This document is a comprehensive structural design notes sheet for Building 606 at West Point, detailing technical specifications for construction and renovation. The notes cover multiple structural elements including steel deck, steel joists, structural steel, foundations, cold-formed metal framing, and rebar development lengths. Key technical requirements include adherence to building codes like the 2018 International Building Code, specific design load parameters for floors, roofs, seismic design data, wind loads, and material specifications for structural components. The project involves renovations and additions to a cadet hospital, with design loads and specifications derived from a geotechnical engineering report dated March 28th, 2022, which established foundational bearing capacities for column and wall footings.
The document provides detailed technical guidance for contractors, specifying material standards, welding requirements, coating specifications, and installation protocols for various structural elements. Notable requirements include using ASTM-specified steel grades, galvanized finishes, AWS welding standards, and specific installation techniques for steel deck, joists, and framing. Structural steel must comply with AISC standards, and all exterior structural steel must be hot-dipped galvanized. The notes also emphasize the contractor's responsibility for temporary bracing, testing existing steel beams, and ensuring proper grout and anchor installations.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. STRUCTURE WAS DESIGNED IN ACCORDANCE WITH THE UNIFIED FACILITIES CRITERIA 3-301-01 AND THE 2018 INTERNATIONAL BUILDING CODE AND THE 2018 INTERNATIONAL EXISTING BUILDING
CODE.
2. CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING CONDITIONS AT THE SITE PRIOR TO BEGINNING ANY WORK. IF EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF
THE WORK IN ACCORDANCE WITH THE DETAILS AS SHOWN, NOTIFY ENGINEER IMMEDIATELY.
3. DESIGN LOADS:
a. FLOOR LIVE LOADS:
1. ASSEMBLY AREA / LOBBY & CORRIDORS SERVING THEM ............................ 100 PSF
2. CLASS ROOMS & CORRIDORS SERVING THEM ............................................... 40 PSF
3. STAIRCASES .......................................................................................................... 100 PSF
b. ROOF LIVE LOADS:
1. GROUND SNOW LOAD ......................................................................................... 30 PSF
2. FLAT-ROOF SNOW LOAD ..................................................................................... 27.5 PSF
3. SNOW EXPOSURE FACTOR ................................................................................ 1.0
4. SNOW LOAD IMPORTANCE FACTOR .................................................................. 1.1
5. THERMAL FACTOR ............................................................................................... 1.0
6. SNOW DRIFT LOADING DETERMINED IN ACCORDANCE WITH ASCE 7-16.
c. SEISMIC DESIGN DATA:
1. OCCUPANCY CATEGORY ..................................................................................... III
2. SEISMIC IMPORTANCE FACTOR ......................................................................... 1.25
3. MAPPED SPECTRAL RESPONSE ACCELERATION ............................................ SS = 0.261 g
4. MAPPED SPECTRAL RESPONSE ACCELERATION ............................................ S1 = 0.059 g
5. SPECTRAL RESPONSE COEFFICIENT ................................................................ SDS = 0.174 g
6. SPECTRAL RESPONSE COEFFICIENT ................................................................ SD1 = 0.039 g
7. SITE CLASS ............................................................................................................. B (ESTIMATED)
8. SEISMIC DESIGN CATEGORY ............................................................................... B
9. REPONSE MODIFICATION ..................................................................................... 1.5
a. EXISTING STRUCTURE RESPONSE COEFFICIENT IS 1.5 BASED ON ORDINARY PLAIN
MASONRY SHEAR WALLS. DESIGN OF NEW ADDITION UTILIZED R = 1.5 FOR
CONSERVATIVE DESIGN. NEW MASONRY WALLS HAVE BEEN DESIGNED AND DETAILED
AS INTERMEDIATE MASONRY SHEAR WALLS
d. WIND LOAD:
1. ULTIMATE DESIGN WIND SPEED (3 SEC GUST) ................................................. 122 MPH
2. RISK CATEGORY ..................................................................................................... III
3. WIND EXPOSURE CATEGORY .............................................................................. B
4. INTERNAL PRESSURE ........................................................................................... ± 0.18
5. COMPONENT AND CLADDING NOT SPECFICALLY DESIGNED HEREIN SHALL BE DESIGNED
FOR THE FOLLOWING NET DESIGN WIND PRESSURES; BASED ON TRIBUTARY AREA.
