05 Architectural 54218106_Drawings_FinalCD_013120.pdf

PDF 25 MB Posted

Attached to
Z2DA--Renovate Building 4 A + B Floors Outpatient Mental Health Clinic, Project No. 542-18-106
Solicitation number
36C24420B0003
Issued by

About this file

This solicitation is for construction services to renovate approximately 28,000 square feet of existing space and 3,000 square feet of basement space at a Department of Veterans Affairs medical facility in Coatesville, Pennsylvania into an outpatient mental health clinic. The scope of work includes total demolition and renovation of the first and second floors, as well as renovations to the basement, and construction of a new elevator and exterior improvements. Disciplines involved are site work, structural, mechanical, plumbing, electrical and more.

The solicitation will be available on June 23, 2020 via the System for Award Management website. The procurement is valued between $10-20 million based on the North American Industry Classification System code for general building construction. Interested service-disabled veteran-owned small businesses must register in the System for Award Management, meet certification requirements through the Veterans Affairs Center for Verification and Evaluation, and comply with Occupational Safety and Health Administration and Environmental Protection Agency regulations to be considered for award. The contract type will be firm-fixed price with a performance period of 588 calendar days from notice to proceed.

View the file

Other files

File Type Posted
Award Announcement 36C24420C0112.pdf PDF
General Decision Number PA20200083.pdf PDF
36C24420B0003 0003.pdf PDF
00 01 15 - List of Drawing Sheets - ADD-01.pdf PDF
07 Architecture.pdf PDF
36C24420B0003 Amendment 0002.pdf PDF
10 22 26.13 - Operable Partitions - ADD-01.pdf PDF
RFI LOG_542-18-106_08052020.r2.pdf PDF
Sign In Sheet no. 3 B4A B 07162020.pdf PDF
Sign In Sheet B4A B 07162020.pdf PDF
03 Structural 54218106_Drawings_ADD-01_080320.pdf PDF
A012 54218106_Drawings_FinalCD_013120.pdf PDF
08 Interiors 54218106_Drawings_ADD-01_080320.pdf PDF
07 13 52 - Modified Bituminous Sheet Waterproofing - ADD-01.pdf PDF
07 60 00 - Flashing and Sheet Metal - ADD-01.pdf PDF
01 33 23 - Shop Drawings Product Data Samples - ADD-01.pdf PDF
00 01 10 - TOC - ADD-01.pdf PDF
11 Plumbing 54218106_Drawings_ADD-01_080320.pdf PDF
ADD-01 Narrative.pdf PDF
10 21 13 - Toilet Compartments - ADD-01.pdf PDF
07 27 27 - Fluid-Applied Membrane Air Barrier Vapor Retardg - ADD-01.pdf PDF
00 General 54218106_Drawings_ADD-01_080320.pdf PDF
11 73 00 - Ceiling Mounted Patient Lift System - ADD-01.pdf PDF
36C24420B0003 Amendment 0001 - Attachment.pdf PDF
36C24420B0003 AMENDMENT 0001.pdf PDF
36C24420B0003 MAP for Site Visit.pdf PDF
04 Structural 54218106_Drawings_FinalCD_013120.pdf PDF
10 Mechanical 54218106_Drawings_FinalCD_013120.pdf PDF
06 Interiors 54218106_Drawings_FinalCD_013120.pdf PDF
09 Plumbing 54218106_Drawings_FinalCD_013120.pdf PDF
08 Fire Protection 54218106_Drawings_FinalCD_013120.pdf PDF
02 Hazardous 54218106_Drawings_FinalCD_013120.pdf PDF
07 Equipment 54218106_Drawings_FinalCD_013120.pdf PDF
01 General 54218106_Drawings_FinalCD_013120.pdf PDF
11 Electrical 54218106_Drawings_FinalCD_013120.pdf PDF
03 Civil Landscape 54218106_Drawings_FinalCD_013120.pdf PDF
54218106-Spec-Vol 3_FinalCD_013120.pdf PDF
36C24420B0003.docx DOCX document
PCRA 3-2019 building 4.pdf PDF
54218106-Spec-Vol 2_FinalCD_013120.pdf PDF
54218106-Spec-Vol 1_FinalCD_013120.pdf PDF
COVID Guidelines.pdf PDF
54218106-Spec-Vol 4_FinalCD_013120.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EARTH

GRAVEL

CONCRETE

CONCRETE MASONRY UNIT,

CLAY TILE, OR MIXTURE

BRICK MASONRY

STEEL/STAINLESS STEEL

ALUMINUM

WOOD BLOCKING / FRAMING SHIM OR NAILER

PLYWOOD

HARDWOOD

RIGID INSULATION

BATT INSULATION

MORTAR/SAND/STUCCO/GYPSUM

BOARD SURFACE

ACOUSTIC CEILING

CERAMIC TILE

SECTION NUMBER

SHEET WHERE DRAWN

DETAIL NUMBER

SHEET WHERE DRAWN

NAME OF LEVEL

HEIGHT ABOVE PROJECT

DATUM

XXX

X

XXXX

BUILDING &

WALL SECTION

EXTERIOR ELEVATION

DETAIL BUBBLE

SECTION DETAIL

INTERIOR ELEVATION

(MULTIPLE)

INTERIOR ELEVATION (SINGLE)

PARTITION TYPE

WINDOW NUMBER

DOOR NUMBER

ROOM TAG

ELEVATION TAG

DRAWING TITLE AND SCALE

EQUIPMENT NUMBER

NOTE:

SEE CORRESPONDING NUMBERED LIST ON SHEET

WHERE TAG OCCURS UNLESS NOTED OTHERWISE.

Room name

XXX

ELEVATION

0'-0"

View Name 1/8" = 1'-0"

NORTH ARROW

REVISION NUMBER

X

XXXX

X

XXXX

X

XXXX

X

X

X

X

ELEVATION NUMBER AND SHEET

WHERE DRAWN

XXXX

X

XX

XX

XXX REVISION NUMBER

ROOM NAME

ROOM

NUMBER

ELEVATION NUMBER

SHEET WHERE DRAWN

ELEVATION NUMBER

AND DIRECTION OF

VIEW

SHEET WHERE DRAWN

DETAIL NUMBER

SHEET WHERE DRAWN

/XXXXX

Ref View Name

0 4' 8' 16'

KEYNOTE TAG DEMOLITIONXX

XX KEYNOTE TAG NEW CONSTRUCTION

4'

M A

X F

O R

C O

N T

R O

LS

F O

R C

O N

T R

O

LS

3'

M

IN

G R

A B

B A

R

2'

T Y

P

2'

(RECESSED)

2'

TOILET TISSUE DISPENSERS

(CENTERED IN

PARTITION)

(SURFACE)

1'

TOP

OF

UNIT

1'

M

IN

3'

T Y

P

DISPENSER

2'

SEAT - COVER

DISPENSER

SANITARY

NAPKIN

DISPOSAL

(RECESSED - SHOWN)

N O

N

A C

C E

S S

IB

LE

5'

3'

2'

COMBINATION TOILET COMPARTMENT ACCESSORIES

PARTITION MOUNTED OR RECESSED SANITARY NAPKIN

DISPOSAL / TOILET

TISSUE DISPENSER

4'

M A

X F

O R

C O

N T

R O

LS

F O

R C

O N

T R

O

LS

3'

M

IN

3'

DISPENSER

R E

C O

M E

N D

E D

T O

5"

3'

M A

X

2'

M

IN

R E

C O

M E

N D

E D

5'

PAPER TOWEL DISPENSERS WASTE RECEPTACLES

(RECESSED) (SURFACE MTD)

PAPER TOWEL DISPENSER / WASTE RECEPTACLES

(RECESSED

& FULLY

RECESSED)

(RECESSED) (RECESSED)

3'

DISPENSER

3'

COIN

SLOT

R E

C O

M E

N D

E D

3'

PUSH

BUTTON

R E

C O

M E

N D

E D

3'

M A

X A

B O

V E

L A

V A

T O

R Y

3'

M

AX

O

TH

ER

L

O

CA

TI

O

NS

(T

O B

O

TT

O M

O F

RE

FL

EC

TI

VE

SU

RF

AC

E)

SANITARY

NAPKIN / TAMPON

VENDORS

(RECESSED

&SURFACE)

SOAP

DISPENSERS

HAND

DRYER

(SURFACE)

ALL FRAMED

MIRRORS

(SURFACE)

2'

9"

CLOCK OR

CLOCK OUTLET

MANUAL FIRE ALARM

PULL

STATION

LIGHT SWITCH &

DIMMER

DUPLEX

OUTLET

DUPLEX

OUTLET

DESK

INTERCOM

OUTLET

INTERCOM STATION TELECOMM

OUTLET

THERMOSTAT SPECIAL

PURPOSE

OUTLETS

SPECIAL

PURPOSE

OUTLETS

JUNCTION BOX WALL-MTD

TELEPHONE

OUTLET

MEDICAL

GAS ALARM

PANEL

FEC OR

FHV

CABINET

ELECTRICAL

PANELBOARD

(FLUSH MTD)

ELECTRICAL

PANELBOARD

(SURFACE MTD)

COAT

HOOKS

(WALL-MTD)

COAT

HOOK

(DOOR-MTD)

CHALKBOARD,

TACKBOARD, OR DRY

MARKER BOARD

RACEWAY

7'

4'

4' -0

M

A X

H

IG

H R

E A

C H

3' -0

M

IN

F

O R

C O

N T

R O

LS

1' -3

M

IN

L

O W

R E

A C

H

1'

4'

M A

X H

IG

H

R E

A C

H

3'

M

IN

F O

R C

O N

T R

O

LS

1' - 0"

3'

6'

2'

M A

X

6'

6"

5'

4'

EQ EQ

6'

7'

4'

5'

ROBE

HOOK

(TYPICAL)

ROBE HOOK

(ACCESSIBLE)

CLOTHES HOOK AND

BUMPER FOLDING

UTILITY SHELF

TOILET

PARTITION

TOP

OF

UNIT

TOP

OF

UNIT

STAINLESS

STEEL SHELF

(BELOW GRAB

BAR)

MOP & BROOM

HOLDER

SHELF WITH

MOP & BROOM

HOLDER &

HOOKS

SHELF WITH

MOP & BROOM

HOLDER &

HOOKS

DIAPER CHANGING

STATION

(SURFACE MTD)

1'

1'

6'

5'

5'

CARD READER,

LOCAL ALARM, OR

ARMING STATION

DARK ROOM

STATUS LIGHT

SWITCH AT

DOOR OR

CASED OPENING

AUDIBLE

AND/OR VISUAL FIRE

ALARM

SECURITY

STROBE LIGHT

(BLUE LIGHT)

FIREMAN'S

TELEPHONE

JACK

DISCONNECT

SWITCH &

MOTOR STARTER

EMERGENCY

STROBE OR

LIGHT AND/OR

NURSE CALL

LIGHT

A

LI

G N

W

IT

H T

O P

O F

A D

JA

C

E N

T F

R A

M E

8" TYP 8" TYP

4'

7'

7'

7'

4'

5'

FEC OR

FHV CABINET,

SURFACE MOUNTED AT

BASEMENT LEVEL ONLY

3'

4'

- 0

TYP.

