S06 - ET501 - DETAILS - TECHNOLOGY.pdf
PDF 795 KB Posted
- Solicitation number
- 36C25221B0002
About this file
This document package includes construction documents and specifications for the Renovate 7AN for GI/GU and Procedure Clinic project at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The project scope involves demolishing existing interior spaces and renovating approximately 11,000 square feet for a relocated GI Procedure Clinic. Mechanical, electrical, plumbing, medical gas, fire protection, and other building systems will also be updated. The estimated value is between $2-5 million. The NAICS code is 236220 with a $39.5 million size standard. The solicitation is scheduled to post on SAM.gov on or about October 15, 2020 with a bid opening of November 16, 2020. A pre-bid conference will be held. The project must be completed within 515 calendar days of the notice to proceed. The opportunity is set aside for Service-Disabled Veteran-Owned Small Businesses. Offerors must represent their SDVOSB eligibility and small business status at time of submission.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1/2"
1"
1"CAT6 CABLE
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 4826 27 28 29 3025
1/2"
242322212019181716151413121110987654321
ROOM #
JACK
PORT
A
8201-1-1 DATA
LABEL KEY
DETAIL NOTES -
1. EACH LABEL SHALL BE MECHANICALLY PRODUCED.
2. EACH LABEL SHALL CONTAIN A MINIMUM OF 6 DIGITS.
VERIFY SCHEME WITH OWNER.
3. THERE SHALL BE 4 LABELS FOR EACH WIRE INSTALLED:
TWO ON THE WIRE CABLE
ONE ON THE PATCH PANEL (DATA) OR PUNCH DOWN
(VOICE)
ONE ON THE FACE PLATE
4. ALL NEW CAT6 VOICE AND DATA CABLES SHALL BE
TERMINATED.
8201-1-1 DATA
8201-2-2
DATA
8201-3-3 DATA
8201-1-1 DATA
8201-1-1 DATA
1/2"
1"
1"CAT6 CABLE
1/2"
8201-1-1 VOICE
8201-1-1 VOICE
DATA OR VOICE
MAIN RUN BRANCH RUN
ALLOWABLE J-HOOK ARRANGEMENTS LVC TO SELECT AS CONSTRUCTION DICTATES
MAIN RUN WALL RUN
DETAIL NOTES -
KEYED NOTES -
1. J HOOK SHALL BE SIZED FOR CABLE SIZE AND LOAD.
2. SPACING BETWEEN J HOOKS 4 FEET ON CENTER.
3. INSTALL ADDITIONAL J HOOKS AS REQUIRED.
1. THIS HOOK IS DEDICATED FOR VOICE CABLING.
2. THIS HOOK IS DEDICATED FOR DATA CABLING.
3. THIS HOOK IS DEDICATED FOR TV CABLING.
4. SPARE
5. CONCRETE FLOOR
6. WORK AREA OUTLET (TYPICAL)
7. CONDUIT TO ABOVE LAY-IN CEILING
8. WALL SLEEVE
9. FLOOR ABOVE
10. HANGER SUPPORTED FROM STRUCTURE OF FLOOR
ABOVE - OR WALL
11. LAY-IN CEILING
12. J-HOOK (TYPICAL)
ATR SUPPORTWALL
SUPPORT
2 1 2
DETAIL NOTES -
E.C. TO PROVIDE AND INSTALL THE REQUIRED AMOUNT OF
BLUE (TELEPHONE) AND WHITE (DATA) ULTRA PLENUM
RATED, SCOPE, CATEGORY 6, 4 PAIR/24AWG. UTP CABLE
BETWEEN THE COMBINATION TELEPHONE/DATA OUTLET
AND THE 110-BLOCK PHONE PANEL AND DATA PATCH PANEL
IN THE DESIGNATED CLOSET INDICATED ON DRAWINGS.
ALL DATA CABLES WILL BE TERMINATED ON A CATEGORY 5E
INSERT (ON EACH END) WITH THE TIA/EIA T568A PIN
CONFIGURATION. VOICE/TELEPHONE CABLE WILL BE
TERMINATED/PUNCHED DOWN ON 110 BLOCKS IN
DESIGNATED CLOSET. THE (2) WHITE JACKETED (DATA)
CABLE WILL BE TERMINATED AT THE COMMUNICATIONS
CLOSET TO THE LEVITON EXTREME 6 UNIVERSAL PATCH
PANEL, 24 PORT, IU, LOW PROFILE, PATCH PANEL AND EACH
CABLE WILL BE MARKED AT THE MODULE AND ON THE
FRONT FACE PANEL WITH THE ROOM NUMBER AND
LOCATION.
FACE PLATES AND CATEGORY 6 INSERTS WILL BE AN IVORY
COLOR. FACE PLATE CONFIGURATION WILL BE PER
COMBINATION TELEPHONE/DATA OUTLET BOX DETAIL.
CONNECT THE CATEGORY 6 CABLE AT EACH OUTLET.
PROVIDE SUFFICIENT LENGTH OF CABLE AT 110-BLOCK
PANEL AND THE PATCH PANEL IN THE DESIGNATED CLOSET
FOR OWNER CONNECTION.
