This architectural drawing is a detailed technical section drawing for West Point Building 606, specifically showing roof and parapet section details. The document includes three detailed views: Section Detail - Roof #8 to Roof #5 (A1), Section Detail - Roof #7 Parapet (A5), and an Axonometric - Typical Crenel & Coping Stone End Detail (E5). The technical details include specific construction specifications such as metal stud configurations (20GA @ 16" OC max), insulation types (2-1/2" insulated metal panels, R-20 insulation), roofing materials (modified bitumen roof system, 5" rigid insulation), and complex flashing and waterproofing techniques involving vapor retarders, membrane barriers, and counter flashing. The drawings provide precise measurements, material specifications, and intricate architectural integration methods for roof and wall intersections, with particular attention to waterproofing, insulation, and structural connections.

View the file

Other files

File Type Posted
Solicitation Amendment W912DS25RA0020011 SF 30 (1).pdf PDF
A-601_AM 9.pdf PDF
MSEC- Building 606 - Amendment 9 - RFIs - 5 Nov 25.pdf PDF
23 30 00_AM 9.pdf PDF
08 71 00_AM 9.pdf PDF
Solicitation Amendment W912DS25RA0020009 SF 30.pdf PDF
C-004_AM 9.pdf PDF
C-002_AM 2 and 9.pdf PDF
Solicitation Amendment W912DS25RA0020008 SF 30.pdf PDF
E-611_AM 7.pdf PDF
MP-101_AM 7.pdf PDF
08 71 00_AM 7.pdf PDF
E-512_AM 7.pdf PDF
MSEC- Building 606 - Amendment 7 - RFIs - 21 Oct 25.pdf PDF
M-707_AM 7.pdf PDF
Solicitation Amendment W912DS25RA0020007 SF 30.pdf PDF
E-601_AM 7.pdf PDF
A-111_AM 7.pdf PDF
H-103_AM 6.pdf PDF
A-503_AM 6.pdf PDF
07 52 00_AM 6.pdf PDF
H-109_AM 6.pdf PDF
A-502_AM 6.pdf PDF
AD-103_AM 6.pdf PDF
A-105_AM 6.pdf PDF
A-206_AM 6.pdf PDF
S-105_AM 6.pdf PDF
S-115_AM 6.pdf PDF
S-113_AM 6.pdf PDF
A-003_AM 6.pdf PDF
I-105_AM 6.pdf PDF
S-001_AM 6.pdf PDF
MH-104_AM 6.pdf PDF
A-314_AM 6.pdf PDF
H-108_AM 6.pdf PDF
MP-101_AM 6.pdf PDF
MP-107_AM 6.pdf PDF
I-130_AM 6.pdf PDF
S-312_AM 6.pdf PDF
MP-104_AM 6.pdf PDF
A-313_AM 6.pdf PDF
33 61 13.13_AM 6.pdf PDF
I-100.4_AM 6.pdf PDF
I-113_AM 6.pdf PDF
MP-102_AM 6.pdf PDF
AD-101_AM 6.pdf PDF
H-001_AM 6.pdf PDF
A-315_AM 6.pdf PDF
A-102_AM 6.pdf PDF
AD-301_AM 6.pdf PDF
Show 40 more

Latest 50 of 148 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B7

COLLAB

14 A

62' - 3"

TOSL-ROOF 8 ( 221' - 6" )

64' - 8 1/4"

TOS-ROOF 5 ( 223' - 11 1/4" )

3'

1/

2"

1'

/2

/2

/2

/2

/2

/2

3/

4"

3 5/8" METAL STUDS;

20GA @ 16" OC MAX.

STEEL BEAM; SEE

STRUCT DWGS,

PROVIDE REQD

FIREPROOFING (TYP).

PROVIDE OPENING IN

EXST CONC SLAB FOR

DUCT PENETRATION.

DUCT; REFER TO

MECHANICAL DWGS.

EXST CONC FLOOR

SLAB.

2-PIECE PRE-FINISHED

METAL COUNTER

FLASHING.

2X6 WD BLOCKING @ INS

MET PANEL START &

LADDER BRACKETS (TYP).