6"

HA

ND

RA

IL

3'

- 0

STANARD HANDRAIL &

WALL PROTECTION

DETAIL

1'

- 2

4'

- 0

WALL CORNER GUARD

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

31 JAN 2020

ARCHITECTURAL

ABBREVIATIONS & SYMBOLS

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

A001

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

RM ROOM R

RO ROUGH OPENING R

S

BOD BASIS OF DESING S

S SOUTH S

SAN SANITARY S

SCHED SCHEDULE S

SF SQUARE FOOT (FEET) S

SHT SHEET S

SIM SIMILAR S

SOW SCOPE OF WORK S

SPEC SPECIFICATION S

SPKLR SPRINKLER S

SPKR SPEAKER S

SQ SQUARE S

SS STAINLESS STEEL S

STD STANDARD S

STL STEEL S

STOR STORAGE S

STRUCT STRUCTURAL S

SUSP SUSPEND S

SV SHEET VINYL S

T

T&G TONGUE AND GROOVE T

T/ TOP OF T

TEMP TEMPERED T

TERR TERRAZZO T

THK THICK T

TO TOP OF T

TSTAT THERMOSTAT T

TYP TYPICAL T

U

UNO UNLESS NOTED OTHERWISE U

V

VAR VARIES V

VC VA SUPPLIED, CONTRACTOR INSTALLED V

VCT VINYL COMPOSITION TILE V

VENT VENTILATION V

VIF VERIFY IN FIELD V

VOL VOLUME V

VV VA SUPPLIED & INSTALLED V

VWC VINYL WALL COVERING V

W

W WEST W

W/ WITH W

W/O WITHOUT W

WC WALL COVERING W

WD WOOD W

WDW WINDOW W

WWM WELDED WIRE FABRIC W

LT LT L

M

M/E/P/FP MECHANICAL, ELECTRICAL, PLUMBING & FIRE

PROTECTION

M

MATL MATERIAL M

MAX MAXIMUM M

MECH MECHANICAL M

MFR MANUFACTURER M

MIN MINIMUM M

MISC MISCELLANEOUS M

MLWK MILLWORK M

MO MASONRY OPENING M

MR MOISTURE RESISTANT M

MTD MOUNTED M

MTG MOUNTING M

MTL METAL M

N

N NORTH N

N/A NOT APPLICABLE N

NAT NATURAL N

NIC NOT IN CONTRACT N

NO NUMBER N

NTS NOT TO SCALE N

O

OA OVERALL O

OC ON CENTER O

OFIC OWNER FURNISHED INSTALLED BY

CONTRACTOR

O

OH OPPOSITE HAND O

OPNG OPENING O

OPT OPTIONAL O

P

P PLUMBING P

PAT PATTERN P

PL PLUMBING P

PLAM PLASTIC LAMINATE P

PLAS PLASTER OR PLASTIC P

PR PAIR P

PRE PREFINISHED P

PREP PREPARATION P

PROVIDE FURNISH AND INSTALL P

PT PAINT P

PTME PAINT TO MATCH EXISTING P

PTN PARTITION P

PWR POWER P

Q

QT QUARRY TILE Q

QTR QUARTER Q

QTY QUANTITY Q

R

R RADIUS R

RB RESILIENT BASE R

RCP REFLECTED CEILING PLAN R

REC RECESSED R

RECPT RECEPTACLE R

REINF REINFORCED R

REQD REQUIRED R

E

E

E EAST E

EA EACH E

EJ EXPANSION JOINT E

EL ELEVATION E

ELEC ELECTRICAL E

ELEV ELEVATOR E

ENCL ENCLOSURE E

EQ EQUAL E

EQUIP EQUIPMENT E

EWC ELECTRIC WATER COOLER E

EXH EXHAUST E

EXIST EXISTING E

EXP EXPOSED E

EXT EXTERIOR E

F

FA FIRE ALARM F

FD FLOOR DRAIN F

FDN FOUNDATION F

FE FIRE EXTINGUISHER F

FEC FIRE EXTINGUISHER CABINET F

FF&E FURNITURE, FIXTURE AND EQUIPMENT F

FHC FIRE HOSE CABINET F

FIG FIGURE F

FIN FINISH F

FIXT FIXTURE F

FL FLOOR F

FO FACE OF F

FP FIRE PROTECTION OR FIREPROOF F

FT FOOT F

FTG FOOTING F

G

GC GENERAL CONTRACTOR G

GL GLASS G

GYP BD GYPSUM BOARD G

H

HAZ MAT HAZARDOUS MATERIALS H

HDW HARWARE H

HM HOLLOW METAL H

HT HEIGHT H

I

INCL INCLUDED I

INSUL INSULATION I

INT INTERIOR I

J

J-BOX JUNCTION BOX J

JAN JANITOR J

JC JANITOR'S CLOSET J

JST JOIST J

JT JOINT J

L

LAM LAMINATE L

LAV LAVATORY L

LED LIGHT EMITTING DIODE L

LF LINEAR FEET (FOOT) L

LL LEAD LINED L

A

ACM ASBESTOS CONTAINING MATERIAL A

ACT ACOUSTICAL CEILING TILE A

ADJ ADJACENT A

AFF ABOVE FINISH FLOOR A

AHU AIR HANDLING UNIT A

ALT ALTERNATE A

ALUM ALUMINUM A

APPROX APPROXIMATE A

AR AS REQUIRED A

ARCH ARCHITECTURAL A

AUTO AUTOMATIC A

AUX AUXILIARY A

AV AUDIO VISUAL A

AVG AVERAGE A

B

B/ BOTTOM OF B

BAT BATTEN B

BD BOARD B

BLDG BUILDING B

BLK BLOCKING B

BM BEAM B

BO BY OWNER B

C

CC CONTRACTOR SUPPLIED & INSTALLED C

CEM CEMENT C

CJ CONTROL JOINT C

CL CENTER LINE C

CLG CEILING C

CLR CLEAR C

CMU CONCRETE MASONRY UNIT C

CO CONTRACTING OFFICER C

COL COLUMN C

CONC CONCRETE C

CONT CONTINUOUS C

COORD COORDINATE C

COR CONSTRUCTION OFFICER'S REPRESENTATIVE C

CORR CORRIDOR C

CPT CARPET C

CT CERAMIC TILE C

CTR CENTER C

CTRL CONTROL C

D

DAT DATUM D

DBL DOUBLE D

DEG DEGREE D

DEMO DEMOLITION D

DEPT DEPARTMENT D

DF DRINKING FOUNTAIN D

DIA DIAMETER D

DIFF DIFFUSER D

DIM DIMENSION D

DN DOWN D

DR DOOR D

DTL DETAIL D

DWG DRAWING D

ARCHITECTURAL ABBREVIATIONS

MATERIAL INDICATIONSGRAPHIC SYMBOLS STANDARD MOUNTING HEIGHTS

Revisions: Date:

FINAL CONCEPT DOCUMENTS SUBMISSION 15 JAN 2019

50% CONSTRUCTION DOCUMENTS SUBMISSION 16 APR 2019

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

100% CONSTRUCTION DOCUMENTS SUBMISSION 3 JAN 2020

FINAL CONSTRUCTION DOCUMENTS SUBMISSION 31 JAN 2020

DN

1 2 3 4 5

6 7

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8F.8

HH

II

JJ

DD

EE

F

F

GG

6.86.2

G.5G.5

C.2 C.1C.1

B9

CRAWL SPACE

B1

B1

B5

B1

B1

B5

B4

B4

B4

B4

B4

B4

B4

B5

B5

B5

B5

B5 B5

B5

B5

B5

B5

B5

B5

B5 B5

B5

B6

B6

B6

B6

B6

B6

B6

B6

B6

B6

B6

B5 B6

B5

B5

B5

B7

B5

B5

B5

B4 B5 B6

B4 B5 B6

B5 B6

B6 B6

B6

B5 B6

B4 B5

B7B4 B5 B6

B7B4 B5 B6

B7B4 B5 B6

B7B4 B5 B6

B7

B4

B5

B6

B7

B6

0 13

A444

SIM

B10

B3

B2

B6B5

B5

B7

B7

B7

B3

B2

B10

B11

B12

B13

MECHANICAL

ROOM

SUB1-4

CUBICLES

B02

CHIEF HIMS

OFFICE

B02C

PIMS

SUPPORT

OFFICE

B02B

LOBBY

B02

CUBICLES

B02A

STORAGE

B02E

CUBICLES

B02F

SW RENE

OFFICE

B02

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED, INCLUDING ALL

MOUNTED ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC.

PATCH ABUTTING WALLS, FLOORS, CEILINGS AND ROOF AS

REQUIRED. REMOVE EXISTING ITEMS SCHEDULED TO REMAIN

AS NECESSARY TO ALLOW THE COMPLETE DEMOLITION OF

SELECTED ITEMS. REPAIR/REPLACE EXISTING ITEMS ONCE

DEMOLITION IS COMPLETED.

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

AREA NOT IN CONTRACT

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES”

REGARDING THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTER-HOURS/OFF-

HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES

FOR STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT

MAY AFFECT SPS.

C. REFER TO DEMOLITION ONTES ON GI003.

D. AREAS OF OTHER TRADES’ WORK ARE TO BE CONSIDERED APPROXIMATE AS SHOWN AND

ALL AREAS MAY NOT BE SHOWN ON THESE PLANS. REFER TO CORRESPONDING DRAWINGS

IN OTHER DISCIPLINES FOR FULL EXTENT OF WORK. THE CONTRACTOR IS RESPONSIBLE

FOR VERIFYING EXISTING CONDITIONS AND COORDINATING LOCATIONS AND EXTENT OF

WORK ACROSS ALL TRADES AND DISCIPLINES.

E. BOUNDARIES OF AREAS SHOWN AS NOT IN CONTRACT (NIC) ARE TO BE CONSIDERED

APPROXIMATE AND ARE PROVIDED FOR THE CONTRACTOR’S REFERENCE AND

COORDINATION ONLY. ANY WORK IN ANY AREA NECESSARY TO COMPLETE THE INTENT OF

THE DRAWINGS, SPECIFICATIONS, AND BASIS OF DESIGN SHALL BE CONSIDERED TO BE IN

CONTRACT, REGARDLESS OF SUCH AN AREA BEING MARKED AS NIC ON ONE OR MORE

DRAWINGS.

