BID FINAL SUBMITTAL
03 APRIL 2017
ASSOCIATE CONSULTANTS LANDSCAPE
ARCHITECTURAL
INTERIORS
STRUCTURAL
MECHANICAL
PLUMBING
FIRE ALARM
FIRE SUPPRESSION
ELECTRICAL
501 North Broadway, St. Louis, Missouri 63102-2121
NATIONAL GUARD READINESS CENTER
WILMINGTON, NORTH CAROLINA
NATIONAL GUARD BUREAU
PROJECT NO: 85498371301
NORTH CAROLINA ARMY NATIONAL GUARD
CIVIL
TELECOMMUNICATIONS & SECURITY
CIVIL LANDSCAPE STRUCTURAL MECHANICAL / PLUMBING
Food Service Consultant:
FAASSEN & ASSOCIATES
8526 SUNFLOWER ROAD
CHARLOTTE, NC 28227 T. 704-536-9234
E-MAIL: HFAASSEN@CAROLINA.RR.COM
GENERAL /
ARCHITECTURAL /
INTERIORS
ELECTRICAL TELECOMMUNICATIONS
& SECURITY
EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSEEXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE
FIRE SUPPRESSION /
FIRE ALARM
EXPIRATION DATE OF THE LICENSE
VOLUME 2 OF 2
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
DRAWING INDEX
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h C a ro lin a A rm y N a ti o n a l G u a rd
F W
/N
C A
R N
G R e a d in e s s C e n te r_ A
R C
H V
.r v t
/1
/2
:5 :4
A
M
G-001bChecker
Author
Designer
GENERAL
DRAWING INDEX
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-401 ENLARGED FLOOR PLANS
A-402 ENLARGED FLOOR PLANS
A-403 ENLARGED STAIR PLANS AND SECTIONS
A-411 TOILET ACCESSORIES / TYPICAL MOUNTING HEIGHTS
A-412 INTERIOR ELEVATIONS
A-413 INTERIOR ELEVATIONS
A-414 INTERIOR ELEVATIONS
A-415 INTERIOR ELEVATIONS
A-416 INTERIOR ELEVATIONS
A-501 EXTERIOR WALL SECTIONS
A-502 EXTERIOR WALL SECTIONS
A-503 EXTERIOR WALL SECTIONS
A-504 EXTERIOR WALL SECTIONS
A-511 EXTERIOR DETAILS
A-512 EXTERIOR DETAILS
A-513 EXTERIOR DETAILS
A-531 EXTERIOR DETAILS
A-532 EXTERIOR DETAILS
A-533 EXTERIOR DETAILS
A-534 EXTERIOR DETAILS
A-541 PLAN DETAILS
A-542 PLAN DETAILS
A-551 INTERIOR DETAILS
A-552 INTERIOR DETAILS
A-553 INTERIOR DETAILS
A-554 INTERIOR DETAILS
A-555 INTERIOR DETAILS
A-556 INTERIOR DETAILS
A-557 INTERIOR DETAILS
A-601 ROOM FINISH SCHEDULE
A-603 DOOR SCHEDULE, TYPES, AND DETAILS
A-604 DOOR SCHEDULE
A-605 DOOR DETAILS
A-606 DOOR DETAILS
A-607 DOOR DETAILS
A-608 LOUVER TYPES AND DETAILS
A-610 WINDOW TYPES
A-701 PARTITION TYPES
A-702 PARTITION TYPES
A-703 PARTITION DETAILS
A-704 PARTITION DETAILS
A-711 FIRST FLOOR SIGNAGE PLAN
A-712 SECOND FLOOR SIGNAGE PLAN
A-713 SIGNAGE TYPES AND DETAILS
A-801 ABI PARTIAL PLANS
A-802 ABI PARTIAL EXTERIOR ELEVATIONS / SECTION
A-803 ABI FIRST FLOOR FINISH PLAN
A-804 ABI SECOND FLOOR FINISH PLAN
A-805 ABI DETAILS
INTERIORS
I-001 GENERAL NOTES AND FINISH LEGEND
I-101 FIRST FLOOR FURNITURE PLAN
I-102 SECOND FLOOR FURNITURE PLAN
I-103 ENLARGED FURNITURE PLANS
FOOD SERVICE EQUIPMENT
FS-1 FOOD SERVICE EQUIPMENT SHCEDULE AND LAYOUTS
FS-2 FOOD SERVICE EQUIPMENT DETAILS
GENERAL
G-001a DRAWING INDEX
G-002 GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
G-101 OVERALL LIFE SAFETY PLANS
G-102 PARTIAL FIRST FLOOR LIFE SAFETY PLAN AREA A
G-103 PARTIAL FIRST FLOOR LIFE SAFETY PLAN AREA B
G-104 PARTIAL SECOND FLOOR LIFE SAFETY PLAN AREA A
G-105 PARTIAL SECOND FLOOR LIFE SAFETY PLAN AREA B
G-120 ACCESSIBILITY REQUIREMENTS AND DETAILS
G-121 OVERALL ACCESSIBILITY PLANS
G-122 PARTIAL FIRST FLOOR ACCESSIBILITY PLAN AREA A
G-123 PARTIAL FIRST FLOOR ACCESSIBILITY PLAN AREA B
G-124 PARTIAL SECOND FLOOR ACCESSIBILITY PLAN AREA A
G-125 PARTIAL SECOND FLOOR ACCESSIBILITY PLAN AREA B
CIVIL
CS100 LOCATION MAP
CS101 DEMOLITION PLAN
CS200 LAYOUT PLAN
CS210 LAYOUT PLAN – ADDITIVE BID ITEMS
CS300 GRADING PLAN
CS310 GRADING PLAN – ADDITIVE BID ITEMS
CS400 UTILITY PLAN
CS401 UTILITY PLAN – ENLARGED PLAN
CS410 UTILITY PLAN – ADDITIVE BID ITEMS
CS500 STORMWATER PLAN
CS510 STORMWATER PLAN – ADDITIVE BID ITEMS
CS600 EROSION CONTROL PLAN
CS610 EROSION CONTROL PLAN – ADDITIVE BID ITEMS
CS700 SITE DETAILS
CS701 SITE DETAILS
CS702 SITE DETAILS
CS703 SITE DETAILS
CS704 WATER DETAILS
CS705 WATER DETAILS
CS706 SANITARY SEWER DETAILS
CS707 SANITARY SEWER DETAILS
CS708 SANITARY SEWER DETAILS
CS709 SANITARY SEWER DETAILS
CS710 STORM DRAINAGE DETAILS
CS711 STORM DRAINAGE DETAILS
LANDSCAPE
L100 LANDSCAPE PLAN – BASE BID
L110 LANDSCAPE PLAN – ABI
STRUCTURAL
S-001 GENERAL NOTES
S-002 GENERAL NOTES
S-101 OVERALL SECOND FLOOR/LOW ROOF FRAMING AND FOUNDATION
PLAN
S-102 PARTIAL FOUNDATION PLAN - AREA A
S-103 PARTIAL FOUNDATION PLAN - AREA B
S-104 PARTIAL SECOND FLOOR / LOW ROOF FRAMING PLAN - AREA A
S-105 PARTIAL SECOND FLOOR / LOW ROOF FRAMING PLAN - AREA B
S-121 OVERALL ROOF FRAMING PLAN
S-122 PARTIAL ROOF FRAMING PLAN - AREA A
S-123 PARTIAL ROOF FRAMING PLAN - AREA B
S-200 WALL ELEVATIONS KEY PLAN
S-201 WALL ELEVATIONS
S-202 WALL ELEVATIONS
S-203 WALL ELEVATIONS
S-204 WALL ELEVATIONS
S-205 WALL ELEVATIONS
S-206 WALL ELEVATIONS
S-207 WALL ELEVATIONS
S-501 TYPICAL DETAILS
S-502 TYPICAL DETAILS
S-503 TYPICAL DETAILS
S-504 TYPICAL DETAILS
S-510 SECTIONS AND DETAILS
S-520 SECTIONS AND DETAILS
S-521 SECTIONS AND DETAILS
S-522 SECTIONS AND DETAILS
S-523 SECTIONS AND DETAILS
S-801 ABI PARTIAL PLANS
ARCHITECTURAL
A-001 GENERAL NOTES
AD101 DEMOLITION PLAN
AD102 DEMOLITION REFERENCE DETAILS
A-101 OVERALL FLOOR PLANS
A-102a PARTIAL FIRST FLOOR PLAN - AREA A
A-102b PARTIAL FIRST FLOOR PLAN - AREA A
A-103a PARTIAL FIRST FLOOR PLAN - AREA B
A-103b PARTIAL FIRST FLOOR PLAN - AREA B
A-104a PARTIAL SECOND FLOOR PLAN - AREA A
A-104b PARTIAL SECOND FLOOR PLAN - AREA A
A-105a PARTIAL SECOND FLOOR PLAN - AREA B
A-105b PARTIAL SECOND FLOOR PLAN - AREA B
A-111 OVERALL REFLECTED CEILING PLAN
A-112 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA A
A-113 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA B
A-114 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - AREA A
A-115 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - AREA B
A-121 ROOF PLAN
A-201 OVERALL EXTERIOR ELEVATIONS
A-202 PARTIAL ELEVATIONS
A-203 PARTIAL ELEVATIONS
A-204 PARTIAL ELEVATIONS
E-401 ENLARGED PLANS
E-501 POWER AND LIGHTING DETAILS
E-502 DETAILS
E-601 ONE-LINE DIAGRAM
E-701 EQUIPMENT DATA SCHEDULE
E-702 SCHEDULES
E-703 PANELBOARD SCHEDULES
E-704 PANELBOARD SCHEDULES
E-705 PANELBOARD SCHEDULES
E-706 PANELBOARD SCHEDULES
E-801 PARTIAL FIRST FLOOR PLANS - ABI No. 2
TELECOMMUNICATIONS & SECURITY
T-001 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
TS100 TELECOMMUNICATIONS PARTIAL SITE PLAN
TS101 TELECOMMUNICATIONS PARTIAL SITE PLAN
T-101 OVERALL FLOOR PLANS
T-102 VOICE, DATA, PA & SECURITY PARTIAL FIRST FLOOR PLAN AREA A
T-103 VOICE, DATA, PA & SECURITY PARTIAL FIRST FLOOR PLAN AREA B
T-104 VOICE, DATA, PA & SECURITY PARTIAL SECOND FLOOR PLAN AREA A
T-105 VOICE, DATA, PA & SECURITY PARTIAL SECOND FLOOR PLAN AREA B
T-201 TELECOM RACK ELEVATION
T-202 TELECOM RACK ELEVATIONS CONT.