e. RAIN LOAD DATA
1. 15 MINUTE INTENSITY ............................................................................................. 6.48 IN / HR
2. 60 MINUTE INTENSITY ............................................................................................. 2.83 IN / HR
GENERAL DESIGN
NOTE:
ALL NEW PENETRATIONS ARE TO BE CORE DRILLED, WHEREVER FEASIBLE, RE-USE EXISTING
PENETRATIONS IN THE STRUCTURE INCLUDING EXISTING BLOCKOUTS, SLEEVES, OR CORES. ANY OFFSETS FOR PIPING OR CONDUIT DUE TO THE RE-USE OF EXISTING PENETRATIONS WILL BE AT
NO COST TO THE U.S. GOVERNMENT. ALL EXISTING PENETRATIONS IN FLOORS OR ROOF NOT
BEING USED ARE TO BE FILLED.
NEW PENETRATIONS IN EXST SLAB NOT SHOWN IN THESE DRAWINGS TO HAVE A MAXIMUM SIZE
OF 8" x 8" AND TO HAVE A MINIMUM DISTANCE OF 8" FROM ADJACENT PENETRATIONS. IF UTILIZING EXISTING PENETRATIONS, GRIND AND/OR PATCH EXISTING EDGE AS REQUIRED TO INFILL GAPS AND MAINTAIN FIRE RATING OF FLOOR SYSTEM. CLEAN EDGES AND REMOVE EXISTING DEBRIS AS
REQUIRED.
ALL DIMENSIONS RELATIVE TO EXISTING BUILDING STRUCTURE ARE BASED ON AS-BUILT
DOCUMENTATION. PRIOR TO NEW CONSTRUCTION, AND STRUCTURAL STEEL FABRICATION,
CONTRACTOR MUST PROVIDE A PRE-CONSTRUCTION SURVEY OF THE EXISTING BULDING AND
EXISTING STRUCTURAL COMPONENTS. SURVEY TO VERIFY STRUCTURAL STEEL CONNECTION
POINTS, BUILDING GRID GEOMETRY, FLOOR ELEVATIONS, ETC.
EXISTING STRUCTURAL INFORMATION IS FROM THE DRAWING SETS LISTED BELOW:
1. ADDITION TO CADET HOSPITAL - DATED 1933
2. ADDITION TO CADET HOSPITAL & ANNEX, BY YORK & SAWYER ARCHITECTS-ENGINEERS
- DATED 1943
3. ALTERATIONS TO EXISTING HOSPITAL BUILDING NO. 606, FY-1959, BY O'CONNOR AND KILHAM
ARCHITECT-ENGINEER - DATED 1961
4. CONVERSION OF BUILDING NO. 606, BY LEO A. DALY COMPANY - DATED 1984
NOTES:
1. ZONE DEFINED IN BUILDING CODE USING A = 12 FT.
2. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.
3. PRESSURES ARE REPORTED AT ULTIMATE DESIGN WIND SPEED LEVEL. USE APPROPRIATE LOAD
COMBINATION ACCORDING TO ASCE 7-16.
ROOF PLAN
WALL ELEVATION
2A 2A
A
A
A
2 3
3 2 3
2 21
2A 2A
45 5
3" A
1. CAST-IN-PLACE CONCRETE CONSTRUCTION SHALL COMPLY WITH THE FOLLOWING
CODES AND STANDARDS.
a. ACI 117 "STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIALS"
b. ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE"
c. ACI 304 "GUIDE FOR MEASURING, MIXING, TRANSPORTING AND PLACING
CONCRETE"
d. ACI 305, ACI 306, ACI 318, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE"
e. ACI 347 "GUIDE TO FORMWORK FOR CONCRETE"
f. ACI DETAILING MANUAL
g. CONCRETE REINFORCING STEEL INSTITUTE (CRSI), "MANUAL OF STANDARD
PRACTICE"
2. CONCRETE SHALL BE READY MIXED PER ASTM C94.
3. THE ADDITION OF WATER TO THE CONCRETE MIX AT THE JOB SITE IS NOT
PERMITTED UNLESS SPECIFICALLY ALLOWED BY THE ENGINEER. IT MUST BE
DOCUMENTED PER C94 AND NOT EXCEED THE W/C RATIO.