F. INCIDENTAL ARCHITECTURAL WORK MAY BE REQUIRED AT ANY LOCATION OF ANY OTHER

DISCIPLINE’S WORK. THE CONTRACTOR SHALL PERFORM WORK AS REQUIRED TO SUPPORT

ANY AND ALL CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE

PROTECTION, AND OTHER WORK SHOWN OR REQUIRED.

G. THE CONTRACTOR’S WORK IN THE BASEMENT WILL INCLUDE BUT IS NOT LIMITED TO:

PROTECTION OF EXISTING SPACES, CONSTRUCTION, WORK, EQUIPMENT, AND THE LIKE

FROM CONSTRUCTION ACTIVITIES; REMOVAL AND REPLACEMENT OF CEILING TILES AND/OR

GRIDS, CREATING NEW OPENINGS AND/OR CLOSING EXISTING OPENINGS IN THE FLOOR

STRUCTURE, AND CLEANING AND DISINFECTING.

H. ANY EXISTING AREAS AND FINISHES DISTURBED BY THE CONTRACTOR’S WORK SHALL BE

RETURNED TO THEIR PRE-WORK CONDITION OR BETTER. BEFORE COMMENCEMENT OF

WORK, THE CONTRACTOR SHALL MAKE THOROUGH AND ANNOTATED PHOTOGRAPHIC

AND/OR VIDEO DOCUMENTATION OF ANY AREAS BEING DISTURBED SO AS TO

DEMONSTRATE COMPLIANCE WITH THIS DIRECTION.

I. THE CONTRACTOR SHALL COORDINATE WITH THE VA REGARDING EXISTING FINISH

PRODUCTS, AVAILABILITY OF ATTIC STOCK, APPROVAL OF PRODUCTS INTENDED TO

REPLACE THOSE EXISTING, INCLUDING BUT NOT LIMITED TO CEILING SYSTEMS OR

COMPONENTS. ALL APPROVALS TO BE OBTAINED PRIOR TO DISTURBING THE PRODUCTS

TO WHICH THOSE APPROVALS PERTAIN.

J. PROTECTION AND CLEANING PROCEDURES SHALL BE SUBMITTED TO AND APPROVED BY

THE VA/COR AND SUCH PROTECTION MEASURES AND CLEANING SHALL BE INSPECTED BY

THE VA/COR AND SHALL MEET THEIR APPROVAL.

A. REFER TO DEMOLITION NOTES ON GI003.

B. NEW SHAFTS AND RISERS: NEW SHAFT AND RISER LOCATIONS ARE INTENDED TO FALL

BETWEEN STRUCTURAL CONCRETE RIBS. UPON COMPLETION OF REMOVAL OF PLASTER

CEILINGS AND OTHER OBSCURING FEATURES IN THE VICINITY OF THE NEW SHAFT/RISER

LOCATIONS AND BEFORE BEGINNING STRUCTURAL DEMO OR FRAMING LAYOUT, GC SHALL

PREPARE AND SUBMIT EXISTING CONDITIONS SHOP DRAWINGS TO VA FOR A/E REVIEW. A/E MAY

ADJUST SHAFT AND PARTITION LOCATIONS AT THIS POINT AS REQUIRED TO MEET DESIGN

INTENT. GC SHALL PLAN AND SCHEDULE WORK TO ACCOMMODATE SUCH REVIEW. REFER TO

GI002 FOR ADDITIONAL DIRECTION.

C. CONTRACTOR TO NOTE EXISTING BUILDING PARTITIONS ARE A MIXTURE OF CLAY BLOCK &

PLASTER PARTITIONS, CONCRETE MASONRY UNIT PARTITIONS, STUD AND PLASTER

PARTITIONS, AND STUD AND GYPSUM BOARD PARTITIONS, REGARDLESS OF PRESUMED WALL

COMPOSITION INDICATED ON PLANS. WHILE TYPICAL CLAY BLOCK & PLASTER PARTITIONS ARE

FULL HEIGHT, PARTITION HEIGHTS MAY VARY.

D. INCIDENTAL ARCHITECTURAL WORK MAY BE REQUIRED AT ANY LOCATION OF ANY OTHER

DISCIPLINE’S WORK. THE CONTRACTOR SHALL PERFORM WORK AS REQUIRED TO SUPPORT ANY

AND ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND OTHER WORK SHOWN

OR REQUIRED.

E. THE CONTRACTOR’S WORK IN THE BASEMENT WILL INCLUDE BUT IS NOT LIMITED TO:

PROTECTION OF EXISTING SPACES, CONSTRUCTION, WORK, EQUIPMENT, AND THE LIKE FROM

CONSTRUCTION ACTIVITIES; REMOVAL AND REPLACEMENT OF CEILING TILES AND/OR GRIDS,

CREATING NEW OPENINGS AND/OR CLOSING EXISTING OPENINGS IN THE FLOOR STRUCTURE,

AND CLEANING AND DISINFECTING.

F. ANY EXISTING AREAS AND FINISHES DISTURBED BY THE CONTRACTOR’S WORK SHALL BE

RETURNED TO THEIR PRE-WORK CONDITION OR BETTER. BEFORE COMMENCEMENT OF WORK,

THE CONTRACTOR SHALL MAKE THOROUGH AND ANNOTATED PHOTOGRAPHIC AND/OR VIDEO

DOCUMENTATION OF ANY AREAS BEING DISTURBED SO AS TO DEMONSTRATE COMPLIANCE

WITH THIS DIRECTION.

G. THE CONTRACTOR SHALL COORDINATE WITH THE VA REGARDING EXISTING FINISH PRODUCTS, AVAILABILITY OF ATTIC STOCK, APPROVAL OF PRODUCTS INTENDED TO REPLACE THOSE

EXISTING, INCLUDING BUT NOT LIMITED TO CEILING SYSTEMS OR COMPONENTS. ALL

APPROVALS TO BE OBTAINED PRIOR TO DISTURBING THE PRODUCTS TO WHICH THOSE

APPROVALS PERTAIN.

H. PROTECTION AND CLEANING PROCEDURES SHALL BE SUBMITTED TO AND APPROVED BY THE

VA/COR AND SUCH PROTECTION MEASURES AND CLEANING SHALL BE INSPECTED BY THE

VA/COR AND SHALL MEET THEIR APPROVAL.

I. CONCEALED ACM PIPING EXISTS THROUGHOUT THE PROJECT AREA. CONTRACTOR TO TAKE

CARE IN DEMOLITION OF PARTITIONS SO AS TO NOT DISTURB POTENTIAL ACM PIPING

INSULATION. IF CONCEALED ACM MATERIAL IS FOUND, PROCEED WITH HAZARDOUS MATERIAL

PROCEDURES AS OUTLINED IN SPECIFICATIONS.

J. REFER TO CORRESPONDING STRUCTURAL, HAZARDOUS, AND M/E/P/FP SHEETS FOR FULL

SCOPE OF DEMOLITION WORK.

K. SEE M/E/P/FP AND STRUCTURAL DRAWINGS FOR ADDITIONAL OPENINGS THAT MAY BE

REQUIRED THROUGH EXISTING PARTITIONS AND WALLS INDICATED TO REMAIN. PROVIDE SHOP

DRAWINGS FOR COORDINATION.

ELECTRICAL

PANELS

XXX

STORAGE

B05

STORAGE

B05A

STAIR

LOCKERS/

SUIT-UP

B07C

TOILET /

SHOWER

B07B

DECONTAMINATION

ROOM

B07L

ANTE ROOM

B07M

BUILDING

HOUSEKEEPING

B14A

HOUSEKEEPING

AIDS CLOSET

B07A

CLEAN SHIP /

REC

B07H

OFFICE

B07K

ELECTRICAL

CLOSET

B071

STAIR

WOMENS

B08

STAFF

WOMENS

BATHROOM

B08A

STAFF MENS

BATHROOM/

LOCKERS

B14B

ELEVATOR

SERVICE

ROOM

B16A

PRIVACY

OFFICER

OFFICE

B12C

WORKSHOP

B11

BANK

B12

STORAGE

B12E

STORAGE

B10

CLOSET

B09

CORRIDOR

B00W

CLEAN STORE

ROOM

B07F

MECHANICAL

ROOM

B07G

STORAGE

B11A

OFFICE

B11B

PROCESSING /

PREP /

STERILIZATION

B07

STORAGE

B07

OFFICE

B12B

OFFICE

B12A

MECHANICAL

ROOM

B12D

CORRIDOR

B00E

NOTE: NOT ALL KEYNOTES MAY BE USED ON THIS DRAWING.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

31 JAN 2020

ARCHITECTURAL DEMO PLAN -

BASEMENT

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

AD100

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

1/8" = 1'-0"

ARCHITECTURAL DEMO PLAN - BASEMENT

BASEMENT DEMOLITION NOTES

DEMOLITION LEGEND BASEMENT GENERAL NOTES

0 4' 8' 16'

BASEMENT DEMOLITION KEYNOTES

B1 ABOVE: APPROXIMATE LOCATION OF NEW OPENING IN STRUCTURE

ABOVE. SEE STRUCT, ARCH, HAZMAT, AND M/E/P/FP DRAWINGS.

B2 SEE CIVIL, STRUCT AND LANDSCAPE DRAWINGS AND ASSOCIATED

MEPFP AND ARCH DRAWINGS FOR EXTERIOR WORK.

B3 APPROXIMATE LOCATION OF STRUCTURAL WORK. SEE STRUCT,

ARCH, HAZMAT, AND M/E/P/FP DRAWINGS.

B4 FIRE PROTECTION WORK IN THIS ROOM/AREA, SEE FIRE PROTECTION

DWGS.

B5 PLUMBING WORK IN THIS ROOM/AREA, SEE PLUMBING DWGS.

B6 MECHANICAL VENTILATION/PIPING WORK IN THIS ROOM/AREA, SEE

MECHANICAL DWGS.

B7 ELECTRICAL WORK IN THIS ROOM/AREA, SEE ELECTRICAL DWGS.

B8 FILL ABANDONED OPENINGS IN FLOOR ABOVE, SEE STRUCT, ARCH,

HAZMAT, AND M/E/P/FP DRAWINGS.

B9 AREA OF EXISTING UTILITY PIT TO BE FILLED. THE CONTRACTOR MAY

BE REQUIRED TO PERFORM THIS WORK. SEE STRUCTURAL,

ARCHITECTURAL, HAZMAT AND MEPFP DRAWINGS.

B10 REMOVE EXISTING WINDOW AND FRAME. REMOVE PORTION OF

EXISTING MASONRY WALL AS REQD; CENTER NEW OPENING ON

EXISTING OPENING. PROVIDE STEEL LINTEL AT ENLARGED MASONRY

OPENING. SEE STRUCT DWGS FOR DTLS.

B11 REMOVE RAILINGS AND STORE FOR REINSTALLATION

B12 REMOVE PORTION OF EXISTING MASONRY WALL AS REQUIRED.