T-203 ANTENNA TOWER SECTION
T-401 TELECOM ROOM ENLARGED PLANS
T-501 TELECOM OUTLET DETAILS
T-502 TELECOM DETAILS
T-503 TELECOM SITE DETAILS
T-504 SECURITY DETAILS
T-601 TELECOM ONE-LINE DIAGRAMS
T-801 ABI No. 2 PARTIAL PLAN
GENERAL
G-001b DRAWING INDEX
FIRE SUPPRESSION
FX001 FIRE SUPPRESSION GENERAL NOTES, ABBREV., AND SYMBOLS
FX010 FIRE SUPPRESSION SITE PLAN
FX101 OVERALL REFLECTED CEILING PLANS
FX102 PARTIAL FIRST FLOOR FIRE SUPPRESION PLAN AREA A
FX103 PARTIAL FIRST FLOOR FIRE SUPPRESION PLAN AREA B
FX104 PARTIAL SECOND FLOOR FIRE SUPPRESION PLAN AREA A
FX105 PARTIAL SECOND FLOOR FIRE SUPPRESION PLAN AREA B
FX401 ENLARGED PLANS
FX501 DETAILS
FX601 SCHEDULES
FX801 PARTIAL FIRE SUPPRESSION PLANS - ABI No. 2
FIRE ALARM
FA001 GENERAL NOTES, ABBREV., AND SYMBOLS
FA010 FIRE ALARM SITE PLAN
FA101 OVERALL FLOOR PLANS
FA102 PARTIAL FIRST FLOOR FIRE ALARM PLAN AREA A
FA103 PARTIAL FIRST FLOOR FIRE ALARM PLAN AREA B
FA104 PARTIAL SECOND FLOOR FIRE ALARM PLAN AREA A
FA105 PARTIAL SECOND FLOOR FIRE ALARM PLAN AREA B
FA501 DETAILS
FA801 PARTIAL FIRE ALARM PLANS - ABI No. 2
PLUMBING
P-001 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS
P-010 PLUMBING SITE PLAN
P-101 OVERALL FLOOR PLANS
P-102 PARTIAL FIRST FLOOR PLUMBING PLAN AREA A
P-103 PARTIAL FIRST FLOOR PLUMBING PLAN AREA B
P-104 PARTIAL SECOND FLOOR PLUMBING PLAN AREA A
P-105 PARTIAL SECOND FLOOR PLUMBING PLAN AREA B
P-401 ENLARGED PLANS
P-402 ENLARGED PLANS
P-403 ENLARGED PLANS
P-501 DETAILS
P-502 DETAILS
P-601 SCHEDULES
P-801 PARTIAL FIRST FLOOR PLUMBING PLAN AREA B - ABI No. 2
P-802 ENLARGED PLAN - ABI No. 2
P-901 SANITARY ISOMETRICS
P-902 DOMESTIC WATER ISOMETRICS
MECHANICAL
M-001 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS
M-101 OVERALL FIRST & SECOND FLOOR PLAN OVERALL
MH102 PARTIAL FIRST FLOOR DUCTWORK PLAN - AREA A
MH103 PARTIAL FIRST FLOOR DUCTWORK PLAN - AREA B
MH104 PARTIAL SECOND FLOOR DUCTWORK PLAN - AREA A
MH105 PARTIAL SECOND FLOOR DUCTWORK PLAN - AREA B
MP106 PARTIAL FIRST FLOOR PIPING PLAN - AREA A
MP107 PARTIAL FIRST FLOOR PIPING PLAN - AREA B
MP108 PARTIAL SECOND FLOOR PIPING PLAN - AREA A
MP109 PARTIAL SECOND FLOOR PIPING PLAN - AREA B
M-301 SECTIONS
M-401 ENLARGED PLANS
M-501 DETAILS
M-502 DETAILS
M-601 SCHEDULES
M-701 VRF PIPING ONE LINE DIAGRAM
M-801 PARTIAL FIRST FLOOR PLAN - ABI No. 2
M-802 BAS NETWORK DIAGRAM
M-803 BAS CONTROL DIAGRAMS
M-804 BAS CONTROL DIAGRAMS
M-805 BAS CONTROL DIAGRAMS
M-806 BAS POINT FUNCTION SCHEDULE
ELECTRICAL
E-001 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
ES010 ELECTRICAL SITE PLAN
EP101 OVERALL POWER PLANS
EP102 PARTIAL FIRST FLOOR POWER PLAN AREA A
EP103 PARTIAL FIRST FLOOR POWER PLAN AREA B
EP104 PARTIAL SECOND FLOOR POWER PLAN AREA A
EP105 PARTIAL SECOND FLOOR POWER PLAN AREA B
EP112 PARTIAL FIRST FLOOR EQUIPMENT PLAN AREA A
EP113 PARTIAL FIRST FLOOR EQUIPMENT PLAN AREA B
EP114 PARTIAL SECOND FLOOR EQUIPMENT PLAN AREA A
EP115 PARTIAL SECOND FLOOR EQUIPMENT PLAN AREA B
EL101 OVERALL LIGHTING PLANS
EL102 PARTIAL FIRST FLOOR LIGHTING PLAN AREA A
EL103 PARTIAL FIRST FLOOR LIGHTING PLAN AREA B
EL104 PARTIAL SECOND FLOOR LIGHTING PLAN AREA A
EL105 PARTIAL SECOND FLOOR LIGHTING PLAN AREA B
LEGEND FIRE SUPPRESSION ABBREVIATIONS FIRE SUPPRESSION GENERAL NOTES
FIRE SUPPRESSION REFERENCES
F
OH
EH
F
NOT ALL SYMBOLS ARE USED
X
TC
ABBREVIATIONSYMBOL DESCRIPTION
FIRE MAIN
UNDERGROUND FIRE MAIN
PENDENT SPRINKLER
UPRIGHT SPRINKLER
UPRIGHT SPRINKLER WITH GUARD
PENDENT SPRINKLER WITH GUARD
HYDRAULIC REFERENCE NODE
1-HOUR FIRE-RATED BARRIER
CONCEALED SPRINKLER
HORIZONTAL SIDEWALL SPRINKLER
FLOW METER
FREE STANDING TEST HEADER
TEST HEADER
JOCKEY PUMP
FIRE PUMP
FLOOR CONTROL ASSEMBLY
FIRE VALVE CABINETFVC
BUTTERFLY VALVE WITH TAMPER
FIRE HOSE VALVE PRESSURE REGULATING TYPEFHV
FHV FIRE HOSE VALVE
FLOW SWITCHFS
EAB ELECTRIC ALARM BELL
FIRE PUMP TEST HEADER
FDC FIRE DEPARTMENT CONNECTION (WALL-MOUNTED)
INSPECTOR'S TEST CONNECTION
WET PIPE RISER
OUTSIDE SCREW AND YOKE GATE VALVE W/TAMPER SWITCH
PRESSURE REGULATING VALVE WITH TAMPER SWITCH
POST INDICATOR VALVE
PREACTION VALVE
DRY PIPE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
ANGLE VALVE
GLOBE VALVE
AV
GLV
CV
DPV
PRV
DIPV
PIV
PRV
OS&Y
SP
CAPPED PIPE/OUTLET
ECCENTRIC REDUCER
CONCENTRIC REDUCER
PIPE TURNING DOWN
PIPE TURNING UP
EXTRA HAZARD GROUP
ORDINARY HAZARD GROUP (X DENOTES ADDITION DESIGN CONSIDERATIONS)
F
AFF
AHJ
AVG
BFP
CFM
COTR
ELEV
FDC
FHV
FP
EOL
FPC
FVC
GALS
GPH
GPM
GV
JP
JPC
JOCKEY PUMP
GATE VALVE
GALLONS PER MINUTE
GALLONS PER HOUR
GALLONS
FIRE VALVE CABINET
FIRE PUMP CONTROLLER
FIRE PUMP
FIRE HOSE VALVE
END OF LINE RESISTOR
ELEVATION
CUBIC FEET PER MINUTE
AVERAGE
AUTHORITY HAVING JURISDICTION
DOUBLE CHECK BACKFLOW PREVENTER
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.
