10-M-803.pdf
PDF 152 KB Posted
- Attached to
- PA 206 HORSHAM HVAC SYSTEMS REPAIRS
- Solicitation number
- W912BU24R0001
About this file
This document provides specifications for building automation system controls and HVAC systems at an Army Reserve Training Center. The specifications cover direct digital control of gas-fired furnaces, fan coils, a central hot water plant, underfloor radiant heating, gas-fired unit heaters, a make-up air unit, exhaust fans, supply fans and louvers. The specifications define control sequences, alarms, temperature setpoints and interlocks for each system. Responsibilities include monitoring and controlling equipment, scheduling operation, and annunciating alarms. The related federal contract opportunity is for HVAC system repairs at a Naval Air Station and has a solicitation number of W912BU24R0001.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912BU24R0001 Amendment 0009_Cancellation.pdf | ||
| W912BU24R0001 Amendment 0005.pdf | ||
| 10-M-800.pdf | ||
| AF85D7-1.PDF | ||
| AFA040-1.PDF | ||
| 00-M-806.pdf | ||
| AF0F76-1.PDF | ||
| 00-MP-4.PDF | ||
| AF6B67-1.PDF | ||
| AFDA0C-1.PDF | ||
| 00-M-201.pdf | ||
| AF7DA6-1.PDF | ||
| AF5B0D-1.PDF | ||
| AF4200-1.PDF | ||
| 10-MH-1.PDF | ||
| AF2EB8-1.PDF | ||
| AF7BD0-1.PDF | ||
| AF4273-1.PDF | ||
| 00-M-803.pdf | ||
| 10-M-801.pdf | ||
| 00-MP-2.PDF | ||
| AF1533-1.PDF | ||
| AF9D68-1.PDF | ||
| AFC2EA-1.PDF | ||
| AF2AEE-1.PDF | ||
| AFD99B-1.PDF | ||
| AF26AC-1.PDF | ||
| W912BU24R0001 Amendment 0004.pdf | ||
| AFFB36-1.PDF | ||
| 00-M-807.pdf | ||
| 00-M-808.pdf | ||
| AF9FDC-1.PDF | ||
| AF47CB-1.PDF | ||
| AFRC55-2.PDF | ||
| 00-M-802.pdf | ||
| AFFC3F-1.PDF | ||
| AFC8A7-1.PDF | ||
| AF8E75-1.PDF | ||
| AFD903-1.PDF | ||
| AF54B2-1.PDF | ||
| AFD078-1.PDF | ||
| 00-MH-1.PDF | ||
| AF0EF7-1.PDF | ||
| 00-MP-1.PDF | ||
| 00-M-805.pdf | ||
| 00-MH-4.PDF | ||
| AF377B-1.PDF | ||
| AF9D55-1.PDF | ||
| AFE9FE-1.PDF | ||
| AF2040-1.PDF |
Show 40 more
Latest 50 of 102 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CP-2 HW HEAT SYSTEM DIAGRAM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
D O
-1
D O
-2
C O
M
D O
-3
D O
-4
C O
M
D O
-5
D O
-6
C O
M
V
A C
4V
A C
C O
M
E G
N D
S H
LD
N E
T -1
N E
T -2
SPYDER
SRV
JACK
SRV
PIN
18 19 20
D O
-7
D O
-8
C O
M
21 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
A O
-1
C O
M
A O
-2
A O
-3
C O
M
D I-1
D I-2
C O
M
D I-3
D I-4
4V
D C
U I-1
C O
M
U I-2
U I-3
C O
M
U I-4
U I-5
C O
M
U I-6
HW HEAT
CONTROL PANEL 2
PLAN NOTES:
GENERAL NOTES:
LEGEND:
CP-3 GAS DETECTION/ RTH DIAGRAM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
D O
-1
D O
-2
C O
M
D O
-3
D O
-4
C O
M
D O
-5
D O
-6
C O
M
V
A C
4V
A C
C O
M
E G
N D
S H
LD
N E
T -1
N E
T -2
SPYDER
SRV
JACK
SRV
PIN
18 19 20
D O
-7
D O
-8
C O
M
21 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
A O
-1
C O
M
A O
-2
A O
-3
C O
M
D I-1
D I-2
C O
M
D I-3
D I-4
4V
D C
U I-1
C O
M
U I-2
U I-3
C O
M
U I-4
U I-5
C O
M
U I-6
GAS DETECTION & RTH
CONTROL PANEL 3
OMS BUILDING
I. GAS-FIRED FURNACE GF-1, GF-2/LOUVERS L-11, L-6
A. GENERAL
1. THE GAS-FIRED FURNACES WILL BE CONTROLLED BY THE
BMS.
