NCARNG_RC_Bid_Final_Submittal_Drawings_Volume_2_20170619.pdf

PDF 17 MB Posted

Attached to
Wilmington Readiness Center
Solicitation number
W91242-17-B-0005
Issued by

About this file

Drawings Volume 2

View the file

Other files

File Type Posted
OF_1419-_Abstract_Wilmington_Armory.pdf PDF
Questions_and_Answers_165.pdf PDF
Questions_and_Answers_162-164.pdf PDF
W91242-17-B-0005-0005_Released.pdf PDF
262913.03_-_Manual_and_Magnetic_Motor_Controllers.pdf PDF
W91242-17-B-0005-0004_Released.pdf PDF
105613_fl_-_metal_storage_shelving.pdf PDF
Questions_and_Answers_135-161.pdf PDF
015000_fl_-_temporary_facilities_and_controls.pdf PDF
010000_fl-_general_requirements.pdf PDF
012300_fl_-_additive_bid_items_(abi).pdf PDF
NCARNG_WIlmington_Amendment_Drawings_20170824.pdf PDF
Questions_and_Answers_80-134.pdf PDF
W91242-17-B-0005-0003_Released.pdf PDF
083313_fl_-_coiling_counter_doors.doc.pdf PDF
MILCON_Erosion_Control_Letter_of_Approval.pdf PDF
271513_FL_-_Communications_Copper_Horizontal_Cabling.pdf PDF
W91242-17-B-0005-0002.pdf PDF
State_Stormwater_Management_Permit_No._SW8_140906.pdf PDF
084113_fl_-_aluminum-framed_entrances_and_storefronts.pdf PDF
NCARNG_Wilmington_RC_Addendum_1_Drawings_20170817_Part_1.pdf PDF
Questions_and_Answers_60-79.pdf PDF
NCARNG_Wilmington_RC_Addendum_1_Drawings_20170817_Part_3.pdf PDF
084413_fl_-_glazed_aluminum_curtain_walls.pdf PDF
083323_fl_-_overhead_coiling_doors.pdf PDF
133423.10_fl_-_fabricated_storage_building.pdf PDF
087100_-_door_hardware.pdf PDF
312000_FL_-_Earth_Moving.pdf PDF
114000_-_food_service_equipment.pdf PDF
NCARNG_Wilmington_RC_Addendum_1_Drawings_20170817_Part_2.pdf PDF
013300_fl_-_submittal_procedures.pdf PDF
Questions_and_Answers_41-59.pdf PDF
Questions_and_Answers_8-17-17.pdf PDF
Prebid_Attendance_Roster.pdf PDF
PreBidSlides_W91242-17-B-0005_a.ppt PPT presentation
NCARNG_RC_Bid_Final_Specs_Volume_2_20170707.pdf PDF
NCARNG_RC_Bid_Final_Specs_Volume_1_20170707.pdf PDF
NCARNG_RC_Bid_Final_Submittal_Drawings_Volume_1__20170619.pdf PDF
W91242-17-B-0005-0001_Released.pdf PDF
W91242-17-B-0005_Released.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BID FINAL SUBMITTAL

03 APRIL 2017

ASSOCIATE CONSULTANTS LANDSCAPE

ARCHITECTURAL

INTERIORS

STRUCTURAL

MECHANICAL

PLUMBING

FIRE ALARM

FIRE SUPPRESSION

ELECTRICAL

501 North Broadway, St. Louis, Missouri 63102-2121

NATIONAL GUARD READINESS CENTER

WILMINGTON, NORTH CAROLINA

NATIONAL GUARD BUREAU

PROJECT NO: 85498371301

NORTH CAROLINA ARMY NATIONAL GUARD

CIVIL

TELECOMMUNICATIONS & SECURITY

CIVIL LANDSCAPE STRUCTURAL MECHANICAL / PLUMBING

Food Service Consultant:

FAASSEN & ASSOCIATES

8526 SUNFLOWER ROAD

CHARLOTTE, NC 28227 T. 704-536-9234

E-MAIL: HFAASSEN@CAROLINA.RR.COM

GENERAL /

ARCHITECTURAL /

INTERIORS

ELECTRICAL TELECOMMUNICATIONS

& SECURITY

EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSEEXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE EXPIRATION DATE OF THE LICENSE

FIRE SUPPRESSION /

FIRE ALARM

EXPIRATION DATE OF THE LICENSE

VOLUME 2 OF 2

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

DRAWING INDEX

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h C a ro lin a A rm y N a ti o n a l G u a rd