4. PREPARE DESIGN MIXES FOR EACH TYPE, AND STRENGTH OF CONCRETE BY
EITHER LABORATORY TRIAL BATCH OR FIELD EXPERIENCE METHODS AS
SPECIFIED IN ACI 318-14.
5. PORTLAND CEMENT - ASTM C150, TYPE I / II.
6. AGGREGATES - ASTM C33.
7. AIR ENTRAINING ADMIXTURE - ASTM C260, CERTIFIED BY MANUFACTURER TO BE
COMPATIBLE WITH OTHER REQUIRED ADMIXTURES.
8. PROHIBITED ADMIXTURES - CALCIUM CHLORIDE THYOCYANATES OR ADMIXTURES
CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS ARE NOT PERMITTED.
9. MINIMUM CONCRETE COMPRESSIVE STRENGTH AT 28 DAYS (NORMAL WEIGHT) :
a. CONTINUOUS FOOTINGS & INDIVIDUAL FOOTINGS ............ F'c = 4,500 PSI
b. FOUNDATION WALLS & PIERS ................................................ F'c = 4,500 PSI
c. SLAB-ON-GRADE ....................................................................... F'c = 4,000 PSI
d. SLAB ON COMPOSITE FLOOR DECK ..................................... F'c = 4,500 PSI
e. CONCRETE TOPPING / MISC. BEARING PADS...................... F'c = 5,000 PSI
f. LIGHTWEIGHT CONCRETE (110 PCF) .................................... F'c = 4,000 PSI
10. UNLESS OTHERWISE NOTED, REINFORCING SHALL HAVE THE FOLLOWING
CONCRETE COVER :
a. CONCRETE CAST AGAINST AND EXPOSED TO EARTH = 3"
b. CONCRETE EXPOSED TO EARTH OR WEATHER = 2"
c. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
1. ELEVATED SLABS AND WALLS = 3/4"
2. PIERS = 1 1/2"
11. REINFORCING BARS - ASTM A615, GRADE 60, DEFORMED.
12. SUPPORTS FOR REINFORCEMENT SHALL BE WIRE BAR TYPE SUPPORTS
COMPLYING WITH CRSI SPECIFICATION.
13. UNLESS OTHERWISE SHOWN, REINFORCING BAR SPLICES ARE TO BE CLASS 'B'
SPLICES.
14. PROTECT CONCRETE WORK FROM THE DETRIMENTAL EFFECTS OF COLD
TEMPERATURES IN COMPLIANCE WITH ACI 306, AND OF HOT WEATHER OR WINDY
CONDITIONS IN COMPLIANCE WITH ACI 305.
15. CONSTRUCTION JOINTS PERMITTED ONLY AS APPROVED BY THE STRUCTURAL
ENGINEER.
16. THE PRIME CONTRACTOR WILL EMPLOY A TESTING AGENCY TO PERFORM
SAMPLING AND TESTING SUBMIT TEST REPORTS.
17. EPS FORMWORK TO BE EITHER EXTRUDED OR EXPANDED TYPE IV OR IX
COMPLYING WITH ASTM C578.
CAST-IN-PLACE CONCRETE
1. FURNISH AND INSTALL STEEL DECK IN ACCORDANCE WITH STEEL DECK INSTITUTE
SPECIFICATIONS AND THE CONTRACT DOCUMENTS.
