This document package includes construction documents and specifications for the Renovate 7AN for GI/GU and Procedure Clinic project at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The project scope involves demolishing existing interior spaces and renovating approximately 11,000 square feet for a relocated GI Procedure Clinic. Mechanical, electrical, plumbing, medical gas, fire protection, and other building systems will also be updated. The estimated value is between $2-5 million. The NAICS code is 236220 with a $39.5 million size standard. The solicitation is scheduled to post on SAM.gov on or about October 15, 2020 with a bid opening of November 16, 2020. A pre-bid conference will be held. The project must be completed within 515 calendar days of the notice to proceed. The opportunity is set aside for Service-Disabled Veteran-Owned Small Businesses. Offerors must represent their SDVOSB eligibility and small business status at time of submission.

View the file

Other files

File Type Posted
36C25221B0002 0003.docx DOCX document
S06 - ET101 - SEVENTH FLOOR PLAN - TECHNOLOGY - Amd03.pdf PDF
36C25221B0002 0002.docx DOCX document
S06 - Appendix E - Physicist Report.pdf PDF
S06 - AE501 - BUILDING DETAILS.pdf PDF
S06 - EP602 - SCHEDULES POWER.pdf PDF
S06 - ET101 - SEVENTH FLOOR PLAN - TECHNOLOGY.pdf PDF
S06 - DG107 - SEVENTH FLOOR MEDICAL GAS PLAN.pdf PDF
S06 - 08 71 13.11 - LOW ENERGY DOOR OPERATORS Amend No2.pdf PDF
S06 - 7AN_ShieldingReport_20200601.pdf PDF
S06 - AE002 - WALL TYPES.pdf PDF
S06 - AE101 - SEVENTH FLOOR ARCHITECTURAL PLAN.pdf PDF
S06 - 11 73 00 - CEILING MOUNT PATIENT LIFT Amend No2.pdf PDF
S06 - GC101 - INFECTION CONTROL_PHASING PLAN.pdf PDF
S06 - EP401 - POWER RISERS.pdf PDF
S04 - Site Visit Sign-In Sheet - 695-19-107.pdf PDF
36C25221B0002 0001.docx DOCX document
S02 - Wage Determination Effective 10.2.2020.pdf PDF
S02 - J_A 695-19-107_Door Hardware.pdf PDF
S02 - J_A 695-19-107_HVAC BAS.pdf PDF
S02 - 695-19-107_2020.09.24_Volume 2 Specifications 100percent.pdf PDF
S02 - 695-19-107_2020.09.24_Volume 1 Specifications 100percent.pdf PDF
S02 - J_A 695-19-107_Interior Signage.pdf PDF
S02 - J_A 695-19-107_Firestop Systems.pdf PDF
S02 - 695-19-107 Drawing Set Updated.pdf PDF
S02 - J_A 695-19-107_Medical Gas Systems.pdf PDF
36C25221B0002_1.docx DOCX document
S02 - J_A 695-19-107_Card Readers.pdf PDF
S02 - J_A 695-19-107_Nurse Call.pdf PDF
S02 - J_A 695-19-107_Fire Alarm System.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/2"

1"

1"CAT6 CABLE

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 4826 27 28 29 3025

1/2"

242322212019181716151413121110987654321

ROOM #

JACK

PORT

A

8201-1-1 DATA

LABEL KEY

DETAIL NOTES -

1. EACH LABEL SHALL BE MECHANICALLY PRODUCED.

2. EACH LABEL SHALL CONTAIN A MINIMUM OF 6 DIGITS.

VERIFY SCHEME WITH OWNER.

3. THERE SHALL BE 4 LABELS FOR EACH WIRE INSTALLED:

TWO ON THE WIRE CABLE

ONE ON THE PATCH PANEL (DATA) OR PUNCH DOWN

(VOICE)

ONE ON THE FACE PLATE

4. ALL NEW CAT6 VOICE AND DATA CABLES SHALL BE

TERMINATED.