F W

/N

C A

R N

G R e a d in e s s C e n te r_ A

R C

H V

.r v t

/1

/2

:5 :4

A

M

G-001bChecker

Author

Designer

GENERAL

DRAWING INDEX

A-301 BUILDING SECTIONS

A-302 BUILDING SECTIONS

A-401 ENLARGED FLOOR PLANS

A-402 ENLARGED FLOOR PLANS

A-403 ENLARGED STAIR PLANS AND SECTIONS

A-411 TOILET ACCESSORIES / TYPICAL MOUNTING HEIGHTS

A-412 INTERIOR ELEVATIONS

A-413 INTERIOR ELEVATIONS

A-414 INTERIOR ELEVATIONS

A-415 INTERIOR ELEVATIONS

A-416 INTERIOR ELEVATIONS

A-501 EXTERIOR WALL SECTIONS

A-502 EXTERIOR WALL SECTIONS

A-503 EXTERIOR WALL SECTIONS

A-504 EXTERIOR WALL SECTIONS

A-511 EXTERIOR DETAILS

A-512 EXTERIOR DETAILS

A-513 EXTERIOR DETAILS

A-531 EXTERIOR DETAILS

A-532 EXTERIOR DETAILS

A-533 EXTERIOR DETAILS

A-534 EXTERIOR DETAILS

A-541 PLAN DETAILS

A-542 PLAN DETAILS

A-551 INTERIOR DETAILS

A-552 INTERIOR DETAILS

A-553 INTERIOR DETAILS

A-554 INTERIOR DETAILS

A-555 INTERIOR DETAILS

A-556 INTERIOR DETAILS

A-557 INTERIOR DETAILS

A-601 ROOM FINISH SCHEDULE

A-603 DOOR SCHEDULE, TYPES, AND DETAILS

A-604 DOOR SCHEDULE

A-605 DOOR DETAILS

A-606 DOOR DETAILS

A-607 DOOR DETAILS

A-608 LOUVER TYPES AND DETAILS

A-610 WINDOW TYPES

A-701 PARTITION TYPES

A-702 PARTITION TYPES

A-703 PARTITION DETAILS

A-704 PARTITION DETAILS

A-711 FIRST FLOOR SIGNAGE PLAN

A-712 SECOND FLOOR SIGNAGE PLAN

A-713 SIGNAGE TYPES AND DETAILS

A-801 ABI PARTIAL PLANS

A-802 ABI PARTIAL EXTERIOR ELEVATIONS / SECTION

A-803 ABI FIRST FLOOR FINISH PLAN

A-804 ABI SECOND FLOOR FINISH PLAN

A-805 ABI DETAILS

INTERIORS

I-001 GENERAL NOTES AND FINISH LEGEND

I-101 FIRST FLOOR FURNITURE PLAN

I-102 SECOND FLOOR FURNITURE PLAN

I-103 ENLARGED FURNITURE PLANS

FOOD SERVICE EQUIPMENT

FS-1 FOOD SERVICE EQUIPMENT SHCEDULE AND LAYOUTS

FS-2 FOOD SERVICE EQUIPMENT DETAILS

GENERAL

G-001a DRAWING INDEX

G-002 GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS

G-101 OVERALL LIFE SAFETY PLANS

G-102 PARTIAL FIRST FLOOR LIFE SAFETY PLAN AREA A

G-103 PARTIAL FIRST FLOOR LIFE SAFETY PLAN AREA B

G-104 PARTIAL SECOND FLOOR LIFE SAFETY PLAN AREA A

G-105 PARTIAL SECOND FLOOR LIFE SAFETY PLAN AREA B

G-120 ACCESSIBILITY REQUIREMENTS AND DETAILS

G-121 OVERALL ACCESSIBILITY PLANS

G-122 PARTIAL FIRST FLOOR ACCESSIBILITY PLAN AREA A

G-123 PARTIAL FIRST FLOOR ACCESSIBILITY PLAN AREA B

G-124 PARTIAL SECOND FLOOR ACCESSIBILITY PLAN AREA A

G-125 PARTIAL SECOND FLOOR ACCESSIBILITY PLAN AREA B

CIVIL

CS100 LOCATION MAP

CS101 DEMOLITION PLAN

CS200 LAYOUT PLAN

CS210 LAYOUT PLAN – ADDITIVE BID ITEMS

CS300 GRADING PLAN

CS310 GRADING PLAN – ADDITIVE BID ITEMS

CS400 UTILITY PLAN

CS401 UTILITY PLAN – ENLARGED PLAN

CS410 UTILITY PLAN – ADDITIVE BID ITEMS

CS500 STORMWATER PLAN

CS510 STORMWATER PLAN – ADDITIVE BID ITEMS

CS600 EROSION CONTROL PLAN

CS610 EROSION CONTROL PLAN – ADDITIVE BID ITEMS

CS700 SITE DETAILS

CS701 SITE DETAILS

CS702 SITE DETAILS

CS703 SITE DETAILS

CS704 WATER DETAILS

CS705 WATER DETAILS

CS706 SANITARY SEWER DETAILS

CS707 SANITARY SEWER DETAILS

CS708 SANITARY SEWER DETAILS

CS709 SANITARY SEWER DETAILS

CS710 STORM DRAINAGE DETAILS

CS711 STORM DRAINAGE DETAILS

LANDSCAPE

L100 LANDSCAPE PLAN – BASE BID

L110 LANDSCAPE PLAN – ABI

STRUCTURAL

S-001 GENERAL NOTES

S-002 GENERAL NOTES

S-101 OVERALL SECOND FLOOR/LOW ROOF FRAMING AND FOUNDATION

PLAN

S-102 PARTIAL FOUNDATION PLAN - AREA A

S-103 PARTIAL FOUNDATION PLAN - AREA B

S-104 PARTIAL SECOND FLOOR / LOW ROOF FRAMING PLAN - AREA A

S-105 PARTIAL SECOND FLOOR / LOW ROOF FRAMING PLAN - AREA B

S-121 OVERALL ROOF FRAMING PLAN

S-122 PARTIAL ROOF FRAMING PLAN - AREA A

S-123 PARTIAL ROOF FRAMING PLAN - AREA B

S-200 WALL ELEVATIONS KEY PLAN

S-201 WALL ELEVATIONS

S-202 WALL ELEVATIONS

S-203 WALL ELEVATIONS

S-204 WALL ELEVATIONS

S-205 WALL ELEVATIONS

S-206 WALL ELEVATIONS

S-207 WALL ELEVATIONS

S-501 TYPICAL DETAILS

S-502 TYPICAL DETAILS

S-503 TYPICAL DETAILS

S-504 TYPICAL DETAILS

S-510 SECTIONS AND DETAILS

S-520 SECTIONS AND DETAILS

S-521 SECTIONS AND DETAILS

S-522 SECTIONS AND DETAILS

S-523 SECTIONS AND DETAILS

S-801 ABI PARTIAL PLANS

ARCHITECTURAL

A-001 GENERAL NOTES

AD101 DEMOLITION PLAN

AD102 DEMOLITION REFERENCE DETAILS

A-101 OVERALL FLOOR PLANS

A-102a PARTIAL FIRST FLOOR PLAN - AREA A

A-102b PARTIAL FIRST FLOOR PLAN - AREA A

A-103a PARTIAL FIRST FLOOR PLAN - AREA B

A-103b PARTIAL FIRST FLOOR PLAN - AREA B

A-104a PARTIAL SECOND FLOOR PLAN - AREA A

A-104b PARTIAL SECOND FLOOR PLAN - AREA A

A-105a PARTIAL SECOND FLOOR PLAN - AREA B

A-105b PARTIAL SECOND FLOOR PLAN - AREA B

A-111 OVERALL REFLECTED CEILING PLAN

A-112 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA A

A-113 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - AREA B

A-114 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - AREA A

A-115 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - AREA B

A-121 ROOF PLAN

A-201 OVERALL EXTERIOR ELEVATIONS

A-202 PARTIAL ELEVATIONS

A-203 PARTIAL ELEVATIONS

A-204 PARTIAL ELEVATIONS

E-401 ENLARGED PLANS

E-501 POWER AND LIGHTING DETAILS

E-502 DETAILS

E-601 ONE-LINE DIAGRAM

E-701 EQUIPMENT DATA SCHEDULE

E-702 SCHEDULES

E-703 PANELBOARD SCHEDULES

E-704 PANELBOARD SCHEDULES

E-705 PANELBOARD SCHEDULES

E-706 PANELBOARD SCHEDULES

E-801 PARTIAL FIRST FLOOR PLANS - ABI No. 2

TELECOMMUNICATIONS & SECURITY

T-001 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES

TS100 TELECOMMUNICATIONS PARTIAL SITE PLAN

TS101 TELECOMMUNICATIONS PARTIAL SITE PLAN

T-101 OVERALL FLOOR PLANS

T-102 VOICE, DATA, PA & SECURITY PARTIAL FIRST FLOOR PLAN AREA A

T-103 VOICE, DATA, PA & SECURITY PARTIAL FIRST FLOOR PLAN AREA B

T-104 VOICE, DATA, PA & SECURITY PARTIAL SECOND FLOOR PLAN AREA A

T-105 VOICE, DATA, PA & SECURITY PARTIAL SECOND FLOOR PLAN AREA B

T-201 TELECOM RACK ELEVATION

T-202 TELECOM RACK ELEVATIONS CONT.