2. THE UNITS WILL BE STARTED AND STOPPED THROUGH A
USER DEFINED OCCUPANCY SCHEDULE.
3. ALARMS
a. THE FOLLOWING GAS-FIRED FURNACE ALARMS WILL BE
MONITORED AND ANNUNCIATED BY THE BMS:
1) SF FAILURE
a) A SF FAILURE ALARM OCCURS WHENEVER THE FAN IS
COMMANDED TO START BY THE FURNACE
CONTROLLER AND THE SUPPLY FAN STATUS PROVING
SWITCH DOES NOT INDICATE THAT THE FAN IS
OPERATING WITHIN 10 SECS.
b) WHEN A SF FAILURE ALARM OCCURS, THE OUTSIDE
AIR (OA) INTAKE DAMPER SHALL CLOSE AND THE
HEATING AND COOLING COILS (GF-2 ONLY) WILL BE
OFF.
2) COMPRESSOR FAILURE (GF-2 ONLY)
a) A COMPRESSOR FAILURE ALARM OCCURS WHENEVER
THE COMPRESSOR IS COMMANDED TO START BY THE
FURNACE CONTROLLER AND THE COMPRESSOR
STATUS PROVING SWITCH DOES NOT INDICATE THAT
THE COMPRESSOR IS OPERATING WITHIN 10 SECS.
b) WHEN A COMPRESSOR FAILURE ALARM OCCURS, NO
ADDITIONAL CONTROL ACTION WILL BE TAKEN.
3) HIGH AND LOW SAT ALARMS WILL BE ANNUNCIATED BY
THE BMS. THE HIGH LIMIT ALARM WILL OCCUR WHEN
THE SAT RISES ABOVE 100 DEGF. THE LOW LIMIT ALARM
WILL OCCUR WHEN THE SAT DROPS BELOW 40 DEGF.
b. ALL ALARMS WILL BE ANNUNCIATED LOCALLY AT THE
USER INTERFACE PC AS WELL AS REMOTELY BY PAGER
OR EMAIL, IF DESIRED BY THE END USER.
B. OCCUPIED MODE
1. SUPPLY FAN
a. THE SUPPLY FAN SHALL START AND RUN CONTINUOUSLY.
b. OA INTAKE LOUVER L-11 SHALL OPEN WHEN THE SF ON
FURNACE GF-1 IS PROVEN ON. THE LOUVER SHALL CLOSE
WHEN THE SF STOPS.
c. OA INTAKE LOUVER L-6 SHALL OPEN WHEN THE SF ON
FURNACE GF-2 IS PROVEN ON. THE LOUVER SHALL CLOSE
WHEN THE SF STOPS.
2. COOLING COIL (GF-2 ONLY)/HEATING COIL
a. WHEN THE SF IS OFF, THE COMPRESSORS SERVING THE
DX COOLING COIL (GF-2 ONLY) AND THE GAS-FIRED
HEATING COILS WILL BE OFF.
b. WHEN THE GF-1 SF IS PROVEN ON, THE HEATING COIL
WILL BE CONTROLLED TO MAINTAIN THE SPACE
TEMPERATURE AT A HEATING SETPOINT OF 68 DEGF
(ADJ.).
c. WHEN THE GF-2 SF IS PROVEN ON, THE HEATING AND
COOLING COILS WILL BE CONTROLLED IN SEQUENCE TO
MAINTAIN A SPACE COOLING SETPOINT OF 78 DEGF (ADJ.).
AND A SPACE HEATING SETPOINT OF 68 DEGF (ADJ.).
C.UNOCCUPIED MODE
1. THE SF, COOLING COIL (GF-2 ONLY) AND HEATING COIL
SHALL CYCLE BETWEEN THE HEATING AND COOLING MODES
TO MAINTAIN THE HEATING AND COOLING SETPOINTS
2. THE HEATING SETPOINT SHALL BE 60 DEGF (ADJ.) AND THE
COOLING SETPOINT (GF-2 ONLY) SHALL BE 85 DEGF (ADJ.).
3. THE OA INTAKE LOUVERS SHALL BE CLOSED AT ALL TIMES.
II. FAN-COIL UNIT FC-6
A. THE FAN-COIL UNITS WILL BE CONTROLLED BY A LOCAL
THERMOSTAT.
