This document package includes construction drawings and specifications for a federal contract solicitation to construct a latrine annex building. The solicitation seeks to construct an annex to Building 3010 in accordance with the attached scope of work, drawings, and specifications. The drawings depict the electrical, lighting, and power plans for the latrine annex and include notes specifying fixture types and installation requirements. The solicitation number is W911SF-20-B-0001 and was issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Eustis for a latrine annex at Fort Benning, Georgia. Responses are due in accordance with the standard solicitation response timeline.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SITE PLAN
E1
SCALE OF FEET
050 50 100
1 ELECTRICAL SITE PLAN
E1
SCALE: 50’ = 1’-0"
SPECIAL ELECTRICAL KEYED NOTES:
4 5
6 7
44054-E1
TO THE LIVE-SIDE OF THE POWER METER BASE (DIRECTIONAL BORING).
FLINT ELECTRIC WILL PROVIDE AND RUN THE UNDERGROUND SECONDARY POWER CABLES FROM THE 75KVA PAD-MOUNTED TRANSFORMER
225A, 120/208V, THREE-PHASE, AND FOUR-WIRE PANELBOARD (PANEL NL) INSIDE THE LATRINE.
ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL POWER CABLES FROM THE LOAD-SIDE OF THE POWER METER TO THE NEW
THE KNOX BOX.
CONTRACTOR SHALL PROVIDE AND INSTALL A KNOX BOX NEAR THE DISCONNECT SWITCH. THE PAD-LOCK KEY SHALL PUT INSIDE
ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL A DISCONNECT SWITCH NEAR THE POWER METER BASE WITH THE PAD-LOCK.
ON THE EXTERIOR WALL OF THE NEW LATRINE ADDITION NEAR BUILDING 3010 AS INDICATED ON THE DRAWING.
ELECTRICAL CONTRACTOR SHALL OBTAIN THE POWER METER BASE FROM FLINT ELECTRIC AND INSTALL THE POWER METER BASE
75KVA, 120/208V, THREE-PHASE, PAD-MOUNTED TRANSFORMER (DIRECTIONAL BORING) AS INDICATED ON THE DRAWING.
FLINT ELECTRIC WILL PROVIDE AND RUN THE UNDERGROUND PRIMARY CABLES FROM THE MEDIUM VOLTAGE JUNCTION BOX TO THE
ON THE DRAWING.
FLINT ELECTRIC WILL PROVIDE AND INSTALL A 75KVA, 120/208V, THREE-PAHSE PAD-MOUNTED TRANSFORMER AS INDICATED
FLINT ELECTRIC WILL PROVIDE AND INSTALL A 3-PHASE MEDIUM VOLTAGE JUNCTION BOX AS INDICATED ON THE DRAWING.
BID DOCUMENTS
85% DESIGN
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
01 NOV 19
FORT BENNING, GEORGIA
BUILDING 3010 FOR 30TH AG
NEW LATRINE ADDITION
E N
TE
R
E X
IT
C O R R
ID
O R
M E C H
AU
D
ITO
R
IU
M
P R O C E S S
IN
G
O P E N
B R E E Z
W
AY
E X
IS
TIN
G
B
LD
G
S3S3
S
THE HARD CEILING
MEZZANINE ABOVE
S
NL-1
NL-3
NL-5
SCALE: 1/4" = 1’-0"
SCALE: 1/4" = 1’-0"
LED WALL
CAT# ELM2-LED-HO (NO REMOTES) - EXTENDED RUN-TIME FOR HIGH-OUTPUT UNIT
LITHONIA LIGHTING - M12 LED THERMOPLASTIC EMERGENCY LIGHT WITH NI-CAD BATTERY
A
TYPE LAMP MOUNTING
E LED SURFACE
FIXTURE SCHEDULE
WALL
SURFACE
AE
LED
LED
B LED
LEDBE
C LED H.E.WILLIANS, INC. CAT# 39W-4-L52/840-A-EM/10WLP-DRV-UNV
LITHONIA LIGHTING CAT# LHQM-LED-R-HO-SD
LED COOPER LIGHTING - CROSSTOUR MAXX LED WALL AND SITE LUMINAIRE
F
(NICKEL-CADMIUM BATTERY) AND SELF-DIAGNOSTICS CAPABILITY
LHQM LED EXIT SIGN (WHITE HOUSING AND RED LETTER COLOR) WITH TWO LED LAMP HEADS
EFFICACY AND ENERGY EFFICIENCY. MADE IN USA
DESIGNED FOR SURFACE OR SUSPENDED APPLICATIONS. LED TECHNOLOGY PROVIDES HIGH
D
AND VOLUMETRIC DISTRIBUTION. HIGH EFFICACT LED LIGHT ENGINES.