T-203 ANTENNA TOWER SECTION

T-401 TELECOM ROOM ENLARGED PLANS

T-501 TELECOM OUTLET DETAILS

T-502 TELECOM DETAILS

T-503 TELECOM SITE DETAILS

T-504 SECURITY DETAILS

T-601 TELECOM ONE-LINE DIAGRAMS

T-801 ABI No. 2 PARTIAL PLAN

GENERAL

G-001b DRAWING INDEX

FIRE SUPPRESSION

FX001 FIRE SUPPRESSION GENERAL NOTES, ABBREV., AND SYMBOLS

FX010 FIRE SUPPRESSION SITE PLAN

FX101 OVERALL REFLECTED CEILING PLANS

FX102 PARTIAL FIRST FLOOR FIRE SUPPRESION PLAN AREA A

FX103 PARTIAL FIRST FLOOR FIRE SUPPRESION PLAN AREA B

FX104 PARTIAL SECOND FLOOR FIRE SUPPRESION PLAN AREA A

FX105 PARTIAL SECOND FLOOR FIRE SUPPRESION PLAN AREA B

FX401 ENLARGED PLANS

FX501 DETAILS

FX601 SCHEDULES

FX801 PARTIAL FIRE SUPPRESSION PLANS - ABI No. 2

FIRE ALARM

FA001 GENERAL NOTES, ABBREV., AND SYMBOLS

FA010 FIRE ALARM SITE PLAN

FA101 OVERALL FLOOR PLANS

FA102 PARTIAL FIRST FLOOR FIRE ALARM PLAN AREA A

FA103 PARTIAL FIRST FLOOR FIRE ALARM PLAN AREA B

FA104 PARTIAL SECOND FLOOR FIRE ALARM PLAN AREA A

FA105 PARTIAL SECOND FLOOR FIRE ALARM PLAN AREA B

FA501 DETAILS

FA801 PARTIAL FIRE ALARM PLANS - ABI No. 2

PLUMBING

P-001 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS

P-010 PLUMBING SITE PLAN

P-101 OVERALL FLOOR PLANS

P-102 PARTIAL FIRST FLOOR PLUMBING PLAN AREA A

P-103 PARTIAL FIRST FLOOR PLUMBING PLAN AREA B

P-104 PARTIAL SECOND FLOOR PLUMBING PLAN AREA A

P-105 PARTIAL SECOND FLOOR PLUMBING PLAN AREA B

P-401 ENLARGED PLANS

P-402 ENLARGED PLANS

P-403 ENLARGED PLANS

P-501 DETAILS

P-502 DETAILS

P-601 SCHEDULES

P-801 PARTIAL FIRST FLOOR PLUMBING PLAN AREA B - ABI No. 2

P-802 ENLARGED PLAN - ABI No. 2

P-901 SANITARY ISOMETRICS

P-902 DOMESTIC WATER ISOMETRICS

MECHANICAL

M-001 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS

M-101 OVERALL FIRST & SECOND FLOOR PLAN OVERALL

MH102 PARTIAL FIRST FLOOR DUCTWORK PLAN - AREA A

MH103 PARTIAL FIRST FLOOR DUCTWORK PLAN - AREA B

MH104 PARTIAL SECOND FLOOR DUCTWORK PLAN - AREA A

MH105 PARTIAL SECOND FLOOR DUCTWORK PLAN - AREA B

MP106 PARTIAL FIRST FLOOR PIPING PLAN - AREA A

MP107 PARTIAL FIRST FLOOR PIPING PLAN - AREA B

MP108 PARTIAL SECOND FLOOR PIPING PLAN - AREA A

MP109 PARTIAL SECOND FLOOR PIPING PLAN - AREA B

M-301 SECTIONS

M-401 ENLARGED PLANS

M-501 DETAILS

M-502 DETAILS

M-601 SCHEDULES

M-701 VRF PIPING ONE LINE DIAGRAM

M-801 PARTIAL FIRST FLOOR PLAN - ABI No. 2

M-802 BAS NETWORK DIAGRAM

M-803 BAS CONTROL DIAGRAMS

M-804 BAS CONTROL DIAGRAMS

M-805 BAS CONTROL DIAGRAMS

M-806 BAS POINT FUNCTION SCHEDULE

ELECTRICAL

E-001 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES

ES010 ELECTRICAL SITE PLAN

EP101 OVERALL POWER PLANS

EP102 PARTIAL FIRST FLOOR POWER PLAN AREA A

EP103 PARTIAL FIRST FLOOR POWER PLAN AREA B

EP104 PARTIAL SECOND FLOOR POWER PLAN AREA A

EP105 PARTIAL SECOND FLOOR POWER PLAN AREA B

EP112 PARTIAL FIRST FLOOR EQUIPMENT PLAN AREA A

EP113 PARTIAL FIRST FLOOR EQUIPMENT PLAN AREA B

EP114 PARTIAL SECOND FLOOR EQUIPMENT PLAN AREA A

EP115 PARTIAL SECOND FLOOR EQUIPMENT PLAN AREA B

EL101 OVERALL LIGHTING PLANS

EL102 PARTIAL FIRST FLOOR LIGHTING PLAN AREA A

EL103 PARTIAL FIRST FLOOR LIGHTING PLAN AREA B

EL104 PARTIAL SECOND FLOOR LIGHTING PLAN AREA A

EL105 PARTIAL SECOND FLOOR LIGHTING PLAN AREA B

LEGEND FIRE SUPPRESSION ABBREVIATIONS FIRE SUPPRESSION GENERAL NOTES

FIRE SUPPRESSION REFERENCES

F

OH

EH

F

NOT ALL SYMBOLS ARE USED

X

TC

ABBREVIATIONSYMBOL DESCRIPTION

FIRE MAIN

UNDERGROUND FIRE MAIN

PENDENT SPRINKLER

UPRIGHT SPRINKLER

UPRIGHT SPRINKLER WITH GUARD

PENDENT SPRINKLER WITH GUARD

HYDRAULIC REFERENCE NODE

1-HOUR FIRE-RATED BARRIER

CONCEALED SPRINKLER

HORIZONTAL SIDEWALL SPRINKLER

FLOW METER

FREE STANDING TEST HEADER

TEST HEADER

JOCKEY PUMP

FIRE PUMP

FLOOR CONTROL ASSEMBLY

FIRE VALVE CABINETFVC

BUTTERFLY VALVE WITH TAMPER

FIRE HOSE VALVE PRESSURE REGULATING TYPEFHV

FHV FIRE HOSE VALVE

FLOW SWITCHFS

EAB ELECTRIC ALARM BELL

FIRE PUMP TEST HEADER

FDC FIRE DEPARTMENT CONNECTION (WALL-MOUNTED)

INSPECTOR'S TEST CONNECTION

WET PIPE RISER

OUTSIDE SCREW AND YOKE GATE VALVE W/TAMPER SWITCH

PRESSURE REGULATING VALVE WITH TAMPER SWITCH

POST INDICATOR VALVE

PREACTION VALVE

DRY PIPE VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

ANGLE VALVE

GLOBE VALVE

AV

GLV

CV

DPV

PRV

DIPV

PIV

PRV

OS&Y

SP

CAPPED PIPE/OUTLET

ECCENTRIC REDUCER

CONCENTRIC REDUCER

PIPE TURNING DOWN

PIPE TURNING UP

EXTRA HAZARD GROUP

ORDINARY HAZARD GROUP (X DENOTES ADDITION DESIGN CONSIDERATIONS)

F

AFF

AHJ

AVG

BFP

CFM

COTR

ELEV

FDC

FHV

FP

EOL

FPC

FVC

GALS

GPH

GPM

GV

JP

JPC

JOCKEY PUMP

GATE VALVE

GALLONS PER MINUTE

GALLONS PER HOUR

GALLONS

FIRE VALVE CABINET

FIRE PUMP CONTROLLER

FIRE PUMP

FIRE HOSE VALVE

END OF LINE RESISTOR

ELEVATION

CUBIC FEET PER MINUTE

AVERAGE

AUTHORITY HAVING JURISDICTION

DOUBLE CHECK BACKFLOW PREVENTER

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.

FIRE DEPARTMENT CONNECTION

WEATHER PROOFWP

UH

SQFT

SLC

NIC

NC

MIN

NP

PIV

PSIG

SOV

VLV

OS&Y

NAC

JOCKEY PUMP CONTROLLER

MINIMUM

NOTIFICATION APPLIANCE CIRCUIT

NOT PERMITTED

NONCOMBUSTIBLE

POST INDICATOR VALVE

NOT IN CONTRACT

OUTSIDE SCREW AND YOKE

POUNDS PER SQUARE INCH GAUGE

SIGNALING LINE CIRCUIT

SOLENOID VALVE

SQUARE FEET

UNIT HEATER

VALVE

ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

OH ORDINARY HAZARD

TYP TYPICAL

DOUBLE CHECK BACKFLOW PREVENTER

1. REFER TO FX101 FOR OVERALL FIRE PROTECTION FLOOR PLANS

2. REFER TO C2 / FX501 FOR SPRINKLER HEAD LOCATION DETAIL.

3. WHEN THE CONTRACTOR IS REQUIRED BY THE GOVERNMENT TO PROVIDE SPECIAL

INSPECTIONS AS PART OF THE WORK, THE CONTRACTOR SHALL RETAIN THIRD-PARTY

QUALITY ASSURANCE AGENCIES TO CONDUCT THE SPECIAL INSPECTIONS REQUIRED

BY THE IBC AND OR THE NORTH CAROLINA BUILDING CODE. THE INSPECTING AGENCY

SHALL PROVIDE REPORTS OF THE SPECIAL INSPECTIONS DIRECTLY TO THE

GOVERNMENT.

1. THE BUILDINGS SHALL BE FULLY SPRINKLERED. THE SYSTEMS SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH UFC 3-600-01, 2016 EDITION, NORTH CAROLINA BUILDING CODE, 2012 EDITION; NFPA 13, 2016 EDITION; SPECIFICATION SECTION 21 13 13 00.10. THE DESIGN IS BASED ON UFC 3-600-01, 2016 EDITION; NORTH CAROLINA FIRE PREVENTION CODE, 2012 EDITION AND THE REQUIREMENTS LISTED BELOW. THE MORE STRINGENT REQUIREMENTS OF UFC

3-600-01 SHALL APPLY.

2. VERIFY ALL LOCATIONS AND MEASUREMENTS AS CONDITIONS MAY VARY THROUGHOUT

CONSTRUCTION. ALL CHANGES FROM THE ORIGINAL DESIGN MUST BE APPROVED BY THE AHJ.

3. INSTALL TAMPER AND FLOW SWITCHES AS INDICATED ON CONTRACT DRAWINGS. CONNECTIONS

TO THE FIRE ALARM SIGNALING LINE SHALL BE MADE UNDER SPECIFICATION DIVISION 28.

4. DESIGN THE AUTOMATIC SPRINKLER SYSTEM BY MEANS OF HYDRAULIC CALCULATIONS IN

ACCORDANCE WITH NFPA 13 AND CONTRACT SPECIFICATION SECTION 21 13 13 REQUIREMENTS.

REFER TO WATER SUPPLY AND DESIGN REQUIREMENTS ON THIS SHEET FOR CLARIFICATION. THE

CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DESIGN OF THE SPRINKLER SYSTEM.

5. DRAWINGS INDICATE THE DESIGN INTENT. SHOP DRAWINGS ARE TO BE SUBMITTED TO INDICATE SPECIFIC PRODUCTS TO BE INSTALLED, HANGER DESIGN CRITERIA, ETC. IN ACCORDANCE WITH

NFPA 13, CHAPTER 22.

6. OBTAIN ALL REQUIRED PERMITS AND APPROVALS FROM THE AHJ PRIOR TO COMMENCING WORK.

7. SEISMIC DESIGN CATEGORY C. REFER TO STRUCTURAL DRAWING S-001 FOR DESIGN CRITERIA.

SEISMIC BRACING AND RESTRAINT OF BRANCH LINES SHALL BE DESIGNED AND INSTALLED FOR ALL SPRINKLER PIPING IN ACCORDANCE WITH NFPA 13 AND NFPA 13 ANNEX'S. BRANCH LINES ARE

REQUIRED TO BE RESTRAINED AGAINST EXCESSIVE MOVEMENT, BOTH VERTICALLY AND

LATERALLY (HORIZONTAL) PER NFPA 13 EARTHQUAKE BRACING.

8. PROVIDE UPRIGHT SPRINKLERS IN ROOMS WITH NO CEILINGS, AND CONCEALED TYPE

SPRINKLERS WITH COVERS IN SUSPENDED CEILINGS, GYPSUM CEILINGS AND SOFFITS.

COORDINATE COVER PLATE COLORS WITH ARCHITECT.

9. COORDINATE ALL FIRE PROTECTION, ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL

WORK WITH CEILING HEIGHTS AND ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR

COORDINATE FINAL LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.