B13 EXISTING SLAB AND FENCE TO BE REMOVED IN THEIR ENTIRETY

Revisions: Date:

FINAL CONCEPT DOCUMENTS SUBMISSION 15 JAN 2019

50% CONSTRUCTION DOCUMENTS SUBMISSION 16 APR 2019

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

M

1 2 3 4 5

6 7

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8F.8

HH

II

JJ

DD

EE

F

F

GG

6.86.2

G.5G.5

C.2

ROOF ROOF

TYP.1

TYP. 1

TYP. 1

TYP.1

TYP. 1

3 3

4 4

4 4 4

TYP. 5

TYP.5

TYP. 5

TYP.5

TYP. 5

TYP.1

TYP.5

TYP. 1

TYP. 5

TYP.13TYP. 13

TYP.13

C.1C.1

111111

10 10

1111 1111

0 13

UP 1 R

OFFICE

120K PATIENT

ROOM

120A

PATIENT

ROOM

120B

PATIENT

ROOM

120J

PATIENT

ROOM

120H

PATIENT

ROOM

120G

PATIENT

ROOM

120F

PATIENT

ROOM

120E

PATIENT

ROOM

126A

PATIENT

ROOM

126B

PATIENT

ROOM

126J

PATIENT

ROOM

126H

PATIENT

ROOM

126C

PATIENT

ROOM

126G

PATIENT

ROOM

126F

PATIENT

ROOM

126E

PATIENT

ROOM

PATIENT

ROOM

114D

PATIENT

ROOM

PATIENT

ROOM

120C

CORRIDOR

CORRIDOR

1201 STORAGE

DAY ROOM

120D

PATIENT

LAUNDRY

ROOM

MEN'S

BATHROOM

STAFF BED

ROOM

STAIR

DR'S OFFICE

PSYCH

NURSE'S

OFFICE

123A

CASE

MANAGER

OFFICE

LOBBY

100A

DIRECTOR'S

OFFICE

OFFICE

LINEN

STORAGE

BATHROOM

101A

WOMEN'S

SHOWER

105A

MEN'S

SHOWER

MEN'S

BATHROOM

BATHROOM

CLOSET

CLOSET

115B

CLOSET

115A

CLOSET

DINING ROOM

113A

STORAGE

113B

BATHROOM

110B

OFFICE

CLOSET

110A

STAIR

PATIENT

LAUNDRY

ROOM

ADMIN OFFICE

114A

UNISEX

BATHROOM

114B

BATHROOM

114C

CORRIDOR

CORRIDOR CORRIDOR

DAY ROOM

126D

ELEVATOR

CORRIDOR

ELECTRICAL

PANELS

CLOSET

121A

CLOSET

ELECTRICAL

PANELS

MEN'S

SHOWER

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES” REGARDING

THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES FOR

STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT MAY

AFFECT SPS.

C. REFER TO DEMO NOTES ON GI003.

D. NEW SHAFTS AND RISERS: NEW SHAFT AND RISER LOCATIONS ARE INTENDED TO FALL BETWEEN

STRUCTURAL CONC RIBS. UPON COMPLETION OF REMOVAL OF PLASTER CLGS AND OTHER

OBSCURING FEATURES IN THE VICINITY OF THE NEW SHAFT/RISER LOCATIONS AND BEFORE

BEGINNING STRUCT DEMO OR FRAMING LAYOUT, GC SHALL PREPARE AND SUBMIT EXIST

CONDITIONS SHOP DRAWINGS TO VA FOR A/E REVIEW. A/E MAY ADJUST SHAFT AND PARTITION LOCATIONS AT THIS POINT AS REQD TO MEET DESIGN INTENT. GC SHALL PLAN AND SCHEDULE

WORK TO ACCOMMODATE SUCH REVIEW. REFER TO GI002 FOR ADDITIONAL DIRECTION.

E. EXIST BLDG PARTITIONS CONSIST OF CLAY TILE BLOCK & PLASTER PARTITIONS, CMU PARTITIONS, STUD & PLASTER PARTITIONS, AND STUD & GYPSUM BOARD PARTITIONS REGARDLESS OF

MATERIAL INDICATIONS ON PLANS. VERIFY EXIST CONDITIONS IN FIELD. BATHROOM PARTITIONS INCLUDE WAINSCOT AND FULL HEIGHT CERAMIC TILE. CLAY BLOCK & PLASTER PARTITIONS ARE

TYP FULL HT, ALTHOUGH PARTITION HTS MAY VARY.

F. ON SURFACES AND PARTITIONS INDICATED TO REMAIN, REMOVE ALL WALL MTD ITEMS AND

DEVICES INCL CORNER GUARDS, HANDRAILS, CHAIR RAILS, AND ALL SURFACE FINISHES INCL CERAMIC WALL TILE AND VINYL WALL COVERING. REFER TO NOTES AND SPECS REGARDING PREP

OF SURFACES FOR NEW FINISHES.

G. PLASTER FINISHES ARE INTENDED TO REMAIN ON CLAY BLOCK & PLASTER PARTITIONS & WALLS

INDICATED TO REMAIN, UNO. PATCH & REPAIR AS REQD FOR NEW WORK.

H. CLAY BLOCK & PLASTER PARTITIONS TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY TO

THE STRUCT ABOVE/BELOW. TOPPING SLAB AND REMAINING/ INTERSECTING WALLS SHALL BE

FILLED, PATCHED, AND MADE PLUMB/LEVEL AND PREPARED FOR NEW WORK. SEE DTLS AND

SPECS.

I. EXIST CONSTRUCTION IS INDICATED TO BE REMOVED: REMOVE ALL MTD ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC. PATCH ABUTTING WALLS, FLOORS, CEILINGS, AND ROOF AS REQD TO

ACCOMMODATE NEW CONSTRUCTION. REMOVE EXIST ITEMS SCHED TO REMAIN AS NECESSARY

TO ALLOW THE COMPLETE DEMO WORK. REPAIR/REPLACE SUCH ITEMS ONCE DEMO IS

COMPLETED.

J. IN AREAS OF WORK, CONTRACTOR TO REMOVE ALL EXIST FLOOR FINISHES AND ASSOCIATED

MASTIC AND PREP FOR NEW FLOORING AS SCHED. REFER TO HAZ MAT REPORT IN SPECS AND

HAZ MAT DWGS FOR LOCATIONS OF ACM FLOORING AND MASTIC.

K. CONCEALED ACM PIPING EXISTS THROUGHOUT THE PROJECT AREA. CONTRACTOR TO TAKE

CARE IN DEMO OF PARITIONS SO AS TO NOT DISTURB POTENTIAL ACM PIPING INSULATION. IF

CONCEALED ACM MATERIAL IS FOUND, PROCEED WITH HAZARDOUS MATERIAL PROCEDURES AS

OUTLINED IN SPECS.

L. PLASTER CLGS CONCEALED ABOVE SUSP CLGS CONTAIN ACM ADHESIVE DOTS. REFER TO HAZ

MAT REPORT IN SPECS AND HAZ MAT DWGS FOR LOCATIONS OF ACM ADHESIVE DOTS.

M. REFER TO CORRESPONDING STRUCT, HAZ MAT, AND M/E/P/FP SHEETS FOR FULL SCOPE OF

DEMO WORK.

N. SEE M/E/P/FP AND STRUCT DWGS FOR ADDITIONAL OPNG THAT MAY BE REQD THROUGH EXIST

PARTITIONS AND WALLS INDICATED TO REMAIN. PROVIDE SHOP DWGS FOR COORDINATION.

O. APPROX LOCATION OF EXIST RISER TO ROOF DRAIN CONCEALED WITHIN WALL. RISERS TO REMAIN

SHALL BE PROTECTED DURING CONSTRUCTION. SEE PLUMBING DWGS FOR RELOCATION.

LOCATIONS SHALL BE COORD WITH ALL INTENDED WORK, REPORT ANY CONFLICTS TO THE

RELOCATION AE AND VA/COR. IF DEEMED NECESSARY, CONTRACTOR SHALL RELOCATE RISERS

OR PORTIONS THEREOF TO APPROVED LOCATIONS.

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED, INCLUDING ALL

MOUNTED ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC.

PATCH ABUTTING WALLS, FLOORS, CEILINGS AND ROOF AS

REQUIRED. REMOVE EXISTING ITEMS SCHEDULED TO REMAIN

AS NECESSARY TO ALLOW THE COMPLETE DEMOLITION OF

SELECTED ITEMS. REPAIR/REPLACE EXISTING ITEMS ONCE

DEMOLITION IS COMPLETED.

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

AREA NOT IN CONTRACT

NOTE: NOT ALL KEYNOTES MAY BE USED ON THIS DRAWING.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

31 JAN 2020

ARCHITECTURAL DEMO PLAN -

FIRST FLOOR

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

AD101

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

1/8" = 1'-0"

ARCHITECTURAL DEMO PLAN - FIRST FLOOR

GENERAL DEMOLITION NOTESDEMOLITION LEGEND

DEMOLITION KEYNOTES

0 4' 8' 16'

1 CONC RADIATOR ENCLOSURE TO REMAIN. TYP AT FIRST AND SECOND

FLOOR WINDOWS. REMOVE EXIST GRATES OR COVERS AS REQD. REFER TO

MECH & HAZ MAT DWGS FOR RADIATOR, SHIELD, AND FAN COIL UNIT

REMOVAL. PATCH FLOOR AND WALLS AS REQD & PREPARE FOR NEW WORK.

2 EXIST IT BACKBONE TO REMAIN. PROTECT DURING CONSTRUCTION.

PROTECTION MEASURES TO BE REVIEWED AND APPROVED BY VA COR AND

IT DEPTS.

3 EXIST PLUMBING CHASE WITH FULL HT CLAY BLOCK WALLS TO BE REMOVED.

4 EXIST FURRED CHASE TO BE REMOVED. COORD WI M/E/P/FP DWGS.

5 PARTIAL HT WALL / RADIATOR RECESS. COORD W/ MECH DWGS FOR

RADIATOR AND PIPING REMOVAL.

6 PORTION OF WALL AND CONTENTS TO BE REMOVED, ORIGINAL WALL

(COMPRISED OF CLAY TILE, PLASTER, AND MASONRY) IS TO REMAIN.

CONCEALED CONDITIONS MAY VARY. EXTENT OF REMOVAL SHALL

ACCOMMODATE INTENT AND REQUIREMENTS OF PLANS. TYPICAL ALONG

COLUMN LINES 1 & 12.

7 REMOVE EXIST WALL AS REQD AND PREPARE FOR INSTALLATION OF NEW

DOOR FRAME. COORD WI/ PLANS AND DTLS.