FIRE DEPARTMENT CONNECTION
WEATHER PROOFWP
UH
SQFT
SLC
NIC
NC
MIN
NP
PIV
PSIG
SOV
VLV
OS&Y
NAC
JOCKEY PUMP CONTROLLER
MINIMUM
NOTIFICATION APPLIANCE CIRCUIT
NOT PERMITTED
NONCOMBUSTIBLE
POST INDICATOR VALVE
NOT IN CONTRACT
OUTSIDE SCREW AND YOKE
POUNDS PER SQUARE INCH GAUGE
SIGNALING LINE CIRCUIT
SOLENOID VALVE
SQUARE FEET
UNIT HEATER
VALVE
ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
OH ORDINARY HAZARD
TYP TYPICAL
DOUBLE CHECK BACKFLOW PREVENTER
1. REFER TO FX101 FOR OVERALL FIRE PROTECTION FLOOR PLANS
2. REFER TO C2 / FX501 FOR SPRINKLER HEAD LOCATION DETAIL.
3. WHEN THE CONTRACTOR IS REQUIRED BY THE GOVERNMENT TO PROVIDE SPECIAL
INSPECTIONS AS PART OF THE WORK, THE CONTRACTOR SHALL RETAIN THIRD-PARTY
QUALITY ASSURANCE AGENCIES TO CONDUCT THE SPECIAL INSPECTIONS REQUIRED
BY THE IBC AND OR THE NORTH CAROLINA BUILDING CODE. THE INSPECTING AGENCY
SHALL PROVIDE REPORTS OF THE SPECIAL INSPECTIONS DIRECTLY TO THE
GOVERNMENT.
1. THE BUILDINGS SHALL BE FULLY SPRINKLERED. THE SYSTEMS SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH UFC 3-600-01, 2016 EDITION, NORTH CAROLINA BUILDING CODE, 2012 EDITION; NFPA 13, 2016 EDITION; SPECIFICATION SECTION 21 13 13 00.10. THE DESIGN IS BASED ON UFC 3-600-01, 2016 EDITION; NORTH CAROLINA FIRE PREVENTION CODE, 2012 EDITION AND THE REQUIREMENTS LISTED BELOW. THE MORE STRINGENT REQUIREMENTS OF UFC
3-600-01 SHALL APPLY.
2. VERIFY ALL LOCATIONS AND MEASUREMENTS AS CONDITIONS MAY VARY THROUGHOUT
CONSTRUCTION. ALL CHANGES FROM THE ORIGINAL DESIGN MUST BE APPROVED BY THE AHJ.
3. INSTALL TAMPER AND FLOW SWITCHES AS INDICATED ON CONTRACT DRAWINGS. CONNECTIONS
TO THE FIRE ALARM SIGNALING LINE SHALL BE MADE UNDER SPECIFICATION DIVISION 28.
4. DESIGN THE AUTOMATIC SPRINKLER SYSTEM BY MEANS OF HYDRAULIC CALCULATIONS IN
ACCORDANCE WITH NFPA 13 AND CONTRACT SPECIFICATION SECTION 21 13 13 REQUIREMENTS.
REFER TO WATER SUPPLY AND DESIGN REQUIREMENTS ON THIS SHEET FOR CLARIFICATION. THE
CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DESIGN OF THE SPRINKLER SYSTEM.
5. DRAWINGS INDICATE THE DESIGN INTENT. SHOP DRAWINGS ARE TO BE SUBMITTED TO INDICATE SPECIFIC PRODUCTS TO BE INSTALLED, HANGER DESIGN CRITERIA, ETC. IN ACCORDANCE WITH
NFPA 13, CHAPTER 22.
6. OBTAIN ALL REQUIRED PERMITS AND APPROVALS FROM THE AHJ PRIOR TO COMMENCING WORK.
7. SEISMIC DESIGN CATEGORY C. REFER TO STRUCTURAL DRAWING S-001 FOR DESIGN CRITERIA.
SEISMIC BRACING AND RESTRAINT OF BRANCH LINES SHALL BE DESIGNED AND INSTALLED FOR ALL SPRINKLER PIPING IN ACCORDANCE WITH NFPA 13 AND NFPA 13 ANNEX'S. BRANCH LINES ARE
REQUIRED TO BE RESTRAINED AGAINST EXCESSIVE MOVEMENT, BOTH VERTICALLY AND
LATERALLY (HORIZONTAL) PER NFPA 13 EARTHQUAKE BRACING.
8. PROVIDE UPRIGHT SPRINKLERS IN ROOMS WITH NO CEILINGS, AND CONCEALED TYPE
SPRINKLERS WITH COVERS IN SUSPENDED CEILINGS, GYPSUM CEILINGS AND SOFFITS.
COORDINATE COVER PLATE COLORS WITH ARCHITECT.
9. COORDINATE ALL FIRE PROTECTION, ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL
WORK WITH CEILING HEIGHTS AND ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR
COORDINATE FINAL LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.
10. CONDUCT OR ACQUIRE CURRENT WATER FLOW TEST DATA IN ACCORDANCE WITH NFPA 291 AND
AS ACCEPTABLE TO THE AHJ. PROVIDE HYDRAULIC CALCULATIONS UTILIZING THIS DATA TO
VERIFY SPRINKLER SYSTEM DESIGN CRITERIA AND PIPE SIZES IN ACCORDANCE WITH NFPA 13.
BASE HYDRAULIC CALCULATIONS ON RESULTS OF THE FLOW TEST AND OPERATION OF THE FIRE
PUMP. HYDRAULIC CALCULATIONS AND DRAWINGS TO INCLUDE DATA AND INDICATE PIPING
COMPLETELY TO WATER SUPPLY SOURCE.
11. NO SPRINKLER PIPING OR EQUIPMENT SHALL PASS THROUGH THE ENTRANCE FACILITIES (EF), TELECOM EQUIP. ROOMS (TER), AND TELECOM ROOMS (TR).
LH LIGHT HAZARD
X
2-HOUR FIRE-RATED BARRIER
CONCEALED SPRINKLER (PAINTED CUSTOM COLOR COVERPLATE)
CC
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :5
A
M
FX001JOT
APB
JMF
FIRE SUPPRESSION
GENERAL NOTES,
ABBREVIATIONS,
AND SYMBOLS
V
A
N
H
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
D
C
B
A
2 3 4 5
C p w w o r k i n g g b n a l e e a d
F
W
F
A
F
X d w g
A
M
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N
O
W I L M
I N
G T
O N
N
O R
H
R
O L I N
A
N A
T I O
N A
L
G
U A
R
E A
D I N
E S
S
C
E N
T E
R
N O
R T
H
C
A R
O L
I N
A
A
R M
Y
N
A T
I O
N A
L
G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY
FOR THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.
RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO
THIS PROJECT IS DISCLAIMED
REGISTRATION NUMBER:
N
NC Engineering Firm License No. F-0287
NC Architectural Firm No. 50757
PROPOSED READINESS
CENTER
I
N
F
A
N
T
Y
JOT
APB
JMF
FIRE SUPPRESSION
SITE PLAN
40'10' 20'5' 60'
1" = 20'
A1
FIRE SUPPRESSION SITE PLAN
1" = 20'
FX001
CONTROLLED WASTE HANDLING FACILITY SHALL BE PROTECTED WITH AN ORDINARY
WET-PIPE SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH APPLICABLE CODES
AND STANDARDS. INSTALL SUITABLE SPRINKLER SYSTEM FOR A CORROSIVE
ENVIRONMENT IN ACCORDANCE WITH UFC 3-600-01. REFER TO WET RISER DETAIL B4 /
FX501.
1. REFER TO FX001 FOR SYMBOLS AND ABBREVIATIONS.
KEYED NOTES
FIRE SUPPRESSION PLAN GENERAL NOTES
EH
CONTROLLED WASTE
HANDLING FACILITY
(ABI No. 1)
GENERAL PURPOSE
TRAINING BAY
(ABI No. 2)
FX010
FX102
A1
FX103
A1
2 3 4 5 6 7 8 9
G
J
E
L
C
H
F
D
B
12 13
K
7.25.5 5.8
FX801
A1
D.3
D.2
E.6
FX104
A1
FX105
A1
2 3 4 5 6 7 8 9
G
J
E
L
C
H
F
D
B
12 13
K
7.25.5 5.8
FX801
C1
D.3
D.2
E.6
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX101JOT
APB
JMF
FIRE SUPPRESSION
OVERALL
REFLECTED CEILING PLANS
1/16" = 1'-0"
8' 16' 32' 48'
1/16" = 1'-0"A1
OVERALL FIRST FLOOR FIRE SUPPRESSION PLAN
1/16" = 1'-0"C1
OVERALL SECOND FLOOR FIRE SUPPRESSION PLAN
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
3. REFER TO FX801 FOR ABI No. 2 FIRE SUPPRESSION PLANS.
FX001
FX001
OH
OHOH
OH
OH
OH
OH
OH
OH
OH
ELECTRICAL
CORRIDOR
FACILITY STORAGE
FACILITY STORAGE
FACILITY STORAGE
MULTIPURPOSE TRAINING ROOM
PHYSICAL FITNESS
UNHEATED STORAGE
141A
FIRE PUMP ROOM
MECHANICAL
STAIRS
CORRIDOR
158A
CLASSROOM
M A
T C
H L
IN
E
A
/ F X
2 3 4 5 61
G
J
E
L
C
5.5 5.8
MAIL PICK UP
MAIL ROOM
MAIL VESTIBULE
UNIT LOCKERS
147A
FX401
A1
UP TO
SECOND
FLOOR
RECYCLE STORAGE
UNIT LOCKERS
147B
UNIT STORAGE
UNIT LOCKERS
147C
UNHEATED STORAGE
141B
OH
OH
OH
110 111
OH
E.6
OH
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX102JOT
APB
JMF
FIRE SUPPRESSION
PARTIAL FIRST FLOOR
REFLECTED CEILING PLAN
AREA A
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FX101
A1
FIRST FLOOR FIRE SUPPRESSION PLAN AREA A
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
110 SPRINKLER HEADGUARDS SHALL BE PROVIDED WHERE SPRINKLER HEADS ARE INSTALLED
AT 7'-0" OR LESS AND/OR SUBJECT TO MECHANICAL DAMAGE.
111 SPRINKLER PROTECTION TO BE PROVIDED BELOW LOWEST STAIR LANDING.
KEYED NOTES
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OHOH
LEARNING CENTER
OFFICE
OFFICE
PHYSICAL FITNESS
TELECOM EQUIPMENT
CUSTODIAL
ELECTRICAL
MENS SHOWERS
150 WOMENS SHOWERS
VESTIBULE
VAULT
UNIT STORAGE
FAMILY READINESS
STAIRS
RECRUITING OFFICE
SEATING
RETENTION OFFICE
RETENTION OFFICE
TABLES AND CHAIRS STORAGE
DRY STORAGE
TOILET
SCULLERY
SERVERY
KITCHEN
MENS TOILET
WOMENS TOILET
VESTIBULE
OFFICE
HHC
OFFICE
LOBBY
CLASSROOM
CUSTODIAL
STORAGE
OH
STORAGE
M A
T C
H L
IN
E
A
/ F X
7 8 9
G
E
L
C
H
F
D
B
12 13
K
7.2
SUPPLY AFF
SUPPLY SGT
STORAGE
ELEVATOR
UP TO
SECOND
FLOOR
FROM SECOND
FLOOR
WELLNESS ROOM
CORRIDOR
158A
ABI No. 2 SCOPE
REFER TO FX800 SERIES FOR ADDITIONAL INFORMATION
110 111
ASSEMBLY HALL
D.3
D.2
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX103JOT
APB
JMF
FIRE SUPPRESSION
PARTIAL FIRST FLOOR
REFLECTED CEILING PLAN
AREA B
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FX101
A1
FIRST FLOOR FIRE SUPPRESSION PLAN AREA B
103 PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW ARMS VAULT CEILING ACCORDING TO
THE HAZARD CATEGORY INDICATED. REFER TO AR190-11 FOR PENETRATION/OPENING
REQUIREMENTS OF ARMS VAULT.
110 SPRINKLER HEADGUARDS SHALL BE PROVIDED WHERE SPRINKLER HEADS ARE INSTALLED
AT 7'-0" OR LESS AND/OR SUBJECT TO MECHANICAL DAMAGE.
111 SPRINKLER PROTECTION TO BE PROVIDED BELOW LOWEST STAIR LANDING.
KEYED NOTES
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
OH OH OH OH OH
S2 OFFICE
S2 OFFICE
S2 OFFICE
AUDITORIUM
AV
TA STORAGE
TA STORAGE
TA STORAGE
ELECTRICAL
PA STORAGE
EXAM
PHYSICIAN ASSISTANT
MEDICAL EXAM
S1 OFFICE
S1 OFFICE
S1 OFFICE
OPEN OFFICE
CHAP OFFICE
S4 OFFICE
S4 OFFICE
S6 OFFICE
S6 OFFICE
ADMINISTRATION
CURRENT OPERATIONS
CORRIDOR
M A
T C
H L
IN
E
A
/ F X
2 3 4 5 61
G
J
E
L
C
5.5 5.8
STAIRS
FROM FIRST
FLOOR
E.6
STORAGE
OH
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX104JOT
APB
JMF
FIRE SUPPRESSION
PARTIAL SECOND FLOOR
REFLECTED CEILING PLAN
AREA A
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FX101
A1
SECOND FLOOR FIRE SUPPRESSION PLAN AREA A
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
108 PROVIDE SECOND FLOOR CONTROL VALVE ASSEMBLY WITH TAMPER SWITCH.
OH OH
OH OH
OHOH
S3 OFFICE
BATTALION COMMAND
CMD SGT MJ OFF
X0 OFFICE
COMMAND CONFERENCE ROOM
STORAGE
STORAGE
CUSTODIAL
FACILITY STORAGE
ELECTRICAL
S3 OFFICE
PRINT ROOM
MENS TOILET
WOMENS TOILET
TELECOM EQUIPMENT
BREAK ROOM
O5 COMMANDER OFFICE
S3 OFFICE
S3 OFFICE
AO OFFICE
BREAK OUT ROOM
M A
T C
H L
IN
E
A
/ F X
7 8 9
G
E
L
C
H
F
D
B
12 13
K
7.2
STAIRS
ELEVATOR
CORRIDOR
FROM
FIRST
FLOOR
DOWN TO FIRST
FLOOR
ABI No. 2 SCOPE (SHOWN DASHED)
REFER TO FX800 SERIES FOR ADDITIONAL INFORMATION
D.3
D.2
CC CC CC CC
CCCCCCCC
CC CC CC
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX105JOT
APB
JMF
FIRE SUPPRESSION
PARTIAL SECOND FLOOR
REFLECTED CEILING PLAN
AREA B
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FX101
A1
SECOND FLOOR FIRE SUPPRESSION PLAN AREA B
105 FOR CONTINUATION REFER TO C1 / FX801.
109 CONCEALED NON-COMBUSTIBLE SPACE. SPRINKLER PROTECTION NOT REQUIRED.
112 CONCEALED SPRINKLER COVERPLATE LOCATED WITHIN LOBBY TO BE PAINTED CUSTOM
COLOR IN COORDINATION WITH ARCHITECT.