FEATURES A POPULAR CENTER BASKET DESIGN THAT OFFERS A CLEAN, VERSATILE STYLE
LITHONIA LIGHTING CAT# BLTX4-48L-ADP-EZ1-LP840-NESPDT7
SURFACE
AND VOLUMETRIC DISTRIBUTION. HIGH EFFICACT LED LIGHT ENGINES.
FEATURES A POPULAR CENTER BASKET DESIGN THAT OFFERS A CLEAN, VERSATILE STYLE
LITHONIA LIGHTING CAT# BLTX4-48L-ADP-EZ1-LP840-NESPDT7-EL14L
SURFACE
AND VOLUMETRIC DISTRIBUTION. HIGH EFFICACT LED LIGHT ENGINES.
FEATURES A POPULAR CENTER BASKET DESIGN THAT OFFERS A CLEAN, VERSATILE STYLE
LITHONIA LIGHTING CAT# 2BLTX2-40L-ADP-EZ1-LP840-NESPDT7
SURFACE
AND VOLUMETRIC DISTRIBUTION. HIGH EFFICACT LED LIGHT ENGINES.
FEATURES A POPULAR CENTER BASKET DESIGN THAT OFFERS A CLEAN, VERSATILE STYLE
LITHONIA LIGHTING CAT# 2BLTX2-40L-ADP-EZ1-LP840-NESPDT7-EL14L
0’ 5’12" 10’
SCALE: 1/4 INCH = 1 FOOT
ELECTRICAL LIGHTING PLANS
ELECTRICAL LIGHTING PLAN - MEZZANINE
ELECTRICAL LIGHTING PLAN - LATRINE
A
A
A
A
A
AE
A
A
A
A
A
AE
B
BB
B
BE
BE
DD
EE
FF
A
AE
B
BE
C
LEGEND
S
S
E
F
CIRCUIT
UNSWITCHED
TO AN
CIRCUIT
UNSWITCHED
TO AN
SPECIAL ELECTRICAL KEYED NOTES:
LED LIGHT FIXTURE
EXTERIOR WALL MOUNT
1’ X 4’ LED FIXTURE
2’ X 2’ LED FIXTURE
2’ X 2’ LED FIXTURE
1’ X 4’ LED FIXTURE
1’ X 4’ LED FIXTURE
D LIGHT SWITCH
LIGHT SWITCH
OCCUPANCY SENSING
SENSOR
CEILING MOUNT OCCUPANCY
UNIT
EMERGENCY LIGHTING
FIXTURE
EXIT SIGN LED
SURFACE
CAT# XTOR8B-W (120V POWER)
E2
E2
44054-E2
E2
CC
CC
TYP.
TYP.
B
TYP.
TYP.
TYP.
ALL EXIT SIGN FIXTURES AND EMERGENCY LIGHTING UNITS SHALL BE INSTALLED ON AN UNSWITCHED CIRCUIT.
PROVIDE AND INSTALL CEILING MOUNT OCCUPANCY SENSOR AS INDICATED ON DRAWING.
PASSIVE INFRARED SENSOR TECHNOLOGY TO MONITOR A ROOM FOR OCCUPANCY.
INSTALL MULTI-TECHNOLOGY OCCUPANCY SENSORS (MTOS) WALL SWITCH AS INDICATED ON DRAWING. THE MTOS WALL SWITCH SHALL COMBINE BOTH ULTRASONIC AND
PROVIDE AND INSTALL A TOGGLE SWITCH ON THE JANITOR CLOSET. MOUNT THE SWITCH AT 48-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL OCCUPANCY SENSING WALL SWITCH WITH MANUAL OVERRIDE IN ALL THE LATRINE. MOUNT THE SWITCHES AT 48-INCH ABOVE FINISHED FLOOR.
