National Guard Readiness Center Wilmington, North Carolina Addendum 1 16 August 2017
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 1
SECTION 262913.03 - MANUAL AND MAGNETIC MOTOR CONTROLLERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Manual motor controllers.
2. Enclosed full-voltage magnetic motor controllers.
3. Enclosed reduced-voltage magnetic motor controllers.
4. Combination Full-voltage magnetic motor controllers.
5. Enclosures.
6. Accessories.
7. Identification.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: For each type of magnetic controller.
1. Include plans, elevations, sections, and mounting details.
2. Indicate dimensions, weights, required clearances, and location and size of each field connection.
3. Wire Termination Diagrams and Schedules: Include diagrams for signal, and control wiring. Identify terminals and wiring designations and color-codes to facilitate installation, operation, and maintenance. Indicate recommended types, wire sizes, and circuiting arrangements for field-installed wiring, and show circuit protection features. Differentiate between manufacturer-installed and field-installed wiring.
4. Include features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components.
1.3 INFORMATIONAL SUBMITTALS
A. Seismic Qualification Data: Certificates, for magnetic controllers, from manufacturer.
B. Field quality-control reports.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 2
1.5 QUALITY ASSURANCE
A. Testing Agency Qualifications: Accredited by NETA.
1. Testing Agency's Field Supervisor: Certified by NETA to supervise on-site testing.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
B. UL Compliance: Fabricate and label magnetic motor controllers to comply with UL 508 and UL 60947-4-1.
C. NEMA Compliance: Fabricate motor controllers to comply with ICS 2.
2.2 MANUAL MOTOR CONTROLLERS
A. Motor-Starting Switches (MSS): "Quick-make, quick-break" toggle or push-button action; marked to show whether unit is off or on.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Eaton.
b. General Electric Company.
c. Rockwell Automation, Inc.
d. SIEMENS Industry, Inc.; Energy Management Division.
2. Standard: Comply with NEMA ICS 2, general purpose, Class A.
3. Configuration: Nonreversing.
4. Surface mounting.
5. Red pilot light.
B. Fractional Horsepower Manual Controllers (FHPMC): "Quick-make, quick-break" toggle or push-button action; marked to show whether unit is off, on, or tripped.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Eaton.
b. General Electric Company.
c. Rockwell Automation, Inc.
d. SIEMENS Industry, Inc.; Energy Management Division.
http://www.specagent.com/Lookup?ulid=2157 http://www.specagent.com/Lookup?uid=123457087333 http://www.specagent.com/Lookup?uid=123457087334 http://www.specagent.com/Lookup?uid=123457087335 http://www.specagent.com/Lookup?uid=123457087332 http://www.specagent.com/Lookup?ulid=2158 http://www.specagent.com/Lookup?uid=123457087339 http://www.specagent.com/Lookup?uid=123457087340 http://www.specagent.com/Lookup?uid=123457087341 http://www.specagent.com/Lookup?uid=123457087338
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 3
2. Configuration: Nonreversing.
3. Overload Relays: Inverse-time-current characteristics; NEMA ICS 2, Class 10 tripping characteristics; heaters matched to nameplate full-load current of actual protected motor; external reset push button; bimetallic type.
4. Pilot Light: Red.
2.3 ENCLOSED FULL-VOLTAGE MAGNETIC MOTOR CONTROLLERS
A. Description: Across-the-line start, electrically held, for nominal system voltage of 600- V ac and less.
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Eaton.
2. General Electric Company.
3. Rockwell Automation, Inc.
4. SIEMENS Industry, Inc.; Energy Management Division.
C. Standard: Comply with NEMA ICS 2, general purpose, Class A.
D. Configuration: Nonreversing.
E. Contactor Coils: Pressure-encapsulated type.
1. Operating Voltage: Manufacturer's standard, unless indicated.
F. Control Power:
1. For on-board control power, obtain from line circuit or from integral CPT. The CPT shall have capacity to operate integral devices and remotely located pilot, indicating, and control devices.
G. Overload Relays:
1. Thermal Overload Relays:
a. Inverse-time-current characteristic.
b. Class 10 tripping characteristic.
c. Heaters in each phase shall be matched to nameplate full-load current of actual protected motor and with appropriate adjustment for duty cycle.
d. Ambient compensated.
e. Automatic resetting.
