About this file

This document is an electrical panel schedule drawing for a US Army Corps of Engineers project at the United States Military Academy, West Point, NY. The drawing (E-611) details panelboard schedules for multiple electrical panels (UP-EB-1, UP-EB-2, AP-EB-1, and LP-EB-1) located in the basement of a building (Building 606, General Instruction Building). The panels are configured for 208Y/120V and 480Y/277V power systems, with various circuit breaker configurations, including emergency and normal power sources. The document includes detailed load summaries per phase, showing total connected loads ranging from 3.01 kVA to 85.25 kVA, with specific circuit assignments for receptacles, lighting, equipment, and spare capacity in rooms such as classrooms, corridors, mechanical spaces, and telecommunications rooms. The drawing is part of a repair project, marked as an RTA (Response to Addendum) submission with the project number P/N 94078 and contract number W912DS19C0034.

View the file

Other files

File Type Posted
MSEC- Building 606 - Amendment 9 - RFIs - 5 Nov 25.pdf PDF
A-601_AM 9.pdf PDF
08 71 00_AM 9.pdf PDF
MP-101_AM 7.pdf PDF
08 71 00_AM 7.pdf PDF
MSEC- Building 606 - Amendment 7 - RFIs - 21 Oct 25.pdf PDF
I-130_AM 6.pdf PDF
I-100.1_AM 6.pdf PDF
AD-301_AM 6.pdf PDF
A-305_AM 6.pdf PDF
A-102_AM 6.pdf PDF
A-413_AM 6.pdf PDF
A-502_AM 6.pdf PDF
A-504_AM 6.pdf PDF
MP-107_AM 6.pdf PDF
MP-105_AM 6.pdf PDF
MP-101_AM 6.pdf PDF
MH-101_AM 6.pdf PDF
S-322_AM 6.pdf PDF
S-315_AM 6.pdf PDF
S-107_AM 6.pdf PDF
07 52 00_AM 6.pdf PDF
08 60 45_AM 6.pdf PDF
08 81 00_AM 6.pdf PDF
I-108_AM 6.pdf PDF
I-105_AM 6.pdf PDF
A-551_AM 5.pdf PDF
MSEC- Building 606 - Amendment 5 - RFIs - 8 Oct 25 rev JF.pdf PDF
Appendix G_AM 5.pdf PDF
A-601_AM 4.pdf PDF
Solicitation Amendment W912DS25RA0020004 SF 30.pdf PDF
A-602_AM 4.pdf PDF
A-564_AM 4.pdf PDF
MS-100_AM3.pdf PDF
01 91 19_AM3.pdf PDF
01 30 00_AM3.pdf PDF
M-303_AM3.pdf PDF
E-512 - DETAILS - ELECTRICAL_AM3.pdf PDF
MSEC- Building 606 - Amendment 3 - RFIs - 16 Sep 25.pdf PDF
Solicitation Amendment W912DS25RA0020003 SF 30.pdf PDF
E-513.pdf PDF
A-121.pdf PDF
07 60 00.pdf PDF
A-319.pdf PDF
MSEC- Building 606 - Amendment 1 - RFIs - 20 Aug 25.pdf PDF
Solicitation Amendment W912DS25RA0020001 SF 30.pdf PDF
W912DS19C0034 PN 94078 Repair Building 606 Revised RTA Drawings - Volume 4.pdf PDF
W912DS19C0034 PN 94078 Repair building 606 REV.RTA Specification Manual Volume 3.pdf PDF
W912DS19C0034 PN 94078 Repair building 606 REV.RTA Specification Manual Volume 1.pdf PDF
JA-007-25 Monaco Fire Alarm MSEC - 31 Jan 25 signedJF sDL_Redacted.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT FOR

CONSTRUCTION

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O J E

C T

N O

E-611

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

U N

IT

E

D S

T A

T E

S M

IL

IT

A R

Y A

C A

D E

M Y

W

E S

T P

O

IN

T N

Y P

/N

F

Y

N E

W Y

O R

K D

IS

T

R

IC

T N

E W

Y O

R K

N

Y

M J P

M J P

D K

M

A Y

W D

S C

Q P

K J

O B

N O

.0

REV RTA SUBMISSION

R E

P A

IR

B

L D

G

G

E N

E R

A L I N

S T

R U

C T

IO

N

B L D

G

NOTES:

ISOLATED GROUND BUS INTEGRAL SURGE PROTECTIVE DEVICE...

