This document is an architectural drawing set for partition types and floor-ceiling assemblies for the West Roxbury VA Medical Center in West Roxbury, Massachusetts. The project, numbered 0506-0012, involves replacing boilers and upgrading controls at the facility. The drawing is part of the bid documents issued for construction dated November 14, 2025, with an addendum issued on March 2, 2026. The drawing was prepared by WBRC INC Consultants as the engineer of record, with Mabbett & Associates serving as architect of record. Additional consultants include Koffel Associates for fire and life safety, GRW for electronic security, PEC for tunnel structural and civil engineering, and Force Protect for physical security.

The drawing details multiple wall and partition configurations including metal stud partitions (types M2, M4, M6, and M8 with stud sizes ranging from 2½ inches to 8 inches), concrete masonry unit (CMU) partitions (types C6, C8, C10, and C12 in various ratings), metal stud chase walls, and rated floor-ceiling assemblies. Construction specifications include 5/8-inch Type X gypsum wallboard application on metal studs at 16-inch spacing, mineral wool or unfaced sound attenuation blanket insulation for sound deadening, continuous acoustical or fire-stop sealants, and specific head and base conditions. The drawing also depicts rated assemblies complying with UL designs U906, U905, and U415, with fire-rating requirements ranging from 1-hour to 2-hour ratings. Deflection track attachments and acoustical putty coverage for electrical and telecommunications outlets are specified throughout the various partition types.

View the file

Other files

File Type Posted
Amendment 5 RFI Response.xlsx XLSX spreadsheet
SF111.3A A0004.pdf PDF
S-002 A0004.pdf PDF
SF121.3A A0004.pdf PDF
SF101.3A A0004.pdf PDF
MH131.3A A0004.pdf PDF
MQ141.3A A0004.pdf PDF
AE102_3 A0004.pdf PDF
AE103_3 A0004.pdf PDF
Geotechnical Report 8 of 8 A0004.pdf PDF
S-003 A0004.pdf PDF
MH121.3A A0004.pdf PDF
PP141.3A A0004.pdf PDF
AE401 A0004.pdf PDF
Geotechnical Report 6 of 8 A0004.pdf PDF
Geotechnical Report 7 of 8 A0004.pdf PDF
Geotechnical Report 2 of 8 A0004.pdf PDF
S02 36C24125R0077 0004.docx DOCX document
S06 36C24125R0077 0003.pdf PDF
S06 Site Visit 2 Sign In Sheet 01282026 523A4-20-208 Replace Boilers and Upgrade Controls.pdf PDF
S02 PCRA 523A4 20 208 Replace Boilers and Upgrade Controls.pdf PDF
S02 Exhibit B.pdf PDF
523A4 20 208_Bid Specifications Volume III.pdf PDF
09c_Mechanical.pdf PDF
11_Security Electronics.pdf PDF
06b_Architectural.pdf PDF
06a_Architectural.pdf PDF
05b_Structural.pdf PDF
07_Fire Protection.pdf PDF
S02 WD MA20250001 12122025.pdf PDF
S02 Exhibit D.xlsx XLSX spreadsheet
P03 Brand Name Door Hardware_Redacted.pdf PDF
P03 Brand Name Trane_Redacted.pdf PDF
P03 Brand Name Fire Alarm_Redacted.pdf PDF
523A4 20 208_Bid Specifications Volume II.pdf PDF
09a_Mechanical.pdf PDF
01_General.pdf PDF
04_Civil.pdf PDF
S02 VHA Boiler and Associated Plant Safety Device Testing Manual 8th Edition 1.pdf PDF
S02 RFP 36C24125R0077 Solicitation.pdf PDF
S02 SOW 523A4 20 208 Replace Boilers and Upgrade Controls.pdf PDF
S02 ICRA 523A4 20 208 Replace Boilers and Upgrade Controls.pdf PDF
S02 Exhibit A.pdf PDF
P03 Brand Name CB Boiler Burner Fire Tube_Redacted.pdf PDF
P03 Brand Name ATS_Redacted.pdf PDF
523A4 20 208_Bid Specifications Volume I.pdf PDF
09b_Mechanical.pdf PDF
08_Plumbing.pdf PDF
05a_Structural.pdf PDF
03b_Civil Site.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACH RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

OUTLET BOX

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

ONE LAYER OF 5/8"

TYPE "X" GWB. ON

BOTH SIDES OF METAL

STUD @ 16" O.C. SEE

SCHEDULE FOR STUD

SIZES

MINERAL WOOL

INSULATION FRICTION

FIT FOR SOUND

DEADENING. FIT TO

FULL WIDTH OF CAVITY

COVER ALL SIDES OF ALL

TEL. & ELEC. OUTLETS WITH

1/4" THICK ACOUSTICAL

PUTTY BEFORE APPLYING

GWB. DO NOT INSTALL

OUTLETS BACK TO BACK. TO

MAINTAIN MAX. SPACING

BETWEEN OUTLETS ON

OPP. SIDES OF PARTITIONS.