2.4 COMBINATION FULL-VOLTAGE MAGNETIC MOTOR CONTROLLER
A. Description: Full-voltage, electrically-held, non-reversing, magnetic motor controllers with 24Vac control circuit, hand-of-auto (HOA) switch, push-to-start switch, manual reset switch, auxiliary control and monitoring contacts and accessories required to http://www.specagent.com/Lookup?ulid=12768 http://www.specagent.com/Lookup?uid=123457087317 http://www.specagent.com/Lookup?uid=123457087318 http://www.specagent.com/Lookup?uid=123457087319 http://www.specagent.com/Lookup?uid=123457087320
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 4
meet the system requirements indicated. Cover door shall have red and green pilot lights. The green light shall illuminated when “on”, and red shall illuminated when “off
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Eaton.
2. General Electric Company.
3. Rockwell Automation, Inc.
4. SIEMENS Industry, Inc.; Energy Management Division.
5. Schneider Electric- Square D.
C. Standard: Comply with NEMA ICS 2, general purpose, Class A.
D. Configuration: Non-reversing.
E. Contactor Coils: Pressure-encapsulated type.
1. Operating Voltage: Manufacturer's standard, unless indicated.
F. Control Power:
a. 24-V ac, integral CPT, with primary and secondary fuses, CPT with 100 VA spare capacity.
G. Overload Relays:
1. Thermal Overload Relays:
a. Inverse-time-current characteristic.
b. Class 10 tripping characteristic.
c. Heaters in each phase shall be matched to nameplate full-load current of actual protected motor and with appropriate adjustment for duty cycle.
d. Ambient compensated.
e. Automatic resetting.
H. Class II ground-fault protection shall comply with UL 1053 to interrupt low-level ground faults. The ground-fault detection system shall include circuitry that will prevent the motor controller from tripping when the fault current exceeds the interrupting capacity of the controller. Equip with start and run delays to prevent nuisance trip on starting, and a trip indicator.
I. Fusible Disconnecting Means:
1. NEMA KS 1, heavy-duty, horsepower-rated, fusible switch with clips or bolt pads to accommodate RK1 fuses.
2. Lockable Handle: Accepts three padlocks and interlocks with cover in closed and open position.
http://www.specagent.com/Lookup?ulid=12768 http://www.specagent.com/Lookup?uid=123457087317 http://www.specagent.com/Lookup?uid=123457087318 http://www.specagent.com/Lookup?uid=123457087319 http://www.specagent.com/Lookup?uid=123457087320
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 5
2.5 ENCLOSURES
A. Comply with NEMA 250, type designations as indicated on Drawings, complying with environmental conditions at installed location.
B. The construction of the enclosures shall comply with NEMA ICS 6.
2.6 ACCESSORIES
A. General Requirements for Control Circuit and Pilot Devices: NEMA ICS 5; factory installed in controller enclosure cover unless otherwise indicated.
1. Push Buttons, Pilot Lights, and Selector Switches: Standard-duty, except as needed to match enclosure type. Heavy-duty or oil-tight where indicated in the controller schedule.
B. Motor protection relays shall be with solid-state sensing circuit and isolated output contacts for hardwired connections.
1. Phase-failure.
2. Phase-reversal, with bicolor LED to indicate normal and fault conditions.
Automatic reset when phase reversal is corrected.
3. Under/overvoltage, operate when the circuit voltage reaches a preset value, and drop out when the operating voltage drops to a level below the preset value.
Include adjustable time-delay setting.
2.7 IDENTIFICATION
A. Controller Nameplates: Baked enamel signs, as described in Section 260553 "Identification for Electrical Systems," for each compartment, mounted with corrosion-resistant screws.
B. Arc-Flash Warning Labels:
1. Comply with requirements in Section 260573.19 "Arc-Flash Hazard Analysis."
Produce a 3.5-by-5-inch (89-by-127-mm) self-adhesive equipment label for each work location included in the analysis.
2. Comply with requirements in Section 260553 "Identification for Electrical Systems." Produce a 3.5-by-5-inch (89-by-127-mm) self-adhesive equipment label for each work location included in the analysis. Labels shall be machine printed, with no field-applied markings.
a. The label shall have an orange header with the wording, "WARNING, ARC- FLASH HAZARD," and shall include the following information taken directly from the arc-flash hazard analysis:
1) Location designation.