10. CONDUCT OR ACQUIRE CURRENT WATER FLOW TEST DATA IN ACCORDANCE WITH NFPA 291 AND

AS ACCEPTABLE TO THE AHJ. PROVIDE HYDRAULIC CALCULATIONS UTILIZING THIS DATA TO

VERIFY SPRINKLER SYSTEM DESIGN CRITERIA AND PIPE SIZES IN ACCORDANCE WITH NFPA 13.

BASE HYDRAULIC CALCULATIONS ON RESULTS OF THE FLOW TEST AND OPERATION OF THE FIRE

PUMP. HYDRAULIC CALCULATIONS AND DRAWINGS TO INCLUDE DATA AND INDICATE PIPING

COMPLETELY TO WATER SUPPLY SOURCE.

11. NO SPRINKLER PIPING OR EQUIPMENT SHALL PASS THROUGH THE ENTRANCE FACILITIES (EF), TELECOM EQUIP. ROOMS (TER), AND TELECOM ROOMS (TR).

LH LIGHT HAZARD

X

2-HOUR FIRE-RATED BARRIER

CONCEALED SPRINKLER (PAINTED CUSTOM COLOR COVERPLATE)

CC

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :5

A

M

FX001JOT

APB

JMF

FIRE SUPPRESSION

GENERAL NOTES,

ABBREVIATIONS,

AND SYMBOLS

V

A

N

H

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

D

C

B

A

2 3 4 5

C p w w o r k i n g g b n a l e e a d

F

W

F

A

F

X d w g

A

M

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N

O

W I L M

I N

G T

O N

N

O R

H

R

O L I N

A

N A

T I O

N A

L

G

U A

R

E A

D I N

E S

S

C

E N

T E

R

N O

R T

H

C

A R

O L

I N

A

A

R M

Y

N

A T

I O

N A

L

G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY

FOR THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.

RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO

THIS PROJECT IS DISCLAIMED

REGISTRATION NUMBER:

N

NC Engineering Firm License No. F-0287

NC Architectural Firm No. 50757

PROPOSED READINESS

CENTER

I

N

F

A

N

T

Y

JOT

APB

JMF

FIRE SUPPRESSION

SITE PLAN

40'10' 20'5' 60'

1" = 20'

A1

FIRE SUPPRESSION SITE PLAN

1" = 20'

FX001

CONTROLLED WASTE HANDLING FACILITY SHALL BE PROTECTED WITH AN ORDINARY

WET-PIPE SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH APPLICABLE CODES

AND STANDARDS. INSTALL SUITABLE SPRINKLER SYSTEM FOR A CORROSIVE

ENVIRONMENT IN ACCORDANCE WITH UFC 3-600-01. REFER TO WET RISER DETAIL B4 /

FX501.

1. REFER TO FX001 FOR SYMBOLS AND ABBREVIATIONS.

KEYED NOTES

FIRE SUPPRESSION PLAN GENERAL NOTES

EH

CONTROLLED WASTE

HANDLING FACILITY

(ABI No. 1)

GENERAL PURPOSE

TRAINING BAY

(ABI No. 2)

FX010

FX102

A1

FX103

A1

2 3 4 5 6 7 8 9

G

J

E

L

C

H

F

D

B

12 13

K

7.25.5 5.8

FX801

A1

D.3

D.2

E.6

FX104

A1

FX105

A1

2 3 4 5 6 7 8 9

G

J

E

L

C

H

F

D

B

12 13

K

7.25.5 5.8

FX801

C1

D.3

D.2

E.6

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX101JOT

APB

JMF

FIRE SUPPRESSION

OVERALL

REFLECTED CEILING PLANS

1/16" = 1'-0"

8' 16' 32' 48'

1/16" = 1'-0"A1

OVERALL FIRST FLOOR FIRE SUPPRESSION PLAN

1/16" = 1'-0"C1

OVERALL SECOND FLOOR FIRE SUPPRESSION PLAN

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

3. REFER TO FX801 FOR ABI No. 2 FIRE SUPPRESSION PLANS.

FX001

FX001

OH

OHOH

OH

OH

OH

OH

OH

OH

OH

ELECTRICAL

CORRIDOR

FACILITY STORAGE

FACILITY STORAGE

FACILITY STORAGE

MULTIPURPOSE TRAINING ROOM

PHYSICAL FITNESS

UNHEATED STORAGE

141A

FIRE PUMP ROOM

MECHANICAL

STAIRS

CORRIDOR

158A

CLASSROOM

M A

T C

H L

IN

E

A

/ F X

2 3 4 5 61

G

J

E

L

C

5.5 5.8

MAIL PICK UP

MAIL ROOM

MAIL VESTIBULE

UNIT LOCKERS

147A

FX401

A1

UP TO

SECOND

FLOOR

RECYCLE STORAGE

UNIT LOCKERS

147B

UNIT STORAGE

UNIT LOCKERS

147C

UNHEATED STORAGE

141B

OH

OH

OH

110 111

OH

E.6

OH

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX102JOT

APB

JMF

FIRE SUPPRESSION

PARTIAL FIRST FLOOR

REFLECTED CEILING PLAN

AREA A

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FX101

A1

FIRST FLOOR FIRE SUPPRESSION PLAN AREA A

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

110 SPRINKLER HEADGUARDS SHALL BE PROVIDED WHERE SPRINKLER HEADS ARE INSTALLED

AT 7'-0" OR LESS AND/OR SUBJECT TO MECHANICAL DAMAGE.

111 SPRINKLER PROTECTION TO BE PROVIDED BELOW LOWEST STAIR LANDING.

KEYED NOTES

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OHOH

LEARNING CENTER

OFFICE

OFFICE

PHYSICAL FITNESS

TELECOM EQUIPMENT

CUSTODIAL

ELECTRICAL

MENS SHOWERS

150 WOMENS SHOWERS

VESTIBULE

VAULT

UNIT STORAGE

FAMILY READINESS

STAIRS

RECRUITING OFFICE

SEATING

RETENTION OFFICE

RETENTION OFFICE

TABLES AND CHAIRS STORAGE

DRY STORAGE

TOILET

SCULLERY

SERVERY

KITCHEN

MENS TOILET

WOMENS TOILET

VESTIBULE

OFFICE

HHC

OFFICE

LOBBY

CLASSROOM

CUSTODIAL

STORAGE

OH

STORAGE

M A

T C

H L

IN

E

A

/ F X

7 8 9

G

E

L

C

H

F

D

B

12 13

K

7.2

SUPPLY AFF

SUPPLY SGT

STORAGE

ELEVATOR

UP TO

SECOND

FLOOR

FROM SECOND

FLOOR

WELLNESS ROOM

CORRIDOR

158A

ABI No. 2 SCOPE

REFER TO FX800 SERIES FOR ADDITIONAL INFORMATION

110 111

ASSEMBLY HALL

D.3

D.2

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX103JOT

APB

JMF

FIRE SUPPRESSION

PARTIAL FIRST FLOOR

REFLECTED CEILING PLAN

AREA B

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FX101

A1

FIRST FLOOR FIRE SUPPRESSION PLAN AREA B

103 PROVIDE SPRINKLER COVERAGE ABOVE AND BELOW ARMS VAULT CEILING ACCORDING TO

THE HAZARD CATEGORY INDICATED. REFER TO AR190-11 FOR PENETRATION/OPENING

REQUIREMENTS OF ARMS VAULT.

110 SPRINKLER HEADGUARDS SHALL BE PROVIDED WHERE SPRINKLER HEADS ARE INSTALLED

AT 7'-0" OR LESS AND/OR SUBJECT TO MECHANICAL DAMAGE.