D
V
18" FROM
CENTERLIN
E OF
DEVICE
PLATE TO
FLOOR AS
NOTED
D
V
FINISHED CEILING
PROVIDE REQUIRED CABLE(S) AND
PULL STRING
3/4" PVC CONDUIT TO ACCESSIBLE
CEILING
BUSHING ON EACH
END OF CONDUIT
WALLPLATE
4" SQ. X 2 1/8" DP BOX & ONE GANG
RING, COVER PLATE AND JACK(S)
BY E.C.
RJ45 MODULAR JACK
TWO VOICE JACKS (1 & 2)
TWO DATA JACKS (3 & 4)
THIS CONFIGURATION IS
STANDARD UNLESS NOTED
ELSEWHERE ON THE DRAWINGS
1.
2.
3.
4.
TYPICAL OF COMBINATION TELEPHONE/DATA OUTLETS: (SEE DETAIL)
ELECTRICAL CONTRACTOR IS TO PROVIDE THE NECESSARY
AMOUNT OF J-HOOKS, BEAM CLAMPS, BRIDAL RINGS AND
CABLE CLIPS TO ATTACH ABOVE THE DROP CEILING
MAINTAINING A MINIMUM CLEARANCE REQUIREMENTS FROM
SUCH ITEMS AS HVAC EQUIPMENT, ELECTRICAL CONDUIT
AND FLUORESCENT LIGHTING FIXTURES.
ELECTRICAL CONTRACTOR IS TO LABEL ALL FACE PLATES
WITH PERMANENT LABELS PER REQUIREMENTS OF THE VA
CONSTRUCTION REPRESENTATIVE.
ELECTRICAL CONTRACTOR SHALL TEXT EACH AND EVERY
CATEGORY 6 CABLE INSTALLED AND TERMINATED AS PART
OF THIS PROJECT. CABLES SHALL BE TESTED WITH A
MICROTEST PENTA-SCANNER AND ARE REQUIRED TO MEET
OF EXCEED ALL CURRENT TIA/EIA STANDARDS FOR
CATEGORY 6 INSTALLATION. PRINTED TEST RESULTS WILL
BE PROVIDED FOR EACH CATEGORY 5E CABLE.
E.C. TO VERIFY POWER REQUIREMENTS FOR AIR
CONDITIONERS, AHUS, ACCU'S, ETC. PROVIDE D/S PER
EQUIPMENT IN ACCORD WITH VA STANDARDS.
E.C. TO COORDINATE POWER REQUIREMENTS, FIRE ALARM
CONNECTIONS, ETC. FOR ALL DOORS. SEE DOOR AND
HARDWARE SCHEDULE AND ARCHITECTURAL FLOOR PLAN.
5.
6.
7.
8.
9.
V
D D
V
D
V
D
V V D D
V
D D
V
D
V
WAP
PATIENT MONITOR 2D 1V1D 1V2D 2V2D
W
FURNITURE PLATE
2V2D
= BLANK INSERT
= VOICE JACK
= DATA JACK
DETAIL NOTES -
KEYED NOTES -
1. REFER TO HORIZONTAL CABLING SCHEDULE FOR
ADDITIONAL INFORMATION.
2. SEE DETAILS AND SPECIFICATIONS FOR IDENTIFICATION
REQUIREMENTS.
1. PROVIDE 302 S.S. WALL PHONE PLATE
2. PROVIDE PLASTIC ANGLED FACE PLATE COLOR IVORY.
3. PROVIDE FURNITURE PLATE MATCHING OWNER
EQUIPMENT.
4. PROVIDE 'F' CONNECTOR.
5. PROVIDE SURFACE MOUNT WAP BOX ABOVE CEILING.
6. PROVIDE 4-PORT FACEPLATE.
7. FACEPLATES SHALL ALLOW JACKS TO BE MOUNTED AT
A 45 DEGREE DOWNWARD ANGLE PROVIDING BEND
RADIUS PROTECTION AND STRAIN RELIEF ON THE
CABLES AND CONNECTION POINTS.
8. PROVIDE 6-PORT FACEPLATE.
2 2 2 2 2
D
TV
2 6
IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION
IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION
IDENTIFICATION
IDENTIFICATION
D D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
MGM MTP
C
R e v it L o c a lF ile s \9
-E
M
P e re z ri n g d u .c o m
.r v t
/1 /2
:1
:0
A M
ET501
DETAILS - TECHNOLOGY
GUIDON DESIGN INC.
1221 N. Pennsylvania St.
Suite 200
Indianapolis, Indiana 46202
317.800.6388
RING & DUCHATEAU, LLP.
17400 W. Capital Drive
Brookfield, WI 53045
414.778.1700
RENOVATE 7AN FOR GI GU &
PROCEDURE CLINIC
5000 W National Ave, Milwaukee, WI 53295
695-19-107
8/21/2020
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
SCALE: NOT TO SCALEET501
2 TYPICAL CABLE IDENTIFICATION DETAIL
SCALE: NOT TO SCALEET501
3 TYPICAL CABLE SUPPORTS
SCALE: NOT TO SCALEET501
1 TYPICAL COMBINATION DATA/TELEPHONE OUTLET BOX DETAIL
SCALE: NOT TO SCALEET501
4 TYPICAL SYSTEMS FACEPLATE DETAIL
Revisions: Date:
Addendum 1 11/13/2020
ACCOMPANYING 36C25221B0002 0002
VHAMIWBeierJ Text Box Amendment 0002
VHAMIWBeierJ Text Box 11/17/2020
| Sheets |
| ET501 - DETAILS - TECHNOLOGY |
File details come from the government source that posted it. Updated .