LAP MEMBRANE AIR

BARRIER OVER

FLASHING; SEAL (TYP).

1/2" EXTERIOR GYPSUM

SHEATHING.

2-1/2" (R-20) INSULATED

METAL PANELS.

GALV STEEL LADDER

RUNG (TYP).

3 1/2" UNFACED

MINERAL WOOL SOUND

BATT INS.

GALV STL BAR GRATING

PLATFORM.

1/4" MIN X 2" GALV STEEL

PLATE.

CANT STRIP.

CONT 2X WOOD

BLOCKING.

1 1/2" RIGID INSULATION

(R-9).

PRE-FINISHED METAL

COPING.

STRIPPING.

BACKER ROD & SEALANT.

ELASTOMERIC

MEMBRANE FLASHING

SHEETING; SET IN

ADHESIVE.

FLUID APPLIED

MEMBRANE BARRIER;

FLASH & LAP OVER

VAPOR RETARDER &

SEAL (TYP).

VAPOR RETARDER;

CONTINUE UP PTN 2"

MIN (TYP UNO).

2"

STEEL BENT PLATE, SEE

STRUCT DWGS.

VAPOR RETARDER.

FLUID APPLIED

MEMBRANE BARRIER;

FLASH & LAP OVER

VAPOR RETARDER &

SEAL (TYP).

7 1/2" CLEAR 7 1/2" CLEAR

2" T

YP

66' - 7 3/4"

TOP OF BLOCKING ( 225' - 10 3/4" )

2"

HOLD STEEL PLATE BACK 1" FROM

FACE OF PANELS; PROVIDE SPRAY

FOAM INSUL @ TOP OF IMP (TYP).

CORRIDOR

TOS-ROOF 5 ( 223' - 11 1/4" )

64' - 8 1/4"

TOSL-ROOF 7 ( 221' - 1" )

61' - 10"

2'

/4

2'

1/

4"

1/ 2"

/8

1'

0" 1'

0"

1'

0" 1'

0"

3'

1/

8"

2" RIGID INSULATION

(R-12 MIN).

5/8" COVER BOARD.

FLUID APPLIED

MEMBRANE AIR

BARRIER.

GALV STEEL BRACKET;

ANCHOR INTO WALL

(TYP).

GALV STEEL LADDER

RUNG (TYP).

STEEL PLATE; SEE

STRUCT DWGS.

CONT 2X WOOD

BLOCKING.

ELASTOMERIC

MEMBRANE FLASHING

SHEETING; SET IN

ADHESIVE.

20 C

EXST BRICK VENEER.

CANT STRIP.

5/8" COVER BOARD.

1 1/2" RIGID INSULATION

(R-9).

1/2" EXTERIOR GYPSUM

SHEATHING.

1/2" EXTERIOR GYPSUM

SHEATHING.

GALV STL BAR GRATING

PLATFORM.

1/4" MIN X 2" GALV

STEEL PLATE.

STEEL BENT PLATE, SEE

STRUCT DWGS.

CANT STRIP.

STRIPPING.

ELASTOMERIC

MEMBRANE FLASHING

SHEETING; SET IN

ADHESIVE.

2-PIECE METAL

COUNTER FLASHING;

REGLET INTO BRICK.

BACKER ROD &

SEALANT.

7 1/2" CLEAR

7"

ELASTOMERIC

MEMBRANE FLASHING

SHEETING; SET IN

ADHESIVE.

PRE-FINISHED METAL

COPING.

6" COLD FORMED STUD

FRAMING; REFER TO

STRUCT DWGS.

1/

2" 1'

0"

2" 1'

0"

2"

/8

STEEL BEAM; SEE

STRUCT DWGS,

PROVIDE REQD

FIREPROOFING (TYP).

VAPOR RETARDER;

CONTINUE UP PTN 2"

MIN (TYP UNO).

FLUID APPLIED

MEMBRANE BARRIER;

FLASH & LAP OVER

VAPOR RETARDER &

SEAL (TYP).

VAPOR RETARDER;

CONTINUE UP PTN 2"

MIN (TYP UNO).