8 REMOVE EXIST WINDOW AND FRAME.

9 REMOVE PORTION OF EXIST MASONRY WALL AS REQD. PROVIDE STEEL

LINTEL AT ENLARGED MASONRY OPENING. SEE STRUCT.

10 REMOVE EXIST STONE THRESHOLD, CERAMIC FLOOR TILE, AND OTHER

FINISHES DOWN TO EXIST CONC SLAB.

11 REMOVE EXIST TILE WAINSCOT OR FULL HT TILE FROM EXIST WALL SHOWN

TO REMAIN, INCLUDING FURRING IF PRESENT. INCLUDES TILED RETURNS TO

EXIST WINDOWS.

12 REMOVE EXIST FLOOR TILE AND ASSOCIATED MASTIC. REFER TO HAZ MAT

DWGS AND SPECS FOR MATERIALS REQUIRING ACM ABATEMENT.

13 REMOVE ALL BLINDS, WINDOW SHADES, AND WINDOW COVERINGS.

14 REMOVE EXIST PLUMBING FIXTS, REFER TO PLUMBING DEMO FOR EXTENT

OF ASSOCIATED PIPING DEMO.

15 EXIST LAUNDRY ROOM: REMOVE EXIST PLUMBING, REFER TO PLUMBING

DEMO FOR EXTENT OF ASSOCIATED DEMO.

16 EXIST WOOD STILE, RAIL, AND PANEL CONSTRUCTION TO REMAIN. REMOVE

EXIST WALL COVERINGS. PREP FOR NEW FINISHES.

17 NEW SLAB OPNG FOR NEW SHAFT/ RISER. SEE STRUCT, ARCH, & M/E/P/FP.

PROVIDE OPENING & FIRESTOPPING AS REQD.

18 SAWCUT/CORE FOR NEW PIPE/CONDUIT RISER. SEE STRUCT, ARCH, &

M/E/P/FP. PROVIDE FIRESTOPPING AS REQD. LOCATE PIPE/CONDUIT RISERS

TO MINIMIZE PROJECTIONS INTO USEABLE SPACE.

19 EXIST 2-HOUR FIRE RESISTANCE RATED CONSTRUCTION TO REMAIN.

DEPRESSIONS OR OPENINGS THROUGH THIS BARRIER CREATED,

ABANDONED, OR DISCOVERED IN THE COURSE OF WORK SHALL BE

PATCHED & FIRESTOPPED AS REQD TO MAINTAIN RATING. SEE GENERAL

NOTES AND SPECS.

20 REMOVE EXIST INFILL AT ORIGINAL MASONRY OPENING; INSPECT CONDITION

OF LINTEL; REPAIR, REPAINT OR REPLACE AS REQD AND PREPARE OPNG

FOR NEW WINDOW. SEE STRUCT AND ARCH DWGS FOR DTLS.

21 GC TO COORD SEQUENCING OF DOOR & FRAME REPLACEMENT SUCH THAT

RATED ENCLOSURES, ICRA BARRIERS & ASBESTOS ENCLOSURES ARE

MAINTAINED AND OTHER REQUIREMENTS ARE MET. REPLACE EXIST WITH

NEW IN ONE CONT WORK SESSION.

22 REMOVE DOOR, FRAME, SIDELIGHTS, AND ASSOCIATED HDW. INSPECT,

REPAIR, REPLACE, & PAINT AS REQD FOR COMPLETED WORK.

Revisions: Date:

FINAL CONCEPT DOCUMENTS SUBMISSION 15 JAN 2019

50% CONSTRUCTION DOCUMENTS SUBMISSION 16 APR 2019

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

1 2 3 4 5

6 7

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8F.8

HH

II

JJ

DD

EE

F

F

GG

6.86.2

G.5G.5

C.2

ROOF ROOF

ROOF

C.1C.1

TYP.1

TYP.5

111111

TYP.5

TYP.1

10 10

TYP.1

TYP.5

3 3

111111

TYP.1

TYP.5

0 13

4'

- 1

3/

4" 3'

- 1 0"

4'

- 1

3/

4"

ROOF ROOF

ROOF

STORAGE

214H

PT SAFETY

OFFICE

214A

QI/MH OFFICE

214B

QI/PCS

OFFICE

214C

WOMEN'S

BATHROOM

STAIR

CLOSET

SUPPORT

OFFICE

STORAGE

CONFERENCE

ROOM

BREAK ROOM

210A

STORAGE

208B

OFFICE

207C

OFFICE

207D

OFFICE

207J

OFFICE

207F

NURSES

OFFICE

207B

STORAGE

MRSA OFFICE

SUPPORT

OFFICE

STORAGE

STAIRS

MEN'S

BATHROOM

RISK

MANAGER

OFFICE

207K

STORAGE

(NEURO)

207G

WAITING

ROOM

207H

INFECTION

CONTROL

OFFICE

207A

SAFETY

OFFICE

TRAINING

ROOM

BATHROOM

200B

DIRECTOR QI

OFFICE

220B

WAITING

ROOM

SUPPORT

OFFICE

220A

SUPPORT

OFFICE

SUPPORT

OFFICE

STORAGE

SAFETY

MANAGERS

OFFICE

214D

CLOSET

217A

QI PC OFFICE

214E

QI GEC

OFFICE

214FSTORAGE

214G

ELECTRICAL

PANELS

210A

ELECTRICAL

PANELS

207I

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES” REGARDING

THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTERHOURS/OFF-HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES FOR

STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT MAY

AFFECT SPS.

C. REFER TO DEMO NOTES ON GI003.

D. NEW SHAFTS AND RISERS: NEW SHAFT AND RISER LOCATIONS ARE INTENDED TO FALL BETWEEN

STRUCTURAL CONC RIBS. UPON COMPLETION OF REMOVAL OF PLASTER CLGS AND OTHER

OBSCURING FEATURES IN THE VICINITY OF THE NEW SHAFT/RISER LOCATIONS AND BEFORE

BEGINNING STRUCT DEMO OR FRAMING LAYOUT, GC SHALL PREPARE AND SUBMIT EXIST

CONDITIONS SHOP DRAWINGS TO VA FOR A/E REVIEW. A/E MAY ADJUST SHAFT AND PARTITION LOCATIONS AT THIS POINT AS REQD TO MEET DESIGN INTENT. GC SHALL PLAN AND SCHEDULE

WORK TO ACCOMMODATE SUCH REVIEW. REFER TO GI002 FOR ADDITIONAL DIRECTION.

E. EXIST BLDG PARTITIONS CONSIST OF CLAY TILE BLOCK & PLASTER PARTITIONS, CMU PARTITIONS, STUD & PLASTER PARTITIONS, AND STUD & GYPSUM BOARD PARTITIONS REGARDLESS OF

MATERIAL INDICATIONS ON PLANS. VERIFY EXIST CONDITIONS IN FIELD. BATHROOM PARTITIONS INCLUDE WAINSCOT AND FULL HEIGHT CERAMIC TILE. CLAY BLOCK & PLASTER PARTITIONS ARE

TYP FULL HT, ALTHOUGH PARTITION HTS MAY VARY.

F. ON SURFACES AND PARTITIONS INDICATED TO REMAIN, REMOVE ALL WALL MTD ITEMS AND

DEVICES INCL CORNER GUARDS, HANDRAILS, CHAIR RAILS, AND ALL SURFACE FINISHES INCL CERAMIC WALL TILE AND VINYL WALL COVERING. REFER TO NOTES AND SPECS REGARDING PREP

OF SURFACES FOR NEW FINISHES.

G. PLASTER FINISHES ARE INTENDED TO REMAIN ON CLAY BLOCK & PLASTER PARTITIONS & WALLS

INDICATED TO REMAIN, UNO. PATCH & REPAIR AS REQD FOR NEW WORK.

H. CLAY BLOCK & PLASTER PARTITIONS TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY TO

THE STRUCT ABOVE/BELOW. TOPPING SLAB AND REMAINING/ INTERSECTING WALLS SHALL BE

FILLED, PATCHED, AND MADE PLUMB/LEVEL AND PREPARED FOR NEW WORK. SEE DTLS AND

SPECS.

I. EXIST CONSTRUCTION IS INDICATED TO BE REMOVED: REMOVE ALL MTD ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC. PATCH ABUTTING WALLS, FLOORS, CEILINGS, AND ROOF AS REQD TO

ACCOMMODATE NEW CONSTRUCTION. REMOVE EXIST ITEMS SCHED TO REMAIN AS NECESSARY

TO ALLOW THE COMPLETE DEMO WORK. REPAIR/REPLACE SUCH ITEMS ONCE DEMO IS

COMPLETED.

J. IN AREAS OF WORK, CONTRACTOR TO REMOVE ALL EXIST FLOOR FINISHES AND ASSOCIATED

MASTIC AND PREP FOR NEW FLOORING AS SCHED. REFER TO HAZ MAT REPORT IN SPECS AND

HAZ MAT DWGS FOR LOCATIONS OF ACM FLOORING AND MASTIC.

K. CONCEALED ACM PIPING EXISTS THROUGHOUT THE PROJECT AREA. CONTRACTOR TO TAKE

CARE IN DEMO OF PARITIONS SO AS TO NOT DISTURB POTENTIAL ACM PIPING INSULATION. IF

CONCEALED ACM MATERIAL IS FOUND, PROCEED WITH HAZARDOUS MATERIAL PROCEDURES AS

OUTLINED IN SPECS.

L. PLASTER CLGS CONCEALED ABOVE SUSP CLGS CONTAIN ACM ADHESIVE DOTS. REFER TO HAZ

MAT REPORT IN SPECS AND HAZ MAT DWGS FOR LOCATIONS OF ACM ADHESIVE DOTS.

M. REFER TO CORRESPONDING STRUCT, HAZ MAT, AND M/E/P/FP SHEETS FOR FULL SCOPE OF

DEMO WORK.

N. SEE M/E/P/FP AND STRUCT DWGS FOR ADDITIONAL OPNG THAT MAY BE REQD THROUGH EXIST

PARTITIONS AND WALLS INDICATED TO REMAIN. PROVIDE SHOP DWGS FOR COORDINATION.

O. APPROX LOCATION OF EXIST RISER TO ROOF DRAIN CONCEALED WITHIN WALL. RISERS TO REMAIN

SHALL BE PROTECTED DURING CONSTRUCTION. SEE PLUMBING DWGS FOR RELOCATION.

LOCATIONS SHALL BE COORD WITH ALL INTENDED WORK, REPORT ANY CONFLICTS TO THE

RELOCATION AE AND VA/COR. IF DEEMED NECESSARY, CONTRACTOR SHALL RELOCATE RISERS

OR PORTIONS THEREOF TO APPROVED LOCATIONS.

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED, INCLUDING ALL

MOUNTED ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC.

