Attch 2 01 45 35 Statement of Special Inspections - 1 28 2022.pdf

PDF 165 KB Posted

Attached to
DLA Building 54 Navy Artifact Restoration
Solicitation number
W9123622B2041
Issued by

About this file

This document is a Statement of Special Inspections for the DLA Building 54 Navy Artifact Restoration project located in Richmond, Virginia. The project involves seismic retrofitting and HVAC upgrades for the structure, which is designated Seismic Design Category D and Risk Category I. Special inspections will be required for cast-in-place concrete work. A Special Inspector of Record from IS Group will monitor all critical main wind and seismic force-resisting systems, including vertical and horizontal lateral force elements. Designated Seismic Systems must be certified by the manufacturer to remain operable and contain hazardous substances after a design earthquake. These include any mechanical, electrical, or other non-structural systems so designated. The Registered Design Professional in Responsible Charge must perform a final walk-down inspection and submit a report documenting inspection of Designated Seismic Systems and collection of manufacturer compliance certificates.

View the file

Other files

File Type Posted
B.01.02_22B2041 Abstract of Offers.pdf PDF
Attch 27 01 45 04.00 50.pdf PDF
W9123622B2041 Amendment 0011.pdf PDF
Amendment 10 Final.pdf PDF
Amendment 9 Final.pdf PDF
W9123622D2041 Amendment 0008.pdf PDF
W9123622B2041 Amendment 0006.pdf PDF
Attch 3 01 45 35 SI Schedule - 1-28-2022.pdf PDF
Attch 24 M801.pdf PDF
Attch 26 EL101.pdf PDF
Attch 12 AD122.pdf PDF
Attch 9 AD102.pdf PDF
Attch 13 A111.pdf PDF
Attch 5 01 50 02 00 50.pdf PDF
Attch 22 M601.pdf PDF
Attch 23 M602.pdf PDF
Attch 1 Project Table of Contents 00 00 00.pdf PDF
Attch 6 03 30 53.pdf PDF
Attch 7 08 33 23.pdf PDF
Attch 21 MP101.pdf PDF
Attch 8 AD101.pdf PDF
Attch 10 AD111.pdf PDF
Attch 17 FA101.pdf PDF
Attch 16 A601.pdf PDF
Attch 11 AD112.pdf PDF
Attch 15 A301.pdf PDF
Attch 19 MH101.pdf PDF
Attch 14 A112.pdf PDF
Attch 18 MD101.pdf PDF
Attch 20 MH111.pdf PDF
Attch 4 01 45 35.pdf PDF
22B2041 Amendment 0006.pdf PDF
Attch 25 M805.pdf PDF
W9123622B2041 Amendment 0005.pdf PDF
22B2041 B54 HVAC Amendment 4.pdf PDF
19 Jan Site visit.pdf PDF
Amendment 0003 Final.pdf PDF
Amendment 0002 Final.pdf PDF
Amendment 0001 Final.pdf PDF
Site Visit 5 January.pdf PDF
W9123622B2041 IFB.pdf PDF
A.01.13_0455737 NAO663A B54-ARTIFACT-SPECS.pdf PDF
A.01.13_0455737 NAO663A B54-HVAC-ARTIFACT-IFB-DRAWINGS.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project:

Location:

Project #:

Date:

D

IV

No

B54 HVAC Artifact

Richmond, VA

1/31/2022

Project Seismic Design Category:

Project Risk Category:

Project Design Wind Speed (mph):

Number of Stories:

Structure Height Above Grade (ft):

Hazardous Occupancy or attached to such?

STATEMENT OF SPECIAL INSPECTIONS

Special Inspector of Record (SIOR) A Special Inspector of Record (SIOR)

SIOR Name (Registered Professional):

Professional Registration Number:

Consulting Firm Name (if any):

SIOR Office AND Mobile Phone Number:

IS

Group H Occupancies required (per UFGS 01 45 35, Section 1.3.8)

Contractor to provide prior to construction start

Following is a listing of critical main wind/seismic force resisting systems for this structure. Carefully inspect these elements as part of the roles and responsiblities of the Special Inspector (reference the Schedule of Special Inspections for inspection checklists).

Lateral Force Resisting System (LFRS) 2018 IBC 1704.3.2 and 1704.3.3

Vertical LFRS Elements Notes

Horizontal LFRS Elements Notes

Statement of Special Inspections Page 1 of 2

Cast in Place Concrete

Project:

Location:

Project #:

Date:

1.

2.

3.

4.

5.

1.

2.

3.

4.

5.

6.

1.

2.

3.

4.

5.

6.

(2018 IBC 1705.13.3) (ASCE 7-16, 13.2.2, C13.2.2) (UFC 3-301-1, 2-5.3)

Non-structural 'Designated Seismic Systems' (DSS) must remain operable and contain hazardous substances following a design earthquake. Accordingly, all Designated Seismic Systems must be listed below and must be certified by the manufacturer to remain both operable and/or to contain hazardous substances after a design earthquake per UFC 3-301-01, Section 3-6.2. Submit said Certificates of Compliance to the Contracting Officer for each DSS after they have been reviewed and accepted by the EOR/DOR.

Additionally, the below listed Designated Seismic Systems must be carefully inspected by the Special Inspector according to the requirements noted in the Schedule of Special Inspections, Section AA.

ELECTRICAL Designated Seismic Systems (DSS) Requiring a Certificate of Compliance

If additional space is required, append an additional sheet listing the remaining DSS

If additional space is required, append an additional sheet listing the remaining DSS

MECHANICAL/PLUMBING Designated Seismic Systems (DSS) Requiring a Certificate of Compliance

OTHER Designated Seismic Systems (DSS) Requiring a Certificate of Compliance

Final Walk Down Inspection and Report

(UFC 3 301 01 SECTION 2-5.4)

Designated Seismic Systems shall receive a final walk-down inspection by the Registered Design Professional in

Responsible Charge

Final Walk Down Report, Prepared by the Registered Design Professional in Responsible Charge, Must Include:

1. Record observations of Final Walk Down Inspection

2. Document that Inspections were performed in accordance with the Schedule of Special Inspections

3. Document that all Designated Seismic Systems are installed according to construction/manufacturer document requirements, and that Compliance Certificates have been collected (UFC 03 301 01, 3-6.2, 13.2.2.2).

Statement of Special Inspections Page 2 of 2

1/31/2022

Richmond, VA

B54 HVAC Artifact

Designated Seismic Systems (DSS)