Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-7 Substation PM
April 20, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-7 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-7 480V Switchboard
USS-7 Switchboard Main Breaker operating mechanism failed to perform basic functions. USS-7
Main Breaker failed to close manually, and the tripping mechanism was defective. Loose parts were also found during breaker inspection. With the customers approval we transferred the main breaker AC pro trip unit, trip coil and current sensor to a similar spare breaker. The spare breaker was tested with satisfactory test results and was used to replace the existing USS-7 main circuit breaker that was sent to schneider electric breaker shop for major overhaul.
USS-7 Transformer
USS-7 Transformer temperature controller was not working and needed to be replaced. Fuse and relays were found to have been pulled out inside the temperature controller control cabinet which may have been done during previous troubleshooting. Transformer temperature is one the biggest contributing factor to the life of the transformer. Excessive heat on the transformer can reduce transformer efficiency and shorten the life of the transformer.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-7_876101-E2_XD
DryTypeTransformerReport Source
4/18/2021 7:52:53 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-E2
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID USS-7 XFMR
Division Houston Circuit Designation USS-7 SUBSTATION
Manufacturer Square D Electric Class
Year Manufactured Type DryTypeTransformer
Mfr Location USA Winding Insulation Open-Wound
Coolant Select Coolant Weight 7710
Tank Type Select Tank Type BIL 110 kV
Dry Tank Type Ventilated VA Rating 1000 kV 12.47,0.48,* Insulation Material Nomex
Administration Test Date 4/18/2021 Test Time: 7:52 PM Weather Indoors
Air Temperature 23.9°C Apparatus Temperature
* Humidity 63 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 1
1 - 6876101-E2
Session Notes
2 - 6876101-E2
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
LSR mA: 4.535/4.535, 1/1 Watts: 0.053/0.053, 1/1 Cap (pF): 1202.843/1202.843, 1/1
LSR mA: 0.924/0.924, 1/1 Watts: 0.036/0.036, 1/1 Cap (pF): 244.998/244.998, 1/1
LSR mA: 3.611/3.611, 1/1 Watts: 0.015/0.015, 1/1 Cap (pF): 957.922/957.922, 1/1
LSR mA: 3.611/3.611, 1/1 Watts: 0.017/0.017, 1/1 Cap (pF): 957.845/957.845, 1/1
LSR mA: 8.865/8.865, 1/1 Watts: 0.149/0.149, 1/1 Cap (pF): 2351.608/2351.608, 1/1
LSR mA: 5.254/5.254, 1/1 Watts: 0.130/0.130, 1/1 Cap (pF): 1393.749/1393.749, 1/1
LSR mA: 3.613/3.613, 1/1 Watts: 0.008/0.008, 1/1 Cap (pF): 958.291/958.291, 1/1
LSR mA: 3.611/3.611, 1/1 Watts: 0.018/0.018, 1/1 Cap (pF): 957.859/957.859, 1/1
Overall Tests - 2K # Insulation Test kV mA Watts % PF Meas. Cap (pF) IR Man.
1 CH+CHL 2.000 4.535 0.053 0.117 1202.843 Good
2 CH 2.000 0.924 0.036 0.387 244.998 Good
3 CHL(UST) 2.000 3.611 0.015 0.041 957.922 Good
4 CHL 0 3.611 0.017 0.047 957.845 Good
5 CL+CHL 1.000 8.865 0.149 0.168 2351.608 Good
6 CL 1.000 5.254 0.130 0.248 1393.749 Good
7 CHL(UST) 1.000 3.613 0.008 0.023 958.291 Good
8 CHL 0 3.611 0.018 0.051 957.859 Good
3 - 6876101-E2
LSR mA: 4.534/4.534, 1/1 Watts: 0.050/0.050, 1/1 Cap (pF): 1202.676/1202.676, 1/1
LSR mA: 0.924/0.924, 1/1 Watts: 0.036/0.036, 1/1 Cap (pF): 244.981/244.981, 1/1
LSR mA: 3.611/3.611, 1/1 Watts: 0.015/0.015, 1/1 Cap (pF): 957.737/957.737, 1/1
LSR mA: 3.610/3.610, 1/1 Watts: 0.014/0.014, 1/1 Cap (pF): 957.695/957.695, 1/1
LSR mA: 8.864/8.864, 1/1 Watts: 0.146/0.146, 1/1 Cap (pF): 2351.229/2351.229, 1/1
LSR mA: 5.254/5.254, 1/1 Watts: 0.124/0.124, 1/1 Cap (pF): 1393.626/1393.626, 1/1
LSR mA: 3.612/3.612, 1/1 Watts: 0.010/0.010, 1/1 Cap (pF): 958.213/958.213, 1/1
LSR mA: 3.610/3.610, 1/1 Watts: 0.022/0.022, 1/1 Cap (pF): 957.603/957.603, 1/1
Overall Tests - LG # Insulation Test kV mA Watts % PF Meas. Cap (pF) Tip UP FRANK™ IR Man.