PATCH ABUTTING WALLS, FLOORS, CEILINGS AND ROOF AS

REQUIRED. REMOVE EXISTING ITEMS SCHEDULED TO REMAIN

AS NECESSARY TO ALLOW THE COMPLETE DEMOLITION OF

SELECTED ITEMS. REPAIR/REPLACE EXISTING ITEMS ONCE

DEMOLITION IS COMPLETED.

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

AREA NOT IN CONTRACT

NOTE: NOT ALL KEYNOTES MAY BE USED ON THIS DRAWING.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

3 JAN 2020

ARCHITECTURAL DEMO PLAN -

SECOND FLOOR

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

AD102

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

1/8" = 1'-0"

ARCHITECTURAL DEMO PLAN - SECOND FLOOR

GENERAL DEMOLITION NOTESDEMOLITION LEGEND

DEMOLITION KEYNOTES

0 4' 8' 16'

1 CONC RADIATOR ENCLOSURE TO REMAIN. TYP AT FIRST AND SECOND

FLOOR WINDOWS. REMOVE EXIST GRATES OR COVERS AS REQD. REFER TO

MECH & HAZ MAT DWGS FOR RADIATOR, SHIELD, AND FAN COIL UNIT

REMOVAL. PATCH FLOOR AND WALLS AS REQD & PREPARE FOR NEW WORK.

2 EXIST IT BACKBONE TO REMAIN. PROTECT DURING CONSTRUCTION.

PROTECTION MEASURES TO BE REVIEWED AND APPROVED BY VA COR AND

IT DEPTS.

3 EXIST PLUMBING CHASE WITH FULL HT CLAY BLOCK WALLS TO BE REMOVED.

4 EXIST FURRED CHASE TO BE REMOVED. COORD WI M/E/P/FP DWGS.

5 PARTIAL HT WALL / RADIATOR RECESS. COORD W/ MECH DWGS FOR

RADIATOR AND PIPING REMOVAL.

6 PORTION OF WALL AND CONTENTS TO BE REMOVED, ORIGINAL WALL

(COMPRISED OF CLAY TILE, PLASTER, AND MASONRY) IS TO REMAIN.

CONCEALED CONDITIONS MAY VARY. EXTENT OF REMOVAL SHALL

ACCOMMODATE INTENT AND REQUIREMENTS OF PLANS. TYPICAL ALONG

COLUMN LINES 1 & 12.

7 REMOVE EXIST WALL AS REQD AND PREPARE FOR INSTALLATION OF NEW

DOOR FRAME. COORD WI/ PLANS AND DTLS.

8 REMOVE EXIST WINDOW AND FRAME.

9 REMOVE PORTION OF EXIST MASONRY WALL AS REQD. PROVIDE STEEL

LINTEL AT ENLARGED MASONRY OPENING. SEE STRUCT.

10 REMOVE EXIST STONE THRESHOLD, CERAMIC FLOOR TILE, AND OTHER

FINISHES DOWN TO EXIST CONC SLAB.

11 REMOVE EXIST TILE WAINSCOT OR FULL HT TILE FROM EXIST WALL SHOWN

TO REMAIN, INCLUDING FURRING IF PRESENT. INCLUDES TILED RETURNS TO

EXIST WINDOWS.

12 REMOVE EXIST FLOOR TILE AND ASSOCIATED MASTIC. REFER TO HAZ MAT

DWGS AND SPECS FOR MATERIALS REQUIRING ACM ABATEMENT.

13 REMOVE ALL BLINDS, WINDOW SHADES, AND WINDOW COVERINGS.

14 REMOVE EXIST PLUMBING FIXTS, REFER TO PLUMBING DEMO FOR EXTENT

OF ASSOCIATED PIPING DEMO.

15 EXIST LAUNDRY ROOM: REMOVE EXIST PLUMBING, REFER TO PLUMBING

DEMO FOR EXTENT OF ASSOCIATED DEMO.

16 EXIST WOOD STILE, RAIL, AND PANEL CONSTRUCTION TO REMAIN. REMOVE

EXIST WALL COVERINGS. PREP FOR NEW FINISHES.

17 NEW SLAB OPNG FOR NEW SHAFT/ RISER. SEE STRUCT, ARCH, & M/E/P/FP.

PROVIDE OPENING & FIRESTOPPING AS REQD.

18 SAWCUT/CORE FOR NEW PIPE/CONDUIT RISER. SEE STRUCT, ARCH, &

M/E/P/FP. PROVIDE FIRESTOPPING AS REQD. LOCATE PIPE/CONDUIT RISERS

TO MINIMIZE PROJECTIONS INTO USEABLE SPACE.

19 EXIST 2-HOUR FIRE RESISTANCE RATED CONSTRUCTION TO REMAIN.

DEPRESSIONS OR OPENINGS THROUGH THIS BARRIER CREATED,

ABANDONED, OR DISCOVERED IN THE COURSE OF WORK SHALL BE

PATCHED & FIRESTOPPED AS REQD TO MAINTAIN RATING. SEE GENERAL

NOTES AND SPECS.

20 REMOVE EXIST INFILL AT ORIGINAL MASONRY OPENING; INSPECT CONDITION

OF LINTEL; REPAIR, REPAINT OR REPLACE AS REQD AND PREPARE OPNG

FOR NEW WINDOW. SEE STRUCT AND ARCH DWGS FOR DTLS.

21 GC TO COORD SEQUENCING OF DOOR & FRAME REPLACEMENT SUCH THAT

RATED ENCLOSURES, ICRA BARRIERS & ASBESTOS ENCLOSURES ARE

MAINTAINED AND OTHER REQUIREMENTS ARE MET. REPLACE EXIST WITH

NEW IN ONE CONT WORK SESSION.

22 REMOVE DOOR, FRAME, SIDELIGHTS, AND ASSOCIATED HDW. INSPECT,

REPAIR, REPLACE, & PAINT AS REQD FOR COMPLETED WORK.

Revisions: Date:

FINAL CONCEPT DOCUMENTS SUBMISSION 15 JAN 2019

50% CONSTRUCTION DOCUMENTS SUBMISSION 16 APR 2019

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8

HH

II

JJ

DD

EE

F

6.86.2

G.5G.5

C.2

DN

A1 A2 A3 A4 A5 A6 A7

A8

A8

A8

A8

A3

A4

A7

A3

A4

A7

C.1C.1

A8

A8

0 13

A12

A11 A11

A11 A11

A11A11

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES”

REGARDING THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTERHOURS/OFF-

HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES

FOR STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT

MAY AFFECT SPS.

C. AREAS OF OTHER TRADES’ WORK ARE TO BE CONSIDERED APPROXIMATE AS SHOWN AND

ARE PROVIDED FOR THE CONTRACTOR’S REFERENCE AND COORDINATION. ALL REQUIRED

WORK IS NOT NECESSARILY SHOWN ON THESE PLANS OR IN DETAIL. REFER TO

CORRESPONDING DRAWINGS IN OTHER DISCIPLINES. THE CONTRACTOR IS RESPONSIBLE

FOR VERIFYING EXISTING CONDITIONS AND COORDINATING LOCATIONS AND EXTENT OF

WORK ACROSS ALL TRADES AND DISCIPLINES.

D. AREAS SHOWN AS NOT IN CONTRACT (NIC) PERTAIN TO THE DISCIPLINES REPRESENTED BY

THOSE DRAWINGS. INCIDENTAL ARCHITECTURAL WORK MAY BE REQUIRED AT ANY

LOCATION OF ANY OTHER DISCIPLINE’S WORK. THE CONTRACTOR SHALL PERFORM WORK

AS REQUIRED TO SUPPORT ANY AND ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE

PROTECTION, AND OTHER WORK SHOWN OR REQUIRED.

E. BOUNDARIES OF AREAS SHOWN AS NOT IN CONTRACT (NIC) ARE TO BE CONSIDERED

APPROXIMATE AND ARE PROVIDED FOR THE CONTRACTOR’S REFERENCE AND

COORDINATION ONLY. ANY WORK IN ANY AREA NECESSARY TO COMPLETE THE INTENT OF

THE DRAWINGS, SPECIFICATIONS, AND BASIS OF DESIGN SHALL BE CONSIDERED TO BE IN

CONTRACT, REGARDLESS OF SUCH AN AREA BEING MARKED AS NIC ON ONE OR MORE

DRAWINGS.

F. THE CONTRACTOR’S WORK IN THE ATTIC WILL INCLUDE BUT IS NOT LIMITED TO:

PROTECTION OF EXISTING SPACES, CONSTRUCTION, WORK, EQUIPMENT, AND THE LIKE

FROM CONSTRUCTION ACTIVITIES; REMOVAL AND REPLACEMENT OF INSULATION,

CREATING NEW OPENINGS AND/OR CLOSING EXISTING OPENINGS IN THE FLOOR AND/OR

STRUCTURE, AND CLEANING AND DISINFECTING.

G. ANY EXISTING AREAS AND FINISHES DISTURBED BY THE CONTRACTOR’S WORK SHALL BE

RETURNED TO THEIR PRE-WORK CONDITION OR BETTER. BEFORE COMMENCEMENT OF

WORK, THE CONTRACTOR SHALL MAKE THOROUGH AND ANNOTATED PHOTOGRAPHIC

AND/OR VIDEO DOCUMENTATION OF ANY AREAS BEING DISTURBED SO AS TO

DEMONSTRATE COMPLIANCE WITH THIS DIRECTION.

H. THE CONTRACTOR SHALL COORDINATE WITH THE VA REGARDING EXISTING FINISH

PRODUCTS, AVAILABILITY OF ATTIC STOCK, APPROVAL OF PRODUCTS INTENDED TO

REPLACE THOSE EXISTING, INCLUDING BUT NOT LIMITED TO CEILING SYSTEMS OR

COMPONENTS. ALL APPROVALS TO BE OBTAINED PRIOR TO DISTURBING THE PRODUCTS

TO WHICH THOSE APPROVALS PERTAIN.

I. PROTECTION AND CLEANING PROCEDURES SHALL BE SUBMITTED TO AND APPROVED BY

THE VA/COR AND SUCH PROTECTION MEASURES AND CLEANING SHALL BE INSPECTED BY

THE VA/COR AND SHALL MEET THEIR APPROVAL.

J. AIR HANDLING UNITS (AHUS) SHOWN FOR REFERENCE ONLY: REFER TO MECHANICAL

DRAWINGS FOR DUCTING AND STRUCTURAL DRAWINGS FOR SUPPORTS.

K. COORDINATE MECHANICAL WORK WITH EXISTNG ROOF FRAMING. SELECTIVELY REMOVE

EXISTING COLLAR TIES & PROVIDE NEW COLLAR TIES AS REQUIRED SUBJECT TO APPROVAL

BY STRUCTURAL ENGINEER OF RECORD. SEE MECH & STRUCT DWGS.