HEAD CONDITION

WALL TYPE VA PARTITION # STUD SIZE

METAL STUD WALL STUD SIZE SCHEDULE

M2 09P22M2 2 1/2"

M6 09P62M6 6"

M8 09P82M8 8"

M4 09P42M4 3 5/8"

AE604

B5

Sim

1/

2"

8" NOM CMU BLOCK

GYPSUM WALL

BOARD CEILING

SHOWN SEE CEILING

PLANS FOR

LOCATION AND

HEIGHTS

ATC CEILING

SHOWN (SEE

CEILING PLANS FOR

LOCATION AND

HEIGHTS)

GYPSUM WALLBOARD

CEILING SYSTEM SEE

SPEC

UNDERSIDE OF METAL

DECKING OR

UNDERSIDE OF ROOF

SHEATHING

SLUSH CELLS 4"

DEEP MIN W/ GROUT

CONTINUOUS

ACOUSTICAL TAPE

AND SEALANT

WALL TYPE CMU SIZE

WALL CMU SIZE SCHEDULE

C6 6"

C10 10"

C12 12"

C8 8"

8" NOM CMU BLOCK

GYPSUM WALL

BOARD CEILING

SHOWN SEE CEILING

PLANS FOR

LOCATION AND

HEIGHTS

ATC CEILING SHOWN

(SEE CEILING PLANS

FOR LOCATION AND

HEIGHTS)

GYPSUM WALLBOARD

CEILING SYSTEM SEE

SPEC

UNDERSIDE OF METAL

DECKING OR

UNDERSIDE OF ROOF

SHEATHING

1/

2"

SLUSH CELLS 4"

DEEP MIN W/ GROUT

CONTINUOUS

ACOUSTICAL TAPE

AND SEALANT

WALL TYPE CMU SIZE

WALL CMU SIZE SCHEDULE

C6.1 6"

C10.1 10"

C12.1 12"

C8.1 8"

8" NOM CMU

BLOCK (CLASS

D-2)

1/

2"

GYPSUM WALL

BOARD CEILING

SHOWN SEE CEILING

PLANS FOR

LOCATION AND

HEIGHTS

ATC CEILING SHOWN

(SEE CEILING PLANS

FOR LOCATION AND

HEIGHTS)

GYPSUM WALLBOARD

CEILING SYSTEM SEE

SPEC

UNDERSIDE OF

METAL DECKING OR

UNDERSIDE OF ROOF

SHEATHINGSLUSH CELLS 4"

DEEP MIN W/ GROUT

CONTINUOUS

ACOUSTICAL TAPE

AND SEALANT

WALL TYPE CMU SIZE

WALL CMU SIZE SCHEDULE

C6.2 6"

C10.2 10"

C12.2 12"

C8.2 8"

UNDERSIDE OF

CONCRETE

PLANK

SLUSH CELLS

4" DEEP MIN

w/ GROUT

CONTINUOUS

ACOUSTICAL TAPE

AND SEALANT

UL DESIGN: U906

SEE STRUCTURAL

FOR ATTACHMENT

ATTACH DEEP LEG

DEFLECTION TRACK TO

STRUCTURE AT 24" O.C.

AND WITHIN 1" OF END

HEAD CONDITION

PERPENDICULAR TO DECK

ONE LAYER OF 5/8" TYPE

"X" GWB ON BOTH SIDES

OF DEFLECTION TRACK

CONTINUOUS ACOUSTICAL

JOINT SEALANT

COPE GWB INTO FLUTES

OF DECKING AND

AROUND BEAMS,

BRIDGING, PIPING, ETC...

ATTACH DEEP LEG

DEFLECTION TRACK TO

STRUCTURE AT 24" O.C.

AND WITHIN 1" OF END

HEAD CONDITION

PARALLEL TO DECK

ONE LAYER OF 5/8" TYPE

"X" GWB ON BOTH SIDES

OF DEFLECTION TRACK

CONTINUOUS ACOUSTICAL

JOINT SEALANT

PROVIDE "Z"-CLIP

AS REQUIRED FOR

DEFLECTION TRACK

ATTACHMENT

UNFACED SOUND

ATTENUATION BLANKET

INSULATION. FRICTION FIT

FOR SOUND DEADENING.

