A-003_AM 6.pdf
PDF 344 KB Posted
- Solicitation number
- W912DS25RA002
About this file
This document is a detailed architectural drawing (Sheet A-003) from the US Army Corps of Engineers for a renovation project at the United States Military Academy, West Point, NY. The sheet provides comprehensive partition and rated ceiling information for Building 606, a General Instruction Building. It includes 27 different wall/partition construction types with detailed specifications for each, covering aspects such as stud materials (metal studs of various gauges), gypsum board (GWB) types, fire ratings, sound transmission class (STC) ratings, and specific construction details. The drawing includes additional notes about acoustic wall requirements, installation guidelines, sealing methods, and specific instructions for exterior walls, such as using closed-cell foam gaskets. The project is part of the FY2024 New York District renovation, with the solicitation number W912DS19C0034 and an issue date of 2 September 2025, with Addendum #6 dated 13 October 2025.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTEND ALL MATERIALS TO
UNDERSIDE OF DECK/SLAB
OR INFILL
_A
STOP ALL MATERIAL AT
CLG & BRACE STUDS AT
STRUCT ABOVE, AS REQD
TO PROVIDE STABILITY
_B
CLGCLG
EXTEND GWB MATERIAL
ABOVE CLG & BRACE
STUDS AT STRUCT ABOVE,
AS REQD TO PROVIDE
STABILITY
_C
CLG 6" STOP GWB ABOVE CLG
ONE SIDE; EXTEND ALL
OTHER MATERIALS TO
UNDERSIDE OF DECK/SLAB
_D
CLG 6"
LOW WALL, SEE
DWGS FOR HT
_E
CLG
VA
R
IE
S
BULKHEAD
CONDITIONS VARY-
SEE DWGS FOR
DETAILS. BRACE
STUDS AT STRUCT
ABOVE, AS REQD TO
PROVIDE STABILITY
_F
CLG 6"
VA
R
IE
S
BULKHEAD
CONDITIONS VARY-
SEE DWGS FOR
DETAILS. BRACE
STUDS AT STRUCT
ABOVE, AS REQD TO
PROVIDE STABILITY
_G
CLG 6"
VA
R
IE
S
CLG
1 A
CONSTRUCTION TYPES :
HEIGHT TYPES :
ADDITIONAL RELATED NOTES: SEE "GENERAL NOTES"
SEE SPECIFIC NOTES ON PLANS AND
DETAILS; SEE SPECIFICATIONS
TEST DESIGNATIONS : UL= UNDERWRITERS LABORATORIES
OSU= OHIO STATE UNIVERSITY
UC= UNIVERSITY OF CALIFORNIA
ALPHABET SUFFIX DESIGNATES
PARTITION HEIGHT NOTED BELOW
NUMERAL PREFIX DESIGNATES PARTITION
CONSTRUCTION NOTED ABOVE
PARTITION
INTEGRATES WITH
CEILING ASSEMBLY -
SEE DETAILS
_H
CLG
FULL BULKHEAD AT
BORROWED LITES,
FRAMELESS GLASS,
FULL WIDTH DOORS.
BRACE STUDS AT
STRUCTURE ABOVE
32" OC
_J
CLG
6"CLG
6"
CLG HTS VARY,
SEE RCP'S
ALIGN GWB
FLUSH WITH CLG
WHERE OCCURS
NOTE: LAP DRYWALL UP
AT END OF WALL WHEN
WALL DOES NOT
TERMINATE AT AN
INTERSECTING PARTITION.
