This is an electrical engineering drawing set for the United States Military Academy at West Point, NY, specifically detailing electrical infrastructure components. The document includes multiple technical drawings focused on lightning protection installation details, ductbank conduit configurations, and smoke damper wiring diagrams. Key technical specifications include ductbank details with 4000 PSI concrete, multiple conduit schedules for service feeders and electrical circuits, and lightning protection mounting instructions for equipment such as exhaust fans and rooftop units. The drawings are part of a project (Job No. 219208.00) with a solicitation number W912DS19C0034QPK, issued by the US Army Corps of Engineers New York District, with submission dates of 09/12/2025 and 10/13/2025 noted as addendum dates. The technical drawings provide precise installation guidelines for electrical infrastructure components, including conduit spacing, concrete embedment, and bonding requirements for various electrical and mechanical systems.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR TERMINAL
BONDING PLATE
TIE TO LP SYSTEM
ON ROOF (TYP)
AIR TERMINAL
BONDING PLATE (TYP.
AT EACH DOWNLEAD)
TIE TO LP SYSTEM
ON ROOF (TYP)
ILLUSTRATED ABOVE ARE TYPICAL
INSTALLATION DETAILS. REFER TO
GENERAL INSTALLATION NOTES FOR
BONDING REQUIREMENTS. ACTUAL
BONDING TO BE DETERMINED IN THE
FIELD. NO POINTS REQUIRED ON
METAL OBJECTS 3/16" THICK.
BELOW ROOF
RUN IN CLG. SPACE
BONDING CONDUCTOR
TYPICAL AIR TERMINAL
BUILDING PARAPET
MTD. AIR TERMINAL
TYPICAL EQUIPMENT
BONDING CONDUCTOR LOOP
TYPICAL SIDE MOUNTED
NOTE:
ADDRESSABLE DUCT SMOKE DETECTOR:
FURNISHED BY DIV. 28 CONTRACTOR;
INSTALLED BY DIV. 23 CONTRACTOR.
WIRED TO BAS BY DIV. 25 CONTRACTOR;
WIRED TO FIRE ALARM BY DIV. 28 CONTRACTOR.
SMOKE DAMPER (SPRING-CLOSED, POWER TO OPEN): SUPPLIED AND
INSTALLED BY DIV. 23 CONTRACTOR. POWERED BY DIV. 26
CONTRACTOR.
ADDRESSABLE INTERFACE MODULE BY DIV. 28
NORMALLY CLOSED CONTACT OF
ADDRESSABLE INTERFACE MODULE
BY DIV. 28
1. FIRE ALARM SYSTEM TO CLOSE SMOKE DAMPER UPON
ACTIVATION OF DUCT MOUNTED SMOKE DETECTOR, AND SEND
SIGNAL TO DDC SYSTEM SO BAS SYSTEM WILL SHUT DOWN FAN
SYSTEM.
2. BAS SYSTEM SHALL SEND SIGNAL TO FIRE ALARM SYSTEM WHEN FAN
SYSTEM IS TO BE ENERGIZED. FA SYSTEM SHALL OPEN ALL SMOKE
DAMPER. AFTER A TIME DELAY, DDC SHALL START FAN SYSTEM.
3. WHENEVER DDC SHUTS DOWN A FAN SYSTEM (IN A NON-FIRE
RELATED SITUATION), THE DDC SYSTEM SHALL CLOSE ALL SMOKE
DAMPERS.
N H
120V WIRING
(BY DIV. 26)
TO FIRE ALARM SYSTEM
C TO FIRE ALARM
SYSTEM BY DIV. 28
STAGGER COUPLINGS
BOTH HORIZONTALLY
AND VERTICALLY
TYPICAL CONDUIT
SPACERS
DUCTBANK CONCRETE
ENVELOPE
4" MIN.
2" MIN.