PROVIDE AND INSTALL LOCAL SWITCHING AS INDICATED ON THE DRAWING.
PACK FOR THE DESIGNATED EMERGENCY LIGHT FIXTURES IN THE BUILDING TO MAINTAIN NFPA 101 LIFE SAFETY REQUIREMENT.
SELECT FIXTURES THROUGHOUT BUILDING WILL BE USED FOR EMERGENCY LIGHTING. CONTRACTOR IS REQUIRED TO PROVIDE AND INSTALL THE EMERGENCY BATTERY
PROVIDE AND INSTALL M12 LED EMERGENCY LIGHTING UNIT WITH TWO LAMP HEADS (FIXTURE F) AS INDICATED ON DRAWING.
AS INDICATED ON DRAWING.
PROVIDE AND INSTALL WALL MOUNT OR CEILING MOUNT LED EXIT SIGN FIXTURE WITH TWO (2) LED LAMP HEADS (FIXTURE E) AND SELF DIAGNOSTICS CAPABILITY
WITH PHOTO-CELL CONTROL.
PROVIDE AND INSTALL CROSSTOUR MAXX LED WALL AND SITE LUMINAIRE (FIXTURE D) AS INDICATED ON DRAWING. CONNECT THE EXTERIOR WALL MOUNT FIXTURES
ON THE ROOF STRUCTURE TO SUPPORT THE FIXTURES.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE C) AS INDICATED ON DRAWING. PROVIDE AND INSTALL MOUNTING STRUCTURE
SURFACE-MOUNTED THE FIXTURE ON THE CENTER OF THE 4’X4’ SQUARE ON THE CEILING.
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE BE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CENTER OF THE 4’X4’ SQUARE ON THE CEILING.
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE B) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON
SURFACE MOUNTED THE FIXTURE ON THE CEILING, CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE AE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CEILING CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE A) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON
9 10 11 12 13 14 15
ALL EXIT SIGN FIXTURES AND EMERGENCY LIGHTING UNITS SHALL BE INSTALLED ON AN UNSWITCHED CIRCUIT.
PROVIDE AND INSTALL CEILING MOUNT OCCUPANCY SENSOR AS INDICATED ON DRAWING.
PASSIVE INFRARED SENSOR TECHNOLOGY TO MONITOR A ROOM FOR OCCUPANCY.
INSTALL MULTI-TECHNOLOGY OCCUPANCY SENSORS (MTOS) WALL SWITCH AS INDICATED ON DRAWING. THE MTOS WALL SWITCH SHALL COMBINE BOTH ULTRASONIC AND
PROVIDE AND INSTALL A TOGGLE SWITCH ON THE JANITOR CLOSET. MOUNT THE SWITCH AT 48-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL OCCUPANCY SENSING WALL SWITCH WITH MANUAL OVERRIDE IN ALL THE LATRINE. MOUNT THE SWITCHES AT 48-INCH ABOVE FINISHED FLOOR.
PROVIDE AND INSTALL LOCAL SWITCHING AS INDICATED ON THE DRAWING.
PACK FOR THE DESIGNATED EMERGENCY LIGHT FIXTURES IN THE BUILDING TO MAINTAIN NFPA 101 LIFE SAFETY REQUIREMENT.
SELECT FIXTURES THROUGHOUT BUILDING WILL BE USED FOR EMERGENCY LIGHTING. CONTRACTOR IS REQUIRED TO PROVIDE AND INSTALL THE EMERGENCY BATTERY
PROVIDE AND INSTALL M12 LED EMERGENCY LIGHTING UNIT WITH TWO LAMP HEADS (FIXTURE F) AS INDICATED ON DRAWING.
AS INDICATED ON DRAWING.
PROVIDE AND INSTALL WALL MOUNT OR CEILING MOUNT LED EXIT SIGN FIXTURE WITH TWO (2) LED LAMP HEADS (FIXTURE E) AND SELF DIAGNOSTICS CAPABILITY
WITH PHOTO-CELL CONTROL.
