National Guard Readiness Center Wilmington, North Carolina Addendum 1 16 August 2017
SECTION 271513 - COMMUNICATIONS COPPER HORIZONTAL CABLING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Category 6 twisted pair cable.
2. Twisted pair cable hardware, including plugs and jacks.
3. Cable management system.
4. Cabling identification products.
5. Grounding provisions for twisted pair cable.
6. Source quality control requirements for twisted pair cable.
1.3 DEFINITIONS
A. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
B. EMI: Electromagnetic interference.
C. FTP: Shielded twisted pair.
D. F/FTP: Overall foil screened cable with foil screened twisted pair.
E. F/UTP: Overall foil screened cable with unscreened twisted pair.
F. IDC: Insulation displacement connector.
G. LAN: Local area network.
H. Jack: Also commonly called an "outlet," it is the fixed, female connector.
I. Plug: Also commonly called a "connector," it is the removable, male telecommunications connector.
J. RCDD: Registered Communications Distribution Designer.
K. Screen: A metallic layer, either a foil or braid, placed around a pair or group of conductors.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 1
L. Shield: A metallic layer, either a foil or braid, placed around a pair or group of conductors.
M. S/FTP: Overall braid screened cable with foil screened twisted pair.
N. S/UTP: Overall braid screened cable with unscreened twisted pairs.
O. UTP: Unscreened (unshielded) twisted pair.
1.4 COPPER HORIZONTAL CABLING DESCRIPTION
A. Horizontal cable cabling system shall provide interconnections between Distributor A, Distributor B, or Distributor C, and the equipment outlet, otherwise known as "Cabling Subsystem 1," in the telecommunications cabling system structure. Cabling system consists of horizontal cables, intermediate and main cross-connects, mechanical terminations, and patch cords or jumpers used for horizontal-to-horizontal cross-connection.
1. TIA-568-C.1 requires that a minimum of two equipment outlets be installed for each work area.
2. Horizontal cabling shall contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications equipment outlet.
3. Bridged taps and splices shall not be installed in the horizontal cabling.
B. A work area is approximately 100 sq. ft. (9.3 sq. m), and includes the components that extend from the equipment outlets to the station equipment.
C. The maximum allowable horizontal cable length is 295 feet (90 m). This maximum allowable length does not include an allowance for the length of 16 feet (4.9 m) to the workstation equipment or in the horizontal cross-connect.
1.5 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Reviewed and stamped by RCDD.
1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner.
2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software.
3. Cabling administration Drawings and printouts.
4. Wiring diagrams and installation details of telecommunications equipment, to show location and layout of telecommunications equipment, including the following:
a. Telecommunications rooms plans and elevations.
b. Telecommunications pathways.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 2
c. Telecommunications system access points.
d. Telecommunications grounding system.
e. Telecommunications conductor drop locations.
f. Typical telecommunications details.
g. Mechanical, electrical, and plumbing systems.
C. Twisted pair cable testing plan.
D. Samples: For telecommunications jacks and plugs, in specified finish, one for each type and configuration and faceplates for color selection and evaluation of technical features.
1.6 INFORMATIONAL SUBMITTALS
A. Installer Qualifications: Cabling installer must have personnel certified by BICSI on staff.
1. Layout Responsibility: Preparation of Shop Drawings shall be under direct supervision of RCDD. Copy of registration must be submitted at time of bid.
2. Installation Supervision Installation shall be under direct supervision of Certified BICSI ITS Technician, who shall be present at all times when Work of this Section is performed at Project site.
3. Field Inspector: Currently registered by BICSI as RCDD to perform the on-site inspection. The RCDD will visit the job site at least twice a week to review work and schedules.
B. Product Certificates: For each type of product.
C. Source quality-control reports.
D. Field quality-control reports.
E. As-Built (Record Drawings): Furnish as-built CAD drawings of completed work including cable numbers. A full size hard copy and electronic copy on CD-ROM shall be furnished to the Owner’s Project Manager. Follow format and labeling conventions as specified in Specification 27 0553 Identification for Communication Systems.
1.7 CLOSEOUT SUBMITTALS
A. Maintenance Data: For splices and connectors to include in maintenance manuals.
B. Software and Firmware Operational Documentation:
1. Software operating and upgrade manuals.
2. Program Software Backup: On USB media or compact disk, complete with data files.
3. Device address list.
4. Printout of software application and graphic screens.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 3
Addendum 1 16 August 2017
1.8 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Connecting Blocks: One (1) of each type.
2. Faceplates: One (1) of each type.
3. Jacks: Ten (10) of each type.
4. Multiuser Telecommunications Outlet Assemblies: One (1) of each type.
5. Patch-Panel Units: One (1) of each type.
6. Plugs: Ten (10) of each type.
1.9 QUALITY ASSURANCE
A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff.
1. Layout Responsibility: Preparation of Shop Drawings and cabling administration Drawings, cabling administration Drawings, and field testing program development by an RCDD.
2. Installation Supervision: Installation shall be under the direct supervision of BICSI ITS Technician, who shall be present at all times when Work of this Section is performed at Project site.