L. ADD 2.5 GAL, TYPE 2A SURFACE-MTD FIRE EXTINGUISHERS AS REQD TO HAVE 75' MAX

TRAVEL DISTANCE AND 5 FIRE EXTINGUISHERS MINIMUM.

M. PROVIDE SIGNAGE NOTIFYING OCCUPANTS OF LOW CLEARANCE.

A. REFER TO DEMOLITION NOTES ON GI003.

B. NEW SHAFTS AND RISERS: NEW SHAFT AND RISER LOCATIONS ARE INTENDED TO FALL BETWEEN

STRUCTURAL CONCRETE RIBS. UPON COMPLETION OF REMOVAL OF PLASTER CEILINGS AND

OTHER OBSCURING FEATURES IN THE VICINITY OF THE NEW SHAFT/RISER LOCATIONS AND

BEFORE BEGINNING STRUCTURAL DEMO OR FRAMING LAYOUT, GC SHALL PREPARE AND SUBMIT

EXISTING CONDITIONS SHOP DRAWINGS TO VA FOR A/E REVIEW. A/E MAY ADJUST SHAFT AND

PARTITION LOCATIONS AT THIS POINT AS REQUIRED TO MEET DESIGN INTENT. GC SHALL PLAN

AND SCHEDULE WORK TO ACCOMMODATE SUCH REVIEW. REFER TO GI002 FOR ADDITIONAL

DIRECTION.

C. CONCEALED ACM PIPING EXISTS THROUGHOUT THE PROJECT AREA. CONTRACTOR TO TAKE

CARE IN DEMOLITION OF PARITIONS SO AS TO NOT DISTURB POTENTIAL ACM PIPING INSULATION.

IF CONCEALED ACM MATERIAL IS FOUND, PROCEED WITH HAZARDOUS MATERIAL PROCEDURES

AS OUTLINED IN SPECIFICATIONS.

D. REFER TO CORRESPONDING MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION,

STRUCTURAL, AND HAZARDOUS MATERIAL DRAWINGS FOR FULL EXTENT OF DEMOLITION OF

RESPECTIVE TRADES.

E. SEE M/E/P/FP AND STRUCTURAL DRAWINGS FOR ADDITIONAL OPENINGS THAT MAY BE REQUIRED

THROUGH EXISTING PARTITIONS AND WALLS INDICATED TO REMAIN. PROVIDE SHOP DRAWINGS

FOR COORDINATION.

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED, INCLUDING ALL

MOUNTED ACCESSORIES, CORNER GUARDS, HANDRAILS, ETC.

PATCH ABUTTING WALLS, FLOORS, CEILINGS AND ROOF AS

REQUIRED. REMOVE EXISTING ITEMS SCHEDULED TO REMAIN

AS NECESSARY TO ALLOW THE COMPLETE DEMOLITION OF

SELECTED ITEMS. REPAIR/REPLACE EXISTING ITEMS ONCE

DEMOLITION IS COMPLETED.

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

AREA NOT IN CONTRACT

NOTE: NOT ALL KEYNOTES MAY BE USED ON THIS DRAWING.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

3 JAN 2020

ARCHITECTURAL DEMO PLAN -

ATTIC

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

AD103

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

1/8" = 1'-0"

ARCHITECTURAL DEMO PLAN - ATTIC

ATTIC DEMOLITION KEYNOTES

ATTIC GENERAL NOTES

ATTIC DEMOLITION NOTES

DEMOLITION LEGEND

0 4' 8' 16'

A10

A10

A1 APPROXIMATE LOCATION ABOVE OF NEW OPENING TO BE CREATED

OR EXISTING OPENING TO BE CLOSED, IN ROOF ABOVE. SEE

STRUCTURAL, ARCHITECTURAL, HAZMAT, AND M/E/P/FP DRAWINGS.

A2 APPROXIMATE LOCATION OF NEW OPENING TO BE CREATED OR

EXISTING OPENING TO BE CLOSED. SEE STRUCTURAL,

ARCHITECTURAL, HAZMAT, AND M/E/P/FP DRAWINGS.

A3 APPROXIMATE LOCATION OF STRUCTURAL WORK TO SUPPORT NEW

OR RELOCATED EQUIPMENT. SEE STRUCTURAL, ARCHITECTURAL,

HAZMAT, AND M/E/P/FP DRAWINGS.

A4 MECHANICAL WORK IN THIS ROOM/AREA, SEE MECHANICAL DRWINGS.

A5 PLUMBING WORK IN THIS ROOM/AREA, SEE PLUMBING DWGS

A6 FIRE PROTECTION WORK IN THIS ROOM/AREA, SEE FIRE PROTECTION.

A7 ELECTRICAL WORK IN THIS ROOM/AREA, SEE ELECTRICAL DRAWINGS.

A8 NEW SHAFT OPENINGS FOR SHAFTS/RISERS: NEW SHAFT/RISER

LOCATIONS ARE INTENDED TO FALL BETWEEN CONCRETE RIBS.

CONCRETE RIBS ARE INACCESSIBLE TO FIELD SURVEY AND ANY

LOCATIONS SHOWN ARE PRESUMED. UPON COMPLETION OF

DEMOLITION IN THE VICINITY OF THE NEW SHAFT/RISER LOCATIONS

AND BEFORE BEGINNING FRAMING LAYOUT, CONTRACTOR SHALL

SUBMIT SHOP DRAWINGS SHOWING LOCATIONS OF EXISTING

STRUCTURE IN THE VICINITY OF THESE SHAFTS/RISERS AND

SHAFT/RISER LOCATIONS SHOWN ON ARCHITECTURAL AND

STRUCTURAL PLANS TO VA COR FOR ARCHITECTURAL AND

STRUCTURAL REVIEW. CONTRACTOR SHALL PLAN AND SCHEDULE

WORK TO ACCOMMODATE SUCH REVIEW. ADJUSTMENTS TO SHAFT

AND PARTITION LOCATIONS MAY BE REQUIRED TO MEET DESIGN

INTENT AND MAXIMIZE OFFICE WIDTHS. GC TO COORDINATE ACROSS

ALL DISCIPLINES.

A9 NEW/ENLARGED MASONRY OPENING WITH LOUVER, SEE STRUCTURAL

AND MECHANICAL. GC COORDINATE ACROSS ALL DICIPLINES.

A10 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE, SEE MECHANICAL

DRAWINGS FOR FULL INFORMATION INCLUDING DUCT ROUTING.

A11 REMOVE EXISTING BRICK TO CREATE NEW, ENLARGED OPENING. SEE

STRUCTURAL DRAWINGS FOR INFORMATION. COORDINATE WORK TO

MAINTAIN TERRA COTTA CORNICE IN PLACE. SALVAGE REMOVED

BRICK FOR RE-USE.

A12 REMOVE EXISTING CORNICE AS REQUIRED FOR NEW ELEVATOR

TOWER. SEE STRUCTURAL DRAWINGS FOR DETAILS.

A13 EXISTING VTR ABOVE TO BE REMOVED. SEE PLUMBING DRAWINGS,

ARCH.ROOF PLAN AND DETAILS.

A13

A8 A8

A8

Revisions: Date:

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8F.8

HH

II

JJ

DD

EE

F

F

GG

6.86.2

G.5G.5

C.2

B1

B4

B1

B1

B1

B4

B4

B4

B4

B4

C.1C.1

CRAWL SPACE

B4

B4

B4

B4

B4

B4B4

B4

B4

B4

B4

B4

B4

B4

B5

B5

B5

B6

B5 B6

B5 B6

B5

B6

B5

B6

B5

B6

B5

B6

B5

B5

B6B5

B6

B5 B6

B5 B6

B5

B6

B5 B6

B5 B6

B5

B6

B4

B5

B6

0 13

MECHANICAL

ROOM

SUB1-4

CUBICLES

B02

CHIEF HIMS

OFFICE

B02C

PIMS

SUPPORT

OFFICE

B02B

LOBBY

B02

CUBICLES

B02A

STORAGE

B02E

CUBICLES

B02F

CORRIDOR

B00W

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES”

REGARDING THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTER-HOURS/OFF-

HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES

FOR STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT

MAY AFFECT SPS.

C. REFER TO DEMOLITION ONTES ON GI003.

D. AREAS OF OTHER TRADES’ WORK ARE TO BE CONSIDERED APPROXIMATE AS SHOWN AND

ALL AREAS MAY NOT BE SHOWN ON THESE PLANS. REFER TO CORRESPONDING DRAWINGS

IN OTHER DISCIPLINES FOR FULL EXTENT OF WORK. THE CONTRACTOR IS RESPONSIBLE

FOR VERIFYING EXISTING CONDITIONS AND COORDINATING LOCATIONS AND EXTENT OF

WORK ACROSS ALL TRADES AND DISCIPLINES.

E. BOUNDARIES OF AREAS SHOWN AS NOT IN CONTRACT (NIC) ARE TO BE CONSIDERED

APPROXIMATE AND ARE PROVIDED FOR THE CONTRACTOR’S REFERENCE AND

COORDINATION ONLY. ANY WORK IN ANY AREA NECESSARY TO COMPLETE THE INTENT OF

THE DRAWINGS, SPECIFICATIONS, AND BASIS OF DESIGN SHALL BE CONSIDERED TO BE IN

CONTRACT, REGARDLESS OF SUCH AN AREA BEING MARKED AS NIC ON ONE OR MORE

DRAWINGS.

F. INCIDENTAL ARCHITECTURAL WORK MAY BE REQUIRED AT ANY LOCATION OF ANY OTHER

DISCIPLINE’S WORK. THE CONTRACTOR SHALL PERFORM WORK AS REQUIRED TO SUPPORT

ANY AND ALL CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE

PROTECTION, AND OTHER WORK SHOWN OR REQUIRED.

G. THE CONTRACTOR’S WORK IN THE BASEMENT WILL INCLUDE BUT IS NOT LIMITED TO:

PROTECTION OF EXISTING SPACES, CONSTRUCTION, WORK, EQUIPMENT, AND THE LIKE

FROM CONSTRUCTION ACTIVITIES; REMOVAL AND REPLACEMENT OF CEILING TILES AND/OR

GRIDS, CREATING NEW OPENINGS AND/OR CLOSING EXISTING OPENINGS IN THE FLOOR

STRUCTURE, AND CLEANING AND DISINFECTING.

H. ANY EXISTING AREAS AND FINISHES DISTURBED BY THE CONTRACTOR’S WORK SHALL BE

RETURNED TO THEIR PRE-WORK CONDITION OR BETTER. BEFORE COMMENCEMENT OF

WORK, THE CONTRACTOR SHALL MAKE THOROUGH AND ANNOTATED PHOTOGRAPHIC

AND/OR VIDEO DOCUMENTATION OF ANY AREAS BEING DISTURBED SO AS TO

DEMONSTRATE COMPLIANCE WITH THIS DIRECTION.