UNFACED SOUND

ATTENUATION BLANKET

INSULATION. FRICTION FIT

FOR SOUND DEADENING.

TOP OF METAL DECK

MINERAL WOOL IN

DECK FLUTES, TYP.

BOTTOM OF MTL. DECK

FIRE-RATED GYPSUM

COMPOUND OR FIRE CAULK

CONTINUOUS ON BOTH SIDES

FIRE TRAK

POSI - CLIPS

5/8" TYPE "X" GWB

CUT TO FIT DECK

FLUTES

METAL STUD

1/

2" 2"

8"

3"

HEAD CONDITION

PARALLEL TO DECK

PROVIDE "Z"-CLIP

AS REQUIRED FOR

DEFLECTION TRACK

ATTACHMENT

TOP OF METAL DECK

FIRE-RATED GYPSUM

COMPOUND OR FIRE CAULK

CONTINUOUS ON BOTH

SIDES

FIRE TRAK

POSI - CLIPS

5/8" TYPE "X" GWB

TO B.O. DECK

METAL STUD

1/

2" 2"

8"

3"

HEAD CONDITION

PERPENDICULAR TO DECK

METAL DECK

SEE STRUC DRAWINGS

3-1/4" LIGHTWEIGHT

CONCRETE SLAB

SEE STRUC DRAWINGS

WELDED WIRE FABRIC

6x6 - W1.4xW1.4

UL DESIGN: D916 AT 1HR & 2HR FLOOR/CEILING ASSEMBLIES

5"

ATTACH J RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

ATTACH J RUNNER

TRACK TO STRUCTURE

AT 24" O.C. AND WITHIN

1" OF END

ONE LAYER OF 5/8"

TYPE "X" GWB. ON

FACE SIDE AND 1"

TYPE "X" GWB ON

BACK SIDE OF 2 1/2"

METAL CT STUD @ 16"

O.C.

CONTINUOUS FIRE

STOP SEALANT

SCHEDULED FLOOR

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

HEAD CONDITION

SEAL WALL TO

DECKING WITH

CONTINUOUS FIRE

STOP SEALANT; BOTH

SIDES

UL DESIGN: U415

ATTACH RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

OUTLET BOX

CONTINUOUS

FIRESTOP SEALANT

EACH SIDE

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

ONE LAYER OF 5/8"

TYPE "X" GWB. ON

BOTH SIDES OF METAL

STUD @ 16" O.C. SEE

SCHEDULE FOR STUD

SIZES

UNFACED MINERAL

WOOL BLANKET

INSULATION FRICTION

FIT FOR SOUND

DEADENING. FIT TO

FULL WIDTH OF CAVITY

COVER ALL SIDES OF ALL

TEL. & ELEC. OUTLETS WITH

1/4" THICK ACOUSTICAL

PUTTY BEFORE APPLYING

GWB. DO NOT INSTALL

OUTLETS BACK TO BACK. TO

MAINTAIN MAX. SPACING

BETWEEN OUTLETS ON

OPP. SIDES OF PARTITIONS.

HEAD CONDITION

WALL TYPE VA PARTITION # STUD SIZE

METAL STUD WALL STUD SIZE SCHEDULE

M2.1 09P22M2 2 1/2"

M6.1 09P62M6 6"

M4.1 09P42M4 3 5/8"

AE604

B7

Sim

ATTACH RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

OUTLET BOX

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

ONE LAYER OF 5/8"

TYPE "X" GWB. ON ONE

SIDE OF METAL STUD

@ 16" O.C. SEE

SCHEDULE FOR STUD

SIZES

MINERAL WOOL

INSULATION FRICTION

FIT FOR SOUND

DEADENING. FIT TO

FULL WIDTH OF CAVITY

COVER ALL SIDES OF ALL

TEL. & ELEC. OUTLETS WITH

1/4" THICK ACOUSTICAL

PUTTY BEFORE APPLYING

GWB. DO NOT INSTALL

OUTLETS BACK TO BACK. TO

MAINTAIN MAX. SPACING

BETWEEN OUTLETS ON

OPP. SIDES OF PARTITIONS.

HEAD CONDITION

WALL TYPE STUD SIZE

METAL STUD WALL STUD

SIZE SCHEDULE

M2C 2 1/2"

M6C 6"

M8C 8"

M4C 3 5/8"

CONTINUOUS

ACOUSTICAL SEALANT

ATTACH DEEP LEG

DEFLECTION TRACK TO

STRUCTURE AT 24" O.C.