KEYED NOTES
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
OH
FIRE PUMP ROOM
6"SUPPLY TO WET SPRINKLER
SYSTEM SECOND FLOOR ZONE 26" TO FIRE PUMP
TEST HEADER
FIRE PUMP
500GPM AT 60PSI
JOCKEY
PUMP
6" TO FIRE DEPARTMENT
CONNECTION
6"SUPPLY TO WET SPRINKLER
SYSTEM FIRST FLOOR ZONE 1
NORMALLY CLOSED TEST
HEATER ISOLATION VALVE
6" TEE TO BYPASS
6" BUTTERFLY VALVE WITH
TAMPER SWITCH
6" CHECK VALVE
8" GATE VALVE WITH
TAMPER SWITCH
8"X6"X8" FLANGED TEE
TO BYPASS
8" ELBOW
6" BUTTERFLY
VALVE WITH
TAMPER SWITCH
6" CHECK VALVE
6" BUTTERFLY
VALVE WITH
TAMPER SWITCH
6" CHECK VALVE IN
RISER WITH BALL DRIP
FIRE PUMP
CONTROLLER/
TRANSFER SWITCH
JOCKEY PUMP
CONTROLLER
FLOW METER
/B1 FX501
/B3 FX501
SPRINKLER CABINET (REFER
TO C1 / FX501)
8" FIRE MAIN BELOW GRADE.
FOR CONTINUATION REFER
TO CIVIL DRAWING.
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :0
A
M
FX401JOT
APB
JMF
FIRE SUPPRESSION
ENLARGED PLANS
1/2" = 1'-0"
1' 2' 4' 6'
100 FIRE PUMP TEST HEADER
101 FIRE DEPARTMENT CONNECTION
104 BYPASS SHOWN OFFSET FOR CLARITY. REFER TO FIRE WATER SERVICE DETAIL B1 / FX501
FOR EXACT LAYOUT.
KEYED NOTES
FIRE SUPPRESSION PLAN GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
1/2" = 1'-0"
FX102
A1
ENLARGED FIRE PUMP ROOM PLAN
SPARE SPRINKLERS SHALL BE PROVIDED IN ACCORDANCE WITH
NFPA 13 AND SHALL BE PACKED IN A SUITABLE METAL OR PLASTIC
CABINET. SPARE SPRINKLERS SHALL BE REPRESENTATIVE OF, AND
IN PROPORTION TO, THE NUMBER OF EACH TYPE AND
TEMPERATURE RATING OF THE SPRINKLERS INSTALLED. AT LEAST
ONE WRENCH OF EACH TYPE REQUIRED SHALL BE PROVIDED.
NOTES:
LOCATE IN
FIRE PUMP
ROOM
EXTERIOR WALL
PROVIDE 2' x 2'
SPLASH BLOCK
1" GLOBE VALVE
1"
LOCATIONS SHALL BE
INDICATED ON SHOP
DRAWINGS
STAINLESS STEEL
PIPE THROUGH WALL
FINISHED GRADE
OR PAVEMENT
SMOOTH BORE 45° ELBOW
CORROSION RESISTANT,
PIPE TO EXTERIOR
NOTE:
LOCATE INSPECTORS TEST CONNECTIONS AT
THE MOST REMOTE PORTION OF THE SYSTEM
IN ACCORDANCE WITH NFPA 13.
M
A X
FLOOR
ESCUTCHEON AT
EXPOSED
LOCATIONS
SEALANT
BACKUP MATERIAL
PROVIDE UL APPROVED
FIRE STOPPING
SYSTEM
PIPE
3" RADIUS TOLERANCE (TYPICAL)
NOTE: SPRINKLERS SHALL BE POSITIONED AS SHOWN WITH A 3"
TOLERANCE. HOWEVER, SHOULD ANY PART OF THE TOLERANCE BE
USED, THEN ALL OF THE SPRINKLERS IN THE ROW SHALL BE OFFSET BY
THE SAME DISTANCE IN THE SAME DIRECTION.
SPRINKLER HEADS SHALL BE LOCATED ONLY AT
THESE LOCATIONS IN 2x4 AND 2x2 CEILING PANELS
1/4 1/4 1/4 1/4
/2
/2
1/2 1/2
/2
/2
SUPPLY (REFER
TO CIVIL DRAWING)
RESTRAINED JOINT
FLANGE AND
SPIGOT PIECE
BY SITE UTILITY
CONTRACTOR
BY FIRE PROTECTION
CONTRACTOR
ESCUTCHEON AT
EXPOSED LOCATIONS
TERMITE
PROTECTION
VERTICAL
RESTRAINED JOINT
HORIZONTAL
RESTRAINED JOINT
BUILDING
FLOOR
DUCTILE
IRON
SEALANT
THRUST
BLOCK
FOR CONTINUATION
REFER TO B3 / FX501
NORMALLY CLOSED TEST
HEADER ISOLATION VALVE
6" TO FIRE PUMP
TEST HEADER
PIPE STAND
(TYPICAL) CONTROL VALVE WITH
TAMPER SWITCH
CHECK VALVE
JOCKEY PUMP
CONTROL VALVE WITH
TAMPER SWITCH
6" PUMP BYPASS
6" BUTTERFLY VALVE
WITH TAMPER SWITCH
6" CHECK VALVE
6" BUTTERFLY VALVE
WITH TAMPER SWITCH
8"X6"X8"
FLANGED TEE
TO BYPASS
8" GATE VALVE WITH
TAMPER SWITCH
PRESSURE GAGE
(TYPICAL)
6" BUTTERFLY VALVE WITH
TAMPER SWITCH
6" CHECK VALVE
BUILDING
FLOOR
FOR CONTINUATION
REFER TO B1 / FX501
6" TO FIRE DEPARTMENT
CONNECTION
6" SUPPLY TO FIRST FLOOR
ZONE 2 WET SPRINKLER
SYSTEM
REFER TO A1 / FX102
6" SUPPLY TO SECOND FLOOR
ZONE 1 WET SPRINKLER
SYSTEM
REFER TO A1 / FX102
VANE-TYPE
WATERFLOW SWITCH
(TYPICAL
PRESSURE GAUGE
ASSEMBLY (TYPICAL
6" WET PIPE ALARM
CHECK VALVE (TYPICAL
6" BUTTERFLY VALVE
WITH TAMPER SWITCH
(TYPICAL)
PIPE STAND (TYPICAL
ROUTE DRAIN PIPING TO
BUILDING EXTERIOR
MAIN DRAIN FROM
RISERS (TYPICAL)
SUPPLY (REFER
TO CIVIL DRAWING)
RESTRAINED JOINT
BY SITE UTILITY
CONTRACTOR
BY FIRE PROTECTION
CONTRACTOR
ESCUTCHEON AT
EXPOSED LOCATIONS
TERMITE
PROTECTION
VERTICAL
RESTRAINED JOINT
HORIZONTAL
RESTRAINED JOINT
DUCTILE
IRON
SEALANT
THRUST
BLOCK
BUTTERFLY VALVE
WITH TAMPER SWITCH
SUPPLY TO
CONTROLLED WASTE
HANDLING FACILITY
WET SPRINKLER
SYSTEM
PRESSURE GAUGE
ASSEBLY
VANE-TYPE
WATERFLOW SWITCH
CHECK VALVE WITH
DRAIN PORT (TO DRAIN
TO EXTERIOR)
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :1
A
M
FX501JOT
APB
JMF
FIRE SUPPRESSION
DETAILS
NOT TO SCALEC1
SPRINKLER CABINET DETAIL
NOT TO SCALEC3
INSPECTOR'S TEST CONNECTION
NOT TO SCALEC4
TYPICAL PENETRATION FOR PIPE THRU FIRE RATED PARTITIONS
NOT TO SCALEC2
SPRINKLER HEAD MOUNTING DETAIL
NOT TO SCALEB1
FIRE WATER SERVICE DETAIL
NOT TO SCALEB3
FIRE PUMP ROOM RISER ELEVATION
NOT TO SCALEB4
CONTROLLED WASTE HANDLING FACILITY WET RISER DETAIL - ABI No. 1
FX401 FX401 FX010
FX401 FX001 FX501 FX501
OCCUPANCY
CLASSIFICATION
DESIGN DENSITY
(GPM / SQ. FT)
DESIGN AREA
(SQ. FT)
HOSE STREAM
ALLOWANCE (GPM)
DURATION
(MIN.)
