MS Imported Test Results).
Doble Engineering Company - 1000 South Loop West Fwy, Suite 100, Houston, TX 77054
Design Rev: 210112-01
APPARATUS DETAIL SAMPLING INFORMATION
Serial Number: 010584VA1
Equipment No: PT-14 Preservation: Gas Blanketed
Temp Rise C:
XFMR/TRN Name:
Substation: Bldng 104A
Syringe No: 20588
Manufacturer: Square D Electric
Year Made:
Cooling:
Max KV: 4.16
Max MVA: 7.5
XFMR/TRN Type:
Design Type:
1 or 3 Phase: N
Volume: 309
Liquid Type: Mineral
Limit Set: Doble
Vol Units: Gallons
Misc. ID: Va Medical Center
Work Order:
Sample Date: 05/19/2021
Sample Time:
Sampling Reason: Routine
Sampled By: CE
Sample Point: Bottom
Top Oil Temp C: 35
Humidity: 60
Amb Temp C: 22
TRANSFORMER
5/19/2021 4/29/2014
6/2/2021 5/6/2014
253131-001 139719-001
35 35
Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 6.4 8.6
Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 2130 3010
Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 64700 81300
Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 25.5 23.0
Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 767 685
Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 6.1 5.5
Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 5217 4140
Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 22.1 22.0
Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 1.2 1.1
Total Gas (ppm ) ^ 72875 89195
Comb. Gas (ppm ) ^ 828 745
Est. TCG, % of Gas Space ^ 0.89 0.64
Ethylene-Acetylene Ratio ^ 18.42 20.00
PPM/Day (ppm/day ) ^ 0.0
Dissolved Gas Analysis
Sample Id: 253131-001 Serial Number: 010584VA1 Misc Id: Va Medical Center
Sample Date:
Analysis Date:
Doble Sample Id:
Top Oil Temperature:
^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 4/10/2020)
*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined
CRITICALITY: Condition is of no immediate concern.
Resample Frequency: 1 year
Comments: High temperature overheating of oil. Overheating of cellulose.
5/19/2021 4/29/2014
6/2/2021 5/6/2014
253131-001 139719-001
35 35
Water Content D1533 IEC 60814 (ppm ) ^ 3 8
Relative Saturation (% ) ^ 3.0 8
Color D1500 D1500 ^ L 1.0 L 1.0
Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 15 40
Interfacial Tension D971 (mN/m ) ^ 33 36
Neut. Number D974 (mgKOH/g ) ^ <0.01 0.01
Power Factor @ RT D924 (% ) ^ 0.030 0.027
Power Factor @ 100°C D924 (% ) ^ 1.098 0.145
Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8880
Visual Examination D1524 ^ C&B C&B-FineP
Oil Quality Tests
Sample Id: 253131-001 Serial Number: 010584VA1 Misc Id: Va Medical Center
Sample Date:
Analysis Date:
Doble Sample Id:
Top Oil Temperature:
^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 4/10/2020)
*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined
Comments: Water content as reported in relative saturation is considered excellent for in service liquid. Dielectric breakdown voltage is unacceptable. Other results are acceptable for in service liquid.
APPARATUS DETAIL SAMPLING INFORMATION
Serial Number: 3302874500201
Equipment No: Preservation: Gas Blanketed
Temp Rise C: 65
XFMR/TRN Name: PT-1
Substation: Chiller XFMR
Syringe No: IBX630
Manufacturer: Square D Electric
Year Made: 2014
Cooling: ONAN
Max KV: 12.47
Max MVA: 1
XFMR/TRN Type: Transformer
Design Type: Core Type
1 or 3 Phase:
Volume: 331
Liquid Type: Mineral
Limit Set: Doble
Vol Units: Gallons
Misc. ID: Va Medical Center
Work Order:
Sample Date: 05/19/2021
Sample Time:
Sampling Reason: Routine
Sampled By: CE
Sample Point: Bottom
Top Oil Temp C: 30
Humidity: 46
Amb Temp C: 25
TRANSFORMER
5/19/2021
6/2/2021
253131-002
Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 38.5
Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 249
Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 61400
Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 11.4
Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 899
Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 3.1
Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 4320
Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 3.0
Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 0.1
Total Gas (ppm ) ^ 66924
Comb. Gas (ppm ) ^ 955
Est. TCG, % of Gas Space ^ 1.20
Ethylene-Acetylene Ratio ^ 30.00
PPM/Day (ppm/day ) ^ Need Data
Dissolved Gas Analysis
Sample Id: 253131-002 Serial Number: 3302874500201 Misc Id: Va Medical Center
Sample Date:
Analysis Date:
Doble Sample Id:
Top Oil Temperature:
^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 4/10/2020)
*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined
CRITICALITY: Condition is moderate.
Resample Frequency: 6 months
Comments: Overheating of cellulose. This appears to be a first-time analysis. It assumes unit has operated continuously under normal conditions for the last year, otherwise resample in 1 month to determine trend.
5/19/2021
6/2/2021
253131-002
Water Content D1533 IEC 60814 (ppm ) ^ 5
Relative Saturation (% ) ^ 6.0
Color D1500 D1500 ^ L 1.0
Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 21
Interfacial Tension D971 (mN/m ) ^ 28
Neut. Number D974 (mgKOH/g ) ^ 0.01
Power Factor @ RT D924 (% ) ^ 0.050
Power Factor @ 100°C D924 (% ) ^ 0.790
Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8901
Visual Examination D1524 ^ C&B
Oil Quality Tests
Sample Id: 253131-002 Serial Number: 3302874500201 Misc Id: Va Medical Center
Sample Date:
Analysis Date:
Doble Sample Id:
Top Oil Temperature:
^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 4/10/2020)
*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined
Comments: Water content as reported in relative saturation is considered good for in service liquid. Other results are acceptable for in service liquid.