111 SPRINKLER PROTECTION TO BE PROVIDED BELOW LOWEST STAIR LANDING.

KEYED NOTES

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

OH OH OH OH OH

S2 OFFICE

S2 OFFICE

S2 OFFICE

AUDITORIUM

AV

TA STORAGE

TA STORAGE

TA STORAGE

ELECTRICAL

PA STORAGE

EXAM

PHYSICIAN ASSISTANT

MEDICAL EXAM

S1 OFFICE

S1 OFFICE

S1 OFFICE

OPEN OFFICE

CHAP OFFICE

S4 OFFICE

S4 OFFICE

S6 OFFICE

S6 OFFICE

ADMINISTRATION

CURRENT OPERATIONS

CORRIDOR

M A

T C

H L

IN

E

A

/ F X

2 3 4 5 61

G

J

E

L

C

5.5 5.8

STAIRS

FROM FIRST

FLOOR

E.6

STORAGE

OH

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX104JOT

APB

JMF

FIRE SUPPRESSION

PARTIAL SECOND FLOOR

REFLECTED CEILING PLAN

AREA A

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FX101

A1

SECOND FLOOR FIRE SUPPRESSION PLAN AREA A

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

108 PROVIDE SECOND FLOOR CONTROL VALVE ASSEMBLY WITH TAMPER SWITCH.

OH OH

OH OH

OHOH

S3 OFFICE

BATTALION COMMAND

CMD SGT MJ OFF

X0 OFFICE

COMMAND CONFERENCE ROOM

STORAGE

STORAGE

CUSTODIAL

FACILITY STORAGE

ELECTRICAL

S3 OFFICE

PRINT ROOM

MENS TOILET

WOMENS TOILET

TELECOM EQUIPMENT

BREAK ROOM

O5 COMMANDER OFFICE

S3 OFFICE

S3 OFFICE

AO OFFICE

BREAK OUT ROOM

M A

T C

H L

IN

E

A

/ F X

7 8 9

G

E

L

C

H

F

D

B

12 13

K

7.2

STAIRS

ELEVATOR

CORRIDOR

FROM

FIRST

FLOOR

DOWN TO FIRST

FLOOR

ABI No. 2 SCOPE (SHOWN DASHED)

REFER TO FX800 SERIES FOR ADDITIONAL INFORMATION

D.3

D.2

CC CC CC CC

CCCCCCCC

CC CC CC

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX105JOT

APB

JMF

FIRE SUPPRESSION

PARTIAL SECOND FLOOR

REFLECTED CEILING PLAN

AREA B

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FX101

A1

SECOND FLOOR FIRE SUPPRESSION PLAN AREA B

105 FOR CONTINUATION REFER TO C1 / FX801.

109 CONCEALED NON-COMBUSTIBLE SPACE. SPRINKLER PROTECTION NOT REQUIRED.

112 CONCEALED SPRINKLER COVERPLATE LOCATED WITHIN LOBBY TO BE PAINTED CUSTOM

COLOR IN COORDINATION WITH ARCHITECT.

KEYED NOTES

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

OH

FIRE PUMP ROOM

6"SUPPLY TO WET SPRINKLER

SYSTEM SECOND FLOOR ZONE 26" TO FIRE PUMP

TEST HEADER

FIRE PUMP

500GPM AT 60PSI

JOCKEY

PUMP

6" TO FIRE DEPARTMENT

CONNECTION

6"SUPPLY TO WET SPRINKLER

SYSTEM FIRST FLOOR ZONE 1

NORMALLY CLOSED TEST

HEATER ISOLATION VALVE

6" TEE TO BYPASS

6" BUTTERFLY VALVE WITH

TAMPER SWITCH

6" CHECK VALVE

8" GATE VALVE WITH

TAMPER SWITCH

8"X6"X8" FLANGED TEE

TO BYPASS

8" ELBOW

6" BUTTERFLY

VALVE WITH

TAMPER SWITCH

6" CHECK VALVE

6" BUTTERFLY

VALVE WITH

TAMPER SWITCH

6" CHECK VALVE IN

RISER WITH BALL DRIP

FIRE PUMP

CONTROLLER/

TRANSFER SWITCH

JOCKEY PUMP

CONTROLLER

FLOW METER

/B1 FX501

/B3 FX501

SPRINKLER CABINET (REFER

TO C1 / FX501)

8" FIRE MAIN BELOW GRADE.

FOR CONTINUATION REFER

TO CIVIL DRAWING.

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :0

A

M

FX401JOT

APB

JMF

FIRE SUPPRESSION

ENLARGED PLANS

1/2" = 1'-0"

1' 2' 4' 6'

100 FIRE PUMP TEST HEADER

101 FIRE DEPARTMENT CONNECTION

104 BYPASS SHOWN OFFSET FOR CLARITY. REFER TO FIRE WATER SERVICE DETAIL B1 / FX501

FOR EXACT LAYOUT.

KEYED NOTES

FIRE SUPPRESSION PLAN GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

1/2" = 1'-0"

FX102

A1

ENLARGED FIRE PUMP ROOM PLAN

SPARE SPRINKLERS SHALL BE PROVIDED IN ACCORDANCE WITH

NFPA 13 AND SHALL BE PACKED IN A SUITABLE METAL OR PLASTIC

CABINET. SPARE SPRINKLERS SHALL BE REPRESENTATIVE OF, AND

IN PROPORTION TO, THE NUMBER OF EACH TYPE AND

TEMPERATURE RATING OF THE SPRINKLERS INSTALLED. AT LEAST

ONE WRENCH OF EACH TYPE REQUIRED SHALL BE PROVIDED.

NOTES:

LOCATE IN

FIRE PUMP

ROOM

EXTERIOR WALL

PROVIDE 2' x 2'

SPLASH BLOCK

1" GLOBE VALVE

1"

LOCATIONS SHALL BE

INDICATED ON SHOP

DRAWINGS

STAINLESS STEEL

PIPE THROUGH WALL

FINISHED GRADE

OR PAVEMENT

SMOOTH BORE 45° ELBOW

CORROSION RESISTANT,

PIPE TO EXTERIOR

NOTE:

LOCATE INSPECTORS TEST CONNECTIONS AT

THE MOST REMOTE PORTION OF THE SYSTEM

IN ACCORDANCE WITH NFPA 13.

M

A X

FLOOR

ESCUTCHEON AT

EXPOSED

LOCATIONS

SEALANT

BACKUP MATERIAL

PROVIDE UL APPROVED

FIRE STOPPING

SYSTEM

PIPE

3" RADIUS TOLERANCE (TYPICAL)

NOTE: SPRINKLERS SHALL BE POSITIONED AS SHOWN WITH A 3"

TOLERANCE. HOWEVER, SHOULD ANY PART OF THE TOLERANCE BE

USED, THEN ALL OF THE SPRINKLERS IN THE ROW SHALL BE OFFSET BY

THE SAME DISTANCE IN THE SAME DIRECTION.

SPRINKLER HEADS SHALL BE LOCATED ONLY AT

THESE LOCATIONS IN 2x4 AND 2x2 CEILING PANELS

1/4 1/4 1/4 1/4

/2

/2

1/2 1/2

/2

/2

SUPPLY (REFER

TO CIVIL DRAWING)

RESTRAINED JOINT

FLANGE AND

SPIGOT PIECE

BY SITE UTILITY

CONTRACTOR

BY FIRE PROTECTION

CONTRACTOR

ESCUTCHEON AT

EXPOSED LOCATIONS

TERMITE

PROTECTION

VERTICAL

RESTRAINED JOINT

HORIZONTAL

RESTRAINED JOINT

BUILDING

FLOOR

DUCTILE

IRON

SEALANT

THRUST

BLOCK

FOR CONTINUATION

REFER TO B3 / FX501

NORMALLY CLOSED TEST

HEADER ISOLATION VALVE

6" TO FIRE PUMP

TEST HEADER

PIPE STAND

(TYPICAL) CONTROL VALVE WITH

TAMPER SWITCH

CHECK VALVE

JOCKEY PUMP

CONTROL VALVE WITH

TAMPER SWITCH

6" PUMP BYPASS

6" BUTTERFLY VALVE

WITH TAMPER SWITCH

6" CHECK VALVE

6" BUTTERFLY VALVE

WITH TAMPER SWITCH

8"X6"X8"

FLANGED TEE

TO BYPASS

8" GATE VALVE WITH

TAMPER SWITCH

PRESSURE GAGE

(TYPICAL)

6" BUTTERFLY VALVE WITH

TAMPER SWITCH

6" CHECK VALVE

BUILDING

FLOOR

FOR CONTINUATION

REFER TO B1 / FX501

6" TO FIRE DEPARTMENT

CONNECTION

6" SUPPLY TO FIRST FLOOR

ZONE 2 WET SPRINKLER

SYSTEM

REFER TO A1 / FX102

6" SUPPLY TO SECOND FLOOR

ZONE 1 WET SPRINKLER

SYSTEM

REFER TO A1 / FX102

VANE-TYPE

WATERFLOW SWITCH

(TYPICAL

PRESSURE GAUGE

ASSEMBLY (TYPICAL

6" WET PIPE ALARM

CHECK VALVE (TYPICAL

6" BUTTERFLY VALVE

WITH TAMPER SWITCH

(TYPICAL)

PIPE STAND (TYPICAL

ROUTE DRAIN PIPING TO

BUILDING EXTERIOR

MAIN DRAIN FROM

RISERS (TYPICAL)

SUPPLY (REFER

TO CIVIL DRAWING)

RESTRAINED JOINT

BY SITE UTILITY

CONTRACTOR

BY FIRE PROTECTION

CONTRACTOR

ESCUTCHEON AT

EXPOSED LOCATIONS

TERMITE

PROTECTION

VERTICAL

RESTRAINED JOINT

HORIZONTAL

RESTRAINED JOINT

DUCTILE

IRON

SEALANT

THRUST

BLOCK

BUTTERFLY VALVE

WITH TAMPER SWITCH

SUPPLY TO

CONTROLLED WASTE

HANDLING FACILITY

WET SPRINKLER

SYSTEM

PRESSURE GAUGE

ASSEBLY

VANE-TYPE

WATERFLOW SWITCH

CHECK VALVE WITH

DRAIN PORT (TO DRAIN

TO EXTERIOR)

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :1

A

M

FX501JOT

APB

JMF

FIRE SUPPRESSION

DETAILS

NOT TO SCALEC1

SPRINKLER CABINET DETAIL

NOT TO SCALEC3

INSPECTOR'S TEST CONNECTION

NOT TO SCALEC4

TYPICAL PENETRATION FOR PIPE THRU FIRE RATED PARTITIONS

NOT TO SCALEC2

SPRINKLER HEAD MOUNTING DETAIL

NOT TO SCALEB1

FIRE WATER SERVICE DETAIL

NOT TO SCALEB3

FIRE PUMP ROOM RISER ELEVATION

NOT TO SCALEB4

CONTROLLED WASTE HANDLING FACILITY WET RISER DETAIL - ABI No. 1

FX401 FX401 FX010

FX401 FX001 FX501 FX501

OCCUPANCY

CLASSIFICATION

DESIGN DENSITY

(GPM / SQ. FT)

DESIGN AREA

(SQ. FT)

HOSE STREAM

ALLOWANCE (GPM)

DURATION

(MIN.)

