Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-2 Substation PM
April 23, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-2 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-2 Main Breaker
USS-2 Switchboard main breaker actuator would not engage the trip bar 100% of the time. The circuit breaker trip bar spring has gotten weak and will cause it to not reset automatically when the breaker is tripped. With the trip bar not resetting properly the circuit breaker will not closed manually unless the trip bar is re-adjusted. The circuit breaker was replaced by one of the circuit breakers that was repair on site.
USS-2 Dry Type Transformer
USS-2 Transformer excitation test did not match the exciting current known pattern for a Delta
Wye transformer. This may indicate a short on the transformer winding. It is also evident on the transformer TTR test. USS-2 Transformer also failed on TTR calculated ratio.
Transformer temperature control is unserviceable. The circuit breaker inside the control cabinet was found to be on off position and ice cube relays has been pulled previously to isolate the circuit.
Temperature controller and components need to be replaced to keep transformer from overheating.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-2_876101-E1_XD
DryTypeTransformerReport Source
4/22/2021 7:06:15 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-E1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID USS-2 XFMR
Division Houston Circuit Designation USS-2 SUBSTATION
Manufacturer Square D Electric Class
Year Manufactured Type DryTypeTransformer
Mfr Location USA Winding Insulation Encapsulated
Coolant Select Coolant Weight 7710
Tank Type Select Tank Type BIL 110 kV
Dry Tank Type Ventilated VA Rating 1500 kV 12.47,0.48,* Insulation Material Epoxy Mica
Administration Test Date 4/22/2021 Test Time: 7:06 PM Weather Indoors
Air Temperature 25°C Apparatus Temperature
* Humidity 61 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 4/22/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 1
1 - 6876101-E1
Session Notes
2 - 6876101-E1
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
LSR mA: 4.552/4.552, 1/1 Watts: 0.066/0.066, 1/1 Cap (pF): 1207.369/1207.369, 1/1
LSR mA: 0.946/0.946, 1/1 Watts: 0.039/0.039, 1/1 Cap (pF): 250.965/250.965, 1/1
LSR mA: 3.606/3.606, 1/1 Watts: 0.024/0.024, 1/1 Cap (pF): 956.510/956.510, 1/1
LSR mA: 3.606/3.606, 1/1 Watts: 0.027/0.027, 1/1 Cap (pF): 956.404/956.404, 1/1
LSR mA: 8.806/8.806, 1/1 Watts: 0.123/0.123, 1/1 Cap (pF): 2335.785/2335.785, 1/1
LSR mA: 5.200/5.200, 1/1 Watts: 0.097/0.097, 1/1 Cap (pF): 1379.210/1379.210, 1/1
LSR mA: 3.608/3.608, 1/1 Watts: 0.016/0.016, 1/1 Cap (pF): 957.009/957.009, 1/1
LSR mA: 3.606/3.606, 1/1 Watts: 0.026/0.026, 1/1 Cap (pF): 956.575/956.575, 1/1
Overall Tests - 2K # Insulation Test kV mA Watts % PF Meas. Cap (pF) IR Man.
1 CH+CHL 2.000 4.552 0.066 0.145 1207.369 Good
2 CH 2.000 0.946 0.039 0.408 250.965 Good
3 CHL(UST) 2.000 3.606 0.024 0.065 956.510 Good
4 CHL 0 3.606 0.027 0.076 956.404 Good
5 CL+CHL 1.000 8.806 0.123 0.139 2335.785 Good
6 CL 1.000 5.200 0.097 0.186 1379.210 Good
7 CHL(UST) 1.000 3.608 0.016 0.044 957.009 Good
8 CHL 0 3.606 0.026 0.071 956.575 Good
3 - 6876101-E1
LSR mA: 4.552/4.552, 1/1 Watts: 0.069/0.069, 1/1 Cap (pF): 1207.415/1207.415, 1/1
LSR mA: 0.946/0.946, 1/1 Watts: 0.042/0.042, 1/1 Cap (pF): 251.059/251.059, 1/1
LSR mA: 3.606/3.606, 1/1 Watts: 0.030/0.030, 1/1 Cap (pF): 956.384/956.384, 1/1
LSR mA: 3.605/3.605, 1/1 Watts: 0.028/0.028, 1/1 Cap (pF): 956.356/956.356, 1/1
LSR mA: 8.806/8.806, 1/1 Watts: 0.122/0.122, 1/1 Cap (pF): 2335.837/2335.837, 1/1
LSR mA: 5.200/5.200, 1/1 Watts: 0.097/0.097, 1/1 Cap (pF): 1379.224/1379.224, 1/1
LSR mA: 3.608/3.608, 1/1 Watts: 0.016/0.016, 1/1 Cap (pF): 957.037/957.037, 1/1
LSR mA: 3.606/3.606, 1/1 Watts: 0.025/0.025, 1/1 Cap (pF): 956.614/956.614, 1/1
Overall Tests - LG # Insulation Test kV mA Watts % PF Meas. Cap (pF) Tip UP FRANK™ IR Man.
