This document contains specifications for concrete reinforcement and a related federal contract opportunity to construct a latrine annex building. The specifications cover requirements for dowels, fabricated bar mats, reinforcing steel, welded wire fabric, wire ties, bar supports, and synthetic fiber reinforcement. Reinforcing steel must meet ASTM standards and contain a minimum of 25% recycled scrap steel. Welding procedures and qualifications are defined. The related federal contract opportunity is issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Eustis to construct a latrine annex building in accordance with the specifications, drawings, and statement of work.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annex Addition to B3010
SECTION 03 20 01 Page 1
SECTION 03 20 01.00 10
CONCRETE REINFORCEMENT
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACI INTERNATIONAL (ACI)
ACI 318 (2008; Errata 2008) Building Code
Requirements for Structural Concrete and Commentary
ACI 318M (2005) Metric Building Code Requirements for
Structural Concrete and Commentary
AMERICAN WELDING SOCIETY (AWS)
AWS D1.4/D1.4M (2005; Errata 2005) Structural Welding Code -
Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A 184/A 184M (2006) Standard Specification for Fabricated
Deformed Steel Bar Mats for Concrete Reinforcement
ASTM A 185/A 185M (2007) Standard Specification for Steel
Welded Wire Reinforcement, Plain, for Concrete
ASTM A 496/A 496M (2007) Standard Specification for Steel Wire, Deformed, for Concrete Reinforcement
ASTM A 497/A 497M (2007) Standard Specification for Steel
Welded Wire Reinforcement, Deformed, for Concrete
ASTM A 53/A 53M (2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A 615/A 615M (2008) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete
ASTM A 675/A 675M (2003e1) Standard Specification for Steel
Bars, Carbon, Hot-Wrought, Special Quality, Mechanical Properties
SECTION 03 20 01 Page 2
ASTM A 706/A 706M (2006a) Standard Specification for Low-Alloy
Steel Deformed and Plain Bars for Concrete
ASTM A 767/A 767M (2005) Standard Specification for Zinc-Coated
(Galvanized) Steel Bars for Concrete
ASTM A 775/A 775M (2007b) Standard Specification for Epoxy-
Coated Steel Reinforcing Bars
ASTM A 82/A 82M (2007) Standard Specification for Steel Wire, Plain, for Concrete Reinforcement
ASTM A 884/A 884M (2006) Standard Specification for Epoxy-
Coated Steel Wire and Welded Wire
ASTM C 1116/C 1116M (2008) Standard Specification for Fiber-
Reinforced Concrete
CONCRETE REINFORCING STEEL INSTITUTE (CRSI)
CRSI 10MSP (2001; 27Ed) Manual of Standard Practice
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control approval.]information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] The following shall be submitted in accordance with Section 01
33 00 SUBMITTAL PROCEDURES:
SD-01 Shop Drawings
Reinforcement; G
Detail drawings showing reinforcing steel placement, schedules, sizes, grades, and splicing and bending details. Drawings shall show support details including types, sizes and spacing.
SD-02 Product Data
Welding
A list of qualified welder’s names.
SD-03 Certificates
Reinforcing Steel
Certified copies of mill reports attesting that the reinforcing steel furnished contains no less than 25 percent recycled scrap steel and meets the requirements specified herein, prior to the installation of reinforcing steel.
SECTION 03 20 01 Page 3
1.3 WELDING
Welders shall be qualified in accordance with AWS D1.4/D1.4M. Qualification test shall be performed at the worksite and the Contractor shall notify the Contracting Officer 24 hours prior to conducting tests. Special welding procedures and welders qualified by others may be accepted as permitted by
AWS D1.4/D1.4M.
1.4 DELIVERY AND STORAGE
Reinforcement and accessories shall be stored off the ground on platforms, skids, or other supports.
PART 2 PRODUCTS
2.1 DOWELS
Dowels shall conform to ASTM A 675/A 675M, Grade 80. Steel pipe conforming to ASTM A 53/A 53M, Schedule 80, may be used as dowels provided the ends are closed with metal or plastic inserts or with mortar.
2.2 FABRICATED BAR MATS
Fabricated bar mats shall conform to ASTM A 184/A 184M.
2.3 REINFORCING STEEL
Reinforcing steel shall be deformed bars conforming to ASTM A 615/A 615M or ASTM A 706/A 706M, grades and sizes as indicated. Cold drawn wire used for spiral reinforcement shall conform to ASTM A 82/A 82M. In highly corrosive environments or when directed by the Contracting Officer, reinforcing steel shall conform to ASTM A 767/A 767M or ASTM A 775/A 775M as appropriate.