3. Testing Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing.
B. Testing Agency Qualifications: Testing agency must have personnel certified by BICSI on staff.
1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD.
1.10 DELIVERY, STORAGE, AND HANDLING
A. Test cables upon receipt at Project site.
1. Test each pair of twisted pair cable for open and short circuits.
1.11 PROJECT CONDITIONS
A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 4
Addendum 1 16 August 2017
1.12 COORDINATION
A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers.
1.13 WARRANTY
A. A minimum twenty (20) year Extended Product Warranty and System Assurance Warranty for this wiring system shall be provided. If items supplied as part of this project have longer warranties, the Contractor shall supply longer warranty.
1. Extended Product Warranty: The Extended Product Warranty shall ensure against product defects, that all approved cabling components exceed the specifications of TIA/EIA 568B and ISO/IEC IS 11801, exceed the requirements of TIA/EIA TSB 67, TIA/EIA TSB 95, and ISO/IEC IS 11801 for cabling links/channels, that the installation shall exceed the loss and bandwidth requirements of TIA/EIA TSB 67, TIA/EIA TSB 95, and ISO/IEC IS 11801 for fiber links/channels, for a twenty (20) year period. The warranty shall apply to all passive PDS components.
a. If items supplied as part of this project have longer warranties, contractor shall supply longer warranty.
2. System Assurance: The System Assurance shall cover the failure of the wiring system to support the application which it was designed to support, as well as additional application(s) introduced in the future by recognized standards or user forums that use the TIA 568C or ISO/IEC IS 11801 component and link/channel specifications for cabling, for a twenty (20) year period.
3. Extended Product Warranty: The Extended Product Warranty and the System Assurance shall cover the replacement or repair of defective product(s) and labor for the replacement or repair of such defective product(s).
4. System Certification: Upon successful completion of the installation and subsequent inspection, the customer shall be provided with a numbered certificate, from the manufacturing company, registering the installation.
1.14 SOFTWARE SERVICE AGREEMENT
A. Technical Support: Beginning with Substantial Completion, provide software support for two (2) years.
B. Upgrade Service: Update software to latest version at Project completion. Install and program software upgrades that become available within two (2) years from date of Substantial Completion. Upgrading software shall include operating system. Upgrade shall include new or revised licenses for use of software.
1. Provide thirty (30) days' notice to Owner to allow scheduling and access to system and to allow Owner to upgrade computer equipment if necessary.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 5
Addendum 1 16 August 2017
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA-568-C.1, when tested according to test procedures of this standard.
B. Telecommunications Pathways and Spaces: Comply with TIA-569-D.
C. Grounding: Comply with TIA-607-B.
2.2 GENERAL CABLE CHARACTERISTICS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with the applicable standard and NFPA 70 for the following types:
1. Communications, Plenum Rated: Type CMP complying with UL 1685 or Type CMP in listed plenum communications raceway or Type CMP in listed cable routing assembly.
B. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: 25 or less.
2. Smoke-Developed Index: 50 or less.
C. RoHS compliant.
2.3 CATEGORY 6 TWISTED PAIR CABLE
A. Description: Four-pair, balanced-twisted pair cable, certified to meet transmission characteristics of Category 6 cable at frequencies up to 250MHz.
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Belden
2. Berk-Tek
3. Commscope
4. Mohawk
5. Panduit
6. Systimax
7. Surperior Essex
C. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568-C.2 for Category 6 cables.
D. Conductors: 100-ohm, 23 AWG solid copper.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 6
http://www.specagent.com/LookUp/?ulid=1754&mf=04&src=wd
E. Shielding/Screening: Unshielded twisted pairs (UTP).
F. Cable Rating: Plenum.
G. Jacket: Color as indicated thermoplastic.
2.4 TWISTED PAIR CABLE HARDWARE
A. Description: Hardware designed to connect, splice, and terminate twisted pair copper communications cable.
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Belden
2. Ortronics
3. Panduit
4. Systimax
5. Surperior Esses
C. General Requirements for Twisted Pair Cable Hardware:
1. Comply with the performance requirements of Category 6.
2. Comply with TIA-568-C.2, IDC type, with modules designed for punch-down caps or tools.
3. Cables shall be terminated with connecting hardware of same category or higher.
D. Source Limitations: Obtain twisted pair cable hardware from single source from single manufacturer.
E. Connecting Blocks:
1. 110-style IDC for Category 6.
2. Provide blocks for the number of cables terminated on the block, plus 25 percent spare, integral with connector bodies, including plugs and jacks where indicated.
F. Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables.
1. Number of Terminals per Field: One for each conductor in assigned cables.
G. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at each jack location for permanent termination of pair groups of installed cables.