8201-1-1 DATA

8201-2-2

DATA

8201-3-3 DATA

8201-1-1 DATA

8201-1-1 DATA

1/2"

1"

1"CAT6 CABLE

1/2"

8201-1-1 VOICE

8201-1-1 VOICE

DATA OR VOICE

MAIN RUN BRANCH RUN

ALLOWABLE J-HOOK ARRANGEMENTS LVC TO SELECT AS CONSTRUCTION DICTATES

MAIN RUN WALL RUN

DETAIL NOTES -

KEYED NOTES -

1. J HOOK SHALL BE SIZED FOR CABLE SIZE AND LOAD.

2. SPACING BETWEEN J HOOKS 4 FEET ON CENTER.

3. INSTALL ADDITIONAL J HOOKS AS REQUIRED.

1. THIS HOOK IS DEDICATED FOR VOICE CABLING.

2. THIS HOOK IS DEDICATED FOR DATA CABLING.

3. THIS HOOK IS DEDICATED FOR TV CABLING.

4. SPARE

5. CONCRETE FLOOR

6. WORK AREA OUTLET (TYPICAL)

7. CONDUIT TO ABOVE LAY-IN CEILING

8. WALL SLEEVE

9. FLOOR ABOVE

10. HANGER SUPPORTED FROM STRUCTURE OF FLOOR

ABOVE - OR WALL

11. LAY-IN CEILING

12. J-HOOK (TYPICAL)

ATR SUPPORTWALL

SUPPORT

2 1 2

DETAIL NOTES -

E.C. TO PROVIDE AND INSTALL THE REQUIRED AMOUNT OF

BLUE (TELEPHONE) AND WHITE (DATA) ULTRA PLENUM

RATED, SCOPE, CATEGORY 6, 4 PAIR/24AWG. UTP CABLE

BETWEEN THE COMBINATION TELEPHONE/DATA OUTLET

AND THE 110-BLOCK PHONE PANEL AND DATA PATCH PANEL

IN THE DESIGNATED CLOSET INDICATED ON DRAWINGS.

ALL DATA CABLES WILL BE TERMINATED ON A CATEGORY 5E

INSERT (ON EACH END) WITH THE TIA/EIA T568A PIN

CONFIGURATION. VOICE/TELEPHONE CABLE WILL BE

TERMINATED/PUNCHED DOWN ON 110 BLOCKS IN

DESIGNATED CLOSET. THE (2) WHITE JACKETED (DATA)

CABLE WILL BE TERMINATED AT THE COMMUNICATIONS

CLOSET TO THE LEVITON EXTREME 6 UNIVERSAL PATCH

PANEL, 24 PORT, IU, LOW PROFILE, PATCH PANEL AND EACH

CABLE WILL BE MARKED AT THE MODULE AND ON THE

FRONT FACE PANEL WITH THE ROOM NUMBER AND

LOCATION.

FACE PLATES AND CATEGORY 6 INSERTS WILL BE AN IVORY

COLOR. FACE PLATE CONFIGURATION WILL BE PER

COMBINATION TELEPHONE/DATA OUTLET BOX DETAIL.

CONNECT THE CATEGORY 6 CABLE AT EACH OUTLET.

PROVIDE SUFFICIENT LENGTH OF CABLE AT 110-BLOCK

PANEL AND THE PATCH PANEL IN THE DESIGNATED CLOSET

FOR OWNER CONNECTION.

D

V

18" FROM

CENTERLIN

E OF

DEVICE

PLATE TO

FLOOR AS

NOTED

D

V

FINISHED CEILING

PROVIDE REQUIRED CABLE(S) AND

PULL STRING

3/4" PVC CONDUIT TO ACCESSIBLE

CEILING

BUSHING ON EACH

END OF CONDUIT

WALLPLATE

4" SQ. X 2 1/8" DP BOX & ONE GANG

RING, COVER PLATE AND JACK(S)

BY E.C.

RJ45 MODULAR JACK

TWO VOICE JACKS (1 & 2)

TWO DATA JACKS (3 & 4)

THIS CONFIGURATION IS

STANDARD UNLESS NOTED

ELSEWHERE ON THE DRAWINGS

1.

2.

3.

4.

TYPICAL OF COMBINATION TELEPHONE/DATA OUTLETS: (SEE DETAIL)

ELECTRICAL CONTRACTOR IS TO PROVIDE THE NECESSARY

AMOUNT OF J-HOOKS, BEAM CLAMPS, BRIDAL RINGS AND

CABLE CLIPS TO ATTACH ABOVE THE DROP CEILING

MAINTAINING A MINIMUM CLEARANCE REQUIREMENTS FROM

SUCH ITEMS AS HVAC EQUIPMENT, ELECTRICAL CONDUIT

AND FLUORESCENT LIGHTING FIXTURES.