2. COMPOSITE FLOOR DECK:
BEAM SPACING IS BASED ON THREE-SPAN CONDITION ASSUMING THE FOLLOWING
PRODUCTS WITH MINIMUM PROPERTIES. SUBSTITUTIONS WILL BE ALLOWED,
FOLLOWING SPECIFICATION, PROVIDED THE PROPOSED SUBSTITUTION MEETS OR
EXCEEDS THESE PROPERTIES.
a. 2" x 20 ga., GALVANIZED STEEL
REQUIRED MINIMUM PROPERTIES:
1. Id+........................................................................0.409 in4 / ft
2. Id-........................................................................ 0.407 in4 / ft
3. Se+...................................................................... 0.326 in3 / ft
4. Se-....................................................................... 0.337 in3 / ft
5. DECK SHALL EXTEND OVER 3 SPANS MINIMUM.
3. COMPOSITE ROOF DECK:
a. 1 1/2" x 22 GA., GALVANIZED STEEL
REQUIRED MINIMUM PROPERTIES:
1. Id+....................................................................... 0.155 in4 / ft
2. Id-........................................................................ 0.178 in4 / ft
3. Se+...................................................................... 0.169 in3 / ft
4. Se-....................................................................... 0.179 in3 / ft
5. DECK SHALL EXTEND OVER 3 SPANS MINIMUM.
4. WELDING TO BE DONE IN ACCORDANCE WITH AWS D1.3, STRUCTURAL WELDING
CODE - SHEET STEEL, AND CONTRACT SPECIFICATIONS, UNLESS NOTED
OTHERWISE. IF THERE IS A DISCREPANCY THE MORE STRINGENT REQUIREMENTS
GOVERN.
5. NO LOADS SHALL BE HUNG FROM THE ROOF DECK.
6. PROVIDE ADDITIONAL SUPPORT FRAMING FOR ALL DECK OPENINGS THAT EXCEED
10 INCHES IN ANY DIRECTION. STRUCTURAL SUPPORT SHALL BE PROVIDED ON ALL
SIDES OF THE OPENING.
7. WELD DECK TO STRUCTURAL MEMBERS WITH 5/8" PUDDLE WELDS SPACED 36/4.
FASTEN SIDELAPS WITH (1) #10 SCREW PER SPAN.
STEEL DECK
1. SEE STRUCTURAL AND ARCHITECTURAL DRAWINGS FOR LOCATION, SIZE AND
SPACING OF REINFORCED MASONRY.
2. CONCRETE MASONRY UNITS ARE TO BE ASTM C-90 TWO CELL NORMAL WEIGHT
(F'm = 2,000 psi.)
3. MORTAR TO BE ASTM C270, SEE SPECIFICATIONS FOR TYPE.
4. CONCRETE MASONRY GROUT IS TO BE COURSE GROUT ASTM C-476 (F'c = 2,000 psi.)
6. GROUT ALL REINFORCED BLOCK CORES SOLID WITH GROUT NOTED ABOVE.
5. CONCRETE MASONRY CONSTRUCTION IS TO BE OBSERVED AND TESTED BY AN
INDEPENDENT TESTING LABORATORY. SEE SPECIFICATIONS FOR REQUIREMENTS.
6. HORIZONTAL LADDER TYPE REINFORCEMENT IS REQUIRED AT 16"OC MAX. (U.N.O.)
MASONRY
1. NOT ALL STEEL OR CONCRETE WORK IS NOTED OR DETAILED ON THE DRAWINGS.
REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL WORK REQUIRED. BOTH
ARCHITECTURAL AND STRUCTURAL DRAWINGS ARE INTENDED TO WORK TOGETHER
AND DEFINE THE COMPLETE SCOPE OF WORK REQUIRED. IF DISCREPANCIES ARE
FOUND, NOTIFY THE ARCHITECT IMMEDIATELY.
2. STRUCTURAL ASSEMBLY SHOWN HEREIN WAS DESIGNED TO BE SELF SUPPORTING IN
ITS FINAL STATE ONLY. TEMPORARY BRACING TO SUPPORT LATERAL LOADS DURING
CONSTRUCTION IS THE CONTRACTOR’S RESPONSIBILITY. BRACING SHALL BE DESIGNED
BY A LICENSED STRUCTURAL ENGINEER.