B. THE FAN-COIL UNITS WILL NOT BE CONNECTED TO THE BMS.
C. A TEMPERATURE SENSOR IN EACH ROOM SERVED A FAN-COIL
UNIT WILL BE MONITORED BY THE BMS.
D. IF THE ROOM TEMPERATURE RISES ABOVE 85 DEGF (ADJ.), A
HIGH TEMPERATURE ALARM WILL BE ANNUNCIATED BY THE
BMS. IF THE ROOM TEMPERATURE FALLS BELOW 60 DEGF, A
LOW TEMPERATURE ALARM WILL BE ANNUNCIATED BY THE
BMS.
E. ALL ALARMS WILL BE ANNUNCIATED AT THE USER INTERFACE
PC AS WELL AS REMOTELY BY PAGER OR EMAIL, IF DESIRED
BY THE END USER.
III. CENTRAL HOT WATER (HW) PLANT
A. BOILER B-1 AND HW PUMP HWP-1 WILL BE MONITORED AND
CONTROLLED BY THE BMS.
B. THE CENTRAL HEATING PLANT WILL BE ENABLED WHEN THE
OUTSIDE (OAT) FALLS BELOW 60 DEGF (ADJ.). IT WILL BE
DISABLED WHEN THE OAT RISES TO 5 DEGF ABOVE THE
ENABLE SETPOINT.
C.ON A CALL FOR HEAT, B-1 AND HWP-1 WILL START.
D. THE BOILER LEAVING HW TEMPERATURE WILL BE
CONTROLLED BY THE BOILER MANUFACTURER'S UNIT
MOUNTED CONTROL PANEL TO MAINTAIN A LEAVING HW
TEMPERATURE OF 180 DEGF.
E. ALARMS
1. THE FOLLOWING HW PLANT ALARMS WILL BE MONITORED
AND ANNUNCIATED BY THE BMS:
a. BOILER COMMON ALARM
1) THIS ALARM COMES FROM A CONTACT CLOSURE INSIDE
THE LOCAL BOILER CONTROL PANEL.
2) AN OPEN CONTACT INDICATES A NORMAL CONDITION. A
CLOSED CONTACT INDICATES AN ALARM.
3) THE FOLLOWING INTERNAL BOILER ALARMS ARE
INDICATED BY THESE CONTACTS:
a) OPEN OR SHORTED SENSOR
b) IGNITION LOCKOUT
c) FLOW SWITCH INTERLOCK
d) COMBUSTION AIR DAMPER FAILURE
e) BLOCKED FLUE OR BLOCKED AIR INLET
b. HW PUMP RUN FAILURE
1) A PUMP FAILURE ALARM OCCURS WHENEVER THE PUMP
IS COMMANDED TO START BY THE PLANT CONTROLLER
AND THE PUMP STATUS PROVING SWITCH DOES NOT
INDICATE THAT THE PUMP IS OPERATING WITHIN 10
SECS.
2) WHEN A PUMP FAILURE ALARM OCCURS, THE BOILER
WILL STOP.
c. A HIGH HW SUPPLY TEMPERATURE ALARM WILL BE
ANNUNCIATED BY THE BMS. THE HIGH LIMIT ALARM WILL
OCCUR WHEN THE HW SUPPLY TEMPERATURE RISES
ABOVE 200 DEGF.
2. ALL ALARMS WILL BE ANNUNCIATED LOCALLY AT THE USER
INTERFACE PC AS WELL AS REMOTELY BY PAGER OR EMAIL,
IF DESIRED BY THE END USER.
IV. UNDER FLOOR HW RADIANT HEATING SYSTEM
A. THE UNDER FLOOR HW RADIANT HEATING SYSTEM WILL BE
MONITORED AND CONTROLLED BY THE BMS.
B. THE SECONDARY HW PUMP HWP-2 WILL BE STARTED WHEN
THE MAINTENANCE BAY SAT FALLS BELOW ITS SETPOINT OF 65
DEGF (ADJ.). IT WILL BE STOPPED WHEN THE SAT RISES TO 5
DEGF ABOVE THE ENABLE SETPOINT.
C. WHEN HWP-2 IS PROVEN ON, THE ZONE HW VALVE WILL BE
MODULATED TO MAINTAIN THE RADIANT LOOP SUPPLY WATER
TEMPERATURE AT 130 DEGF (ADJ.).
D. ALARMS
1. HIGH AND LOW RADIANT LOOP SUPPLY WATER
TEMPERATURE ALARMS WILL BE ANNUNCIATED BY THE BMS.