200% RATED NEUTRAL CONTROLLABLE CIRCUIT BREAKER PANEL

X SURFACE SUB FEED MAIN LUGS (DOUBLE LUGS)

RECESSED FEED THRU LUGS

MULTIPLE SECTION PANEL CONTACTOR CONTROLLED

OPTIONS AND ACCESSORIES - (X) INDICATES SELECTION

TOTAL CONNECTED LOAD (KVA) 9.44 kVA

LOAD SUMMARY PER PHASE (KVA) 4.00 kVA 3.44 kVA 2.00 kVA

41 -- 1 SPACE -- -- SPACE 1 -- 42

39 -- 1 SPACE -- -- SPACE 1 -- 40

37 -- 1 SPACE -- -- SPACE 1 -- 38

35 -- 1 SPACE -- -- SPACE 1 -- 36

33 -- 1 SPACE -- -- SPACE 1 -- 34

31 -- 1 SPACE -- -- SPACE 1 -- 32

29 20 1 SPARE 0.00 0.00 SPARE 1 20 30

27 20 1 SPARE 0.00 0.00 SPARE 1 20 28

25 20 1 SPARE 0.00 0.00 SPARE 1 20 26

23 20 1 SPARE 0.00 0.00 SPARE 1 20 24

21 20 1 SPARE 0.00 0.00 SPARE 1 20 22

19 20 1 SPARE 0.00 0.00 SPARE 1 20 20

17 20 1 SPARE 0.00 0.00 SPARE 1 20 18

15 20 1 SPARE 0.00 0.00 SPARE 1 20 16

13 20 1 ANTENNA RA-1, MDF B10 1.00 0.00 SPARE 1 20 14

11 30 1 REC - L5-30R MDF-B10 1.00 0.00 SPARE 1 20 12

9 20 1 REC - MDF B10 0.90 1.00 RACK RECEPTACLE - MDF B10 1 20 10

7 20 1 REC - SECURITY POWER - MDF B10 0.50 1.00 RACK RECEPTACLE - MDF B10 1 20 8

5 20 1 SPARE 0.00 1.00 RACK RECEPTACLE - MDF B10 1 20 6

3 20 1 REC - MDF B10 0.54 1.00 RACK RECEPTACLE - MDF B10 1 20 4

1 20 1 REC - CCTV POWER, MDF B10 0.50 1.00 RACK RECEPTACLE - MDF B10 1 20 2

NOTES

CKT

NO.

A P DESCRIPTION

PHASE A

LOAD...

PHASE B

LOAD...

PHASE C

LOAD...

DESCRIPTION P A

CKT

NO.

NOTES

ROOM. MDF B10 M.C.B. OR M.L.O.: M.L.O. POLES: 42

LOCATION: BASEMENT MAIN (AMPS): 100.00 A X UPS A.I.C. RATING: 10 KAIC

SECTIONS: 1 PHASE & WIRE: 3ø/4W EMERGENCY X NEW

PANEL: UP-EB-1 VOLTAGE: 208Y/120V NORMAL EXISTING

NOTES:

ISOLATED GROUND BUS INTEGRAL SURGE PROTECTIVE DEVICE...

200% RATED NEUTRAL CONTROLLABLE CIRCUIT BREAKER PANEL

X SURFACE SUB FEED MAIN LUGS (DOUBLE LUGS)

