View the file

Other files

File Type Posted
Exhibit N - PT-12 BLDG 29 Test Report.pdf PDF
Exhibit G - Chiller Water XFMR Test Report.pdf PDF
Exhibit AF - USS-L Test Report.pdf PDF
Exhibit P - SESG Test Report.pdf PDF
Exhibit AA - USS-10 Test Report.pdf PDF
Exhibit V - USS-5 Test Report.pdf PDF
Exhibit D - Building 108 Visor Clininc IR Sheet.pdf PDF
Exhibit C - Bldg. 122, IR Sheets.pdf PDF
Exhibit K - MSG Circuit B1 XFMR and Breakers Test Reports.pdf PDF
Exhibit W - USS-6 Test Report.pdf PDF
Exhibit H - CHP Bldg. Test Report.pdf PDF
Exhibit AC - USS-12 Test Report.pdf PDF
Exhibit AE - USS-14 Test Report.pdf PDF
Exhibit T - USS-3 Test Report.pdf PDF
Exhibit M - PT-1 and PT-14 Oil report.pdf PDF
36C25623Q0012 0001.docx DOCX document
Exhibit R - USS-1 Test Report.pdf PDF
Exhibit X - USS-7 Test Report.pdf PDF
Exhibit AD - USS-13 Test Report.pdf PDF
Exhibit E - Building 109 Lab IR Sheets.pdf PDF
Exhibit L - MSG Test Report.pdf PDF
Exhibit Y - USS-8 Test report.pdf PDF
Exhibit AB - USS-11 Test Report.pdf PDF
Exhibit U - USS-4 Test Report.pdf PDF
Exhibit Z - USS-9 Test Report.pdf PDF
Exhibit Q - USS L Laundry Report.pdf PDF
Exhibit A - Bldg. 104A Test Report.pdf PDF
Exhibit F - Building 110 IR Sheets.pdf PDF
Exhibit S - USS-2 Test Report.pdf PDF
Exhibit B - Bldg. 105 IR Sheet (1).pdf PDF
36C25623Q0012.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Prepared By:

Chris Espartero Sr Field Service Representative

North America Service Operations

Houston, TX

MBSG Substation PM

May 24, 2021

Work Order: 08391081

2 | P a g e

EXECUTIVE SUMMARY

Schneider Electric Services perform medium voltage HVL switch PM in accordance with project specification and applicable industry standard on MBSG Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe

Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.

MBSG Spare 2 medium voltage air switch is missing a stationary and moving contact. B-Phase insulation barrier is also missing. Switch needs to be repaired or replaced.

If there are any questions or concerns, please contact:

Chris Espartero

832-205-1547

Christopher.Espartero@se.com

20°C

MEDIUM VOLTAGE AIR SWITCH

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A (RB)

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

C & L

C & L N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES Acceptable Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 28

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

28 25

TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.

COMMENTS:

DEFICIENCIES:

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A (A1)

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

C & L

C & L N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES N/A Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 63

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

73 81

TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A (RA)

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

C & L

C & L N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES Acceptable Comment N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 28

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

25 25

TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.

COMMENTS: Tested PT to verify it wasn't bad.

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A SPARE-1

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

Cleaned

Cleaned N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES Acceptable Deficiency N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 36

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at 100 A

POLE 1

40 38

TECH NOTE(S):

COMMENTS: Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A SPARE-2

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

Cleaned

Cleaned N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Deficiency Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES Acceptable Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Deficiency

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VTERA-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

4.8

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

11.9

6.0

4.8

15 kv

Square D

RANGE

(µ-ohms) 42

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

TECH NOTE(S):

COMMENTS: Switch needed to be repair or replace.

DEFICIENCIES: C-Phase of the switch is missing and B-Phase barrier is broken. Switch can not be put in service.

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A (B1)

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

C & L

C & L N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES N/A Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

480 VAC N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 28

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

27 25

TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.

TEMPERATURE 82 °F

PAGE

END USER

CUSTOMER

2002 HOLCOMBE BLVD.

DEPARTMENT OF VETERAN AFFAIRS

SITE LOCATION

MBSGDESIGNATION

SUBSTATION BUILDING 100

05/22/2021 96

JOB #

DBID

END USER ASSET/ID

HUMIDITYDATE

TESTED BYELEMENT

SUB-ELEMENT

DEVICE

EQUIPMENT USED

BC-100A (B2)

Cory Llewellyn

N/A

N/A

VA Hospital WO-08391081

C & L

C & L N/A

MATCHES DWG OR SPEC

GROUND CONNECTION

COUNTER READING AF/AL

ARCING CONTACTS

HEATER CIRCUIT

MAIN CONTACTS

CUBICLE

CLEAN/LUBE Description CLEAN/LUBECONDITION

Acceptable

Acceptable

Acceptable

N/A

N/A

CONTROL CIRCUIT

FUSE HOLDERS

CONDITIONDescription CLEAN/LUBE

N/AN/A

Description

Cleaned

Cleaned

N/AOPERATING MECHANISM C & L

PHASE BARRIERS Acceptable Cleaned

N/AAUXILIARY DEVICES

ARC CHUTES N/A N/A N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES

OVERALL CONDITION Acceptable

CONDITION

N/A

N/A

Acceptable

Acceptable

Acceptable

SWITCH NAMEPLATE

INSPECTION

CONTROL WIRING

MEG-OHMS

06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us

@500V

INSULATION RESISTANCE IN:

N/A

MANUFACTURER

RATED CURRENT INT. RATING

N/A

44035-241-51

15 kv

SN / SO NO.

RATED VOLTAGE

CATALOG NO.

MAX. VOLTAGE BIL RATING

TYPE / STYLE N/A

95KV

N/A

ADDITIONAL INFO

PICKUP VOLTS PICKUP VOLTS

ADDITIONAL INFO

VOLT RANGE VOLT RANGE

PICKUP VOLTS

VOLT RANGE

ADDITIONAL INFO

DROP-OUT VOLTS

CHARGING MOTOR INFORMATION

N/A

CLOSE COIL INFORMATION

N/A N/A VoltsVolts

PICKUP VOLTS

Volts

TRIP COIL INFORMATION

Volts

ADDITIONAL INFO

VOLT RANGE

N/A

OPTIONAL INFORMATION

TEST RESULTS

MANUF. DATE

FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A

@1000VMEG-OHMS 20°C

TEST 1

TEST 3

1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF

TEST 2

INSULATION RESISTANCE IN: CLOSED: POLE-POLE

20°C ACTUAL

PH A

ACTUALACTUAL

A - B A-GND

CLOSED: POLE-GROUND OPEN: LINE-LOAD

20°C

PH B

PH C

B-GND

C-GND

B - C

C - A

15 kv

Square D

RANGE

(µ-ohms) 33

POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS

BYPASS CONTACT RESISTANCE at

POLE 1

31 29

TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment and cables connected to switch.