2. THE HIGH LIMIT ALARM WILL OCCUR WHEN THE RADIANT
LOOP SUPPLY WATER TEMPERATURE RISES ABOVE 150
DEGF. THE LOW LIMIT ALARM WILL OCCUR WHEN THE
TEMPERATURE FALLS BELOW 110 DEGF.
V. OVERHEAD GAS-FIRED RADIANT TUBE HEATERS RTH-1, 2, 3, 4
A. THE RADIANT TUBE HEATERS WILL BE CONTROLLED BY THE
BMS.
B. EACH RADIANT TUBE HEATER ZONE WILL BE CYCLED ON AND
OFF TO MAINTAIN ITS RESPECTIVE SPACE TEMPERATURE AT A
SETPOINT OF 68 DEGF (ADJ.).
C. ALARMS
1. HIGH AND LOW SAT ALARMS WILL BE ANNUNCIATED.
2. THE HIGH SAT ALARM WILL OCCUR WHEN THE SAT RISES
ABOVE 80 DEGF. THE LOW SAT ALARM WILL OCCUR WHEN
THE SAT FALLS BELOW 55 DEGF.
VI. HOT WATER UNIT HEATERS UH-1, 2, 3, 4, 5
A.EACH HW UNIT HEATER WILL BE CONTROLLED BY A UNIT
MOUNTED THERMOSTAT TO MAINTAIN ITS SETPOINT.
B. THE HW UNIT HEATERS WILL NOT BE CONNECTED TO THE BMS.
VII. MAKE-UP AIR UNIT MUA-2/EXHAUST FAN EF-5
A. THE MAKE-UP AIR UNIT (MUA) MUA-2 WILL BE DIRECTLY
CONTROLLED BY A LOCAL, MANUFACTURER PROVIDED
CONTROLLER THAT WILL COMMUNICATE TO THE BMS OVER
THE LON NETWORK.
B. THE BMS SHALL HAVE THE CAPABILITY TO START AND STOP
THE UNIT AND CHANGE THE DAT SETPOINT.
C.MUA-2 AND ITS ASSOCIATED EXHAUST FAN (EF) EF-5 WILL BE
STARTED WHEN THE CO OR NO2 LEVELS IN THE MAINTENANCE
BAY SPACE EXCEED PERMISSIBLE LEVELS. THE UNITS WILL BE
STOPPED WHEN THE CO AND NO2 LEVELS RETURN TO
NORMAL.
D. ON A CALL FOR THE MUA TO OPERATE, THE LOCAL
CONTROLLER SHALL OPEN ITS OA INTAKE DAMPER. ONCE THE
DAMPER HAS BEEN PROVEN OPEN, THE CONTROLLER SHALL
START THE MUA-2 SF.
E. ONCE THE SF HAS BEEN PROVEN ON, THE LOCAL CONTROLLER
WILL CONTROL THE HEATING COIL TO MAINTAIN THE DAT AT A
SETPOINT OF 65 DEGF (ADJ.).
F. ALARMS
1. THE FOLLOWING MUA AND EF ALARMS WILL BE MONITORED
AND ANNUNCIATED BY THE BMS:
a. INTERNAL MUA ALARMS
1) INTERNAL ALARMS GENERATED BY THE MUA
MANUFACTURER'S CONTROL SYSTEM SHALL BE
ANNUNCIATED BY THE BMS.
2) SEE THE MANUFACTURER'S LITERATURE FOR A LIST OF
THE SYSTEM ALARMS.
b. SF FAILURE
1) A SF FAILURE ALARM OCCURS WHENEVER THE FAN IS
COMMANDED TO START BY THE MUA CONTROLLER AND
THE SUPPLY FAN STATUS PROVING SWITCH DOES NOT
INDICATE THAT THE FAN IS OPERATING WITHIN 10 SECS.
2) WHEN A SF FAILURE ALARM OCCURS, THE OUTSIDE AIR
(OA) INTAKE DAMPER SHALL CLOSE.
c. EF-5 FAILURE
1) AN EF FAILURE ALARM OCCURS WHENEVER THE FAN IS
COMMANDED TO START BY THE MUA CONTROLLER AND
THE SUPPLY FAN STATUS PROVING SWITCH DOES NOT
INDICATE THAT THE FAN IS OPERATING WITHIN 10 SECS.