LIGHT HAZARD 0.10 1500 250 60
ORDINARY HAZARD 0.20
ORDINARY HAZARD 1 0.20
2500 250 60
3250 250 60
COVERAGE PER SPRINKLER
(SQ. FT)
EXTRA HAZARD 0.30 2500 (OR ENTIRE
AREA)
500 90 100
SPRINKLER SYSTEM DESIGN CRITERIA
STATIC 70 psi
RESIDUAL 53 psi
FLOW 904 gpm
DATE 07/21/2015
FIRE HYDRANT FLOW TEST
1. FLOW TEST DATA WILL BE VOID WHEN NEW UTILITY
WORK IS COMPLETE.
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :1
A
M
FX601JOT
APB
JMF
FIRE SUPPRESSION
SCHEDULES
JOCKEY PUMP SCHEDULE
LOCATION
PUMP
DESIGNATION TYPE GPM
TOTAL HEAD
(psi) SUCTION DISCHARGE MOTOR HP RPM V PH HZ BASIS OF DESIGN
PUMP ROOM JP-1 VERTICAL IN-LINE 5 65 1 1/4" 1 1/4" 1.5 3500 480 3 60 PEERLESS PUMP COMPANY (GRUNDFOS)
FIRE PUMP SCHEDULE
LOCATION
PUMP
DESIGNATION TYPE GPM
TOTAL HEAD
(psi) SUCTION DISCHARGE MOTOR HP RPM V PH HZ BASIS OF DESIGN
PUMP ROOM FP-1 CENTRIFUGAL 500 60 6" 6" 30 1760 480 3 60 PEERLESS PUMP COMPANY
A
B
OH
GENERAL PURPOSE TRAINING BAYS
VESTIBULE
134 ASSEMBLY HALL
C
A
B
AREA: 2,500 SQ. FT.
DENSITY: 0.20 GPM/SQ. FT.
FLOW: 655 GPM
PRESSURE REQUIRED
AT BASE OF RISER: 49.5 PSI
HYDRAULIC DESIGN AREA
S1 S2 S3 S4 S5 S6
S7 S8 S9 S10
S11 S12
S18S17S16S15S14S13
S19 S20 S21 S22 S23 S24
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :1
A
M
FX801JOT
APB
JMF
FIRE SUPPRESSION
PARTIAL FLOOR PLANS
ABI No. 2
1/8" = 1'-0"
FX101
A1 FIRST FLOOR FIRE SUPPRESSION PLAN AREA B - ABI No. 2
FIRE SUPPRESSION GENERAL NOTES
1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.
2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO
FX001 FOR DESIGN CRITERIA.
1/8" = 1'-0"
FX101
C1 TRAINING BAY FIRE SUPPRESSION PLAN AREA B - ABI No. 2
CEILING-MOUNTED MASS NOTIFICATION STROBE (XX DENOTES CANDELA RATING)
CEILING-MOUNTED SPEAKER/STROBE (XX DENOTES CANDELA RATING)
WALL-MOUNTED SPEAKER/STROBE (XX DENOTES CANDELA RATING)
(WP DENOTES WEATHER PROOF DEVICE)
WALL-MOUNTED FIRE ALARM STROBE (XX DENOTES CANDELA RATING)
(WP DENOTES WEATHER PROOF DEVICE)
WALL-MOUNTED MASS NOTIFICATION STROBE (XX DENOTES CANDELA RATING)
(WP DENOTES WEATHER PROOF DEVICE)
WALL-MOUNTED SPEAKER
H/L
MM
P
CM
WP
FAMN
FSA
NAC
FATC
LOC
F
RAT
M
WP
M
SD
K
FIRE ALARM AND MASS NOTIFICATION GENERAL NOTESFIRE ALARM AND MASS NOTIFICATION LEGEND
NOT ALL SYMBOLS USED
FIRE ALARM BELL
RADIO ALARM TRANSMITTER
WALL-MOUNTED EXTERIOR WEATHERPROOF SPEAKER
FIRE SERVICE TELEPHONE
CONTROL MODULE
HI/LOW AIR PRESSURE SWITCH
PRESSURE SWITCH
MONITOR MODULE
SPRINKLER TAMPER SWITCH
SPRINKLER FLOW SWITCH
DUCT SMOKE DETECTOR
PHOTOELECTRIC SMOKE DETECTOR
(P,A INDICATES PREACTION SYSTEM DEVICE)
MANUAL PULL STATION
HEAT DETECTOR
LOCAL OPERATING CONSOLE
FIRE ALARM TERMINAL CABINET
NAC EXTENDER PANEL
FIRE ALARM SYSTEM ANNUNCIATOR
FIRE ALARM CONTROL PANEL, COMBINED WITH
MASS NOTIFICATION AUTONOMOUS CONTROL UNIT
AFF
AHJ
AVG
COTR
ELEV
EOL
FPC
MIN
NAC
NIC
NP
NC
SIM
SLC
SQFT
SP
TD
WP WEATHER PROOF
TRAVEL DISTANCE
SMOKE PARTITION
SQUARE FEET
SIGNALING LINE CIRCUIT
SIMILAR
NONCOMBUSTIBLE
NOT PERMITTED
NOT IN CONTRACT
NOTIFICATION APPLIANCE CIRCUIT
MINIMUM
FIRE PUMP CONTROLLER
END OF LINE RESISTOR
ELEVATION
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
AVERAGE
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
FIRE ALARM ABBREVIATIONS
CARBON MONOXIDE DETECTORCO
POLE-MOUNTED CONE TYPE EXTERIOR WEATHERPROOF SPEAKER
CIS COMMON INTELLIGIBILITY LEVEL
DOR
AFG ABOVE FINISHED GRADE
DESIGNER OF RECORD
SD SMOKE DAMPER
SMOKE DAMPER
EX EXPLOSION PROOF
FIRE DEPARTMENT KEY LOCK BOX
1. PROVIDE AND INSTALL A COMPLETE COMBINED ADDRESSABLE FIRE ALARM AND MASS NOTIFICATION SYSTEM THROUGHOUT THE FACILITY IN ACCORDANCE WITH NFPA 72 AND AS INDICATED. SYSTEM SHALL BE CONFIGURED
WITH CLASS B SIGNALING AND CLASS B NOTIFICATION APPLIANCE CIRCUITS.
2. DESIGN, INSTALL AND TEST THE FIRE ALARM/MASS NOTIFICATION SYSTEM IN ACCORDANCE WITH UFC 1-200-01, 20 JUNE 2016 EDITION; UFC 3-600-01, 8 AUGUST 2016 EDITION ; UFC 4-021-01 9 APRIL 2008 WITH CHANGE 1, JANUARY 2010; NORTH CAROLINA BUILDING CODE, 2012 EDITION; NORTH CAROLINA FIRE PREVENTION CODE, 2012 EDITION;
AND NFPA 72, 2016 EDITION.
3. FOR COMPLETE SYSTEM CONTROL, REFER TO FIRE ALARM LOGIC MATRIX ON FA502.
4. PERFORM ALL ACCEPTANCE AND OPERATIONAL TESTS IN ACCORDANCE WITH NFPA 72.
5. A "RECORD OF COMPLETION" PREPARED IN ACCORDANCE WITH NFPA 72, AND THE FIRE ALARM TEST REPORT TO
BE FILED WITH THE LOCAL FIRE MARSHAL'S OFFICE.
6. THE FLASH RATE OF VISIBLE NOTIFICATION APPLIANCES SHALL NOT EXCEED TWO FLASHES PER SECOND, NOR BE LESS THAN ONE FLASH EVERY SECOND, IN ACCORDANCE WITH NFPA 72. A MAXIMUM PULSE DURATION SHALL BE
0.2 SECONDS WITH A MAXIMUM DUTY CYCLE OF 40 PERCENT, IN ACCORDANCE WITH NFPA 72. VISIBLE NOTIFICATION APPLIANCES SHALL BE SPACED IN ACCORDANCE WITH NFPA 72 AND AS INDICATED.
