This document contains a pre-solicitation notice and construction documents for a federal contract opportunity to renovate the 7th floor A-wing north of Building 111 at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The contractor shall demolish existing interior spaces and renovate approximately 11,000 square feet for a relocated GI Procedure Clinic, updating mechanical, electrical, plumbing, medical gas, fire protection and pneumatic tube systems. The project magnitude is estimated between $2 million and $5 million. The North American Industry Classification System code is 236220 with a size standard of $39.5 million. The completion period is 515 calendar days from notice to proceed. The solicitation will be posted to https://beta.sam.gov/ on or about October 15, 2020 with a bid opening of November 16, 2020. A pre-bid conference will be held at an unspecified date. The opportunity is set aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2-1/2"C.
250 kcmil &3
#4 GRD1
COPPER
MC
MC
1-1/2"C.
#3 &4
#8 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
1"C.
#6 &3
#10 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
P: 480V DELTA
S: 208Y/120V
EE 150°C
DT 30 kVA
MC
1"C.
#8 &4
#8 GRD1
COPPER
1-1/2"C.
#2 &3
#2 GRD1
COPPER
RMS SYM @ 480 VOLTS
480/277 VOLTS 3Ø 4W
POWER PANEL CONSTRUCTION
65k AMPS
GROUP MOUNTED
SS
L2
2-1/2"C.
#1/0 &4
#1/0 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
1-1/2"C.
#3 &4
#8 GRD1
COPPER
P: 480V DELTA
S: 208Y/120V
EE 150°C
DT 30 kVA
FS
1"C.
#8 &4
#8 GRD1
COPPER
1"C.
#8 &4
#8 GRD1
COPPER
1. RELOCATE DISCONNECT IN ORDER TO ACHIEVE NEC CLEARANCE.
2. PROVIDE NEW SOLID STATE MAIN CIRCUIT BREAKER WITH MINIMUM
14kAIC RATING.
3. REMOVE EXISTING PANELBOARD. COORDINATE TRANSFER OF
EXISTING BRANCH CIRCUITS AND OUTAGE WITH VA COR PRIOR TO
DEMOLITION.
4. PROVIDE ALL NECESSARY MOUNTING HARDWARE AND
ACCESSORIES TO RETROFIT NEW BREAKER INTO EXISTING PANEL.
5. EPO CONTACTS TO BE NORMALLY CLOSED, WIRED IN SERIES,
CONNECTED TO UPS ONLY.
6. UPS AND XFRMR CABINET TO BE FURNISHED BY SIEMENS,
ELECTRICAL CONTRACTOR TO INSTALL. COORDINATE THE WIRING
HARNESS BETWEEN THE UPS AND THE TRANSFORMER CABINET
PRIOR TO INSTALL. INCLUDE NEW WIRING AND FLEX CONNECTION
BETWEEN BOTH UNITS IN BASE BID. REFER TO FINAL SIEMENS
DRAWINGS FOR ADDITIONAL INFORMATION.
7. PROVIDE FUSIBLE DISCONNECT WITH RK5 FUSES.
8. ELECTRICAL EQUIPMENT WILL BE FURNISHED BY VA PROJECT
695-19-131. VA PROJECT 695-19-107 WILL BE CONSTRUCTED
SHORTLY AFTER VA PROJECT 695-19-131. THEREFORE, THIS
EQUIPMENT IS ESSENTIALLY “EXISTING” TO THE 7AN/ENDOSCOPY
CONTRACTOR. THE ELECTRICAL CONTRACTOR UNDER THIS
PROJECT DOES HAVE ADDITIONAL COMPONENTS TO INSTALL IN THIS
EXISTING EQUIPMENT. EQUIPMENT INFORMATION IS NOT AVAILABLE
DURING TIME OF DESIGN. MANUFACTURER AND EQUIPMENT
INFORMATION WILL BE PROVIDED UPON DISTRIBUTION OF FINAL
APPROVED SHOP DRAWINGS.
9. PROVIDE PANELBOARD FOR SIEMENS EQUIPMENT. INTENT IS TO
HAVE PANEL FLUSHED MOUNTED IN ROOM, BUT CAN BE SURFACE
MOUNTED. COORDINATE FINAL LOCATION WITH SIEMENS PROJECT
MANAGER, ENGINEER, AND VA COR PRIOR TO INSTALL.