2) WHEN AN EF FAILURE ALARM OCCURS, THE OUTSIDE AIR
(OA) INTAKE DAMPER SHALL CLOSE.
d. HIGH AND LOW LIMIT DISCHARGE AIR TEMPERATURE
ALARMS WILL BE ANNUNCIATED. THE HIGH LIMIT ALARM
WILL OCCUR WHEN THE DISCHARGE AIR TEMPERATURE
RISES ABOVE 80 DEGF. THE LOW LIMIT ALARM WILL
OCCUR WHEN THE TEMPERATURE FALLS BELOW 40 DEGF.
2. ALL ALARMS WILL BE ANNUNCIATED LOCALLY AT THE USER
INTERFACE PC AS WELL AS REMOTELY BY PAGER OR EMAIL,
IF DESIRED BY THE END USER.
VIII. EXHAUST FAN EF-4/LOUVER L-8
A.EXHAUST FAN EF-4 WILL BE MONITORED AND CONTROLLED BY
THE BMS BASED ON A USER DEFINED OCCUPANCY SCHEDULE.
B. THE FAN WILL OPERATE CONTINUOUSLY DURING THE
OCCUPIED PERIOD. IT WILL BE OFF DURING THE UNOCCUPIED
PERIOD.
C.LOUVER L-8 WILL OPEN THROUGH A HARD-WIRED INTERLOCK
WHEN EF-4 STARTS. L-8 WILL CLOSE WHEN EF-4 STOPS.
D. AN EF-4 FAILURE ALARM WILL BE ANNUNCIATED BY THE BMS.
THE ALARM OCCURS WHENEVER THE FAN IS COMMANDED TO
START BY THE CONTROLLER AND THE EXHAUST FAN STATUS
PROVING SWITCH DOES NOT INDICATE THAT THE FAN IS
OPERATING WITHIN 10 SECS.
E. WHEN AN EF-4 FAILURE ALARM OCCURS, LOUVER L-8 SHALL
CLOSE.
IX. MAINTENANCE BAY EXHAUST FANS EF-6 THRU EF-13/LOUVERS
L-19, L-20
A. THE MAINTENANCE BAY DIRECT CAPTURE EXHAUST FAN EF-6
THRU EF-13 WILL BE STARTED AND STOPPED MANUALLY.
B. THESE FANS WILL NOT BE CONNECTED TO THE BMS.
C.LOUVER L-19 WILL BE INTERLOCKED TO OPEN WHEN ANY OF
FANS EF-6 THRU EF-9 ARE ON. L-19 WILL CLOSE WHEN ALL OF
THESE FANS ARE OFF.
D.LOUVER L-20 WILL BE INTERLOCKED TO OPEN WHEN ANY OF
FANS EF-10 THRU EF-13 ARE ON. L-20 WILL CLOSE WHEN ALL
OF THESE FANS ARE OFF.
X. SUPPLY FAN SF-2/LOUVERS L-10, L-12
A. SUPPLY FAN SF-2 WILL BE MONITORED AND CONTROLLED BY
THE BMS.
B. THE FAN WILL BE CYCLED TO MAINTAIN ITS SPACE
TEMPERATURE AT A SETPOINT OF 85 DEGF (ADJ.).
C.LOUVER L-10 WILL BE INTERLOCKED TO OPEN WHEN SF-2
STARTS. L-10 WILL CLOSE WHEN SF-2 STOPS.
D. ON A CALL FOR COOLING, LOUVER L-12 WILL OPEN FIRST.
WHEN L-12 IS PROVEN OPEN, SF-2 WILL START.
E. ALARMS
1. THE FOLLOWING SF ALARMS WILL BE MONITORED AND
ANNUNCIATED BY THE BMS:
a. SF FAILURE
1) A SF FAILURE ALARM OCCURS WHENEVER THE FAN IS
COMMANDED TO START BY THE CONTROLLER AND THE
SUPPLY FAN STATUS PROVING SWITCH DOES NOT
INDICATE THAT THE FAN IS OPERATING WITHIN 10 SECS.
2) WHEN A SF FAILURE ALARM OCCURS, ITS ASSOCIATED
LOUVER SHALL CLOSE.
b. HIGH AND LOW SAT ALARMS WILL BE ANNUNCIATED BY
THE BMS. THE HIGH LIMIT ALARM WILL OCCUR WHEN THE
SAT RISES ABOVE 100 DEGF. THE LOW LIMIT ALARM WILL
OCCUR WHEN THE SAT DROPS BELOW 40 DEGF.
2. ALL ALARMS WILL BE ANNUNCIATED LOCALLY AT THE USER
INTERFACE PC AS WELL AS REMOTELY BY PAGER OR EMAIL,
IF DESIRED BY THE END USER.