UNDISTURBED
EARTH
(6) 4" SCH. 40
PVC TYPICAL
4000 PSI CONCRETE
#4 DEFORMED BAR
EACH CORNER
DEPTH AS
SPECIFIED
36" MIN
FINISHED GRADE
YELLOW LINE MARKER AS
SPECIFIED 18" BELOW GRADE
ENTIRE WIDTH OF DUCTBANK
TOP 1" SHALL BE SPRINKLED AND
THROUGHLY MIXED WITH RED DYE
#3 STIRRUPS,
4'-0" ON CENTER
-1
/2
M
IN
5"
CONDUIT SPACERS
5"
29 -1/2"
CONDUIT SCHEDULE
1 - ACTIVE - SERVICE FEEDER
2 - ACTIVE - SERVICE FEEDER
3 - ACTIVE-SERVICE FEEDER
7-1/2"
MIN.
7-1/2"
MIN.
4 - ACTIVE - SERVICE FEEDER
5 - ACTIVE - SERVICE FEEDER
6 - SPARE, PULLWIRE ONLY
UNDISTURBED
EARTH
(9) SCH. 40 PVC
4000 PSI CONCRETE
#4 DEFORMED BAR
EACH CORNER
DEPTH AS
SPECIFIED
36" MIN
FINISHED GRADE YELLOW LINE MARKER AS
SPECIFIED 18" BELOW GRADE
ENTIRE WIDTH OF DUCTBANK
TOP 1" SHALL BE SPRINKLED AND
THROUGHLY MIXED WITH RED DYE
#3 STIRRUPS,
4'-0" ON CENTER
-1
/2
M
IN
5"
CONDUIT SPACERS
5"
29 -1/2"
CONDUIT SCHEDULE
1 ACTIVE - 4"C - TEMP CHILLER FEEDER
2 ACTIVE - 2"C - TEMP GEN. FEEDER(FIRE PUMP)
3 ACTIVE - 1"C - RECEPT BRANCH CKT AP-EB-1 #1
4 ACTIVE - 1"C - RECEPT BRANCH CKT AP-EB-1 #40,42
5 ACTIVE - 4"C - TEMP CHILLER FEEDER
6 ACTIVE - 4"C - TEMP GEN. FEEDER
7 ACTIVE - 4"C - TEMP GEN. FEEDER
8 ACTIVE - 4"C - TEMP GEN. FEEDER
9 ACTIVE - 4"C - TEMP GEN. FEEDER
10 ACTIVE - 4"C - TEMP GEN. FEEDER
7-1/2"
MIN.
7-1/2"
MIN.
8 9 10
-1
/2
M
IN
3 4
2 RESPONSE TO RFI #345
NOT FOR
CONSTRUCTION
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
P R
O J E
C T
N O
E-512
D E
T A
IL
S
E
L E
C T
R
IC
A L
U N
IT
E
D S
T A
T E
S M
IL
IT
A R
Y A
C A
D E
M Y
W
E S
T P
O
IN
T N
Y P
/N
F
Y
N E
W Y
O R
K D
IS
T
R
IC
T N
E W
Y O
R K
N
Y
M J P
M J P
D K
M
A Y
W D
S C
Q P
K J
O B
N O
.0
REV RTA SUBMISSION
R E
P A
IR
B
L D
G
G
E N
E R
A L I N
S T
R U
C T
IO
N
B L D
G
SCALE: NTSE-512
LIGHTNING PROTECTION - EXHAUST FAN AIR TERMINALA8
SCALE: NTSE-512
LIGHTNING PROTECTION - RTUA5
SCALE: NTSE-512
LIGHTNING PROTECTION TYPICAL INSTALLATIONA2
SCALE: NTSE-512
DUCT SMOKE DAMPER WIRING DIAGRAMD8
SCALE: NTSE-512
DUCTBANK CONDUIT COUPLINGSD5
SCALE: NTSE-512
DUCTBANK DETAIL - A-AD2
A
D D
E N
D U
M
/1
/2
A
D D
E N
D U
M
/1
/2
SCALE: NTSE-512
DUCTBANK DETAIL - B-BF5