1. Features:
a. Universal T568A and T568B wiring labels.
b. Labeling areas adjacent to conductors.
c. Replaceable connectors.
d. 24 or 48 ports.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 7
http://www.specagent.com/LookUp/?ulid=1754&mf=04&src=wd
2. Construction: 16-gauge steel and mountable on 19-inch (483 mm) equipment racks.
3. Number of Jacks per Field: One for each four-pair cable indicated.
H. Patch Cords: Factory-made, four-pair cables terminated with an eight-position modular plug at each end are GFGI.
I. Plugs and Plug Assemblies:
1. Male; eight position; color-coded modular telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable.
2. Standard: Comply with TIA-568-C.2.
3. Marked to indicate transmission performance.
J. Jacks and Jack Assemblies:
1. Female; eight position; modular; fixed telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable.
2. Designed to snap-in to a patch panel or faceplate.
3. Standard: Comply with TIA-568-C.2.
4. Marked to indicate transmission performance.
K. Faceplate:
1. Two, Four, Six port, vertical single gang faceplates designed to mount to double gang wall boxes with a single gang mud ring.
2. Eight, Ten, Twelve port, vertical double gang faceplates designed to mount to double gang wall boxes.
3. Plastic Faceplate: High-impact plastic. Coordinate color with Section 262726 "Wiring Devices."
4. Metal Faceplate: Stainless steel, complying with requirements in Section 262726 "Wiring Devices."
5. For use with snap-in jacks accommodating any combination of twisted pair, optical fiber, and coaxial work area cords.
a. Flush mounting jacks, positioning the cord at a 45-degree angle.
L. Legend:
1. Machine printed, in the field, using adhesive-tape label.
2. Snap-in, clear-label covers and machine-printed paper inserts.
2.5 IDENTIFICATION PRODUCTS
A. Comply with TIA-606-B and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 8
Addendum 1 16 August 2017
2.6 GROUNDING
A. Comply with requirements in Section 270526 "Grounding and Bonding for Communications Systems" for grounding conductors and connectors.
B. Comply with TIA-607-B.
2.7 SOURCE QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to evaluate cables.
B. Factory test cables on reels according to TIA-568-C.1.
C. Factory test twisted pair cables according to TIA-568-C.2.
D. Cable will be considered defective if it does not pass tests and inspections.
E. Prepare test and inspection reports.
PART 3 - EXECUTION
3.1 WIRING METHODS
A. Wiring Method: Install cables in raceways and cable trays, except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, attics, and gypsum board partitions where unenclosed wiring method may be used. Conceal raceway and cables, except in unfinished spaces.
1. Install plenum cable in environmental air spaces, including plenum ceilings.
2. Comply with requirements for raceways and boxes specified in Section 270528
"Pathways for Communications Systems."
B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.
C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. Install conductors parallel with or at right angles to sides and back of enclosure.
3.2 INSTALLATION OF PATHWAYS
A. Comply with requirements for demarcation point, cabinets, and racks specified in Section 271100 "Communications Equipment Room Fittings."
B. Comply with Section 270528 "Pathways for Communications Systems."
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 9
C. Comply with Section 270529 "Hangers and Supports for Communications Systems."
D. Comply with Section 270536 "Cable Trays for Communications Systems."
E. Drawings indicate general arrangement of pathways and fittings.
3.3 INSTALLATION OF TWISTED-PAIR HORIZONTAL CABLES
A. Comply with NECA 1 and NECA/BICSI 568.
B. General Requirements for Cabling:
1. Comply with TIA-568-C.0, TIA-568-C.1, and TIA-568-C.2.
2. Comply with BICSI's "Information Transport Systems Installation Methods
Manual (ITSIMM), Ch. 5, "Copper Structured Cabling Systems," "Cable Termination Practices" Section.
3. Install 110-style IDC termination hardware unless otherwise indicated.
4. Do not untwist twisted pair cables more than 1/2 inch (12 mm) from the point of termination to maintain cable geometry.
5. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.
6. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals.
7. Install lacing bars to restrain cables, prevent straining connections, and prevent bending cables to smaller radii than minimums recommended by manufacturer.
8. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI Information Transport Systems Installation Methods Manual , Ch. 5, "Copper Structured Cabling Systems," "Cable Termination Practices" Section.
Use lacing bars and distribution spools.
9. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation, and replace it with new cable.
10. Cold-Weather Installation: Bring cable to room temperature before dereeling.
Heat lamps shall not be used for heating.
11. In the communications equipment room, install a 10-foot- (3-m-) long service loop on each end of cable.
12. Pulling Cable: Comply with BICSI Information Transport Systems Installation Methods Manual, Ch. 5, "Copper Structured Cabling Systems," "Pulling and Installing Cable" Section. Monitor cable pull tensions.
C. Open-Cable Installation:
1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 10
2. Suspend twisted pair cabling, not in a wireway or pathway, a minimum of 8 inches (200 mm) above ceilings by cable supports not more than 60 inches (1524 mm) apart.
3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items.
D. Group connecting hardware for cables into separate logical fields.
E. Separation from EMI Sources:
1. Comply with recommendations from BICSI's "Telecommunications Distribution Methods Manual" and TIA-569-D for separating unshielded copper communication cable from potential EMI sources, including electrical power lines and equipment.
2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 5 inches (127 mm).
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 12 inches (300 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 24 inches (600 mm).