PROVIDE AND INSTALL CROSSTOUR MAXX LED WALL AND SITE LUMINAIRE (FIXTURE D) AS INDICATED ON DRAWING. CONNECT THE EXTERIOR WALL MOUNT FIXTURES
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE C) AS INDICATED ON DRAWING. PROVIDE AND INSTALL MOUNTING STRUCTURE
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE BE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CENTER OF THE 4’X4’ SQUARE ON THE CEILING.
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE B) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON
SURFACE MOUNTED THE FIXTURE ON THE CEILING, CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE AE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CEILING CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE A) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON1
SPECIAL ELECTRICAL KEYED NOTES:
SPECIAL ELECTRICAL KEYED NOTES:
MEZZANINE FLOOR UP TO THE ROOF STRUCTURE.
PROVIDE AND INSTALL A MOUNTING STRUCTURE ABOVE THE MEZZANINE FOR THE LIGHT SWITCH AND RECEPTACLE. THE MOUNTING STRUCTURE SHALL BE BUILT FROM THE
ALL EXIT SIGN FIXTURES AND EMERGENCY LIGHTING UNITS SHALL BE INSTALLED ON AN UNSWITCHED CIRCUIT.
PROVIDE AND INSTALL CEILING MOUNT OCCUPANCY SENSOR AS INDICATED ON DRAWING.
PASSIVE INFRARED SENSOR TECHNOLOGY TO MONITOR A ROOM FOR OCCUPANCY.
INSTALL MULTI-TECHNOLOGY OCCUPANCY SENSORS (MTOS) WALL SWITCH AS INDICATED ON DRAWING. THE MTOS WALL SWITCH SHALL COMBINE BOTH ULTRASONIC AND
PROVIDE AND INSTALL A TOGGLE SWITCH ON THE JANITOR CLOSET. MOUNT THE SWITCH AT 48-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL OCCUPANCY SENSING WALL SWITCH WITH MANUAL OVERRIDE IN ALL THE LATRINE. MOUNT THE SWITCHES AT 48-INCH ABOVE FINISHED FLOOR.
PROVIDE AND INSTALL LOCAL SWITCHING AS INDICATED ON THE DRAWING.
PACK FOR THE DESIGNATED EMERGENCY LIGHT FIXTURES IN THE BUILDING TO MAINTAIN NFPA 101 LIFE SAFETY REQUIREMENT.
SELECT FIXTURES THROUGHOUT BUILDING WILL BE USED FOR EMERGENCY LIGHTING. CONTRACTOR IS REQUIRED TO PROVIDE AND INSTALL THE EMERGENCY BATTERY
PROVIDE AND INSTALL M12 LED EMERGENCY LIGHTING UNIT WITH TWO LAMP HEADS (FIXTURE F) AS INDICATED ON DRAWING.
AS INDICATED ON DRAWING.
PROVIDE AND INSTALL WALL MOUNT OR CEILING MOUNT LED EXIT SIGN FIXTURE WITH TWO (2) LED LAMP HEADS (FIXTURE E) AND SELF DIAGNOSTICS CAPABILITY
WITH PHOTO-CELL CONTROL.
PROVIDE AND INSTALL CROSSTOUR MAXX LED WALL AND SITE LUMINAIRE (FIXTURE D) AS INDICATED ON DRAWING. CONNECT THE EXTERIOR WALL MOUNT FIXTURES
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE C) AS INDICATED ON DRAWING. PROVIDE AND INSTALL MOUNTING STRUCTURE
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE BE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CENTER OF THE 4’X4’ SQUARE ON THE CEILING.
PROVIDE AND INSTALL 2’X2’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE B) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON
SURFACE MOUNTED THE FIXTURE ON THE CEILING, CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE AE) WITH 1400 NOMINAL LUMEN BATTERY PACK AS INDICATED ON DRAWING.
THE CEILING CLOSE TO THE WALL.