XI. SUPPLY FANS EF-18 THRU EF-21/LOUVERS L-9, L-7, L-17, L-5, L-15,
L16, L-14, L-13
A. THE RUN STATUS OF EXHAUST FANS EF-18 THRU EF-21 WILL BE
MONITORED BY THE BMS.
B. THESE FANS WILL RUN CONTINUOUSLY.
C.IF ANY OF THESE FANS STOP, AN ALARM WILL BE
ANNUNCIATED THROUGH THE BMS.
D.LOUVER L-7 WILL OPEN THROUGH A HARD-WIRED INTERLOCK
WHEN EF-18 STARTS. L-7 WILL CLOSE WHEN EF-18 STOPS.
E. ON A CALL FOR EF-18 TO RUN, LOUVER L-9 WILL OPEN FIRST.
WHEN L-9 IS PROVEN OPEN, EF-18 WILL START.
F. LOUVER L-5 WILL OPEN THROUGH A HARD-WIRED INTERLOCK
WHEN EF-19 STARTS. L-5 WILL CLOSE WHEN EF-19 STOPS.
G. ON A CALL FOR EF-19 TO RUN, LOUVER L-17 WILL OPEN FIRST.
WHEN L-17 IS PROVEN OPEN, EF-19 WILL START.
H.LOUVER L-16 WILL OPEN THROUGH A HARD-WIRED INTERLOCK
WHEN EF-20 STARTS. L-16 WILL CLOSE WHEN EF-20 STOPS.
I. ON A CALL FOR EF-20 TO RUN, LOUVER L-15 WILL OPEN FIRST.
WHEN L-15 IS PROVEN OPEN, EF-20 WILL START.
J. LOUVER L-13 WILL OPEN THROUGH A HARD-WIRED INTERLOCK
WHEN EF-21 STARTS. L-13 WILL CLOSE WHEN EF-21 STOPS.
K. ON A CALL FOR EF-21 TO RUN, LOUVER L-14 WILL OPEN FIRST.
WHEN L-14 IS PROVEN OPEN, EF-21 WILL START.
XII. GAS-FIRED UNIT HEATERS GUH-1, GUH-2
A.EACH GAS-FIRED UNIT HEATER WILL BE CONTROLLED BY A
UNIT MOUNTED THERMOSTAT TO MAINTAIN ITS SETPOINT.
B. THE GAS-FIRED UNIT HEATERS WILL NOT BE CONNECTED TO
THE BMS.
XIII. ELECTRIC UNIT HEATER EUH-2
A.ELECTRIC UNIT HEATER EUH-2 WILL BE CONTROLLED BY A
UNIT MOUNTED THERMOSTAT TO MAINTAIN ITS SETPOINT.
B. THIS ELECTRIC UNIT HEATER WILL NOT BE CONNECTED TO
THE BMS.
FO
R
U M
S
TU
D
IO
S T.
L O
U
IS
, M O
S O
LI
C
IT
A
TI
O
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
K D
B Y:
D E
S
IG
N
ED
B Y:
D E
S C
R
IP
TI
O
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
TE
FI
LE
N U
M
BE
R
S
IZ
E:
S U
B M
IT
TE
D B
Y:
P
LO
T S
C
AL
E:
P
LO
T
D
AT
E:
D A
TE
M
A R
K D
E S
C R
IP
TI
O N
C O
N
TR
A C
T N
O
SHEET
IDENTIFICATION
D A
TE
A
P P
R
SHEET OF
US Army Corps of Engineers
M R
-P -6
4/
C O
N -0
6- B
-N U
M B
A N
S I D
MHOWARD
6/29/2011 12:06 PM
T:\ENGINEERING\PROJECTS\WILLOW GROVE\CONTROLS\10-M-803.DWG
A R
M Y
R E
S E
R V
E T
R
AI
N
IN
G C
EN
TE
R W
IL
LO
W G
R O
V E
N A
VA
L
AI
R
S
TA
TI
O
N W
2Q
R -0
9- C
-0
AS-BUILT
/2
9/
C O
N
TR
O L
P A
N E
LS
&3 (C
P- 2&
C P-
3) H
W H
E A
T/ G
A S
D
ET
EC
TI
O N
R
TH
D
IA
G
R
AM
S
M M
D W
M M
M H
1/ 8"
'-0
2/ 9/
-M
-8
.D W
G
10-M-803
File details come from the government source that posted it. Updated .