3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 2-1/2 inches (64 mm).
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 6 inches (150 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 12 inches (300 mm).
4. Separation between communications cables in grounded metallic raceways, power lines, and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:
a. Electrical Equipment Rating Less Than 2 kVA: No requirement.
b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 3 inches
(76 mm).
c. Electrical Equipment Rating More Than 5 kVA: A minimum of 6 inches (150 mm).
5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 48 inches (1200 mm).
6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm).
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 11
Addendum 1 16 August 2017
3.4 FIRESTOPPING
A. Comply with requirements in Section 078413 "Penetration Firestopping."
B. Comply with TIA-569-D, Annex A, "Firestopping."
C. Comply with "Firestopping Systems" Article in BISCI's "Telecommunications Distribution Methods Manual."
3.5 GROUNDING
A. Install grounding according to the "Grounding, Bonding, and Electrical Protection" chapter in BICSI's "Telecommunications Distribution Methods Manual."
B. Comply with TIA-607-B and NECA/BICSI-607.
3.6 IDENTIFICATION
A. Identify system components, wiring, and cabling complying with TIA-606-B. Comply with requirements for identification specified in Section 270553 "Identification for Communications Systems."
1. Administration Class: Class 2.
2. Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels.
B. Paint and label colors for equipment identification shall comply with TIA-606-B for Class 2 level of administration, including optional identification requirements of this standard.
C. Cable Schedule: Install in a prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic copy of final comprehensive schedules for Project.
D. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, terminal hardware and positions, horizontal cables, work areas and workstation terminal positions, grounding buses and pathways, and equipment grounding conductors.
E. Cable and Wire Identification:
1. Label each cable within 4 inches (100 mm) of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated.
2. Each wire connected to building-mounted devices is not required to be numbered at the device if wire color is consistent with associated wire connected and numbered within panel or cabinet.
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 12
3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 15 feet (4.5 m).
4. Label each terminal strip, and screw terminal in each cabinet, rack, or panel.
a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group, extended from a panel or cabinet to a building-mounted device, with the name and number of a particular device.
b. Label each unit and field within distribution racks and frames.
5. Identification within Connector Fields in Equipment Rooms and Wiring Closets:
Label each connector and each discrete unit of cable-terminating and -connecting hardware. Where similar jacks and plugs are used for both voice and data communication cabling, use a different color for jacks and plugs of each service.
F. Labels shall be preprinted or computer-printed type, with a printing area and font color that contrast with cable jacket color but still comply with TIA-606-B requirements for the following:
1. Cables use flexible vinyl or polyester that flexes as cables are bent.
3.7 FIELD QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections.
B. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
C. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
D. Perform tests and inspections with the assistance of a factory-authorized service representative.
E. Tests and Inspections:
1. Visually inspect jacket materials for NRTL certification markings. Inspect cabling terminations in communications equipment rooms for compliance with color-coding for pin assignments, and inspect cabling connections for compliance with
TIA-568-C.1.
2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.
3. Test twisted pair cabling for DC loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination but not cross-connection.
a. Test instruments shall meet or exceed applicable requirements in TIA-568- C.2. Perform tests with a tester that complies with performance
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 13
requirements in "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.
F. Data for each measurement shall be documented. Data for submittals shall be printed in a summary report that is formatted similarly to Table 10.1 in BICSI's "Telecommunications Distribution Methods Manual," or shall be transferred from the instrument to the computer, saved as text files, printed, and submitted.
G. Remove and replace cabling where test results indicate that they do not comply with specified requirements.
H. End-to-end cabling will be considered defective if it does not pass tests and inspections.
I. Prepare test and inspection reports.
3.8 SOFTWARE SERVICE AGREEMENT
A. Technical Support: Beginning with Substantial Completion, provide software support for two (2) years.
B. Upgrade Service: Update software to latest version at Project completion. Install and program software upgrades that become available within two years from date of Substantial Completion. Upgrading software shall include operating system. Upgrade shall include new or revised licenses for use of software.
1. Provide thirty (30) days' notice to Owner to allow scheduling and access to system and to allow Owner to upgrade computer equipment if necessary.