1 CH+CHL 10.004 4.534 0.050 0.111 1202.676 *
2 CH 10.003 0.924 0.036 0.389 244.981 0.001 Good
3 CHL(UST) 10.003 3.611 0.015 0.042 957.737 0.001 Investigate
4 CHL 0 3.610 0.014 0.040 957.695 *
5 CL+CHL 0.499 8.864 0.146 0.164 2351.229 *
6 CL 0.500 5.254 0.124 0.235 1393.626 -0.012 Good
7 CHL(UST) 0.499 3.612 0.010 0.026 958.213 0.003
8 CHL 0 3.610 0.022 0.060 957.603 * Investigate
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 301.7 milli Ohms * * * *
3 B 301.3 milli Ohms * * * *
3 C 301.1 milli Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 465.7 micro Ohms * * * *
3 B 436.2 micro Ohms * * * *
3 C 420.9 micro Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
4 - 6876101-E2
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 5 93.937 764.804 L 51.222 420.076 L 94.442 768.077 L Good
LSR mA: 93.937/93.937, 1/1 Watts: 764.804/764.804, 1/1 Cap (pF): */*, 1/1
LSR mA: 51.222/51.222, 1/1 Watts: 420.076/420.076, 1/1 Cap (pF): */*, 1/1
LSR mA: 94.442/94.442, 1/1 Watts: 768.077/768.077, 1/1 Cap (pF): */*, 1/1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections - - -
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 45.102 45.012 45.015 44.772 45.222 Good Good
5 - 6876101-E2
Exciting Current Plot
6 - 6876101-E2
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 68 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/01/21 50
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
SPARE BREAKER/USS-7 replacement
Javier Rojas
VA Hospital WO-08391081
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 416
50 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Westinghouse
AC PRO N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
753.0 753.0
73.0 73.0
TEST 1
TEST 3
1TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
797.0797.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
826.0
690.0
433.0
406.0
104.0
874.0433.0
826.0
874.0
690.0 406.0
104.0
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1.0
2.5
3.0
.20
2 OFF 3200 2 OFF
.2
.2
1.0
2.5
.4
1.0
2.5
3.0
.20
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.20 .4
320.2
AS FOUND
RANGE
MINIMUM MAXIMUM
3,337
0.22
0.41
3,337
0.22
5,081
0.41
3,392
0.21
5,140
0.45
3,392
0.21
5,140
0.45
3,307
0.21
5,174
0.44
3,307
0.21
5,174
0.44
6,000 0.08 0.18
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 10.43 1,043 1,043 10.38 10.38
1,638 1,624 1,624 1,642 1,642
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 7
1,638
10.43
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
4,320 5,220
3,5202,880
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S): This spare breaker is replacing the existing USS-7 Main circuit breaker
COMMENTS: Installed new AC PRO retrofit kit. Performed preventive maintenance, repair, primary injected. All tests proved satisfactory.
DEFICIENCIES:
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
4/19/2021 63
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
N/A
N/A
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
Torqued
N/A N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
Acceptable
N/A
GAUGES
SUPPORT INSULATORS
N/ATorqued
Comment
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
GAUGES
N/A
CLEAN
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
46 46
1,2031,2031,203
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,904
TAP POSITION/CONNECTION
12,782 12,158
1,000
CLASS
12,470
Phase 3876101-E2SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
YEAR OF MANUF.N/A 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA/FA K FACTOR N/A °CTEMPERATURE RISE
U.S.A
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
1,000 / 1,000
12,470
TOTAL WEIGHT
Dry
SqD
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1.195
5,000
1,000
5,000
765,000.0 914,175.0 1,300,000 1,553,500
1,033,675865,000.0810,210.0678,000.0
645,000.0 770,775.0 988,000.0 1,180,660
1.70
1.28
1.53
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X0 - X2
H1 - H3 H2 - H1 H3 - H2
X3 - X0
TAP TO
TEST
3 45.102 45.012 45.0150.04 % PASS 0.04 % PASSPASS44.996 0.24 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE N/ADBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 301.700 361.363 301.300 360.884 301.100 360.644 0.465 0.557 436.200 522.461 0.420 0.5031
Primary Secondary
TECH NOTE(S):
COMMENTS: Temperature control is not working fuse and relay have been pulled from control cabinet. All test results are satisfactory at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT A
David Gordon
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
8 7 8
.2
1 OUT
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 800RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 OUT 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
1.983
0.555
NT NT NT NT NT
4,200 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
3,200
8.936
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
720 A A880
A A
AA
A A
3,600 4,400
6,1605,040
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT B
David Gordon
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR Acceptable N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
7 7 7
.3
1 OUT
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 600RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 OUT 4 IN
.4.3
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
1.987
0.537
NT NT NT NT NT
3,150 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
2,400
8.937
SHORT TIME PICKUP
SHORT TIME DELAY 5.25
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
540 A A660
A A
AA
A A
2,700 3,300
4,6203,780
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 78 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
04/19/2021 57
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
Chris Espartero
VA Hospital WO-08391081
480/277
N/A
MANUFACTURER
1600 AMP
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
N/A
Acceptable
N/A
CONDITION
N/A
Description
Cleaned
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION N/A N/A Cleaned