3. LEGEND OF ABBREVIATIONS:
ADDL...................................................................................... ADDITIONAL ALT......................................................................................... ALTERNATE ANCH..................................................................................... ANCHOR APPROX................................................................................ APPROXIMATE ARCH. ................................................................................... ARCHITECT(URAL) BFE......................................................................................... BOTTOM OF FOOTING ELEVATION BM .......................................................................................... BEAM BOT........................................................................................ BOTTOM BS............................................................................................ BOTH SIDES CFMF ...................................................................................... COLD-FORMED METAL FRAMING CJ .......................................................................................... CONTROL JOINT CLR ........................................................................................ CLEAR COL. ....................................................................................... COLUMN CONC ..................................................................................... CONCRETE CONT ..................................................................................... CONTINUOUS DIA ......................................................................................... DIAMETER DTL ........................................................................................ DETAIL DWG or DWGs ..................................................................... DRAWING DWLs .................................................................................... DOWELS EA .......................................................................................... EACH EF .......................................................................................... EACH FACE EJ ........................................................................................... EXPANSION JOINT EL ........................................................................................... ELEVATION ELEV ...................................................................................... ELEVATOR EOC ........................................................................................ EDGE OF CONCRETE EOD ........................................................................................ EDGE OF DECK EOS ........................................................................................ EDGE OF SLAB EQ ..........................................................................................EQUAL EW .......................................................................................... EACH WAY EXP .........................................................................................EXPANSION EXST ...................................................................................... EXISTING EXT ......................................................................................... EXTERIOR FDN .........................................................................................FOUNDATION FF ........................................................................................... FINISH FLOOR FF EL ...................................................................................... FINISH FLOOR ELEVATION FIN .......................................................................................... FINISH FRMG ..................................................................................... FRAMING FTG ........................................................................................ FOOTING FTG ST.................................................................................... FOOTING STEP GA ...........................................................................................GAUGE GALV ...................................................................................... GALVANIZED HS ........................................................................................... HEADED STUD IF ............................................................................................. INSIDE FACE INS ......................................................................................... INSULATION INT........................................................................................... INTERIOR INV .......................................................................................... INVERT JT ............................................................................................ JOINT L .............................................................................................. LONG Ld ............................................................................................ DEVELOPMENT LENGTH LG ........................................................................................... LONG LL ............................................................................................ LIVE LOAD LLH ......................................................................................... LONG LEG HORIZONTAL LLV ......................................................................................... LONG LEG VERTICAL MAX ....................................................................................... MAXIMUM MET ........................................................................................ METAL MIN ........................................................................................ MINIMUM MISC ...................................................................................... MISCELLANEOUS MO ......................................................................................... MASONRY OPENING NA ........................................................................................... NOT APPLICABLE NF ........................................................................................... NEAR FACE NTS .........................................................................................NOT TO SCALE OC .......................................................................................... ON CENTER OF ........................................................................................... OUTSIDE FACE OPH ........................................................................................ OPPOSITE HAND OPNG ..................................................................................... OPENING PSF ......................................................................................... POUNDS PER SQUARE FOOT PSI .......................................................................................... POUNDS PER SQUARE INCH R ............................................................................................. RISER RAD ........................................................................................ RADIUS RD .......................................................................................... ROOF DRAIN REINF .................................................................................... REINFORCE(D)(ING)(MENT) REQD .................................................................................... REQUIRED SCHED ................................................................................... SCHEDULE SECT ...................................................................................... SECTION SF ........................................................................................... SQUARE FOOT (FEET) SHT ........................................................................................ SHEET(ING) SIM ......................................................................................... SIMILAR SOG ....................................................................................... SLAB-ON-GRADE SP .......................................................................................... SPACE(ING) SPEC ...................................................................................... SPECIFICATION SST ......................................................................................... STAINLESS STEEL STD .........................................................................................STANDARD STIF ........................................................................................ STIFFENER STL ..........................................................................................STEEL STRUCT ................................................................................. STRUCTURE or STRUCTURAL SYM ....................................................................................... SYMBOL TOC ....................................................................................... TOP OF CONCRETE TOS ....................................................................................... TOP OF STEEL T&B ......................................................................................... TOP AND BOTTOM TEMP ...................................................................................... TEMPORARY TFE ......................................................................................... TOP OF FOOTING ELEVATION THK..........................................................................................THICK(NESS) TPE ......................................................................................... TOP OF PIER TYP ......................................................................................... TYPICAL TWE ........................................................................................TOP OF WALL ELEVATION UNO ....................................................................................... UNLESS NOTED OTHERWISE VB............................................................................................ VAPOR BARRIER VERT ...................................................................................... VERTICAL VEJ ......................................................................................... VERTICAL EXPANSION JOINT VIF .......................................................................................... VERIFY IN FIELD VSC ........................................................................................ VERTICAL SLIDE CLIP W ............................................................................................ WIDE WD ..........................................................................................WOOD WDW ...................................................................................... WINDOW WF .......................................................................................... WIDE FLANGE WP ......................................................................................... WORK POINT WWF ...................................................................................... WELDED WIRE FABRIC W/ ............................................................................................WITH W/O .........................................................................................WITHOUT WP .......................................................................................... WATERPROOF(ING)
MISCELLANEOUS
1. FURNISH AND INSTALL STEEL JOISTS AS INDICATED ON PLANS IN
ACCORDANCE WITH THE LATEST STEEL JOIST INSTITUTE SPECIFICATIONS,
OSHA AND THE CONTRACT DOCUMENTS.
2. DESIGN JOISTS FOR NET UPLIFT DERIVED PER A7/S-001 - NOTE 3.d MINUS 0.6 x (18 psf DL)
3. BRIDGING NOT SHOWN. LAYOUT PER SJI SPECIFICATIONS (LOCATION & TYPE).
ADJUST FOR UPLIFT AS REQUIRED.
STEEL JOIST
1. STRUCTURAL STEEL WORK INCLUDES ALL STRUCTURAL STEEL TO BE
FURNISHED AND ERECTED INCLUDING BEAMS, ANGLES, AND BEARING PLATES
AS INDICATED ON THE DRAWINGS.
2. COMPLY WITH THE FOLLOWING CODES AND STANDARDS:
a. AISC STEEL CONSTRUCTION MANUAL, ASD, 15TH EDITION.
b. AMERICAN WELDING SOCIETY (AWS) Dl.1 "STRUCTURAL WELDING CODE
STEEL".
3. SHOP DRAWINGS:
SUBMIT SHOP DRAWINGS INCLUDING COMPLETE DETAILS AND SCHEDULES
FOR FABRICATION AND ASSEMBLY OF STRUCTURAL STEEL MEMBERS,
PROCEDURES AND DIAGRAMS.
4. MATERIALS:
a. STRUCTURAL STEEL W SHAPES & CHANNELS.......... ASTM A992, GRADE 50
b. HOLLOW STRUCTURAL SECTIONS.............................. ASTM A 500, GRADE B
c. SCHEDULE 40 STEEL PIPE............................................ ASTM A53
d. ANGLES AND PLATES..................................................... ASTM A36
e. ANCHOR RODS................................................................ ASTM F1554, GRADE 36
f. CONNECTION BOLTS
BOLTS...........................................................................ASTM A325 N (U.N.O.)
LATERAL BRACE BOLTS............................................ SLIP CRITICAL
g. THREADED RODS............................................................ ASTM A36
h. POST-INSTALLED ANCHORS..........................................AS SHOWN
i. WELDING ELECTRODES................................................. E-70XX SERIES
j. SHRINKAGE COMPENSATING GROUT..........................ASTM C1107
k. ALL EXTERIOR STRUCTURAL STEEL TO BE HOT-DIPPED GALVANIZED.
5. FOR STRUCTURAL STEEL, ALL FILLET WELD SIZES TO BE 3/16" UNLESS NOTED
OTHERWISE. WELDED JOINTS SHALL BE CONSIDERED CONTINUOUS ALONG
THE FULL LENGTH OF THE DEFINED STEEL JOINT, UNLESS NOTED OTHERWISE.