END OF SECTION 271513
COMMUNICATIONS COPPER HORIZONTAL CABLING 271513 - 14
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section Includes: |
| 1. Category 6 twisted pair cable. |
| 2. Twisted pair cable hardware, including plugs and jacks. |
| 3. Cable management system. |
| 4. Cabling identification products. |
| 5. Grounding provisions for twisted pair cable. |
| 6. Source quality control requirements for twisted pair cable. |
| 1.3 DEFINITIONS |
| A. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. |
| B. EMI: Electromagnetic interference. |
| C. FTP: Shielded twisted pair. |
| D. F/FTP: Overall foil screened cable with foil screened twisted pair. |
| E. F/UTP: Overall foil screened cable with unscreened twisted pair. |
| F. IDC: Insulation displacement connector. |
| G. LAN: Local area network. |
| H. Jack: Also commonly called an "outlet," it is the fixed, female connector. |
| I. Plug: Also commonly called a "connector," it is the removable, male telecommunications connector. |
| J. RCDD: Registered Communications Distribution Designer. |
| K. Screen: A metallic layer, either a foil or braid, placed around a pair or group of conductors. |
| L. Shield: A metallic layer, either a foil or braid, placed around a pair or group of conductors. |
| M. S/FTP: Overall braid screened cable with foil screened twisted pair. |
| N. S/UTP: Overall braid screened cable with unscreened twisted pairs. |
| O. UTP: Unscreened (unshielded) twisted pair. |
| 1.4 COPPER HORIZONTAL CABLING DESCRIPTION |
| A. Horizontal cable cabling system shall provide interconnections between Distributor A, Distributor B, or Distributor C, and the equipment outlet, otherwise known as "Cabling Subsystem 1," in the telecommunications cabling system structure. Cabling s... |
| 1. TIA-568-C.1 requires that a minimum of two equipment outlets be installed for each work area. |
| 2. Horizontal cabling shall contain no more than one transition point or consolidation point between the horizontal cross-connect and the telecommunications equipment outlet. |
| 3. Bridged taps and splices shall not be installed in the horizontal cabling. |
| B. A work area is approximately 34T100 sq. ft.34T44T (9.3 sq. m)44T, and includes the components that extend from the equipment outlets to the station equipment. |
| C. The maximum allowable horizontal cable length is 34T295 feet34T44T (90 m)44T. This maximum allowable length does not include an allowance for the length of 34T16 feet34T44T (4.9 m)44T to the workstation equipment or in the horizontal cross-connect. |
| 1.5 ACTION SUBMITTALS |
| A. Product Data: For each type of product. |
| B. Shop Drawings: Reviewed and stamped by RCDD. |
| 1. System Labeling Schedules: Electronic copy of labeling schedules, in software and format selected by Owner. |
| 2. System Labeling Schedules: Electronic copy of labeling schedules that are part of the cabling and asset identification system of the software. |
| 3. Cabling administration Drawings and printouts. |
| 4. Wiring diagrams and installation details of telecommunications equipment, to show location and layout of telecommunications equipment, including the following: |
| a. Telecommunications rooms plans and elevations. |
| b. Telecommunications pathways. |
| c. Telecommunications system access points. |
| d. Telecommunications grounding system. |
| e. Telecommunications conductor drop locations. |
| f. Typical telecommunications details. |
| g. Mechanical, electrical, and plumbing systems. |
| C. Twisted pair cable testing plan. |
| D. Samples: For telecommunications jacks and plugs, in specified finish, one for each type and configuration and faceplates for color selection and evaluation of technical features. |
| 1.6 INFORMATIONAL SUBMITTALS |
| A. Installer Qualifications: Cabling installer must have personnel certified by BICSI on staff. |
| 1. Layout Responsibility: Preparation of Shop Drawings shall be under direct supervision of RCDD. Copy of registration must be submitted at time of bid. |
| 2. Installation Supervision Installation shall be under direct supervision of Certified BICSI ITS Technician, who shall be present at all times when Work of this Section is performed at Project site. |
| 3. Field Inspector: Currently registered by BICSI as RCDD to perform the on-site inspection. The RCDD will visit the job site at least twice a week to review work and schedules. |
| B. Product Certificates: For each type of product. |
| C. Source quality-control reports. |
| D. Field quality-control reports. |
| E. As-Built (Record Drawings): Furnish as-built CAD drawings of completed work including cable numbers. A full size hard copy and electronic copy on CD-ROM shall be furnished to the Owner’s Project Manager. Follow format and labeling conventions as ... |
| 1.7 CLOSEOUT SUBMITTALS |
| A. Maintenance Data: For splices and connectors to include in maintenance manuals. |
| B. Software and Firmware Operational Documentation: |
| 1. Software operating and upgrade manuals. |
| 2. Program Software Backup: On USB media or compact disk, complete with data files. |
| 3. Device address list. |
| 4. Printout of software application and graphic screens. |
| 1.8 MAINTENANCE MATERIAL SUBMITTALS |
| A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| 1. Connecting Blocks: One (1) of each type. |
| 2. Faceplates: One (1) of each type. |
| 3. Jacks: Ten (10) of each type. |
| 4. Multiuser Telecommunications Outlet Assemblies: One (1) of each type. |
| 5. Patch-Panel Units: One (1) of each type. |
| 6. Plugs: Ten (10) of each type. |