3 1/8"
2-1/2" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 1
RATING = ---
TEST = ---
STC = ---
10 3/4"
8" CONCRETE MASONRY UNIT
TYPE 18
RATING = 2 HR
TEST = UL-U905
STC = ---
2-1/2" METAL STUDS- 20 GAUGE
AT 16" OC
5/8" GWB - TYPE X
SEE STRUCTURAL DRAWINGS FOR
HORIZONTAL JOINT REINFORCEMENT
5/8" GWB - TYPE X
4 1/4"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
5/8" GWB - TYPE X
TYPE 3
RATING = ---
TEST = ---
STC = ---
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 7
RATING = ---
TEST = ---
STC = 40
5/8" GWB - TYPE X
5/8" GWB - TYPE X
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 8
RATING = 1 HR
TEST = UL-U419
STC = 40
5/8" GWB - TYPE X
5/8" GWB - TYPE X
6 1/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 11
RATING = ---
TEST = ---
STC = 49
5/8" GWB - TYPE X
5/8" GWB - TYPE X
8" CONCRETE MASONRY UNIT
TYPE 17
RATING = 2 HR
TEST = UL-U905
STC = ---
SEE STRUCTURAL DWGS FOR
HORIZONTAL JOINT REINFORCEMENT
3" SOUND BATTS
3" SOUND BATTS
6 1/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 12
RATING = 2 HR
TEST = UL-U411
STC = 49
5/8" GWB - TYPE X
5/8" GWB - TYPE X
3" SOUND BATTS
5/8" GWB - TYPE X
5/8" GWB - TYPE X
2 1/4"
1-5/8" METAL STUDS (20 GAUGE)
AT 16" OC
5/8" GWB - TYPE X
TYPE 20
RATING = ---
TEST = ---
STC = ---
1 3
5 1/4"
1" GWB SHAFT LINER
TYPE 13
RATING = 2 HR
TEST = UL-U497
STC = 50
5/8" GWB - TYPE X
5/8" GWB - TYPE X
1 1/2"
7/8" FURRING CHANNEL; 20GA,
INSTALL VERTICALLY @ 16"OC
TYPE 21
RATING = ---
TEST = ---
STC = ---
5/8" GWB
3" SOUND BATTS
5/8" GWB - TYPE X
5/8" GWB - TYPE X
5 1/2"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 10
RATING = 1 HR
TEST = UL-U438
STC = 45
5/8" GWB - TYPE X
3" SOUND BATTS
5/8" GWB - TYPE X
5/8" GWB - TYPE X
UNO
6 1/4"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 16
RATING = ---
TEST = ---
STC = ---
1" MIN AIR SPACE
1" THICK CLOSED CELL SPRAY
FOAM (R-6.3)
5/8" GWB
4" METAL C-H STUDS- 18 GAUGE
AT 24" OC
3" SOUND BATTS
EXST EXTERIOR WALL
5/8"
TYPE 22
RATING = ---
TEST = ---
STC = ---
5/8" GWB - TYPE X
EXISTING WALL
5 5/8"
TYPE 19
RATING = --
TEST = --
STC = --
6" CONCRETE MASONRY UNIT
6 5/8"
TYPE 15
RATING = 2 HR
TEST = UL - U419
STC = 50
(2) LAYERS 5/8" GWB - TYPE X
1/2" RESILENT CHANNEL; 20GA,
INSTALL HORIZ @ 24"OC
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
(2) LAYERS 5/8" GWB - TYPE X
6 5/8"
TYPE 14
RATING = ---
TEST = ---
STC = 50
(2) LAYERS 5/8" GWB - TYPE X
14 1/2" RESILENT CHANNEL; 20GA,
INSTALL HORIZ @ 24"OC
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
(2) LAYERS 5/8" GWB - TYPE X
3" SOUND BATTS
5 1/2"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 9
RATING = ---
TEST = ---
STC = 45
5/8" GWB - TYPE X
3" SOUND BATTS
5/8" GWB - TYPE X
5/8" GWB - TYPE X
3 1/8"
2-1/2" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 2
RATING = ---
TEST = ---
STC = ---
5/8" GWB - TYPE X2
2 1/2" SOUND BATTS
4 1/4"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
5/8" GWB - TYPE X
TYPE 4
RATING = ---
TEST = ---
STC = ---
3 1/2" SOUND BATTS
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 5
RATING = ---
TEST = ---
STC = ---
5/8" GWB - TYPE X
5/8" GWB - TYPE X
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 6
RATING = 1 HR
TEST = UL-U419
STC = 35
5/8" GWB - TYPE X
5/8" GWB - TYPE X
UNO
5 1/8"
2-1/2" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 24
RATING = ---
TEST = ---
STC = ---
1" MIN AIR SPACE
1" THICK CLOSED CELL SPRAY
FOAM (R-6.3)
5/8" GWB
EXST EXTERIOR WALL3 5/8"
2-1/2" METAL STUDS- 20 GAUGE
AT 16" OC
TYPE 23
RATING = ---
TEST = ---
STC = ---
5/8" GWB - TYPE X
EXST EXTERIOR WALL
CLIP STUD @ MIDPOINT
BACK TO EXST WALL
1/2" AIR SPACE
TYPE 25
RATING = 2 HR
TEST = UL-U906
STC = ---
SEE STRUCTURAL DWGS FOR
HORIZONTAL JOINT REINFORCEMENT
6" CONCRETE MASONRY UNIT
TYPE 26
RATING = 2 HR
TEST = UL-V488
STC = 64
(2) LAYERS 5/8" GWB - TYPE X
1' - 6 1/4"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
3-5/8" METAL STUDS- 20 GAUGE
AT 16" OC
(2) LAYERS 5/8" GWB - TYPE X
4 5/8"
1" GWB SHAFT LINER
TYPE 27
RATING = 1 HR
TEST = UL-U415
STC = 42
5/8" GWB - TYPE X
4" METAL C-H STUDS- 18 GAUGE
AT 24" OC
3" SOUND BATTS
7 5/8"
5 5/8"
HORIZONTAL ASSEMBLIES
1 HOUR RATED CEILING
RATED SEALANT
1" SHAFT LINER
RATING = 1 HR
TEST = AER-9038
2 1/2" MET C-H STUDS - 20 ga
2 1/2" 'J' RUNNER @ WALLS.