6. STEEL CONTRACTOR SHALL TEST EXISTING STEEL BEAMS TO CONFIRM
WELDING SUITABILITY AND SUFFICIENT ELECTRODE. STEEL BEAMS ON
DIFFERENT FLOORS AND IN SEPARATE WINGS OF THE BUILDING MUST EACH
BE TESTED INDEPENDENTLY. NOTIFY COR.
7. CONTRACTOR TO INCLUDE N.S. GROUT AT ALL NEW STEEL SURFACES TO
EXISTING CONCRETE, WHERE GAPS ARE PRESENT.
STRUCTURAL STEEL
1. THE FOUNDATION REQUIREMENTS FOR THIS PROJECT ARE BASED ON "REPORT OF
SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING EVALUATION FOR
THE PROPOSED BUILDING 606 RENOVATIONS AT USMA WEST POINT, HIGHLANDS,
NY" BY JOHN P. STOPEN ENGINEERING, LLP, DATED MARCH 28TH, 2022.
2. FOUNDATIONS ARE PROPORTIONED FOR THE FOLLOWING NET ALLOWABLE
BEARING CAPACITIES:
a. COLUMN FOOTINGS: 8,000 PSF.
b. WALL FOOTINGS BEARING ON WEATHERD ROCK: 4,000 PSF.
3. FOOTINGS REQUIRING PROTECTION FROM FROST HEAVE MUST BEAR AT LEAST
4'-6" BELOW FINSHED GRADE. (HEATED STRUCTURES)
FOUNDATIONS
1. COLD-FORMED STRUCTURAL FRAMING SHALL BE DESIGNED IN ACCORDANCE WITH
THE STANDARD AMERICAN IRON AND STEEL INSTITUTE (AISI).
2. MATERIALS AND FINISH:
a. FOR 16 GAUGE AND HEAVIER UNITS, FABRICATE METAL FRAMING COMPONENTS
OF STRUCTURAL QUALITY STEEL SHEET WITH A MINIMUM YIELD POINT OF 50 KSI
ASTM A446, A570 OR A611.
b. FOR 18 GAUGE AND LIGHTER UNITS, FABRICATE METAL FRAMING COMPONENTS
OF STRUCTURAL QUALITY STEEL MINIMUM YIELD POINT OF 33 KSI ASTM A446,
A570, OR A611.
c. PROVIDE GALVANIZED FINISH TO ALL METAL FRAMING COMPONENTS
COMPLYING WITH ASTM A525 FOR MINIMUM G 60 COATING. USE GALVANIZING
REPAIR TOUCH-UP PAINT IN FIELD. INSTALL UN-CUT ENDS OF STUDS IN BOTTOM
TRACK.
d. MINIMUM FLANGE DEPTH OF 1-5/8" IN C-SHAPED TRACK AND RUNNER TO MATCH
GAUGE OF STUD.
3. BRIDGING FOR ALL WALLS SUPPORTING AXIAL LOADS TO BE 1-1/2" COLD ROLLED
CHANNEL WITH BRIDGING CLIPS. FABRICATION LAYOUT MAY LIMIT THE CAPABILITY
OF BRIDGING TO PROVIDE ADEQUATE BRACING OF THE WEAK AXIS OF STUDS. IT IS
THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN STUD STABILITY DURING
CONSTRUCTION.
4. WELDING TO BE PERFORMED BY AWS CERTIFIED WELDER. USE 0.035 FLUX-CORE
WIRE USING A MIG WELDER OR APPROVED SUBSTITUTE.
5. SQUARELY SEAT STUDS WITHIN 1/16" AGAINST WEB PORTION OF TOP AND
BOTTOM TRACKS.
6. FOR COLD-FORMED METAL FRAMING, ALL FILLET WELD TO BE SIZED AT
THICKNESS OF THINNEST MATERIAL, UNLESS NOTED OTHERWISE. WELDED JOINTS
SHALL BE CONSIDERED CONTINUOUS ALONG THE FULL LENGTH OF THE DEFINED
STEEL JOINT, UNLESS NOTED OTHERWISE.