| 1.9 QUALITY ASSURANCE |
| A. Installer Qualifications: Cabling Installer must have personnel certified by BICSI on staff. |
| 1. Layout Responsibility: Preparation of Shop Drawings and cabling administration Drawings, cabling administration Drawings, and field testing program development by an RCDD. |
| 2. Installation Supervision: Installation shall be under the direct supervision of BICSI ITS Technician, who shall be present at all times when Work of this Section is performed at Project site. |
| 3. Testing Supervisor: Currently certified by BICSI as an RCDD to supervise on-site testing. |
| B. Testing Agency Qualifications: Testing agency must have personnel certified by BICSI on staff. |
| 1. Testing Agency's Field Supervisor: Currently certified by BICSI as an RCDD. |
| 1.10 DELIVERY, STORAGE, AND HANDLING |
| A. Test cables upon receipt at Project site. |
| 1. Test each pair of twisted pair cable for open and short circuits. |
| 1.11 PROJECT CONDITIONS |
| A. Environmental Limitations: Do not deliver or install cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy level... |
| 1.12 COORDINATION |
| A. Coordinate layout and installation of telecommunications pathways and cabling with Owner's telecommunications and LAN equipment and service suppliers. |
| 1.13 WARRANTY |
| A. A minimum twenty (20) year Extended Product Warranty and System Assurance Warranty for this wiring system shall be provided. If items supplied as part of this project have longer warranties, the Contractor shall supply longer warranty. |
| 1. Extended Product Warranty: The Extended Product Warranty shall ensure against product defects, that all approved cabling components exceed the specifications of TIA/EIA 568B and ISO/IEC IS 11801, exceed the requirements of TIA/EIA TSB 67, TIA/EIA T... |
| a. If items supplied as part of this project have longer warranties, contractor shall supply longer warranty. |
| 2. System Assurance: The System Assurance shall cover the failure of the wiring system to support the application which it was designed to support, as well as additional application(s) introduced in the future by recognized standards or user forums th... |
| 3. Extended Product Warranty: The Extended Product Warranty and the System Assurance shall cover the replacement or repair of defective product(s) and labor for the replacement or repair of such defective product(s). |
| 4. System Certification: Upon successful completion of the installation and subsequent inspection, the customer shall be provided with a numbered certificate, from the manufacturing company, registering the installation. |
| 1.14 SOFTWARE SERVICE AGREEMENT |
| A. Technical Support: Beginning with Substantial Completion, provide software support for two (2) years. |
| B. Upgrade Service: Update software to latest version at Project completion. Install and program software upgrades that become available within two (2) years from date of Substantial Completion. Upgrading software shall include operating system. Upgra... |
| 1. Provide thirty (30) days' notice to Owner to allow scheduling and access to system and to allow Owner to upgrade computer equipment if necessary. |
| PART 2 - PRODUCTS |
| 2.1 PERFORMANCE REQUIREMENTS |
| A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA-568-C.1, when tested according to test procedures of this standard. |
| B. Telecommunications Pathways and Spaces: Comply with TIA-569-D. |
| C. Grounding: Comply with TIA-607-B. |
| 2.2 GENERAL CABLE CHARACTERISTICS |
| A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with the applicable standard and NFPA 70 for the following types: |
| 1. Communications, Plenum Rated: Type CMP complying with UL 1685 or Type CMP in listed plenum communications raceway or Type CMP in listed cable routing assembly. |
| B. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. |
| 1. Flame-Spread Index: 25 or less. |
| 2. Smoke-Developed Index: 50 or less. |
C. RoHS compliant.
| 2.3 CATEGORY 6 TWISTED PAIR CABLE |
| A. Description: Four-pair, balanced-twisted pair cable, certified to meet transmission characteristics of Category 6 cable at frequencies up to 250MHz. |
| B. 42TUManufacturers:U42T Subject to compliance with requirements, provide products by one of the following: |
| 1. Belden |
| 2. Berk-Tek |
| 3. Commscope |
| 4. Mohawk |
| 5. Panduit |
| 6. Systimax |
| 7. Surperior Essex |
| C. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568-C.2 for Category 6 cables. |
| D. Conductors: 100-ohm, 23 AWG solid copper. |
| E. Shielding/Screening: Unshielded twisted pairs (UTP). |
| F. Cable Rating: Plenum. |
| G. Jacket: Color as indicated thermoplastic. |
| 2.4 TWISTED PAIR CABLE HARDWARE |
| A. Description: Hardware designed to connect, splice, and terminate twisted pair copper communications cable. |
| B. 42TUManufacturers:U42T Subject to compliance with requirements, provide products by one of the following: |
| 1. Belden |
| 2. Ortronics |
| 3. Panduit |
| 4. Systimax |
| 5. Surperior Esses |
| C. General Requirements for Twisted Pair Cable Hardware: |
| 1. Comply with the performance requirements of Category 6. |
| 2. Comply with TIA-568-C.2, IDC type, with modules designed for punch-down caps or tools. |
| 3. Cables shall be terminated with connecting hardware of same category or higher. |
| D. Source Limitations: Obtain twisted pair cable hardware from single source from single manufacturer. |
| E. Connecting Blocks: |
| 1. 110-style IDC for Category 6. |
| 2. Provide blocks for the number of cables terminated on the block, plus 25 percent spare, integral with connector bodies, including plugs and jacks where indicated. |