7. THE SPRINKLER SYSTEM CONTROL VALVE TAMPER AND FLOW SWITCHES SHALL BE CONNECTED TO THE
SIGNALING LINE CIRCUITS. REFER TO FX DRAWINGS FOR LOCATIONS.
8. OBTAIN APPROVALS FROM THE LOCAL FIRE MARSHAL'S OFFICE PRIOR TO COMMENCING WORK. SUBMIT SHOP DRAWINGS TO THE AHJ FOR APPROVAL. WORK SHALL NOT COMMENCE UNTIL APPROVAL OF THE SHOP DRAWINGS IS RECEIVED FROM THE AHJ. FIRE ALARM SYSTEM SHOP DRAWINGS, AT A MINIMUM, SHALL INCLUDE THE
REQUIREMENTS OF NFPA 72, SECTION 4.5.1.1 AND A.4.5.1.1.
9. AUDIBLE FIRE ALARM SOUND LEVEL SHALL BE AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FEET ABOVE THE FLOOR IN THE OCCUPIABLE AREA, BUT NOT GREATER THAN 120 dBA AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE. PROVIDE ADEQUATE NOTIFICATION APPLIANCES
THROUGHOUT THE SPACE TO MEET NFPA 72 REQUIREMENTS.
10. THE CANDELA RATING INDICATED FOR MASS NOTIFICATION STROBES IS THE MINIMUM ACTUAL OUTPUT AFTER DERATING FOR THE AMBER LENS. AUDIBLE MASS NOTIFICATION REQUIREMENTS SHALL MEET THE CLARITY LEVELS
OF UFC 4-021-01. (0.8 CIS MINIMUM)
11. ANY PENETRATIONS MADE THROUGH FIRE RATED PARTITIONS SHALL BE FIRE STOPPED WITH A U.L. LISTED
SYSTEM. SUBMIT PENETRATION LOCATION TO THE ARCHITECT OF RECORD FOR APPROVAL.
12. SMOKE DETECTORS FOR AIR HANDLING UNITS WILL BE SUPPLIED BY THE FIRE ALARM CONTRACTOR AND INSTALLED DUCT DETECTORS ARE REQUIRED ON THE FOLLOWING AIR HANDLING UNITS (REFER TO MECHANICAL
PLANS FOR UNIT LOCATIONS):
• DOAS-1
13. PROVIDE MONITOR MODULES TO FIRE SMOKE DAMPERS AND DUCT SMOKE DETECTORS FOR THE FIRE ALARM
SYSTEM. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF THE DEVICES.
14. FOR MINIMUM MOUNTING HEIGHTS ABOVE FINISHED FLOOR REFER TO DETAILS.
15. COORDINATE ALL FIRE PROTECTION, ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL WORK WITH CEILING HEIGHTS, FURNITURE LAYOUT, AND ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR COORDINATE FINAL
LOCATIONS WITH ARCHITECT, AHJ, AND FIRE PROTECTION ENGINEER.
16. ALL TERMINATIONS SHALL BE AT A TERMINAL STRIP. ALL DEVICES SHALL HAVE SCREW TERMINALS. IDENTIFY ALL
CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS.
17. INSTALL ALL WIRING IN METALLIC CONDUIT. ALL SIGNALING LINE AND INITIATING DEVICE CIRCUITS SHALL BE
MINIMUM 16 GAUGE WIRE.
18. PAINT ALL FIRE ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED AREAS (I.E. ABOVE CEILINGS, MECHANICAL ROOMS, ETC. ). IN FINISHED AREAS, BOXES SHALL BE PAINTED TO MATCH THE ROOM FINISH, THE INSIDE COVER OF THE JUNCTION BOX SHALL BE IDENTIFIED AS "FIRE ALARM" AND THE CONDUIT SHALL HAVE PAINTED RED BANDS 3/4" WIDE AT 20 FOOT CENTERS AND AT EACH SIDE OF A FLOOR, WALL OR CEILING PENETRATION. PROVIDE TYPE THW OR XHHW FOR WIRING IN WET LOCATIONS. TYPE THWN/THHN INSULATED WIRE
IS NOT ACCEPTABLE FOR UNDERGROUND WIRING OF FIRE ALARM CIRCUITS .
19. PROVIDE AND INSTALL RED STROBE LIGHT AT A VISIBLE POINT ON THE TOP OF THE BUILDING FOR IDENTIFICATION
BY FIRST RESPONDERS.
MN
XX
XX
MN
XX
WP
XX
WP
XX
WP
F
WP
P
GRAPHIC ANNUNCIATOR PANELGAN
FACP FIRE ALARM CONTROL PANEL
T TEMPERATURE SENSOR
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :4
A
M
FA001JOT
APB
JMF
FIRE ALARM
GENERAL NOTES,
ABBREVIATIONS,
AND SYMBOLS
N
D
Y
H
D
Y
H
FLOOD ZONE: X
H
H
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
CONTROLLED
WASTE HANDLING
FACILITY (ABI No. 1)
GENERAL PURPOSE
TRAINING BAY
(ABI No. 2)
PROPOSED
READINESS
CENTER
I
N
F
A
N
T
D
C
B
A
2 3 4 5
C p w w o r k i n g g b n a l e e a d
F
W
F
A
F
X d w g
A
M
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
W I L M
I N
G T
O N
N
O R
R
O L I N
A
N A
T I O
N A
L
G
U A
A
D I N
E S
S
C
E N
T E
R
N O
R T
H
C
A R
O L
I N
A
A
R M
Y
N
A T
I O
N A
L
G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY
FOR THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.
RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO
THIS PROJECT IS DISCLAIMED
REGISTRATION NUMBER:
N
NC Engineering Firm License No. F-0287
NC Architectural Firm No. 50757
JOT
APB
JMF
FIRE ALARM
SITE PLAN
60'15' 30' 90'
1" = 30'
A1
FIRE ALARM SITE PLAN
1" = 30'
FA001
CONTROLLED WASTE HANDLING FACILITY SHALL BE PROVIDED WITH A MANUAL PULL
STATION AND OCCUPANT NOTIFICATION INSTALLED IN ACCORDANCE WITH APPLICABLE
CODES AND STANDARDS. ALL DEVICES SHALL MEET CLASS 1, DIVISION 1 CLASSIFICATION.
CONDUIT BELOW GRADE FOR FIRE ALARM WIRING BETWEEN READINESS CENTER AND
CONTROLLED WASTE HANDLING FACILITY. PROVIDE SURGE SUPPRESSORS FOR CONDUIT
AT EXTERIOR OF EACH BUILDING.
PROVIDE BACKFLOW PREVENTER VALVE TAMPER SWITCHES AND SITE POST INDICATOR
VALVE TAMPER SWITCH AND ASSOCIATED MONITORING MODULES
RED STROBE/FLASHING LIGHT MOUNTED IN VISIBLE LOCATION ON EXTERIOR OF BUILDING
AND USED AS INDICATOR FOR FIRE DEPARTMENT WHEN ALARM IS ACTIVATED.
COORDINATE FINAL LOCATION AND MOUNTING HEIGHT WITH ARCHITECT.
REFER TO CIVIL DRAWING FOR FIRE DEPARTMENT ACCESS REQUIREMENTS.
1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.