LIGHT HAZARD 0.10 1500 250 60

ORDINARY HAZARD 0.20

ORDINARY HAZARD 1 0.20

2500 250 60

3250 250 60

COVERAGE PER SPRINKLER

(SQ. FT)

EXTRA HAZARD 0.30 2500 (OR ENTIRE

AREA)

500 90 100

SPRINKLER SYSTEM DESIGN CRITERIA

STATIC 70 psi

RESIDUAL 53 psi

FLOW 904 gpm

DATE 07/21/2015

FIRE HYDRANT FLOW TEST

1. FLOW TEST DATA WILL BE VOID WHEN NEW UTILITY

WORK IS COMPLETE.

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :1

A

M

FX601JOT

APB

JMF

FIRE SUPPRESSION

SCHEDULES

JOCKEY PUMP SCHEDULE

LOCATION

PUMP

DESIGNATION TYPE GPM

TOTAL HEAD

(psi) SUCTION DISCHARGE MOTOR HP RPM V PH HZ BASIS OF DESIGN

PUMP ROOM JP-1 VERTICAL IN-LINE 5 65 1 1/4" 1 1/4" 1.5 3500 480 3 60 PEERLESS PUMP COMPANY (GRUNDFOS)

FIRE PUMP SCHEDULE

LOCATION

PUMP

DESIGNATION TYPE GPM

TOTAL HEAD

(psi) SUCTION DISCHARGE MOTOR HP RPM V PH HZ BASIS OF DESIGN

PUMP ROOM FP-1 CENTRIFUGAL 500 60 6" 6" 30 1760 480 3 60 PEERLESS PUMP COMPANY

A

B

OH

GENERAL PURPOSE TRAINING BAYS

VESTIBULE

134 ASSEMBLY HALL

C

A

B

AREA: 2,500 SQ. FT.

DENSITY: 0.20 GPM/SQ. FT.

FLOW: 655 GPM

PRESSURE REQUIRED

AT BASE OF RISER: 49.5 PSI

HYDRAULIC DESIGN AREA

S1 S2 S3 S4 S5 S6

S7 S8 S9 S10

S11 S12

S18S17S16S15S14S13

S19 S20 S21 S22 S23 S24

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :1

A

M

FX801JOT

APB

JMF

FIRE SUPPRESSION

PARTIAL FLOOR PLANS

ABI No. 2

1/8" = 1'-0"

FX101

A1 FIRST FLOOR FIRE SUPPRESSION PLAN AREA B - ABI No. 2

FIRE SUPPRESSION GENERAL NOTES

1. REFER TO FX001 FOR FIRE SUPPRESSION GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL AREAS SHALL BE LIGHT HAZARD CATAGORY UNLESS OTHERWISE NOTED. REFER TO

FX001 FOR DESIGN CRITERIA.

1/8" = 1'-0"

FX101

C1 TRAINING BAY FIRE SUPPRESSION PLAN AREA B - ABI No. 2

CEILING-MOUNTED MASS NOTIFICATION STROBE (XX DENOTES CANDELA RATING)

CEILING-MOUNTED SPEAKER/STROBE (XX DENOTES CANDELA RATING)

WALL-MOUNTED SPEAKER/STROBE (XX DENOTES CANDELA RATING)

(WP DENOTES WEATHER PROOF DEVICE)

WALL-MOUNTED FIRE ALARM STROBE (XX DENOTES CANDELA RATING)

(WP DENOTES WEATHER PROOF DEVICE)

WALL-MOUNTED MASS NOTIFICATION STROBE (XX DENOTES CANDELA RATING)

(WP DENOTES WEATHER PROOF DEVICE)

WALL-MOUNTED SPEAKER

H/L

MM

P

CM

WP

FAMN

FSA

NAC

FATC

LOC

F

RAT

M

WP

M

SD

K

FIRE ALARM AND MASS NOTIFICATION GENERAL NOTESFIRE ALARM AND MASS NOTIFICATION LEGEND

NOT ALL SYMBOLS USED

FIRE ALARM BELL

RADIO ALARM TRANSMITTER

WALL-MOUNTED EXTERIOR WEATHERPROOF SPEAKER

FIRE SERVICE TELEPHONE

CONTROL MODULE

HI/LOW AIR PRESSURE SWITCH

PRESSURE SWITCH

MONITOR MODULE

SPRINKLER TAMPER SWITCH

SPRINKLER FLOW SWITCH

DUCT SMOKE DETECTOR

PHOTOELECTRIC SMOKE DETECTOR

(P,A INDICATES PREACTION SYSTEM DEVICE)

MANUAL PULL STATION

HEAT DETECTOR

LOCAL OPERATING CONSOLE

FIRE ALARM TERMINAL CABINET

NAC EXTENDER PANEL

FIRE ALARM SYSTEM ANNUNCIATOR

FIRE ALARM CONTROL PANEL, COMBINED WITH

MASS NOTIFICATION AUTONOMOUS CONTROL UNIT

AFF

AHJ

AVG

COTR

ELEV

EOL

FPC

MIN

NAC

NIC

NP

NC

SIM

SLC

SQFT

SP

TD

WP WEATHER PROOF

TRAVEL DISTANCE

SMOKE PARTITION

SQUARE FEET

SIGNALING LINE CIRCUIT

SIMILAR

NONCOMBUSTIBLE

NOT PERMITTED

NOT IN CONTRACT

NOTIFICATION APPLIANCE CIRCUIT

MINIMUM

FIRE PUMP CONTROLLER

END OF LINE RESISTOR

ELEVATION

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

AVERAGE

ABOVE FINISHED FLOOR

AUTHORITY HAVING JURISDICTION

FIRE ALARM ABBREVIATIONS

CARBON MONOXIDE DETECTORCO

POLE-MOUNTED CONE TYPE EXTERIOR WEATHERPROOF SPEAKER

CIS COMMON INTELLIGIBILITY LEVEL

DOR

AFG ABOVE FINISHED GRADE

DESIGNER OF RECORD

SD SMOKE DAMPER

SMOKE DAMPER

EX EXPLOSION PROOF

FIRE DEPARTMENT KEY LOCK BOX

1. PROVIDE AND INSTALL A COMPLETE COMBINED ADDRESSABLE FIRE ALARM AND MASS NOTIFICATION SYSTEM THROUGHOUT THE FACILITY IN ACCORDANCE WITH NFPA 72 AND AS INDICATED. SYSTEM SHALL BE CONFIGURED

WITH CLASS B SIGNALING AND CLASS B NOTIFICATION APPLIANCE CIRCUITS.

2. DESIGN, INSTALL AND TEST THE FIRE ALARM/MASS NOTIFICATION SYSTEM IN ACCORDANCE WITH UFC 1-200-01, 20 JUNE 2016 EDITION; UFC 3-600-01, 8 AUGUST 2016 EDITION ; UFC 4-021-01 9 APRIL 2008 WITH CHANGE 1, JANUARY 2010; NORTH CAROLINA BUILDING CODE, 2012 EDITION; NORTH CAROLINA FIRE PREVENTION CODE, 2012 EDITION;

AND NFPA 72, 2016 EDITION.

3. FOR COMPLETE SYSTEM CONTROL, REFER TO FIRE ALARM LOGIC MATRIX ON FA502.

4. PERFORM ALL ACCEPTANCE AND OPERATIONAL TESTS IN ACCORDANCE WITH NFPA 72.

5. A "RECORD OF COMPLETION" PREPARED IN ACCORDANCE WITH NFPA 72, AND THE FIRE ALARM TEST REPORT TO

BE FILED WITH THE LOCAL FIRE MARSHAL'S OFFICE.