| F. Cross-Connect: Modular array of connecting blocks arranged to terminate building cables and permit interconnection between cables. |
| 1. Number of Terminals per Field: One for each conductor in assigned cables. |
| G. Patch Panel: Modular panels housing numbered jack units with IDC-type connectors at each jack location for permanent termination of pair groups of installed cables. |
| 1. Features: |
| a. Universal T568A and T568B wiring labels. |
| b. Labeling areas adjacent to conductors. |
| c. Replaceable connectors. |
| d. 24 or 48 ports. |
| 2. Construction: 16-gauge steel and mountable on 34T19-inch34T44T (483 mm)44T equipment racks. |
| 3. Number of Jacks per Field: One for each four-pair cable indicated. |
| H. Patch Cords: Factory-made, four-pair cables terminated with an eight-position modular plug at each end are GFGI. |
| I. Plugs and Plug Assemblies: |
| 1. Male; eight position; color-coded modular telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable. |
| 2. Standard: Comply with TIA-568-C.2. |
| 3. Marked to indicate transmission performance. |
| J. Jacks and Jack Assemblies: |
| 1. Female; eight position; modular; fixed telecommunications connector designed for termination of a single four-pair, 100-ohm, unshielded or shielded twisted pair cable. |
| 2. Designed to snap-in to a patch panel or faceplate. |
| 3. Standard: Comply with TIA-568-C.2. |
| 4. Marked to indicate transmission performance. |
| K. Faceplate: |
| 1. Two, Four, Six port, vertical single gang faceplates designed to mount to double gang wall boxes with a single gang mud ring. |
| 2. Eight, Ten, Twelve port, vertical double gang faceplates designed to mount to double gang wall boxes. |
| 3. Plastic Faceplate: High-impact plastic. Coordinate color with Section 262726 "Wiring Devices." |
| 4. Metal Faceplate: Stainless steel, complying with requirements in Section 262726 "Wiring Devices." |
| 5. For use with snap-in jacks accommodating any combination of twisted pair, optical fiber, and coaxial work area cords. |
| a. Flush mounting jacks, positioning the cord at a 45-degree angle. |
| L. Legend: |
| 1. Machine printed, in the field, using adhesive-tape label. |
| 2. Snap-in, clear-label covers and machine-printed paper inserts. |
| 2.5 IDENTIFICATION PRODUCTS |
| A. Comply with TIA-606-B and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers. |
| 2.6 GROUNDING |
| A. Comply with requirements in Section 270526 "Grounding and Bonding for Communications Systems" for grounding conductors and connectors. |
| B. Comply with TIA-607-B. |
| 2.7 SOURCE QUALITY CONTROL |
| A. Testing Agency: Engage a qualified testing agency to evaluate cables. |
| B. Factory test cables on reels according to TIA-568-C.1. |
| C. Factory test twisted pair cables according to TIA-568-C.2. |
| D. Cable will be considered defective if it does not pass tests and inspections. |
| E. Prepare test and inspection reports. |
| PART 3 - EXECUTION |
| 3.1 WIRING METHODS |
| A. Wiring Method: Install cables in raceways and cable trays, except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces, attics, and gypsum board partitions where unenclosed wiring method may be used. Conceal racewa... |
| 1. Install plenum cable in environmental air spaces, including plenum ceilings. |
| 2. Comply with requirements for raceways and boxes specified in Section 270528 "Pathways for Communications Systems." |
| B. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible. |
| C. Wiring within Enclosures: Bundle, lace, and train cables within enclosures. Connect to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Provide and use lacing bars and distribution spools. Install co... |
| 3.2 INSTALLATION OF PATHWAYS |
| A. Comply with requirements for demarcation point, cabinets, and racks specified in Section 271100 "Communications Equipment Room Fittings." |
| B. Comply with Section 270528 "Pathways for Communications Systems." |
| C. Comply with Section 270529 "Hangers and Supports for Communications Systems." |
| D. Comply with Section 270536 "Cable Trays for Communications Systems." |
| E. Drawings indicate general arrangement of pathways and fittings. |
| 3.3 INSTALLATION OF TWISTED-PAIR HORIZONTAL CABLES |
| A. Comply with NECA 1 and NECA/BICSI 568. |
| B. General Requirements for Cabling: |
| 1. Comply with TIA-568-C.0, TIA-568-C.1, and TIA-568-C.2. |
| 2. Comply with BICSI's "Information Transport Systems Installation Methods Manual (ITSIMM), Ch. 5, "Copper Structured Cabling Systems," "Cable Termination Practices" Section. |
| 3. Install 110-style IDC termination hardware unless otherwise indicated. |
| 4. Do not untwist twisted pair cables more than 34T1/2 inch34T44T (12 mm)44T from the point of termination to maintain cable geometry. |
| 5. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels. |
| 6. Cables may not be spliced. Secure and support cables at intervals not exceeding 34T30 inches34T44T (760 mm)44T and not more than 34T6 inches34T44T (150 mm)44T from cabinets, boxes, fittings, outlets, racks, frames, and terminals. |
| 7. Install lacing bars to restrain cables, prevent straining connections, and prevent bending cables to smaller radii than minimums recommended by manufacturer. |
| 8. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI Information Transport Systems Installation Methods Manual , Ch. 5, "Copper Structured Ca... |
| 9. Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between termination, tap, or junction points. Remove and discard cable if damaged during installation, and replace it with new cable. |