ELECTRICAL CONTRACTOR IS TO LABEL ALL FACE PLATES

WITH PERMANENT LABELS PER REQUIREMENTS OF THE VA

CONSTRUCTION REPRESENTATIVE.

ELECTRICAL CONTRACTOR SHALL TEXT EACH AND EVERY

CATEGORY 6 CABLE INSTALLED AND TERMINATED AS PART

OF THIS PROJECT. CABLES SHALL BE TESTED WITH A

MICROTEST PENTA-SCANNER AND ARE REQUIRED TO MEET

OF EXCEED ALL CURRENT TIA/EIA STANDARDS FOR

CATEGORY 6 INSTALLATION. PRINTED TEST RESULTS WILL

BE PROVIDED FOR EACH CATEGORY 5E CABLE.

E.C. TO VERIFY POWER REQUIREMENTS FOR AIR

CONDITIONERS, AHUS, ACCU'S, ETC. PROVIDE D/S PER

EQUIPMENT IN ACCORD WITH VA STANDARDS.

E.C. TO COORDINATE POWER REQUIREMENTS, FIRE ALARM

CONNECTIONS, ETC. FOR ALL DOORS. SEE DOOR AND

HARDWARE SCHEDULE AND ARCHITECTURAL FLOOR PLAN.

5.

6.

7.

8.

9.

V

D D

V

D

V

D

V V D D

V

D D

V

D

V

WAP

PATIENT MONITOR 2D 1V1D 1V2D 2V2D

W

FURNITURE PLATE

2V2D

= BLANK INSERT

= VOICE JACK

= DATA JACK

DETAIL NOTES -

KEYED NOTES -

1. REFER TO HORIZONTAL CABLING SCHEDULE FOR

ADDITIONAL INFORMATION.

2. SEE DETAILS AND SPECIFICATIONS FOR IDENTIFICATION

REQUIREMENTS.

1. PROVIDE 302 S.S. WALL PHONE PLATE

2. PROVIDE PLASTIC ANGLED FACE PLATE COLOR IVORY.

3. PROVIDE FURNITURE PLATE MATCHING OWNER

EQUIPMENT.

4. PROVIDE 'F' CONNECTOR.

5. PROVIDE SURFACE MOUNT WAP BOX ABOVE CEILING.

6. PROVIDE 4-PORT FACEPLATE.

7. FACEPLATES SHALL ALLOW JACKS TO BE MOUNTED AT

A 45 DEGREE DOWNWARD ANGLE PROVIDING BEND

RADIUS PROTECTION AND STRAIN RELIEF ON THE

CABLES AND CONNECTION POINTS.

8. PROVIDE 6-PORT FACEPLATE.

2 2 2 2 2

D

TV

2 6

IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION

IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

D D

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

MGM MTP

C

R e v it L o c a lF ile s \9

-E

M

P e re z ri n g d u .c o m

.r v t

/1 /2

:1

:0

A M

ET501

DETAILS - TECHNOLOGY

GUIDON DESIGN INC.

1221 N. Pennsylvania St.

Suite 200

Indianapolis, Indiana 46202

317.800.6388

RING & DUCHATEAU, LLP.

17400 W. Capital Drive

Brookfield, WI 53045

414.778.1700

RENOVATE 7AN FOR GI GU &

PROCEDURE CLINIC

5000 W National Ave, Milwaukee, WI 53295

695-19-107

8/21/2020

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

SCALE: NOT TO SCALEET501

2 TYPICAL CABLE IDENTIFICATION DETAIL

SCALE: NOT TO SCALEET501

3 TYPICAL CABLE SUPPORTS

SCALE: NOT TO SCALEET501

1 TYPICAL COMBINATION DATA/TELEPHONE OUTLET BOX DETAIL

SCALE: NOT TO SCALEET501

4 TYPICAL SYSTEMS FACEPLATE DETAIL

Revisions: Date:

Addendum 1 11/13/2020

ACCOMPANYING 36C25221B0002 0002

VHAMIWBeierJ Text Box Amendment 0002

VHAMIWBeierJ Text Box 11/17/2020

Sheets
ET501 - DETAILS - TECHNOLOGY