2) Nominal voltage.
3) Flash protection boundary.
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 6
4) Hazard risk category.
5) Incident energy.
6) Working distance.
7) Engineering report number, revision number, and issue date.
b. Labels shall be machine printed, with no field-applied markings.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Comply with NECA 1.
B. Wall-Mounted Controllers: Install magnetic controllers on walls with tops at uniform height indicated, and by bolting units to wall or mounting on lightweight structural-steel channels bolted to wall. For controllers not at walls, provide freestanding racks complying with Section 260529 "Hangers and Supports for Electrical Systems" unless otherwise indicated.
C. Floor-Mounted Controllers: Install controllers on cast-in-place concrete equipment base(s). Comply with requirements for equipment bases and foundations specified in Section 033000 "Cast-in-Place Concrete."
D. Comply with requirements for seismic control devices specified in Section 260548.16 "Seismic Controls for Electrical Systems."
E. Maintain minimum clearances and workspace at equipment according to manufacturer's written instructions and NFPA 70.
F. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Install lacing bars and distribution spools.
G. Setting of Overload Relays: Select and set overloads on the basis of full-load current rating as shown on motor nameplate. Adjust setting value for special motors as required by NFPA 70 for motors that are high-torque, high-efficiency, and so on.
3.2 IDENTIFICATION
A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."
3.3 FIELD QUALITY CONTROL
A. Perform tests and inspections.
B. Tests and Inspections:
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 7
1. Comply with the provisions of NFPA 70B, "Testing and Test Methods" Chapter.
2. Visual and Mechanical Inspection
a. Compare equipment nameplate data with drawings and specifications.
b. Inspect physical and mechanical condition.
c. Inspect anchorage, alignment, and grounding.
d. Verify the unit is clean.
e. Inspect contactors:
1) Verify mechanical operation.
2) Verify contact gap, wipe, alignment, and pressure are according to manufacturer's published data.
f. Motor-Running Protection:
1) Verify overload element rating is correct for its application.
2) If motor-running protection is provided by fuses, verify correct fuse rating.
g. Inspect bolted electrical connections for high resistance using one of the two following methods:
1) Use a low-resistance ohmmeter. Compare bolted connection resistance values with values of similar connections. Investigate values that deviate from those of similar bolted connections by more than 50 percent of the lowest value.
2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method according to manufacturer's published data or NETA ATS Table 100.12. Bolt-torque levels shall be according to manufacturer's published data. In the absence of manufacturer's published data, use NETA ATS Table 100.12.
h. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces.
3. Electrical Tests
a. Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-to-ground with switch closed, and across each open pole. Insulation-resistance values shall be according to manufacturer's published data or NETA ATS Table 100.1. In the absence of manufacturer's published data, use Table 100.5. Values of insulation resistance less than those of this table or manufacturer's recommendations shall be investigated and corrected.
b. Measure fuse resistance. Investigate fuse-resistance values that deviate from each other by more than 15 percent.
c. Test motor protection devices according to manufacturer's published data.
d. Test circuit breakers as follows:
1) Operate the circuit breaker to ensure smooth operation.
MANUAL AND MAGNETIC MOTOR CONTROLLERS 262913.03 - 8
2) For adjustable circuit breakers, adjust protective device settings according to the coordination study. Comply with coordination study recommendations.
e. Perform operational tests by initiating control devices.
C. Motor controller will be considered defective if it does not pass tests and inspections.
D. Prepare test and inspection reports.
3.4 SYSTEM FUNCTION TESTS
A. System function tests shall prove the correct interaction of sensing, processing, and action devices. Perform system function tests after field quality control tests have been completed and all components have passed specified tests.
1. Develop test parameters and perform tests for the purpose of evaluating performance of integral components and their functioning as a complete unit within design requirements and manufacturer's published data.
2. Verify the correct operation of interlock safety devices for fail-safe functions in addition to design function.
3. Verify the correct operation of sensing devices, alarms, and indicating devices.
B. Motor controller will be considered defective if it does not pass the system function tests and inspections.
C. Prepare test and inspection reports.
3.5 DEMONSTRATION
A. Train Owner's maintenance personnel to adjust, operate, and maintain switchgear.
END OF SECTION 262913.03