| 10. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating. |
| 11. In the communications equipment room, install a 34T10-foot-34T44T (3-m-)44T long service loop on each end of cable. |
| 12. Pulling Cable: Comply with BICSI Information Transport Systems Installation Methods Manual, Ch. 5, "Copper Structured Cabling Systems," "Pulling and Installing Cable" Section. Monitor cable pull tensions. |
| C. Open-Cable Installation: |
| 1. Install cabling with horizontal and vertical cable guides in telecommunications spaces with terminating hardware and interconnection equipment. |
| 2. Suspend twisted pair cabling, not in a wireway or pathway, a minimum of 34T8 inches34T44T (200 mm)44T above ceilings by cable supports not more than 34T60 inches34T44T (1524 mm)44T apart. |
| 3. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. |
| D. Group connecting hardware for cables into separate logical fields. |
| E. Separation from EMI Sources: |
| 1. Comply with recommendations from BICSI's "Telecommunications Distribution Methods Manual" and TIA-569-D for separating unshielded copper communication cable from potential EMI sources, including electrical power lines and equipment. |
| 2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows: |
| a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 34T5 inches34T44T (127 mm)44T. |
| b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 34T12 inches34T44T (300 mm)44T. |
| c. Electrical Equipment Rating More Than 5 kVA: A minimum of 34T24 inches34T44T (600 mm)44T. |
| 3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows: |
| a. Electrical Equipment Rating Less Than 2 kVA: A minimum of 34T2-1/2 inches34T44T (64 mm)44T. |
| b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 34T6 inches34T44T (150 mm)44T. |
| c. Electrical Equipment Rating More Than 5 kVA: A minimum of 34T12 inches34T44T (300 mm)44T. |
| 4. Separation between communications cables in grounded metallic raceways, power lines, and electrical equipment located in grounded metallic conduits or enclosures shall be as follows: |
| a. Electrical Equipment Rating Less Than 2 kVA: No requirement. |
| b. Electrical Equipment Rating between 2 and 5 kVA: A minimum of 34T3 inches34T44T (76 mm)44T. |
| c. Electrical Equipment Rating More Than 5 kVA: A minimum of 34T6 inches34T44T (150 mm)44T. |
| 5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or HP and Larger: A minimum of 34T48 inches34T44T (1200 mm)44T. |
| 6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 34T5 inches34T44T (127 mm)44T. |
| 3.4 FIRESTOPPING |
| A. Comply with requirements in Section 078413 "Penetration Firestopping." |
| B. Comply with TIA-569-D, Annex A, "Firestopping." |
| C. Comply with "Firestopping Systems" Article in BISCI's "Telecommunications Distribution Methods Manual." |
| 3.5 GROUNDING |
| A. Install grounding according to the "Grounding, Bonding, and Electrical Protection" chapter in BICSI's "Telecommunications Distribution Methods Manual." |
| B. Comply with TIA-607-B and NECA/BICSI-607. |
| 3.6 IDENTIFICATION |
| A. Identify system components, wiring, and cabling complying with TIA-606-B. Comply with requirements for identification specified in Section 270553 "Identification for Communications Systems." |
| 1. Administration Class: Class 2. |
| 2. Color-code cross-connect fields and apply colors to voice and data service backboards, connections, covers, and labels. |
| B. Paint and label colors for equipment identification shall comply with TIA-606-B for Class 2 level of administration, including optional identification requirements of this standard. |
| C. Cable Schedule: Install in a prominent location in each equipment room and wiring closet. List incoming and outgoing cables and their designations, origins, and destinations. Protect with rigid frame and clear plastic cover. Furnish an electronic c... |
| D. Cabling Administration Drawings: Show building floor plans with cabling administration-point labeling. Identify labeling convention and show labels for telecommunications closets, terminal hardware and positions, horizontal cables, work areas and w... |
| E. Cable and Wire Identification: |
| 1. Label each cable within 34T4 inches34T44T (100 mm)44T of each termination and tap, where it is accessible in a cabinet or junction or outlet box, and elsewhere as indicated. |
| 2. Each wire connected to building-mounted devices is not required to be numbered at the device if wire color is consistent with associated wire connected and numbered within panel or cabinet. |
| 3. Exposed Cables and Cables in Cable Trays and Wire Troughs: Label each cable at intervals not exceeding 34T15 feet34T44T (4.5 m)44T. |
| 4. Label each terminal strip, and screw terminal in each cabinet, rack, or panel. |
| a. Individually number wiring conductors connected to terminal strips, and identify each cable or wiring group, extended from a panel or cabinet to a building-mounted device, with the name and number of a particular device. |
| b. Label each unit and field within distribution racks and frames. |
5. Identification within Connector Fields in Equipment Rooms and Wiring Closets: Label each connector and each discrete unit of cable-terminating and -connecting hardware. Where similar jacks and plugs are used for both voice and data communication ca...
| F. Labels shall be preprinted or computer-printed type, with a printing area and font color that contrast with cable jacket color but still comply with TIA-606-B requirements for the following: |