FLUID APPLIED

MEMBRANE BARRIER;

FLASH & LAP OVER

VAPOR RETARDER &

SEAL (TYP).

5" ± RIGID INS (AVG

R-30); (2) LAYERS MIN,

STAGGER JOINTS.

CONT 2X WOOD

BLOCKING.

CONT 2X WOOD

BLOCKING.

CONT 2X WOOD BLOCKING.2"

T

YP

HOLD STEEL PLATE BACK 1"

FROM FACE OF PANELS;

PROVIDE SPRAY FOAM INSUL

@ TOP OF IMP (TYP).

BD

TOSL-ROOF 7 ( 221' - 1" )

61' - 10"

2'

2'

1/

2"

/2

16 A

EXST BRICK VENEER.

EXST CONCRETE BEAM.

EXST LIMESTONE

LINTEL.

WINDOW; REFER TO

BLDG ELEVATIONS &

WDW SCHEDULE.

EXTEND SPRAY FOAM

INS HORIZ TO BACK

FACE OF STUDS.

EXST CONCRETE ROOF

DECK.

WD BLOCKING &

PLYWOOD; REFER TO

WDW HEAD DETAILS.

5" ± RIGID INS (AVG

R-30); (2) LAYERS MIN,

STAGGER JOINTS.

CANT STRIP.

5/8" COVER BOARD.

MODIFIED BITUMEN

ROOF SYSTEM.

1 1/2" RIGID INSULATION

(R-9).

CRENEL (BEYOND);

FLASH. REFER TO TYP

CRENEL DETAIL.

A-124

F5

2-PIECE METAL

COUNTER FLASHING.

SIM

VAPOR RETARDER;

CONTINUE UP WALL.

1 1/2" 1 1/2"

BACK HEM & PROVIDE

BACKER ROD &

SEALANT (TYP).

PROVIDE HI-TEMP

SELF-ADHERING

MEMBRANE FLASHING

UNDER METAL

FLASHING.

LAP COPING

FLASHING OVER

FLANGE OF CRENEL

FLASHING.

REINSTALL SALVAGED

COPING; SEE DETAILS.

FORM COPING FLASHING

AROUND ANCHORS;

PROVIDE THIMBLE OVER

DOWEL (SAME MATERIAL

AS COPING FLASHING) &

SOLDER TO COPING

FLASHING (TYP).

LEAD COATED

COPPER FLASHING.

5/16" DIA SST PIN

ANCHOR; EPOXY

ANCHOR INTO MASONRY

WALL BELOW 3" MIN

EMBEDMENT IN WALL &

COPING (TYP @ ALL

COPING ENDS).

3"

PROVIDE 5/8" DIA HOLE

IN COPING TO RECEIVE

PIN ANCHOR; DRY PACK

BEFORE SETTING (TYP @

ALL COPING ENDS).

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

P R

O J E

C T

N O

Autodesk Docs://West Point Bldg 606/219208-WP606-A20.rvt

10/13/2025 2:32:28 PM

A-312

W A

L L

S E

C T

IO

N

S

U N

IT

E

D S

T A

T E

S M

IL

IT

A R

Y A

C A

D E

M Y

W

E S

T P

O

IN

T

N Y

P N

F

Y

N E

W Y

O R

K D

IS

T

R

IC

T N

E W

Y O

R K

N

Y

W D

R

E A

L

M P

K

V N

S

E P

T E

M B

E R

W

D

S

C

Q P

K J

O B

N O

.0

ADDENDUM #6

R E

P A

IR

B

L D

G

G E

N E

R A

L I N

S T

R U

C T

IO

N

B L

D G

SCALE: 1 1/2" = 1'-0"A1

SECTION DETAIL - ROOF #8 TO ROOF #5

SCALE: 1 1/2" = 1'-0"A7

SECTION DETAIL - ROOF #7 TO ROOF #5

SCALE: 1 1/2" = 1'-0"A5

SECTION DETAIL - ROOF #7 PARAPET

SCALE: 1 1/2" = 1'-0"E5

AXONOMETRIC - TYP CRENEL & COPING STONE END DET

A

D D

E N

D U

M

/1

/2

File details come from the government source that posted it. Updated .