SCALE: NOT TO SCALE
EP401SCALE: NOT TO SCALE
EP401SCALE: NOT TO SCALE
EP401
SCALE: NOT TO SCALE
EP401 SCALE: NOT TO SCALE
EP401
SCALE: NOT TO SCALE
EP401
SCALE: NOT TO SCALE
EP401
SCALE: NOT TO SCALE
EP401
1. PROVIDE SELECTIVE COORDINATION FOR ALL NEW CIRCUIT
BREAKERS ASSOCIATED WITH THE EMERGENCY SYSTEM PER THE
NEC (LIFE SAFETY, CRITICAL, AND EQUIPMENT BRANCH).
PB EUL
CR72-1
CB
LL-72-1
CB
UL-72-1
PB-LH
71-1
PB UL
72-1
PB UL
72-1
CB
UL-71-2/3
PB-UL
71-2
DS
SC1
EUL-CR
72-1
EX FEEDER
FED FROM
EDH-22-CR-2
LL
72-1
EX FEEDER
FED FROM
DL-B02-1
ELH-LS
91-1
EX
100A FEEDER
EX
100A FEEDER
LH
71-1
100 A
3P
UL
72-1
EX FEEDER
FED FROM
DL-B02-1
100 A
3P
UL
72-2
EX FEEDER
FROM
EDH-307-Q-4
EPH-Q
71-1
EUL-Q
71-1
UL
71-2/3
EX FEEDER
FED FROM
DL-B02-1
100 A
3P
MP
SC1
PU1
1200AMPS @
MAIN SECTION:
DISTRIBUTION SECTION:
MIN AIC RATING =
FED FROM SWB-2
125AT
3P
250AF
SQUARE D I-LINE 5486-12U
EUL-CR
72-1
ELL-LS
91-1
EPO
UPS
XFMR
30AS
3P
30AF
LOW VOLTAGE DISCONNECT SWITCH INFORMATION
PARTIAL ONE LINE DIAGRAM - NORMALPARTIAL ONE LINE DIAGRAM-NORMALPARTIAL ONE LINE DIAGRAM-CRITICAL
PARTIAL ONE LINE DIAGRAM - EQUIPMENT
PARTIAL ONE LINE DIAGRAM-LIFE SAFETY PARTIAL ONE LINE DIAGRAM-NORMAL
KEYED NOTES -
7TH FLOOR A NORTH7TH FLOOR A NORTH7TH FLOOR A NORTH
9TH FLOOR A SOUTH 7TH FLOOR AREA A NORTH
7TH FLOOR AREA A SOUTH
T/EULQ711
PARTIAL ONE LINE DIAGRAM-NORMAL
7TH FLOOR A SOUTH
EPH-Q-24-1
PARTIAL ONE LINE DIAGRAM - NORMAL
7TH FLOOR AREA A NORTH
SHEET NOTES -
T/ELLLS911
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
MGM MTP
C
R e v it L o c a lF ile s \9
-E
M
P e re z ri n g d u .c o m
.r v t
/1 /2
:1
:0
A M
EP401
POWER RISERS
GUIDON DESIGN INC.
1221 N. Pennsylvania St.
Suite 200
Indianapolis, Indiana 46202
317.800.6388
RING & DUCHATEAU, LLP.
17400 W. Capital Drive
Brookfield, WI 53045
414.778.1700
RENOVATE 7AN FOR GI GU &
PROCEDURE CLINIC
5000 W National Ave, Milwaukee, WI 53295
695-19-107
8/21/2020
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
Addendum 1 11/13/2020
ACCOMPANYING 36C25221B0002 0002
VHAMIWBeierJ Text Box Amendment 0002
VHAMIWBeierJ Text Box 11/17/2020
| Sheets |
| EP401 - POWER RISERS |
| EP601 - SCHEDULE POWER |
| EP602 - SCHEDULES POWER |
| ET101 - SEVENTH FLOOR PLAN - TECHNOLOGY |
| ET501 - DETAILS - TECHNOLOGY |
File details come from the government source that posted it. Updated .