PROVIDE AND INSTALL 1’X4’, SURFACE MOUNT, LED LIGHT FIXTURE (FIXTURE A) AS INDICATED ON DRAWING. SURFACE-MOUNTED THE FIXTURE ON
BID DOCUMENTS
85% DESIGN
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
01 NOV 19
FORT BENNING, GEORGIA
BUILDING 3010 FOR 30TH AG
NEW LATRINE ADDITION
OPEN BREEZWAY
0’ 5’12" 10’
SCALE: 1/4 INCH = 1 FOOT
GFIGFI
1 ELECTRICAL POWER PLAN - LATRINE
SCALE: 1/4" = 1’-0"
ELECTRICAL POWER PLAN - MEZZANINE
SCALE: 1/4" = 1’-0"
E3
E3
44054-E3
E3
ELECTRICAL POWER PLANS
NL-2
NL-6
NL-4
NL-8
SPECIAL ELECTRICAL KEYED NOTES:
GFI
HW
HW
HW
HW
HW
HW
HW
HW
HW
HW NL-7
NL-9
NL-11
NL-13
NL-10
NL-12
NL-14
NL-15
NL-17
NL-19
NL-16
FAN
EXHAUST
GFI
WP
S
BID DOCUMENTS
85% DESIGN
WITH 32 CIRCUIT SPACES IN THE LATRINE.
PROVIDE AND INSTALL 225A, 120/208V, THREE-PHASE, AND 4-WIRE, RECESSED MOUNTED PANELBOARD
THE PAD-LOCK FOR THE DISCONNECT SWITCH.
METER BASE TO SHUT DOWN THE POWER SERVICE TO THE LATRINE DURING EMERGENCY. PROVIDE
ELECTRICAL CONTARCTOR SHALL PROVIDE AND INSTALL A DISCONNECT SWITCH NEXT TO THE POWER
WALL TO A NEW 225A, 120/208V, 3-PHASE, AND 4-WIRE PANELBOARD (PANEL NL) INSDIE THE LATRINE.
ELECTRICAL CONTRACTOR SHALL CONNECT THE LOAD-SIDE OF THE POWER METER BASE MOUNTED ON THE EXTERIOR
METER BASE ON THE EXTERIOR WALL AS INDICATED ON THE DRAWING.
ELECTRICAL CONTRACTOR SHALL OBTAIN THE POWER METER BASE FROM FLINT ELECTRIC AND INSTALL THE POWER
EXHAUST FAN CONTROL PER MECHANICAL SCOPE OF WORK AND DRAWING SPECIFICATIONS.
INSTALL POWER SERVICE TO THE EXHAUST FAN PER MANUFACTURER’S RECOMMENDATIONS. PROVIDE AND INSTALL
PROVIDE AND ISNTALL 120V, SINGLE-PHASE POWER SERVICE TO THE 1/4-HP EXHAUST FAN INSIDE THE LATRINE.
MANUFACTURER’S RECOMMENDATIONS.
WIRING, CONDUIT, CIRCUIT BREAKER, AND ENCLOSURE. INSTALL POWER SERVICE TO THE INDOOR UNIT PER
LATRINE. CONTRACTOR SHALL INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER
PROVIDE 208 VOLTS, 60 HZ, 3-PHASE POWER SERVICE TO THE INDOOR UNIT (RVE-40-30-30L-5D-R) INSIDE THE
(CD) UNIT PER MANUFACTURER’S RECOMMENDATIONS.
WIRING, CONDUIT, CIRCUIT BREAKER, AND ENCLOSURE. INSTALL POWER SERVICE TO THE OUTSIDE CONDENSER
LATRINE. CONTRACTOR SHALL INSTALL DISCONNECT SWITCH AND CONNECT SWITCH TO POWER PANEL WITH PROPER
PROVIDE 208 VOLTS, 60 HZ, 3-PHASE POWER SERVICE TO THE REMOTE CONDENSER UNIT (CD) OUTSIDE THE
DRAWINGS FOR DETAILS.
PROVIDE POWER TO THERMOSTATS THROUGHOUT THE LATRINE. REFER TO MECHANICAL SCOPE OF WORK AND
INSTANTANEOUS HOT WATER HEATER PER MANUFACTURER’S RECOMMENDATIONS.
THE ECO SMART INSTANTANEOUS HOT WATER HEATER UNDER THE MOP SINK. INSTALL POWER SERVICE TO THE
PROVIDE AND INSTALL 2 #10 AWG COPPER CABLES AND 1 #10 AWG COPPER GROUND IN 1/2-INCH CONDUIT FOR
INSTANTANEOUS HOT WATER HEATER PER MANUFACTURER’S RECOMMENDATIONS.