1" GYP SHAFT LINER PANELS.
(1) LAYER 5/8" TYPE 'C' GWB.
METAL 'L' TRIM & SEALANT.
2 HOUR RATED CEILING
RATED SEALANT
1" SHAFT LINER
RATING = 2 HR
TEST = AER-9038
4" MET C-H STUDS - 20 ga
4" 'J' RUNNER @ WALLS.
1" GYP SHAFT LINER PANELS.
(2) LAYER 1/2" TYPE 'C' GWB.
METAL 'L' TRIM & SEALANT.
GLASS/ALUMINUM FIRE RATED WALL ASSEMBLIES
1 HOUR RATED GLASS/ALUMINUM FIRE
RATED WALL ASSEMBLY
1 3/8"
1/
2"
4"
5 1/2"
1/
2"
2 5/8"
2 HOUR RATED GLASS/ALUMINUM
FIRE RATED WALL ASSEMBLY
1/
2"
1/ 2"
FILL MATERIAL AND SLNT
AT FRAME PERIMETERS
PER MFRS
REQUIREMENTS.
FILL MATERIAL AND SLNT
AT FRAME PERIMETERS
PER MFRS
REQUIREMENTS.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
Autodesk Docs://West Point Bldg 606/219208-WP606-A20.rvt
10/13/2025 2:48:47 PM
A-003
P A
R T
IT
IO
N
R A
T E
D C
E
IL
IN
G
I N
F O
R M
A T
IO
N
U N
IT
E
D S
T A
T E
S M
IL
IT
A R
Y A
C A
D E
M Y
W
E S
T P
O
IN
T
N Y
P N
F
Y
N E
W Y
O R
K D
IS
T
R
IC
T N
E W
Y O
R K
N
Y
C B
C B
M P
K
V N
S
E P
T E
M B
E R
W
D
S
C
Q P
K J
O B
N O
.0
ADDENDUM #6
R E
P A
IR
B
L D
G
G E
N E
R A
L I N
S T
R U
C T
IO
N
B L
D G
PARTITION NOTES
1 PROVIDE GYPSUM TILE BACKER BOARD AT WALLS TO RECEIVE TILE FINISH. PROVIDE MOISTURE RESISTANT GWB ON SINK WALLS IN
KITCHENETTES (KIT), AND JANITOR'S CLOSETS (ALL WALLS TOUCHING MOP SINKS).
2 SEAL ALL GWB INTERIOR PARTITIONS AT FULL PERIMETER AND AT PERIMETER OF NON-FIRE STOPPED CUTOUTS & PENETRATIONS
WITH ACOUSTICAL SEALANT.
3 PROVIDE HEAD OF WALL FIRE RESISTIVE JOINT SYSTEM PER HEAD OF WALL DETAILS FOR RATED PARTITIONS OR PARTITIONS FOR
SMOKE ENCLOSURE. PROVIDE NON-RATED HEAD OF WALL DETAILS AT NON-RATED PARTITIONS.
4 PROVIDE SOLID WOOD BLOCKING BEHIND GYPSUM BOARD PARTITION FOR ATTACHMENT OF ALL FIXTURES, FITTINGS, ACCESSORIES, WINDOW TREATMENTS AND OWNER SUPPLIED EQUIPMENT, TV'S ETC. COORDINATE WITH OWNER.
5 PROVIDE 5/8" B-C PLYWOOD IN LIEU OF GWB AT WOOD WALL PANELS 803 (TYPICAL, UNLESS WALL TYPE IS FIRE RATED
CONSTRUCTION).
6 SEE LIFE SAFETY DRAWINGS FOR RATINGS.
7 SET BOTTOM TRACK ON CLOSED CELL FOAM GASKET AT ALL NEW EXTERIOR AND BASEMENT WALLS.
ACOUSTIC RATED WALL NOTES:
PROVIDE THE FOLLOWING AT ALL PARTITIONS SCHEDULED TO BE ACOUSTICALLY RATED (STC).
1. CONTINUOUS BACKER ROD AND ACOUSTICAL SEALANT AT PARTITION HEADS AND SILLS.
2. MOLDABLE FIRESTOP PUTTY PADS AT ELECTRICAL AND COMMUNICATION BOXES.
3. SEAL ALL PENETRATIONS WITH PACKED SOUND BATT, BACKER ROD, AND ACOUSTICAL SEALANT.
A
D D
E N
D U
M
/1
/2
* SET ALL NEW EXTERIOR FRAMING ON CLOSED CELL FOAM GASKET.
* SET ALL NEW EXTERIOR FRAMING ON CLOSED CELL FOAM GASKET.
| Sheets |
| A-003 - PARTITION & RATED CEILING INFORMATION |
File details come from the government source that posted it. Updated .