COLD-FORMED METAL FRAMING
BAR SIZE
DEVELOPMENT LENGTH FOR BARS IN CONCRETE WALLS & SLABS
COVER or SPACING > Db COVER or SPACING < Db
TOP OTHER TOP OTHER
#3
#4
#5
#6
#7
#8
#9
#10
BAR SIZE
DEVELOPMENT LENGTH FOR BARS IN CONCRETE WALLS & SLABS (CLASS B)
COVER or SPACING > Db COVER or SPACING < Db
TOP OTHER TOP OTHER
#3
#4
#5
#6
#7
#8
#9
#10
NOTES:
1. 'TOP' - DEFINED AS HORIZONTAL REINFORCING BAR WHICH HAS MORE THAN 12" OF FRESH
CONCRETE CAST BELOW BAR.
2. USE UNLESS NOTED OTHERWISE.
3. LENGTH TO BE INCREASED BY 33% FOR LIGHTWEIGHT CONCRETE.
19 in. 15 in. 28 in. 22 in.
25 in. 19 in. 37 in. 29 in.
31 in. 24 in. 47 in. 36 in.
37 in. 29 in. 56 in. 43 in.
54 in. 42 in. 81 in. 63 in.
62 in. 48 in. 93 in. 72 in.
70 in. 54 in. 105 in. 81 in.
78 in. 60 in. 116 in. 89 in.
25 in. 19 in. 37 in. 28 in.
33 in. 25 in. 49 in. 37 in.
41 in. 31 in. 61 in. 47 in.
49 in. 37 in. 73 in. 56 in.
71 in. 54 in. 106 in. 81 in.
81 in. 62 in. 121 in. 93 in.
91 in. 70 in. 136 in. 105 in.
101 in. 78 in. 151 in. 116 in.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
Autodesk Docs://West Point Bldg 606/219208-WP606-S20.rvt
10/10/2025 10:04:42 AM
S-001
BLDG 606
G E
N E
R A
L N
O T
E S
U N
IT
E
D S
T A
T E
S M
IL
IT
A R
Y A
C A
D E
M Y
W
E S
T P
O
IN
T N
Y P
N
F
Y
N E
W Y
O R
K D
IS
T
R
IC
T N
E W
Y O
R K
N
Y
M M
F
T
H C
H
Q P
K
M M
M
A Y
W D
S C
Q P
K J
O B
N O
.0
ADDENDUM #6
R E
P A
IR
B
L D
G
G
E N
E R
A L I N
S T
R U
C T
IO
N
B L D
G
NO SCALE SCALE:
A7
GENERAL DESIGN NOTES
NO SCALE SCALE:
C9
CAST-IN-PLACE CONCRETE NOTES
NO SCALE SCALE:
E5
STEEL DECK NOTES
NO SCALE SCALE:
A9
MASONRY NOTES
NO SCALE SCALE:
A1
MISCELLANEOUS NOTES
NO SCALE SCALE:
A5
STEEL JOIST NOTES
NO SCALE SCALE:
B5
STRUCTURAL STEEL NOTES
NO SCALE SCALE:
A3
FOUNDATION NOTES
BUILDING COMPONENT & CLADDING PRESSURE (psf)
Effective Wind Area
WALL ROOF
Zone 5 Zone 4 Zone 3 Zone 2 Zone 1
10 SF -57.00 31.00 -31.00 31.00 -98.00 16.00 -72.00 16.00 -46.00 16.00
20 SF -57.00 31.00 -31.00 31.00 -95.00 16.00 -69.00 16.00 -43.00 16.00
50 SF -51.00 30.00 -30.00 30.00 -88.00 16.00 -63.00 16.00 -40.00 16.00
100 SF -46.00 25.00 -28.00 25.00 -83.00 16.00 -60.00 16.00 -37.00 16.00
NO SCALE SCALE:
B3
COLD-FORMED METAL NOTES
NO SCALE SCALE:
D3
REBAR LENGTH SCHEDULE
A
D D
E N
D U
M
/1
/2