RECESSED FEED THRU LUGS

MULTIPLE SECTION PANEL CONTACTOR CONTROLLED

OPTIONS AND ACCESSORIES - (X) INDICATES SELECTION

TOTAL CONNECTED LOAD (KVA) 6.98 kVA

LOAD SUMMARY PER PHASE (KVA) 2.90 kVA 2.18 kVA 1.90 kVA

41 -- 1 SPACE -- -- SPACE 1 -- 42

39 -- 1 SPACE -- -- SPACE 1 -- 40

37 -- 1 SPACE -- -- SPACE 1 -- 38

35 -- 1 SPACE -- -- SPACE 1 -- 36

33 -- 1 SPACE -- -- SPACE 1 -- 34

31 -- 1 SPACE -- -- SPACE 1 -- 32

29 20 1 SPARE 0.00 0.00 SPARE 1 20 30

27 20 1 SPARE 0.00 0.00 SPARE 1 20 28

25 20 1 SPARE 0.00 0.00 SPARE 1 20 26

23 20 1 SPARE 0.00 0.00 SPARE 1 20 24

21 20 1 SPARE 0.00 0.00 SPARE 1 20 22

19 20 1 SPARE 0.00 0.00 SPARE 1 20 20

17 20 1 SPARE 0.00 0.00 SPARE 1 20 18

15 20 1 SPARE 0.00 0.00 SPARE 1 20 16

13 20 1 SPARE 0.00 0.00 SPARE 1 20 14

11 20 1 SPARE 0.00 0.00 SPARE 1 20 12

9 20 1 SPARE 0.00 1.00 RACK RECEPTACLE - MDF B10 1 20 10

7 20 1 SPARE 0.00 1.00 RACK RECEPTACLE - MDF B10 1 20 8

5 20 1 CEILING MTD REC. - NEMA L5-20R, DAS B08 0.90 1.00 RACK RECEPTACLE - MDF B10 1 20 6

3 20 1 REC - MDFB10 0.18 1.00 RACK RECEPTACLE - MDF B10 1 20 4

1 20 1 CEILING MED REC - NEMA L5-20R - MDF B10 0.90 1.00 RACK RECEPTACLE - MDF B10 1 20 2

NOTES

CKT

NO.

A P DESCRIPTION

PHASE A

LOAD...

PHASE B

LOAD...

PHASE C

LOAD...

DESCRIPTION P A

CKT

NO.

NOTES

ROOM MDF B10 M.C.B. OR M.L.O.: M.L.O. POLES: 42

LOCATION: BASEMENT MAIN (AMPS): 100.00 A X UPS A.I.C. RATING: 10 KAIC

SECTIONS: 1 PHASE & WIRE: 3ø/4W EMERGENCY X NEW

PANEL: UP-EB-2 VOLTAGE: 208Y/120V NORMAL EXISTING

a. PROVIDE GFI CIRCUIT BREAKER

b. PROVIDE HANDLE LOCK

NOTES:

ISOLATED GROUND BUS INTEGRAL SURGE PROTECTIVE DEVICE...

200% RATED NEUTRAL CONTROLLABLE CIRCUIT BREAKER PANEL

X SURFACE SUB FEED MAIN LUGS (DOUBLE LUGS)