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
N/A
N/A
N/A
N/A
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
45-08000-62S
INSPECTION
Acceptable
PT'S AND CT'S
New Cleaned AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS
Acceptable N/ADOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
CleanedINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
N/A
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
@1000VGIG-OHMS 20°C
8.9 11.5
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
29.723.0
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
25.0
40.0
31.0
16.5
40.0
32.2
51.6 21.3TEST 3
N-GNDTEST 4
1.2896TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
SECTION 1 SECTION 2 33 39 37 31
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
TRIP UNIT TYPE
CP22113
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
04/19/21 43
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Javier Rojas
VA Hospital WO-08391081
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 416
50 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Deficiency
CONDITION
N/A
Acceptable
Acceptable
Deficiency
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Westinghouse
AC PRO N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
381.0 476.3
305.0 381.3
TEST 1
TEST 3
1.25TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
448.8359.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
306.0
357.0
342.0
294.0
354.0
351.0427.5
382.5
438.8
446.3 367.5
442.5
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1.0
2.5
3.0
.20
2 OFF 3200 2 OFF
.2
.2
1.0
2.5
.4
1.0
2.5
3.0
.20
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.20 .4
320.2
AS FOUND
RANGE
MINIMUM MAXIMUM
3,330
0.18
0.40
3,330
0.18
4,920
0.40
3,210
0.18
4,952
0.45
3,210
0.18
4,952
0.45
3,200
0.18
4,780
0.42
3,200
0.18
4,780
0.42
6,000 0.08 0.18
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 9.15 8.66 8.66 8.83 8.83
1,750 1,698 1,698 1,721 1,721
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 7
1,750
9.15
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
4,320 5,220
3,5202,880
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S): Original breaker is in the Schneider Electric breaker shop for major overhaul.
COMMENTS: To remedy the issue we removed the trip unit, the flux shifter and the current sensors along with harness and mounted it on a spare breaker compatible with the original. This breaker was tested and passed all tests. Its back in service without issues.
DEFICIENCIES: Breaker operating mechanism fail to performed basic functions. breaker failed to close manually the tripping mechanism was defective, loose parts also found.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
B0I NHC
David Gordon
VA Hospital WO-08391081
N/A
N/A
N/A Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONILL
200KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. ILL34401021
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
GROUND SENSOR N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
312332
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT C
David Gordon
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
New
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
8 7 8
.2
1 OUT
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 800RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 OUT 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
5,608
2.020
0.546
NT NT NT NT NT
4,200 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
3,200
9.081
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
720 A A880
A A
AA
A A
3,600 4,400
6,1605,040
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °C
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH -RA
David Gordon
VA Hospital WO-08391081
C & L
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES N/A Cleaned CleanedINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
44035-233-51
N/A
15 kv
N/A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE POWER ZONE
95 KA
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 AMP
FUSE AMPS9F60BHH905FUSE MFG. GOUND FUSE CAT. NO. .5 amp
@1000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
17.48TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
SQUARED
65KV
RANGE
(µ-ohms) 65
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
86 70
10 AFUSE RESISTANCE at (m-ohms)
TECH NOTE(S): Did not test insulation resistance due to feeder cables connected to the switch.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH -A1
David Gordon
VA Hospital WO-08391081
C & L
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned CleanedINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
44035-234-57
N/A
15 kv
N/A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE POWER ZONE
95 KA
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 AMP
FUSE AMPS155OX80E-1DFUSE MFG. GOUND FUSE CAT. NO.
@1000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
SQUARED
65 KA
RANGE
(µ-ohms) 48
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at
POLE 1
40 37
10 A 13.5 13.814.9FUSE RESISTANCE at (m-ohms)
TECH NOTE(S): Did not test insulation resistance in the closed position due to feeder cables connected to the switch.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-7DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
ATS 37
David Gordon
3284,3230
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A Torqued N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
8 7 8
.2
1 OUT
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 600RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 OUT 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
4,188
1.984
0.555
NT NT NT NT NT
3,150 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
2,400
8.935
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
540 A A660
A A
AA
A A
2,700 3,300
4,6203,780
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.