6. THE FLASH RATE OF VISIBLE NOTIFICATION APPLIANCES SHALL NOT EXCEED TWO FLASHES PER SECOND, NOR BE LESS THAN ONE FLASH EVERY SECOND, IN ACCORDANCE WITH NFPA 72. A MAXIMUM PULSE DURATION SHALL BE

0.2 SECONDS WITH A MAXIMUM DUTY CYCLE OF 40 PERCENT, IN ACCORDANCE WITH NFPA 72. VISIBLE NOTIFICATION APPLIANCES SHALL BE SPACED IN ACCORDANCE WITH NFPA 72 AND AS INDICATED.

7. THE SPRINKLER SYSTEM CONTROL VALVE TAMPER AND FLOW SWITCHES SHALL BE CONNECTED TO THE

SIGNALING LINE CIRCUITS. REFER TO FX DRAWINGS FOR LOCATIONS.

8. OBTAIN APPROVALS FROM THE LOCAL FIRE MARSHAL'S OFFICE PRIOR TO COMMENCING WORK. SUBMIT SHOP DRAWINGS TO THE AHJ FOR APPROVAL. WORK SHALL NOT COMMENCE UNTIL APPROVAL OF THE SHOP DRAWINGS IS RECEIVED FROM THE AHJ. FIRE ALARM SYSTEM SHOP DRAWINGS, AT A MINIMUM, SHALL INCLUDE THE

REQUIREMENTS OF NFPA 72, SECTION 4.5.1.1 AND A.4.5.1.1.

9. AUDIBLE FIRE ALARM SOUND LEVEL SHALL BE AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER, MEASURED 5 FEET ABOVE THE FLOOR IN THE OCCUPIABLE AREA, BUT NOT GREATER THAN 120 dBA AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE. PROVIDE ADEQUATE NOTIFICATION APPLIANCES

THROUGHOUT THE SPACE TO MEET NFPA 72 REQUIREMENTS.

10. THE CANDELA RATING INDICATED FOR MASS NOTIFICATION STROBES IS THE MINIMUM ACTUAL OUTPUT AFTER DERATING FOR THE AMBER LENS. AUDIBLE MASS NOTIFICATION REQUIREMENTS SHALL MEET THE CLARITY LEVELS

OF UFC 4-021-01. (0.8 CIS MINIMUM)

11. ANY PENETRATIONS MADE THROUGH FIRE RATED PARTITIONS SHALL BE FIRE STOPPED WITH A U.L. LISTED

SYSTEM. SUBMIT PENETRATION LOCATION TO THE ARCHITECT OF RECORD FOR APPROVAL.

12. SMOKE DETECTORS FOR AIR HANDLING UNITS WILL BE SUPPLIED BY THE FIRE ALARM CONTRACTOR AND INSTALLED DUCT DETECTORS ARE REQUIRED ON THE FOLLOWING AIR HANDLING UNITS (REFER TO MECHANICAL

PLANS FOR UNIT LOCATIONS):

• DOAS-1

13. PROVIDE MONITOR MODULES TO FIRE SMOKE DAMPERS AND DUCT SMOKE DETECTORS FOR THE FIRE ALARM

SYSTEM. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF THE DEVICES.

14. FOR MINIMUM MOUNTING HEIGHTS ABOVE FINISHED FLOOR REFER TO DETAILS.

15. COORDINATE ALL FIRE PROTECTION, ELECTRICAL, PLUMBING, MECHANICAL, AND STRUCTURAL WORK WITH CEILING HEIGHTS, FURNITURE LAYOUT, AND ARCHITECTURAL WORK. WHERE CONFLICTS OCCUR COORDINATE FINAL

LOCATIONS WITH ARCHITECT, AHJ, AND FIRE PROTECTION ENGINEER.

16. ALL TERMINATIONS SHALL BE AT A TERMINAL STRIP. ALL DEVICES SHALL HAVE SCREW TERMINALS. IDENTIFY ALL

CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS.

17. INSTALL ALL WIRING IN METALLIC CONDUIT. ALL SIGNALING LINE AND INITIATING DEVICE CIRCUITS SHALL BE

MINIMUM 16 GAUGE WIRE.

18. PAINT ALL FIRE ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED AREAS (I.E. ABOVE CEILINGS, MECHANICAL ROOMS, ETC. ). IN FINISHED AREAS, BOXES SHALL BE PAINTED TO MATCH THE ROOM FINISH, THE INSIDE COVER OF THE JUNCTION BOX SHALL BE IDENTIFIED AS "FIRE ALARM" AND THE CONDUIT SHALL HAVE PAINTED RED BANDS 3/4" WIDE AT 20 FOOT CENTERS AND AT EACH SIDE OF A FLOOR, WALL OR CEILING PENETRATION. PROVIDE TYPE THW OR XHHW FOR WIRING IN WET LOCATIONS. TYPE THWN/THHN INSULATED WIRE

IS NOT ACCEPTABLE FOR UNDERGROUND WIRING OF FIRE ALARM CIRCUITS .

19. PROVIDE AND INSTALL RED STROBE LIGHT AT A VISIBLE POINT ON THE TOP OF THE BUILDING FOR IDENTIFICATION

BY FIRST RESPONDERS.

MN

XX

XX

MN

XX

WP

XX

WP

XX

WP

F

WP

P

GRAPHIC ANNUNCIATOR PANELGAN

FACP FIRE ALARM CONTROL PANEL

T TEMPERATURE SENSOR

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :4

A

M

FA001JOT

APB

JMF

FIRE ALARM

GENERAL NOTES,

ABBREVIATIONS,

AND SYMBOLS

N

D

Y

H

D

Y

H

FLOOD ZONE: X

H

H

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

CONTROLLED

WASTE HANDLING

FACILITY (ABI No. 1)

GENERAL PURPOSE

TRAINING BAY

(ABI No. 2)

PROPOSED

READINESS

CENTER

I

N

F

A

N

T

D

C

B

A

2 3 4 5

C p w w o r k i n g g b n a l e e a d

F

W

F

A

F

X d w g

A

M

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

W I L M

I N

G T

O N

N

O R

R

O L I N

A

N A

T I O

N A

L

G

U A

A

D I N

E S

S

C

E N

T E

R

N O

R T

H

C

A R

O L

I N

A

A

R M

Y

N

A T

I O

N A

L

G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE ONLY

FOR THE PURPOSE OF AUTHENTICATING THIS DOCUMENT.

RESPONSIBILITY FOR ALL OTHER DOCUMENTS RELATING TO

THIS PROJECT IS DISCLAIMED

REGISTRATION NUMBER:

N

NC Engineering Firm License No. F-0287

NC Architectural Firm No. 50757

JOT

APB

JMF

FIRE ALARM

SITE PLAN

60'15' 30' 90'

1" = 30'

A1

FIRE ALARM SITE PLAN

1" = 30'

FA001

CONTROLLED WASTE HANDLING FACILITY SHALL BE PROVIDED WITH A MANUAL PULL

STATION AND OCCUPANT NOTIFICATION INSTALLED IN ACCORDANCE WITH APPLICABLE

CODES AND STANDARDS. ALL DEVICES SHALL MEET CLASS 1, DIVISION 1 CLASSIFICATION.

CONDUIT BELOW GRADE FOR FIRE ALARM WIRING BETWEEN READINESS CENTER AND

CONTROLLED WASTE HANDLING FACILITY. PROVIDE SURGE SUPPRESSORS FOR CONDUIT

AT EXTERIOR OF EACH BUILDING.

PROVIDE BACKFLOW PREVENTER VALVE TAMPER SWITCHES AND SITE POST INDICATOR

VALVE TAMPER SWITCH AND ASSOCIATED MONITORING MODULES

RED STROBE/FLASHING LIGHT MOUNTED IN VISIBLE LOCATION ON EXTERIOR OF BUILDING

AND USED AS INDICATOR FOR FIRE DEPARTMENT WHEN ALARM IS ACTIVATED.

COORDINATE FINAL LOCATION AND MOUNTING HEIGHT WITH ARCHITECT.

REFER TO CIVIL DRAWING FOR FIRE DEPARTMENT ACCESS REQUIREMENTS.

1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.