1 CH+CHL 10.004 4.552 0.069 0.152 1207.415 *
2 CH 10.003 0.946 0.042 0.443 251.059 0.035 Good
3 CHL(UST) 10.003 3.606 0.030 0.082 956.384 0.017 Investigate
4 CHL 0 3.605 0.028 0.076 956.356 *
5 CL+CHL 0.999 8.806 0.122 0.139 2335.837 *
6 CL 1.000 5.200 0.097 0.186 1379.224 0.000 Good
7 CHL(UST) 1.000 3.608 0.016 0.044 957.037 -0.001
8 CHL 0 3.606 0.025 0.071 956.614 * Investigate
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
1 A 288.7 milli Ohms * * * *
1 B 284.7 milli Ohms * * * *
1 C 286.5 milli Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
1 A 468.5 micro Ohms * * * *
1 B 445 micro Ohms * * * *
1 C 420.2 micro Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
4 - 6876101-E1
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 5 95.953 773.852 L 126.608 888.560 L 49.621 408.240 L Investigate
LSR mA: 95.953/95.953, 1/1 Watts: 773.852/773.852, 1/1 Cap (pF): */*, 1/1
LSR mA: 126.608/126.608, 1/1 Watts: 888.560/888.560, 1/1 Cap (pF): */*, 1/1
LSR mA: 49.621/49.621, 1/1 Watts: 408.240/408.240, 1/1 Cap (pF): */*, 1/1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 42.864 45.147 45.099 44.772 45.222 Investigate Investigate
5 - 6876101-E1
Exciting Current Plot
6 - 6876101-E1
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
4/22/2021 61
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
N/A
N/A
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
Torqued
N/A N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
N/A
N/A
GAUGES
SUPPORT INSULATORS
N/ATorqued
Deficiency
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
GAUGES
N/A
CONTROLLED
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
69 69
1,8041,8041,804
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,094
TAP POSITION/CONNECTION
12,782 12,158
1,500
CLASS
12,470
Phase 3876101-E1SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
YEAR OF MANUF.N/A 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA/FA K FACTOR N/A °CTEMPERATURE RISE
U.S.A
805.7
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
1,500 / 1,500
12,470
TOTAL WEIGHT
Dry
Square D
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
Acceptable
Acceptable
Acceptable
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1.25
5,000
1,000
5,000
171,000.0 213,750.0 190,900.0 238,625.0
1,762,5001,410,0001,470,0001,176,000
305,000.0 381,250.0 383,000.0 478,750.0
1.12
1.20
1.26
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X3 - X1
H1 - H3 H2 - H1 H3 - H2
X0 - X1
TAP TO
TEST
3 42.864 45.147 45.0990.34 % PASS 0.23 % PASSFAIL44.996 4.74 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE N/ADBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 288.700 344.326 284.700 339.555 286.500 341.702 468.500 558.770 445.000 530.742 420.200 501.1631
Primary Secondary
TECH NOTE(S):
COMMENTS: Caculated ratio on H1-H3 to X0-X1 failed.
DEFICIENCIES: Temperature controler is not working fuse and relay have been found to be pulled out from previous troubleshooting.
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/2021 40
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
Chris Espartero
VA Hospital WO-08391081
480/277
N/A
MANUFACTURER
1600 AMP
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
Acceptable
N/A
CONDITION
N/A
Description
Cleaned
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION N/A N/A
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
N/A
N/A
N/A
N/A
N/A
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
45-08000-62S
INSPECTION
Acceptable
PT'S AND CT'S
N/A N/A AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS
AcceptableDOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
CleanedINTERIOR SECTIONS / CUBICLES
Cleaned
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
N/A
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
@1000Vohms 20°C
115.0 131.1
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
19.417.0
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
10.0
15.0
13.0
10.0
14.8
11.4
17.1 11.4TEST 3
N-GNDTEST 4
1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
SECTION 1 SECTION 2 45 61 66 19
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
DEFICIENCIES:
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
8IY8028
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 75 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
4/22/21 40
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Javier Rojas
01025, 1797, 3115
VA Hospital WO-08391081
1600 AMP
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS-416
50 KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
AC PRO N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
1,770.0 2,115.2
703.0 840.1
TEST 1
TEST 3
1.195TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
1,167.5977.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
919.0
961.0
631.0
686.0
1,747.0
1,739.0754.0
1,098.2
2,078.1
1,148.4 819.8
2,087.7
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
.1
19200 3200 19200
.4
.4
.1
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.4 .4
480640
AS FOUND
RANGE
MINIMUM MAXIMUM
3,205
0.48
0.46
3,205
0.48
6,330
0.46
3,122
0.45
6,520
0.46
3,122
0.45
6,520
0.46
3,020
0.45
6,510
0.46
3,020
0.45
6,510
0.46
9,600 0.4 0.5
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 7.8 7.4 7.4 7.31 7.31
1,651 1,647 1,647 1,680 1,680
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 10 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 6
1,651
7.8
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
5,760 7,040
3,5202,880
452 528
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S):
COMMENTS: All tests proved satisfactory.