AND WITHIN 1" OF END

ATTACH RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

OUTLET BOX

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

(2) LAYERS OF 5/8"

TYPE "X" GWB. ON ONE

SIDE OF METAL STUD

@ 16" O.C. SEE

SCHEDULE FOR STUD

SIZES

MINERAL WOOL

INSULATION FRICTION

FIT FOR SOUND

DEADENING. FIT TO

FULL WIDTH OF CAVITY

COVER ALL SIDES OF ALL

TEL. & ELEC. OUTLETS WITH

1/4" THICK ACOUSTICAL

PUTTY BEFORE APPLYING

GWB. DO NOT INSTALL

OUTLETS BACK TO BACK. TO

MAINTAIN MAX. SPACING

BETWEEN OUTLETS ON

OPP. SIDES OF PARTITIONS.

HEAD CONDITION

WALL TYPE STUD SIZE

METAL STUD WALL STUD

SIZE SCHEDULE

M4C.1 3 5/8"

CONTINUOUS

ACOUSTICAL SEALANT

ATTACH DEEP LEG

DEFLECTION TRACK TO

STRUCTURE AT 24" O.C.

AND WITHIN 1" OF END

ATTACH RUNNERS TO

FLOOR @ 24" O.C. AND

WITHIN 1" OF ENDS.

OUTLET BOX

CONTINUOUS

FIRESTOP SEALANT

EACH SIDE

SCHEDULED BASE

BASE CONDITION

PLAN CONDITION

ONE LAYER OF 5/8"

TYPE "X" GWB. ON

BOTH SIDES OF METAL

STUD @ 16" O.C. SEE

SCHEDULE FOR STUD

SIZES

UNFACED MINERAL

WOOL BLANKET

INSULATION FRICTION

FIT FOR SOUND

DEADENING. FIT TO

FULL WIDTH OF CAVITY

COVER ALL SIDES OF ALL

TEL. & ELEC. OUTLETS WITH

1/4" THICK ACOUSTICAL

PUTTY BEFORE APPLYING

GWB. DO NOT INSTALL

OUTLETS BACK TO BACK. TO

MAINTAIN MAX. SPACING

BETWEEN OUTLETS ON

OPP. SIDES OF PARTITIONS.

HEAD CONDITION

WALL TYPE STUD SIZE

METAL STUD WALL

STUD SIZE SCHEDULE

M2.2 2 1/2"

M6.2 6"

M4.2 3 5/8"

AE604

B7

Sim

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD WBRC INC

ARCHITECT OF RECORDCONSULTANTS

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE ARCHITECT OF RECORD

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t

523A4-20-208

MR PROJECT NO:

Hazardous Materials:

MABBETT & ASSOCIATES

Architect & Civil Engineering:

WBRC

Fire & Life Safety:

KOFFEL ASSOCIATES

Electronic Security:

GRW

Tunnel Structural & Civil Engineering:

PEC

Physical Security:

FORCE PROTECT

2/

/2

3:

:5

PM

AE604

ARCHITECTURAL

PARTITION TYPES & FLOOR CEILING ASSEMBLY

REPLACE BOILERS AND

UPGRADE CONTROLS

WEST ROXBURY VA MEDICAL CENTER

WEST ROXBURY, MA

11/14/2025 TRJ BRS

BID DOCUMENTS

ISSUED FOR CONSTRUCTION

0506-0012

3" = 1'-0"

F8 M# - METAL STUD PARTITIONS

3/4" = 1'-0"

D9 C# - NOM CMU PARTITION

3/4" = 1'-0"

D7 C#.1 - NOM CMU RATED 1 HOUR- U.L. #U906

3/4" = 1'-0"

D5 C#.2 - NOM CMU 2 HOUR- U.L. #U905

3" = 1'-0"

D1 TYPICAL HEAD CONDITION - CMU

3" = 1'-0"

B5 EXPOSED T.O. WALL TO B.O. DECK

HEAD CONDITIONS 3" = 1'-0"

B7 T.O. MTL. STUD - 1-HR - 3" DEFLECTION

3" = 1'-0"

B2 RATED FLOOR/CEILING ASSEMBLY DETAIL

3" = 1'-0"

F1 CH2.1 - 2 1/2" CH STUD SHAFTWALL - 1HR

NO. DESCRIPTION DATE

1 ADDENDUM 01 03/02/2026

3" = 1'-0"

F5 M#.1 - METAL STUD PARTITIONS - 1HR - U.L. #419

3" = 1'-0"

F3 M# - METAL STUD CHASE

3" = 1'-0"

D3 M#C.1 - METAL STUD CHASE - 1HR

1 1

3" = 1'-0"

B3 M#.2 - METAL STUD PARTITIONS - 2HR - U.L. #419

3/3/2026

File details come from the government source that posted it. Updated .