I. THE CONTRACTOR SHALL COORDINATE WITH THE VA REGARDING EXISTING FINISH

PRODUCTS, AVAILABILITY OF ATTIC STOCK, APPROVAL OF PRODUCTS INTENDED TO

REPLACE THOSE EXISTING, INCLUDING BUT NOT LIMITED TO CEILING SYSTEMS OR

COMPONENTS. ALL APPROVALS TO BE OBTAINED PRIOR TO DISTURBING THE PRODUCTS

TO WHICH THOSE APPROVALS PERTAIN.

J. PROTECTION AND CLEANING PROCEDURES SHALL BE SUBMITTED TO AND APPROVED BY

THE VA/COR AND SUCH PROTECTION MEASURES AND CLEANING SHALL BE INSPECTED BY

THE VA/COR AND SHALL MEET THEIR APPROVAL.

EXISTING CONSTRUCTION TO REMAIN

NOTE: REFER TO GI003 FOR GENERAL DEMOLITION NOTES. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR

FULL SCOPE OF DEMOLITION WORK.

REMOVE WIRELESS ACCESS

POINT

REMOVE NURSE CALL LIGHT

REMOVE EXIT SIGN (DOUBLE

SIDED SHOWN)

REMOVE LIGHT FIXTURE (2'x4'

FIXTURE SHOWN)

WAP

N

EXISTING PARTITION TO BE

REMOVED IN ITS ENTIRETY.

COMPLETELY REMOVE EXISTING

SUSPENDED CEILING AND ALL

ASSOCIATED SUPPORTS.

REMOVE EXISTING GYPSUM BOARD

CEILING AND ALL ASSOCIATED

SUPPORTS.

AREA NOT IN CONTRACT

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

ELECTRICAL

PANELS

STORAGE

B05

STORAGE

B05A

STAIR

LOCKERS/

SUIT-UP

B07C

TOILET /

SHOWER

B07B

DECONTAMINATION

ROOM

B07L

ANTE ROOM

B07M

39 SF

BUILDING

HOUSEKEEPING

B14A

HOUSEKEEPING

AIDS CLOSET

B07A

CLEAN

SHIP/REC

B07H

OFFICE

B07K

ELECTRICAL

CLOSET

B071

STAIR

WOMENS

B08

STAFF

WOMENS

BATHROOM

B08A

STAFF MENS

BATHROOM/

LOCKERS

B14B

PRIVACY

OFFICER

OFFICE

B12C

WORKSHOP

B11

BANK

B12

STORAGE

B12E

STORAGE

B10

CLOSET

B09

CORRIDOR

CLEAN STORE

ROOM

B07F

MECHANICAL

ROOM

B07G

STORAGE

B11A

175 SF

OFFICE

B11B

PROCESSING /

PREP /

STERILIZATION

B07

STORAGE

B07

OFFICE

B12B

OFFICE

B12A

MECHANICAL

ROOM

B12D

426 SF

CORRIDOR

B00E

CLEAN

SHIP/REC

B07H ELEVATOR

SERVICE

ROOM 2

B16B

CORRIDOR

B00C

NOTE: NOT ALL KEYNOTES MAY BE USED ON THIS DRAWING.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Drawing Title

Approved: Project Director

Phase Project Title Project Number

Building Number

Drawing NumberLocation

Issue Date Checked Drawn

VA FORM 08-6231

FULLY SPRINKLERED

FINAL CONSTRUCTION DOCUMENTS - NOT FOR CONSTRUCTION

31 JAN 2020

REFLECTED CEILING

DEMOLITION PLAN - BASEMENT

RENOVATE BUILDING 4A&B FLOORS

OUTPATIENT MENTAL HEALTH CLINIC

VA Medical Center, Coatesville PA

RFR ARCH

542-18-106

AD130

FINAL CONSTRUCTION

DOCUMENTS SUBMISSION

1/8" = 1'-0"

REFLECTED CEILING DEMOLITION PLAN - BASEMENT

BASEMENT GENERAL NOTES

BASEMENT DEMOLITION KEYNOTES

CEILING DEMOLITION LEGEND

0 4' 8' 16'

B1 ABOVE: APPROXIMATE LOCATION OF NEW OPENING IN STRUCTURE

ABOVE. SEE STRUCT, ARCH, HAZMAT, AND M/E/P/FP DRAWINGS.

B2 SEE CIVIL, STRUCT AND LANDSCAPE DRAWINGS AND ASSOCIATED

MEPFP AND ARCH DRAWINGS FOR EXTERIOR WORK.

B3 APPROXIMATE LOCATION OF STRUCTURAL WORK. SEE STRUCT,

ARCH, HAZMAT, AND M/E/P/FP DRAWINGS.

B4 FIRE PROTECTION WORK IN THIS ROOM/AREA, SEE FIRE

PROTECTION DWGS.

B5 PLUMBING WORK IN THIS ROOM/AREA, SEE PLUMBING DWGS.

B6 MECHANICAL VENTILATION/PIPING WORK IN THIS ROOM/AREA, SEE

MECHANICAL DWGS.

B7 ELECTRICAL WORK IN THIS ROOM/AREA, SEE ELECTRICAL DWGS.

B8 FILL ABANDONED OPENINGS IN FLOOR ABOVE, SEE STRUCT, ARCH,

HAZMAT, AND M/E/P/FP DRAWINGS.

B9 AREA OF EXISTING UTILITY PIT TO BE FILLED. THE CONTRACTOR

MAY BE REQUIRED TO PERFORM THIS WORK. SEE STRUCTURAL,

ARCHITECTURAL, HAZMAT AND MEPFP DRAWINGS.

B10 REMOVE EXISTING WINDOW AND FRAME. REMOVE PORTION OF

EXISTING MASONRY WALL AS REQD; CENTER NEW OPENING ON

EXISTING OPENING. PROVIDE STEEL LINTEL AT ENLARGED

MASONRY OPENING. SEE STRUCT DWGS FOR DTLS.

B11 REMOVE RAILINGS AND STORE FOR REINSTALLATION

B12 REMOVE PORTION OF EXISTING MASONRY WALL AS REQUIRED.

B13 EXISTING SLAB AND FENCE TO BE REMOVED IN THEIR ENTIRETY

Revisions: Date:

FINAL CONCEPT DOCUMENTS SUBMISSION 15 JAN 2019

50% CONSTRUCTION DOCUMENTS SUBMISSION 16 APR 2019

MOD - 50% CONSTRUCTION DOCUMENTS SUBMISSION 21 JUN 2019

8 9 10 11 12

AA

BB

CC

D.2D.2

E.2E.2

E.8

E.8

F.8F.8

HH

II

JJ

DD

EE

F

F

GG

6.86.2

C.2 C.1C.1

0 13

OFFICE

120K

PATIENT

ROOM

120A

PATIENT

ROOM

120J

PATIENT

ROOM

126A

PATIENT

ROOM

126B

PATIENT

ROOM

126J

PATIENT

ROOM

126C

PATIENT

ROOM

PATIENT

ROOM

114D

PATIENT

ROOM

CORRIDOR

CORRIDOR

STORAGE

DAY ROOM

120D

PATIENT

LAUNDRY

ROOM

MEN'S

BATHROOM

STAFF BED

ROOM

STAIR

DR'S OFFICE

PSYCH

NURSE'S

OFFICE

123A

CASE

MANAGER

OFFICE

LOBBY

100A

DIRECTOR'S

OFFICE

OFFICE

LINEN

STORAGE

BATHROOM

101A

WOMEN'S

SHOWER

105A

MEN'S

SHOWER

MEN'S

BATHROOM

BATHROOM

CLOSET

CLOSET

115B

CLOSET

115A

CLOSET

DINING ROOM

113A

STORAGE

113B

BATHROOM

110B

OFFICE

CLOSET

110A

STAIR

PATIENT

LAUNDRY

ROOM

ADMIN OFFICE

114A

UNISEX

BATHROOM

114B

BATHROOM

114C

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

126D

ELEVATOR

CORRIDOR

ELECTRICAL

PANELS

CLOSET

121A

CLOSET

ELECTRICAL

PANELS

MEN'S

SHOWER

PATIENT

ROOM

120H

PATIENT

ROOM

120G

PATIENT

ROOM

120F

PATIENT

ROOM

120E

PATIENT

ROOM

120B

PATIENT

ROOM

120C

PATIENT

ROOM

126H

PATIENT

ROOM

126G

PATIENT

ROOM

126F

PATIENT

ROOM

126E

EXISTING CONSTRUCTION TO REMAIN

NOTE: REFER TO GI003 FOR GENERAL DEMOLITION NOTES. REVIEW THIS DRAWING IN CONJUNCTION WITH CORRESPONDING FIRE PROTECTION, PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR

FULL SCOPE OF DEMOLITION WORK.

REMOVE WIRELESS ACCESS

POINT

REMOVE NURSE CALL LIGHT

REMOVE EXIT SIGN (DOUBLE

SIDED SHOWN)

REMOVE LIGHT FIXTURE (2'x4'

FIXTURE SHOWN)

WAP

N

EXISTING PARTITION TO BE

REMOVED IN ITS ENTIRETY.

COMPLETELY REMOVE EXISTING

SUSPENDED CEILING AND ALL

ASSOCIATED SUPPORTS.

REMOVE EXISTING GYPSUM BOARD

CEILING AND ALL ASSOCIATED

SUPPORTS.

AREA NOT IN CONTRACT

2 HOUR FIRE & SMOKE SEPARATION

1 HOUR FIRE & SMOKE SEPARATION

A. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – GENERAL NOTES”

REGARDING THE VA’S DISCRETION IN SELECTING WORK TO BE DONE AFTERHOURS/OFF-

HOURS.

B. REFER TO GI002 “CONSTRUCTION PERIOD SCHEDULING OF WORK – ADDITIONAL NOTES FOR

STERILE PROCESSING SERVICE (SPS)” REGARDING WORK IN, ADJACENT TO, OR THAT MAY

AFFECT SPS.

C. REFER TO DEMOLITION NOTES ON GI003.

D. REFER TO CORRESPONDING STRUCTURAL, HAZMAT, AND M/E/P/FP SHEETS FOR FULL SCOPE

OF DEMOLITION WORK.

E. NEW SHAFTS AND RISERS: NEW SHAFT AND RISER LOCATIONS ARE INTENDED TO FALL

BETWEEN STRUCTURAL CONCRETE RIBS. UPON COMPLETION OF REMOVAL OF PLASTER

CEILINGS AND OTHER OBSCURING FEATURES IN THE VICINITY OF THE NEW SHAFT/RISER

LOCATIONS AND BEFORE BEGINNING STRUCTURAL DEMO OR FRAMING LAYOUT, GC SHALL

PREPARE AND SUBMIT…

This is the start of the file's text. The full file is on GovTribe.