RECESSED FEED THRU LUGS

MULTIPLE SECTION PANEL CONTACTOR CONTROLLED

OPTIONS AND ACCESSORIES - (X) INDICATES SELECTION

TOTAL CONNECTED LOAD (KVA) 85.25 kVA

LOAD SUMMARY PER PHASE (KVA) 28.41 kVA 28.91 kVA 27.93 kVA

53 20 1 SPARE 0.00 2.33 54

51 20 1 SPARE 0.00 2.33 52

49 20 1 SPARE 0.00 2.33

FP-EB-1 3 60

b

47 20 1 SPARE 0.00 -- SPACE 1 -- 48

45 20 1 SPARE 0.00 -- SPACE 1 -- 46

43 20 1 SPARE 0.00 -- SPACE 1 -- 44

41 20 1 SPARE 0.00 0.00 42

39 20 1 SPARE 0.00 0.00

TEMP GEN RECEPTACLE 2 50

37 20 1 SPARE 0.00 0.30 SUMP ALARM - CORRIDOR B13 1 20 38

35 20 1 SMOKE DAMPERS 1.00 5.00 36

33 20 1 REC - DAS B08 0.90 5.00 34

a 31 20 1 J.B - ROOM. TLT B07 & B05 0.36 5.00

SPECIAL PURPOSE REC - NEMA L15-50R,

CORRIDOR B04

3 50

29 20 1 REC - EXTERIOR 0.36 5.00 30

27 20 1 REC - RM. CLASSROOM B03 1.44 5.00 28

25 20 1 REC - RM. CLASSROOM B03 1.62 5.00

SPECIAL PURPOSE REC - NEMA L15-50R,

CORRIDOR B04

3 50

23 20 1 REC - RM. CLASSROOM B03 1.44 5.00 24

21 20 1 REC - ROOM. B05, B06 & B07 0.54 5.00 22

a 19 20 1 J.B. - EWC, CORRIDOR B01 0.50 5.00

SPECIAL PURPOSE REC - NEMA L15-50R,

CORRIDOR B01

3 50

17 20 1 REC - ROOM. B09 0.18 0.50 LIGHTING HUB - ELEC ROOM B14 1 20 18

15 20 1 REC - ROOM. B11 0.72 1.08 REC - RM. CLASSROOM B02 1 20 16

13 20 1 LIGHTING 0.06 1.44 REC - RM. CLASSROOM B02 1 20 14

11 5.00 1.44 REC - RM. CLASSROOM B02 1 20 12

9 5.00 1.20 REC - TV, MICROPHONE - CLASSROOM B02,... 1 20 10

50 3

SPECIAL PURPOSE REC - NEMA L15-50R,

CORRIDOR B12

5.00 0.72 REC - ROOM CORRIDOR B04 1 20 8

5 20 1 REC - REFRIGERATOR, ROOM. B11 0.50 0.18 REC - ROOM. CUSTODIAL B11 1 20 6

3 20 1 REC - MICROWAVE, ROOM. B11 0.50 0.20 REC - ROOM. CUSTODIAL B11 1 20 4

1 20 1 TEMP GEN RECEPTACLE 0.00 1.08 REC - ROOM MECH B16 1 20 2

NOTES

CKT

NO.

A P DESCRIPTION A B C DESCRIPTION P A

CKT

NO.

NOTES

ROOM ELEC B14 M.C.B. OR M.L.O.: M.C.B. POLES: 54

LOCATION: BASEMENT MAIN (AMPS): 225.00 A UPS A.I.C. RATING: 10 KAIC

SECTIONS: 1 PHASE & WIRE: 3ø/4W EMERGENCY X NEW

PANEL: AP-EB-1 VOLTAGE: 208Y/120V X NORMAL EXISTING

NOTES:

ISOLATED GROUND BUS INTEGRAL SURGE PROTECTIVE DEVICE...

200% RATED NEUTRAL CONTROLLABLE CIRCUIT BREAKER PANEL

X SURFACE SUB FEED MAIN LUGS (DOUBLE LUGS)

RECESSED FEED THRU LUGS

MULTIPLE SECTION PANEL CONTACTOR CONTROLLED

OPTIONS AND ACCESSORIES - (X) INDICATES SELECTION

TOTAL CONNECTED LOAD (KVA) 3.01 kVA

LOAD SUMMARY PER PHASE (KVA) 2.10 kVA 0.66 kVA 0.25 kVA

23 -- 1 SPACE -- -- SPACE 1 -- 24

21 -- 1 SPACE -- -- SPACE 1 -- 22

19 -- 1 SPACE -- -- SPACE 1 -- 20

17 20 1 SPARE 0.00 0.00 SPARE 1 20 18

15 20 1 SPARE 0.00 0.00 SPARE 1 20 16

13 20 1 SPARE 0.00 0.00 SPARE 1 20 14

11 20 1 SPARE 0.00 0.00 SPARE 1 20 12

9 20 1 SPARE 0.00 0.00 SPARE 1 20 10

7 20 1 SPARE 0.00 0.00 SPARE 1 20 8

5 15 1 INVERTER INV-EB-1 0.25 0.00 6

3 20 1 LTG - CLASSROOMS 0.66 0.00 4

1 20 1 LTG - BASEMENT 2.10 0.00

SPD 3 15

NOTES

CKT

NO.

A P DESCRIPTION

PHASE A

LOAD...

PHASE B

LOAD...

PHASE C

LOAD...

DESCRIPTION P A

CKT

NO.

NOTES

ROOM. ELEC B14 M.C.B. OR M.L.O.: M.L.O. POLES: 24

LOCATION: BASEMENT MAIN (AMPS): 100.00 A UPS A.I.C. RATING: 22 KAIC

SECTIONS: 1 PHASE & WIRE: 3ø/4W EMERGENCY X NEW

PANEL: LP-EB-1 VOLTAGE: 480Y/277V X NORMAL EXISTING

A

D D

E N

D U

M

/1

/2

SOURCE: PANEL DUP-EB-1 SOURCE: PANEL DUP-EB-1

SOURCE: PANEL DP-EB-1 VIA XFMR T-AP-EB-1 SOURCE: PANEL DP-EB-11

RESPONSE TO RFI #345

RESPONSE TO RFI #345