KEYED NOTES
FIRE ALARM PLAN GENERAL NOTES
MM
F
MM
T
MM
F
FA010
UP UP
DN
DN
FA102
A1
FA103
A1
2 3 4 5 6 7 8 9
G
J
E
L
C
A
H
F
D
B
12 13
K
7.25.5 5.8
FA801
A1
D.3
D.2
E.6
FA104
A1
FA105
A1
2 3 4 5 6 7 8 9
G
J
E
L
C
A
H
F
D
B
12 13
K
7.25.5 5.8
FA801
C1
D.3
D.2
E.6
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :4
A
M
FA101JOT
APB
JMF
FIRE ALARM
OVERALL
FLOOR PLANS
1/16" = 1'-0"A1
OVERALL FIRST FLOOR FIRE ALARM PLAN
1/16" = 1'-0"C1
OVERALL SECOND FLOOR FIRE ALARM PLAN
1/16" = 1'-0"
8' 16' 32' 48'
FIRE ALARM PLAN GENERAL NOTES
G-001
G-001
1. REFER TO FA801 FOR ABI No. 2 FIRE ALARM PLANS.
UP
60 60
45 45
75 45
P
MN MN MN
MN
MNMN
MN
MN MN
MN
MNMN
L O
C F
S A
W P
M
WP
M
W P
M
F F
F F
F F
F
M N
M N
MN
MN
MN
MN
MN
15P
LOC
FSA
F
M N
M N
K
ELECTRICAL
CORRIDOR
FACILITY STORAGE
FACILITY STORAGE
FACILITY STORAGE
MULTIPURPOSE TRAINING ROOM
UNIT LOCKERS
147A
UNHEATED STORAGE
141A
FIRE PUMP ROOM
MECHANICAL
STAIRS
MAIL ROOM
CORRIDOR
158A
CLASSROOM
M A
T C
H L
IN
E
A
/ F A
2 3 4 5 61
G
J
E
L
C
5.5 5.8
201 201
MAIL PICK UP
PHYSICAL FITNESS
148MAIL VESTIBULE
UNHEATED STORAGE
141B
UNIT LOCKERS
147B
UNIT LOCKERS
147C
RECYCLE STORAGE
MM
MM
MM
MM
MM
MM
MM
MM
MM
MM
M M
M M
T
CM
MM
UNIT STORAGE
E.6
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :4
A
M
FA102JOT
APB
JMF
FIRE ALARM
PARTIAL FIRST FLOOR
FLOOR PLAN
AREA A
1/8" = 1'-0"
FA101
A1
FIRST FLOOR FIRE ALARM PLAN AREA A
1/8" = 1'-0"
24'4' 8' 16'
200 PROVIDE FIRE ALARM BELL ON EXTERIOR WALL.
201 MOUNT FIRE ALARM DEVICE(S) TO UNDERSIDE OF JOIST.
203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S
REQUIREMENTS AND NFPA 72.
217 DUCT SMOKE DETECTOR. INSTALL ON SUPPLY SIDE OF DOAS-1 (REFER TO A1 /
M-401 FOR LOCATION). MOUNT DEVICE IN ACCORDANCE WITH
MANUFACTURER'S REQUIREMENTS AND NFPA 72.
1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.
FIRE ALARM PLAN GENERAL NOTES
P
MN
MN
MN MN
MN
MN
MN
MN MN
MN
K
W P
M
WP
M
WP
M
W P
M
G A
N F
A M
N F
F
FF
FF
MN
M N
M
N
M N
MN
MN
M N
MN
FSA
LOC
P
F
MN
CM
MM
MN
MN
MN
WP
M
MN
CM
CM
LEARNING CENTER
OFFICE
OFFICE
PHYSICAL FITNESS
TELECOM EQUIPMENT
CUSTODIAL
ELECTRICAL
MENS SHOWERS
WOMENS SHOWERS
VESTIBULE
VAULT
UNIT STORAGE
FAMILY READINESS
STAIRS
RECRUITING OFFICE
SEATING
RETENTION OFFICE
RETENTION OFFICE
STORAGE
TABLES AND CHAIRS STORAGE
DRY STORAGE
TOILET
SCULLERY
SERVERY
KITCHEN
STORAGE
MENS TOILET
WOMENS TOILET
VESTIBULE
OFFICE
HHC
OFFICE
LOBBY
CLASSROOM
CUSTODIAL
M A
T C
H L
IN
E
A
/ F A
7 8 9
G
E
L
C
H
F
D
B
12 13
K
7.2
SUPPLY AFF
SUPPLY SGT
STORAGE
ELEVATOR
WELLNESS ROOM
CORRIDOR
158A
ABI No. 2 SCOPE (SHOWN DASHED)
REFER TO FA800 SERIES FOR ADDITIONAL INFORMATION
CORRIDOR
158B
ASSEMBLY HALL
D.3
D.2
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :5
A
M
FA103JOT
APB
JMF
FIRE ALARM
PARTIAL FIRST FLOOR
FLOOR PLAN
AREA B
1/8" = 1'-0"
FA101
A1
FIRST FLOOR FIRE ALARM PLAN AREA B
1/8" = 1'-0"
24'4' 8' 16'
201 MOUNT FIRE ALARM DEVICE(S) TO UNDERSIDE OF JOIST.
202 NOTIFICATION DEVICES TO BE PROVIDED WITH PROTECTIVE CAGES.
203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND
NFPA 72.
215 INTERFACE CONTROL MODULE WITH PAGING SYSTEM.
216 PROVIDE MONITOR MODULE FOR KITCHEN HOOD.
221 CONTROL MODULE FOR DOOR HOLDER INTERFACE. REFER TO B1/FA501 FOR SEQUENCE
OF OPERATIONS.
222 FAMN AND GAN TO BE SEMI-RECESSED.
KEYED NOTES
1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.
F
MN
MN MN
30 30
M N
MN MN
MN
MN
MN
S2 OFFICE
S2 OFFICE
S2 OFFICE
AUDITORIUM
AV
TA STORAGE
TA STORAGE
TA STORAGE
ELECTRICAL
PA STORAGE
EXAM
PHYSICIAN ASSISTANT
MEDICAL EXAM
S1 OFFICE
S1 OFFICE
S1 OFFICE
OPEN OFFICE
CHAP OFFICE
S4 OFFICE
S4 OFFICE
S6 OFFICE
S6 OFFICE
ADMINISTRATION
CURRENT OPERATIONS
CORRIDOR
M A
T C
H L
IN
E
A
/ F A
2 3 4 5 61
G
J
E
L
C
5.5 5.8
STAIRS
MM
MM
E.6
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :5
A
M
FA104JOT
APB
JMF
FIRE ALARM
PARTIAL SECOND FLOOR
FLOOR PLAN
AREA A
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FA101
A1
SECOND FLOOR FIRE ALARM PLAN AREA A
1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.
P
MN
F
M
N
MNMN
MNMN
MN
MN
P
MN
LOC
NAC
P
S3 OFFICE
BATTALION COMMAND
CMD SGT MJ OFF
X0 OFFICE
COMMAND CONFERENCE ROOM
STORAGE
226STORAGE
CUSTODIAL
FACILITY STORAGE
ELECTRICAL
S3 OFFICE
PRINT ROOM
MENS TOILET
229 WOMENS TOILET
TELECOM EQUIPMENT
BREAK ROOM
O5 COMMANDER OFFICE
S3 OFFICE
S3 OFFICE
AO OFFICE
BREAK OUT ROOM
M A
T C
H L
IN
E
A
/ F A
7 8 9
G
E
L
C
H
F
D
B
12 13
K
147.2
ELEVATOR
CORRIDOR
STAIRS
CURRENT OPERATIONS
ABI No. 2 SCOPE (SHOWN DASHED)
REFER TO FA800 SERIES FOR ADDITIONAL INFORMATION
D.3
D.2
N
D
C
B
A
1 2 3 4 5
BID FINAL SUBMITTAL
Designed:
Drawn :
Checked:
Drawing No.:
Date:
Drawing Title:
Scales:
Key Plan:
P R
O J E
C T
N O
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
N A
T
IO
N A
L G
U A
R D
R E
A D
IN
E
S S
C E
N T
E R
N O
R T
H C
A R
O L
IN
A
A R
M Y
N A
T
IO
N A
L G
U A
R D
03 APRIL 2017
DATEREV DESCRIPTION
501 North Broadway, Saint Louis, Missouri 63102
DISCLAIMER
ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE
ONLY FOR THE PURPOSE OF AUTHENTICATING THIS
DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS
RELATING TO THIS PROJECT IS DISCLAIMED
NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757
B
IM
/U
S
N o rt h
C a ro lin a A rm y N a tio n a l G u a rd
F
W
/N C
A R
N G
R e a d in e s s C e n te r_
F
IR
E V
.r v t
/1
/2
:2 :5
A
M
FA105JOT
APB
JMF
FIRE ALARM
PARTIAL SECOND FLOOR
FLOOR PLAN
AREA B
1/8" = 1'-0"
24'4' 8' 16'
1/8" = 1'-0"
FA101
A1
SECOND FLOOR FIRE ALARM PLAN AREA B
1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.
KEYED NOTES
FIRE ALARM PLAN GENERAL NOTES
203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND
NFPA 72.
BUILDING ENVELOPE
CLASS "B" NOTIFICATION APPLIANCE CIRCUIT (TYP)
TS
MM
FS
MMMM CM
AHU…