DEFICIENCIES: Acuator is not engaging the tripper bar 100% of the time. Replacing actuator is recommended.
TRIP UNIT TYPE
CNTJ99430
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 74 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
4/27/21 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER Replacement
Cuong Ho
3230,3115,01025
VA Hospital WO-08391081
1600 AMP
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 416H
65 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Not Checked
N/A
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Deficiency
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
AC Pro N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
357.7
323.9
TEST 1
TEST 3
1.165TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
357.7
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
351.8
312.2
308.7
362.3 381.0
206.2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
.70
2.5
3.0
.15
4 OFF 2 4 OFF
.3
.2
1.0
2.5
2.5
.15
.70
2.5
3.0
.15
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.2 .4
.4.3
AS FOUND
RANGE
MINIMUM MAXIMUM
0.12
0.45
0.12
5,082
0.45
0.14
4,960
0.47
0.14
4,960
0.47
3,001
0.14
5,060
0.47
3,001
0.14
5,060
0.47
7,200 0.08 0.18
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 10.45 10.11 10.11 11.01 11.01
1,636 1,624 1,624 1,641 1,641
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 7
1,636
10.45
SHORT TIME PICKUP
SHORT TIME DELAY 3
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
4,320 5,220
3,5202,880
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 74 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/21 40
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
ATS-38
David Gordon
3285,3208
VA Hospital WO-08391081
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF436LSIG
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
10 7 10
.2
1 IN
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 400RATING PLUG:400 400
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2,804
2.022
0.547
NT
2.022
0.547
NT
2.022
0.547
NT
2.022
0.547
NT
2.022
0.547
NT
2.022
0.547
2,808
1,992 1.6 2.6
168 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
1.02 9.05 9.05 9.05 9.05 9.05
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
9.05
SHORT TIME PICKUP
SHORT TIME DELAY 4.98
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY 7.02
GROUND FAULT PICKUP
GROUND FAULT DELAY 0.42
sec sec sec sec sec sec
AS LEFT
360 A A440
A A
AA
A A
1,800 2,200
3,0802,520
144 176
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 74 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
B04 NHC
David Gordon
VA Hospital WO-08391081
N/A
N/A
N/A Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONILL
200KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. ILL342501021
N/AFUSE CAT. NO.
250 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
N/A
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
GROUND SENSOR N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
412403
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT A
David Gordon
3284,3230
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
10 7 10
.2
1 OUT
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 600RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 OUT 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
4,188
1.982
0.542
NT
1.982
0.542
NT
1.982
0.542
NT
1.982
0.542
NT
1.982
0.542
NT
1.982
0.542
4,182
2,988 1.6 2.6
328 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
1.03 8.935 8.935 8.935 8.935 8.935
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
8.935
SHORT TIME PICKUP
SHORT TIME DELAY 4.98
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY 6.97
GROUND FAULT PICKUP
GROUND FAULT DELAY 0.41
sec sec sec sec sec sec
AS LEFT
540 A A660
A A
AA
A A
2,700 3,300
4,6203,780
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS: is ground fault delay setting 1 OUT or 2 OUT . The breaker was set to 2 OUT but the test report said 1 OUT.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT B
David Gordon
3285,3208
VA Hospital WO-08391081
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF436LSIG
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
2 IN
8 7 8
.2
1 IN
.9
4 IN
2 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 400RATING PLUG:400 400
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2,788
1.982
0.54
NT
1.982
0.54
NT
1.982
0.54
NT
1.982
0.54
NT
1.982
0.54
NT
1.982
0.54
2,792
1,984 1.6 2.6
164 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
1.03 8.945 8.945 8.945 8.945 8.945
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
8.945
SHORT TIME PICKUP
SHORT TIME DELAY 4.96
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY 6.98
GROUND FAULT PICKUP
GROUND FAULT DELAY 0.41
sec sec sec sec sec sec
AS LEFT
360 A A440
A A
AA
A A
1,600 2,400
3,0802,520
144 176
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 171 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-2DESIGNATION
SUBSTATION BUILDING 100
04/22/21 40
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT C
David Gordon
3285,3208
VA Hospital WO-08391081
1200 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONNE
100KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. NEF1236LSIG
N/AFUSE CAT. NO.
1200 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
N/A
N/A
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
Cleaned
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
6 7 6
.2
1 IN
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1000RATING PLUG:1200 1200
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 1 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
6,950
1.984
0.544
NT
1.984
0.544
NT
1.984
0.544
NT
1.984
0.544
NT
1.984
0.544
NT
1.984
0.544
6,950
4,950 1.6 2.8
512 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
1.01 8.93 8.93 8.93 8.93 8.93
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12.5 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
1,010
1,020
8.93
SHORT TIME PICKUP
SHORT TIME DELAY 4.95
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY 6.95
GROUND FAULT PICKUP
GROUND FAULT DELAY 0.41
sec sec sec sec sec sec
AS LEFT
990 A A1,100
A A
AA
A A
4,500 5,500
7,7006,300
432 528
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.