THE ECO SMART INSTANTANEOUS HOT WATER HEATER UNDER THE SINK. INSTALL POWER SERVICE TO THE
PROVIDE AND INSTALL 2 #10 AWG COPPER CABLES AND 1 #10 AWG COPPER GROUND IN 1/2-INCH CONDUIT FOR
SEE DRAWING SHEET 44054-E2.
MOUNTING STRUCTURE FOR THE LIGHT SWITCH AND RECEPTACLE NEAR THE STAIRWAY ABOVE THE MEZZANINE.
OUTLET NEXT TO THE LIGHT SWITCH ABOVE THE MEZZANINE NEAR THE STAIRWAY. PROVIDE AND INSTALL
PROVIDE AND INSTALL 120V, 20A, GENERAL DUPLEX RECEPTACLE AS INDICATED ON THE DRAWING. MOUNT THE
MOUNT THE OUTLET 18-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL 120V, 20A, WEATHER-PROOF GFI RECEPTACLE CIRCUIT AS INDICATED ON THE DRAWING.
18-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL 120V, 20A, GFI RECEPTACLE CIRCUIT AS INDICATED ON DRAWING. MOUNT THE OUTLETS
MOUNT THE OUTLETS 18-INCH ABOVE THE FINISHED FLOOR.
PROVIDE AND INSTALL 120V, 20A, DEDICATED GFI RECEPTACLE CIRCUIT FOR THE WATER DRINKING FOUNTAINS.
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
01 NOV 19
FORT BENNING, GEORGIA
BUILDING 3010 FOR 30TH AG
NEW LATRINE ADDITION
OPEN BREEZWAY
AUDITORIUM
PROCESSING
110 112
CORRIDOR
MECHANICAL
44054-E4
E4
PANEL SCHEDULE
NO.
POLES
TRIP
AMPS
CIRC
NO.
LOAD SERVEDLOAD SERVED
NO.
POLES
TRIP
AMPS
CIRC
NO. CB
PHASE LOAD VA
A
PHASE 3 WIRES 4
PANEL AIC RATING: XX,000 AMPS
VOLTS 120/208SURFACE MOUNTED
LOCATION :
PANEL: NL
MCB: 225 A BY: KMC
100%
75%
TOTAL CONNECTED LOAD
ESTIMATED DEMAND LOAD
15 3
LTG ABOVE MEZZANINE
LTGS ON RIGHT SIDE
LTGS ON LEFT SIDE
ABOVE MEZZANINE REC
B3010 LATRINE
ADDITION
INSTANT. HW (JAN)
INSTANT. HW (1/3)
INSTANT. HW (2/3)
INSTANT. HW (3/3)
INSTANT. HW (2/4)
INSTANT. HW (3/4)
INSTANT. HW (4/4)
INSTANT. HW (1/2)
INSTANT. HW (2/2)
INSTANT. HW (1/4)
JANITOR/OUTSIDE REC
WATER FOUNTAIN REC R
WATER FOUNTAIN REC L
OUTDOOR UNIT
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
1/4-HP EXHAUST FAN
20500 17740 17040
41.46 KVA
55.28 KVA
DEMAND LINE AMPS = 115 A
45INDOOR UNIT 3
20 1SPARE20 1 SPARE
BID DOCUMENTS
85% DESIGN
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
01 NOV 19
FORT BENNING, GEORGIA
BUILDING 3010 FOR 30TH AG
NEW LATRINE ADDITION
| 44054-A0 |
| 44054-C1 |
| 44054-C2 |
| 44054-C3 |
| 44054-A1 |
| 44054-A2 |
| 44054-A3 |
| 44054-A4 |
| 44054-A5 |
| 44054-A6 |
| 44054-A7 |
| 44054-A8 |
| 44054-M1 |
| 44054-P1 |
| 44054-P2 |
| 44054-P3 |
| 44054-P4 |
| 44054-E1 |
| 44054-E2 |
| 44054-E3 |
| 44054-E4 |
| 44054-E1 |
| 44054-E2 |
| 44054-E3 |
| 44054-E4 |