KEYED NOTES

FIRE ALARM PLAN GENERAL NOTES

MM

F

MM

T

MM

F

FA010

UP UP

DN

DN

FA102

A1

FA103

A1

2 3 4 5 6 7 8 9

G

J

E

L

C

A

H

F

D

B

12 13

K

7.25.5 5.8

FA801

A1

D.3

D.2

E.6

FA104

A1

FA105

A1

2 3 4 5 6 7 8 9

G

J

E

L

C

A

H

F

D

B

12 13

K

7.25.5 5.8

FA801

C1

D.3

D.2

E.6

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :4

A

M

FA101JOT

APB

JMF

FIRE ALARM

OVERALL

FLOOR PLANS

1/16" = 1'-0"A1

OVERALL FIRST FLOOR FIRE ALARM PLAN

1/16" = 1'-0"C1

OVERALL SECOND FLOOR FIRE ALARM PLAN

1/16" = 1'-0"

8' 16' 32' 48'

FIRE ALARM PLAN GENERAL NOTES

G-001

G-001

1. REFER TO FA801 FOR ABI No. 2 FIRE ALARM PLANS.

UP

60 60

45 45

75 45

P

MN MN MN

MN

MNMN

MN

MN MN

MN

MNMN

L O

C F

S A

W P

M

WP

M

W P

M

F F

F F

F F

F

M N

M N

MN

MN

MN

MN

MN

15P

LOC

FSA

F

M N

M N

K

ELECTRICAL

CORRIDOR

FACILITY STORAGE

FACILITY STORAGE

FACILITY STORAGE

MULTIPURPOSE TRAINING ROOM

UNIT LOCKERS

147A

UNHEATED STORAGE

141A

FIRE PUMP ROOM

MECHANICAL

STAIRS

MAIL ROOM

CORRIDOR

158A

CLASSROOM

M A

T C

H L

IN

E

A

/ F A

2 3 4 5 61

G

J

E

L

C

5.5 5.8

201 201

MAIL PICK UP

PHYSICAL FITNESS

148MAIL VESTIBULE

UNHEATED STORAGE

141B

UNIT LOCKERS

147B

UNIT LOCKERS

147C

RECYCLE STORAGE

MM

MM

MM

MM

MM

MM

MM

MM

MM

MM

M M

M M

T

CM

MM

UNIT STORAGE

E.6

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :4

A

M

FA102JOT

APB

JMF

FIRE ALARM

PARTIAL FIRST FLOOR

FLOOR PLAN

AREA A

1/8" = 1'-0"

FA101

A1

FIRST FLOOR FIRE ALARM PLAN AREA A

1/8" = 1'-0"

24'4' 8' 16'

200 PROVIDE FIRE ALARM BELL ON EXTERIOR WALL.

201 MOUNT FIRE ALARM DEVICE(S) TO UNDERSIDE OF JOIST.

203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S

REQUIREMENTS AND NFPA 72.

217 DUCT SMOKE DETECTOR. INSTALL ON SUPPLY SIDE OF DOAS-1 (REFER TO A1 /

M-401 FOR LOCATION). MOUNT DEVICE IN ACCORDANCE WITH

MANUFACTURER'S REQUIREMENTS AND NFPA 72.

1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.

FIRE ALARM PLAN GENERAL NOTES

P

MN

MN

MN MN

MN

MN

MN

MN MN

MN

K

W P

M

WP

M

WP

M

W P

M

G A

N F

A M

N F

F

FF

FF

MN

M N

M

N

M N

MN

MN

M N

MN

FSA

LOC

P

F

MN

CM

MM

MN

MN

MN

WP

M

MN

CM

CM

LEARNING CENTER

OFFICE

OFFICE

PHYSICAL FITNESS

TELECOM EQUIPMENT

CUSTODIAL

ELECTRICAL

MENS SHOWERS

WOMENS SHOWERS

VESTIBULE

VAULT

UNIT STORAGE

FAMILY READINESS

STAIRS

RECRUITING OFFICE

SEATING

RETENTION OFFICE

RETENTION OFFICE

STORAGE

TABLES AND CHAIRS STORAGE

DRY STORAGE

TOILET

SCULLERY

SERVERY

KITCHEN

STORAGE

MENS TOILET

WOMENS TOILET

VESTIBULE

OFFICE

HHC

OFFICE

LOBBY

CLASSROOM

CUSTODIAL

M A

T C

H L

IN

E

A

/ F A

7 8 9

G

E

L

C

H

F

D

B

12 13

K

7.2

SUPPLY AFF

SUPPLY SGT

STORAGE

ELEVATOR

WELLNESS ROOM

CORRIDOR

158A

ABI No. 2 SCOPE (SHOWN DASHED)

REFER TO FA800 SERIES FOR ADDITIONAL INFORMATION

CORRIDOR

158B

ASSEMBLY HALL

D.3

D.2

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :5

A

M

FA103JOT

APB

JMF

FIRE ALARM

PARTIAL FIRST FLOOR

FLOOR PLAN

AREA B

1/8" = 1'-0"

FA101

A1

FIRST FLOOR FIRE ALARM PLAN AREA B

1/8" = 1'-0"

24'4' 8' 16'

201 MOUNT FIRE ALARM DEVICE(S) TO UNDERSIDE OF JOIST.

202 NOTIFICATION DEVICES TO BE PROVIDED WITH PROTECTIVE CAGES.

203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND

NFPA 72.

215 INTERFACE CONTROL MODULE WITH PAGING SYSTEM.

216 PROVIDE MONITOR MODULE FOR KITCHEN HOOD.

221 CONTROL MODULE FOR DOOR HOLDER INTERFACE. REFER TO B1/FA501 FOR SEQUENCE

OF OPERATIONS.

222 FAMN AND GAN TO BE SEMI-RECESSED.

KEYED NOTES

1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.

F

MN

MN MN

30 30

M N

MN MN

MN

MN

MN

S2 OFFICE

S2 OFFICE

S2 OFFICE

AUDITORIUM

AV

TA STORAGE

TA STORAGE

TA STORAGE

ELECTRICAL

PA STORAGE

EXAM

PHYSICIAN ASSISTANT

MEDICAL EXAM

S1 OFFICE

S1 OFFICE

S1 OFFICE

OPEN OFFICE

CHAP OFFICE

S4 OFFICE

S4 OFFICE

S6 OFFICE

S6 OFFICE

ADMINISTRATION

CURRENT OPERATIONS

CORRIDOR

M A

T C

H L

IN

E

A

/ F A

2 3 4 5 61

G

J

E

L

C

5.5 5.8

STAIRS

MM

MM

E.6

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :5

A

M

FA104JOT

APB

JMF

FIRE ALARM

PARTIAL SECOND FLOOR

FLOOR PLAN

AREA A

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FA101

A1

SECOND FLOOR FIRE ALARM PLAN AREA A

1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.

P

MN

F

M

N

MNMN

MNMN

MN

MN

P

MN

LOC

NAC

P

S3 OFFICE

BATTALION COMMAND

CMD SGT MJ OFF

X0 OFFICE

COMMAND CONFERENCE ROOM

STORAGE

226STORAGE

CUSTODIAL

FACILITY STORAGE

ELECTRICAL

S3 OFFICE

PRINT ROOM

MENS TOILET

229 WOMENS TOILET

TELECOM EQUIPMENT

BREAK ROOM

O5 COMMANDER OFFICE

S3 OFFICE

S3 OFFICE

AO OFFICE

BREAK OUT ROOM

M A

T C

H L

IN

E

A

/ F A

7 8 9

G

E

L

C

H

F

D

B

12 13

K

147.2

ELEVATOR

CORRIDOR

STAIRS

CURRENT OPERATIONS

ABI No. 2 SCOPE (SHOWN DASHED)

REFER TO FA800 SERIES FOR ADDITIONAL INFORMATION

D.3

D.2

N

D

C

B

A

1 2 3 4 5

BID FINAL SUBMITTAL

Designed:

Drawn :

Checked:

Drawing No.:

Date:

Drawing Title:

Scales:

Key Plan:

P R

O J E

C T

N O

W

IL

M

IN

G T

O N

N

O R

T H

C A

R O

L

IN

A

N A

T

IO

N A

L G

U A

R D

R E

A D

IN

E

S S

C E

N T

E R

N O

R T

H C

A R

O L

IN

A

A R

M Y

N A

T

IO

N A

L G

U A

R D

03 APRIL 2017

DATEREV DESCRIPTION

501 North Broadway, Saint Louis, Missouri 63102

DISCLAIMER

ATTACHMENT OF THIS SEAL TO THIS DOCUMENT IS MADE

ONLY FOR THE PURPOSE OF AUTHENTICATING THIS

DOCUMENT. RESPONSIBILITY FOR ALL OTHER DOCUMENTS

RELATING TO THIS PROJECT IS DISCLAIMED

NC Engineering Firm License No. F-0287 NC Architectural Firm No. 50757

B

IM

/U

S

N o rt h

C a ro lin a A rm y N a tio n a l G u a rd

F

W

/N C

A R

N G

R e a d in e s s C e n te r_

F

IR

E V

.r v t

/1

/2

:2 :5

A

M

FA105JOT

APB

JMF

FIRE ALARM

PARTIAL SECOND FLOOR

FLOOR PLAN

AREA B

1/8" = 1'-0"

24'4' 8' 16'

1/8" = 1'-0"

FA101

A1

SECOND FLOOR FIRE ALARM PLAN AREA B

1. REFER TO FA001 FOR SYMBOLS AND ABBREVIATIONS.

KEYED NOTES

FIRE ALARM PLAN GENERAL NOTES

203 MOUNT INITIATION DEVICE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS AND

NFPA 72.

BUILDING ENVELOPE

CLASS "B" NOTIFICATION APPLIANCE CIRCUIT (TYP)

TS

MM

FS

MMMM CM

AHU…