2.4 WELDED WIRE FABRIC
Welded wire fabric shall conform to ASTM A 185/A 185M, ASTM A 496/A 496M ASTM A 497/A 497M. When directed by the Contracting Officer for special applications, welded wire fabric shall conform to ASTM A 884/A 884M.
2.5 WIRE TIES
Wire ties shall be 16 gauge or heavier black annealed steel wire.
2.6 SUPPORTS
Bar supports for formed surfaces shall be designed and fabricated in accordance with CRSI 10MSP and shall be steel or precast concrete blocks.
Precast concrete blocks shall have wire ties and shall be not less than 100 by 100 mm( 4 inches square) when supporting reinforcement on ground.
Precast concrete block shall have compressive strength equal to that of the surrounding concrete. Where concrete formed surfaces will be exposed to weather or where surfaces are to be painted, steel supports within 13 mm(
SECTION 03 20 01 Page 4
1/2 inch) of concrete surface shall be galvanized, plastic protected or of stainless steel. Concrete supports used in concrete exposed to view shall have the same color and texture as the finish surface. For slabs on grade, supports shall be precast concrete blocks, plastic coated steel fabricated with bearing plates, or specifically designed wire-fabric supports fabricated of plastic.
2.7 SYNTHETIC FIBER REINFORCEMENT
Synthetic fiber shall be polypropylene with a denier less than 100 and a nominal fiber length of 50 mm( 2 inches).
PART 3 EXECUTION
3.1 REINFORCEMENT
Reinforcement shall be fabricated to shapes and dimensions shown and shall conform to the requirements of ACI 318M( ACI 318). Reinforcement shall be cold bent unless otherwise authorized. Bending may be accomplished in the field or at the mill. Bars shall not be bent after embedment in concrete.
Safety caps shall be placed on all exposed ends of vertical concrete reinforcement bars that pose a danger to life safety. Wire tie ends shall face away from the forms.
3.1.1 Placement
Reinforcement shall be free from loose rust and scale, dirt, oil, or other deleterious coating that could reduce bond with the concrete.
Reinforcement shall be placed in accordance with ACI 318M( ACI 318) at locations shown plus or minus one bar diameter. Reinforcement shall not be continuous through expansion joints and shall be as indicated through construction or contraction joints. Concrete coverage shall be as indicated or as required by ACI 318M( ACI 318). If bars are moved more than one bar diameter to avoid interference with other reinforcement, conduits or embedded items, the resulting arrangement of bars, including additional bars required to meet structural requirements, shall be approved before concrete is placed.
3.1.2 Splicing
Splices of reinforcement shall conform to ACI 318M( ACI 318) and shall be made only as required or indicated. Splicing shall be by lapping or by mechanical or welded butt connection; except that lap splices shall not be used for bars larger than No. 11 unless otherwise indicated. Welding shall conform to AWS D1.4/D1.4M. Welded butt splices shall be full penetration butt welds. Lapped bars shall be placed in contact and securely tied or spaced transversely apart to permit the embedment of the entire surface of each bar in concrete. Lapped bars shall not be spaced farther apart than one-fifth the required length of lap or 150 mm( 6 inches). Mechanical butt splices shall be in accordance with the recommendation of the manufacturer of the mechanical splicing device. Butt splices shall develop 125 percent of the specified minimum yield tensile strength of the spliced bars or of the smaller bar in transition splices. Bars shall be flame dried before butt splicing. Adequate jigs and clamps or other devices shall be provided to support, align, and hold the longitudinal centerline of the bars to be butt spliced in a straight line.
SECTION 03 20 01 Page 5
3.2 WELDED-WIRE FABRIC PLACEMENT
Welded-wire fabric shall be placed in slabs as indicated. Fabric placed in slabs on grade shall be continuous between expansion, construction, and contraction joints. Fabric placement at joints shall be as indicated.
Lap splices shall be made in such a way that the overlapped area equals the distance between the outermost crosswires plus 50 mm( 2 inches). Laps shall be staggered to avoid continuous laps in either direction. Fabric shall be wired or clipped together at laps at intervals not to exceed 1.2 m( 4 feet).
Fabric shall be positioned by the use of supports.
3.3 DOWEL INSTALLATION
Dowels shall be installed in slabs on grade at locations indicated and at right angles to joint being doweled. Dowels shall be accurately positioned and aligned parallel to the finished concrete surface before concrete placement. Dowels shall be rigidly supported during concrete placement.
One end of dowels shall be coated with a bond breaker.
3.4 SYNTHETIC FIBER REINFORCED CONCRETE
Fiber reinforcement shall be added to the concrete mix in accordance with the applicable sections of ASTM C 1116/C 1116M and the recommendations of the manufacturer, and in an amount of 0.1 percent by volume.
-- End of Section --