05 40 00 Cold Form Steel Framing.pdf
PDF 57 KB Posted
- Attached to
- Construct Latrine Annex Building Federal contract opportunity
- Solicitation number
- W911SF-20-B-0001
About this file
This document provides specifications for cold-formed steel framing for the construction of a latrine annex building. The specifications cover steel studs, joists, tracks, bracing and accessories to be made from galvanized or painted steel sheet. Requirements include material standards, connection details, installation methods, quality assurance procedures and defect tolerances. Erection is to follow tolerances of 1/4 inch for finishes and 1/8 inch for ceramic tile. Special inspection and testing is required for seismic resisting systems. The related opportunity is for a firm fixed price construction contract to build the latrine annex in accordance with the provided specifications, drawings and statement of work. The soliciting agency is the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Eustis.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annex Addition to B3010
SECTION 05 40 00 Page 1
SECTION 05 40 00
COLD-FORMED METAL FRAMING
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI SG02-1 (2001) North American Specification for the
Design of Cold-Formed Steel Structural Members
AISI SG03-3 (2002) Cold-Formed Steel Design Manual Set
AMERICAN WELDING SOCIETY (AWS)
AWS D1.3/D1.3M (2008) Structural Welding Code - Sheet Steel
ASTM INTERNATIONAL (ASTM)
ASTM A 1008/A 1008M (2007a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High- Strength Low-Alloy and High-Strength Low- Alloy with Improved Formability, Solution Hardened, and Bake Hardened
ASTM A 1011/A 1011M (2007) Standard Specification for Steel, Sheet, and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy and High- Strength Low-Alloy with Improved Formability
ASTM A 123/A 123M (2002) Standard Specification for Zinc (Hot-
Dip Galvanized) Coatings on Iron and Steel Products
ASTM A 153/A 153M (2005) Standard Specification for Zinc
Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A 370 (2007b) Standard Test Methods and Definitions for Mechanical Testing of Steel Products
ASTM A 653/A 653M (2007) Standard Specification for Steel
Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B 633 (2007) Standard Specification for
Electrodeposited Coatings of Zinc on Iron and Steel
SECTION 05 40 00 Page 2
ASTM C 955 (2008) Load-Bearing (Transverse and Axial)
Steel Studs, Runners (Tracks), and Bracing or Bridging for Screw Application of Gypsum Panel Products and Metal Plaster Bases
ASTM E 329 (2007a) Standard Specification for Agencies
Engaged in the Testing and/or Inspection of Materials Used in Construction
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J78 (1998) Steel Self Drilling Tapping Screws
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 25 (1997; E 2004) Paint Specification No. 25Zinc
Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel Type I and Type II
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] The following shall be submitted in accordance with Section 01
33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Framing Components; G
a. Cross sections, plans, and/or elevations showing component types and locations for each framing application; including shop coatings and material thicknesses for each framing component.
b. Connection details showing fastener type, quantity, location, and other information to assure proper installation.
c. Drawings depicting panel configuration, dimensions, components, locations, and construction sequence if the Contractor elects to install prefabricated/prefinished frames.
SD-03 Product Data
Steel studs, joists, tracks, bracing, bridging and accessories
SD-05 Design Data
Metal framing calculations; G
SD-07 Certificates
Load-bearing cold-formed metal framing
SECTION 05 40 00 Page 3
Mill certificates or test reports from independent testing agency, qualified in accordance with ASTM E 329, showing that the steel sheet used in the manufacture of each cold-formed component complies with the minimum yield strengths and uncoated steel thickness specified. Test reports shall be based on the results of three coupon tests in accordance with ASTM A 370.
Welds
Certified copies of welder qualifications test records showing qualification in accordance with AWS D1.3/D1.3M.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to job site and store in adequately ventilated, dry locations. Storage area shall permit easy access for inspection and handling. If necessary to store materials outside, stack off the ground, support on a level platform, and protect from the weather as approved.
Handle materials to prevent damage. Finish of the framing members shall be maintained at all times, using an approved high zinc dust content, galvanizing repair paint whenever necessary to prevent the formation of rust. Replace damaged items with new, as directed by the Contracting Officer.
1.4 LOAD-BEARING COLD-FORMED METAL FRAMING
Include top and bottom tracks, bracing, fastenings, and other accessories necessary for complete installation. Framing members shall have the structural properties indicated. Where physical structural properties are not indicated, they shall be as necessary to withstand all imposed loads.
Design framing in accordance with AISI SG03-3. Non-load-bearing metal framing, furring, and ceiling suspension systems are specified in Section 09 22 00 METAL SUPPORT ASSEMBLIES. Metal suspension systems for acoustical ceilings are specified in Section 09 51 00 ACOUSTICAL CEILINGS.
1.5 MAXIMUM DEFLECTION
a. Exterior Studs:
Deflection Criteria Exterior Finish
L/240 or L/360 Synthetic Plaster, Metal Panels L/360 Cement Plaster, Wood Veneer L/600 Brick Veneer, Stone Panels
Wall deflections shall be computed on the basis that studs withstand all lateral forces independent of any composite action from sheathing materials.
Studs abutting windows or louvers shall also be designed not to exceed 6 mm( 1/4 inch) maximum deflection.
b. Floor Joists:
L/360 - Live load only L/240 - Total load
c. Roof Rafters:
L/240 - Live load only
SECTION 05 40 00 Page 4
1.6 QUALITY ASSURANCE
1.6.1 Drawing Requirements
Submit framing components to show sizes, thicknesses, layout, material designations, methods of installation, and accessories.
1.6.2 Design Data Required
Submit metal framing calculations to verify sizes, gages, and spacing of members and connections. Show methods and practices used in installation.
PART 2 PRODUCTS
2.1 STEEL STUDS, JOISTS, TRACKS, BRACING, BRIDGING AND ACCESSORIES
Framing components shall comply with ASTM C 955 and the following.
2.1.1 Studs and Joists of 1.5 mm( 16 Gage (0.0598 Inch)) and Heavier
Galvanized steel, ASTM A 653/A 653M, SS Grade 50, Z180 Z275 (G60 G90) ; or carbon steel, ASTM A 1011/A 1011M, Grade 50, painted.
2.1.2 Studs and Joists of 1.2 mm( 18 Gage (0.0478 Inch)) and Lighter
Studs and Joists of 1.2 mm( 18 Gage (0.0478 Inch)) and Lighter, Track, and Accessories (All Gages): Galvanized steel, ASTM A 653/A 653M, SS, Grade 345 230 MPa( Grade 50 33,000 psi) Z180( G60) [; or carbon steel, ASTM A 1008/A 1008M, Grade C, painted].
2.1.3 Sizes, Gages, Section Modulus, and Other Structural Properties
Size and gage as indicated. Steel stud deflection shall be limited to L/600 for exterior wall brick veneer construction.
2.2 MARKINGS
Studs and track shall have product markings stamped on the web of the section. The markings shall be repeated throughout the length of the member at a maximum spacing of 1200 mm (4 feet) on center and shall be legible and easily read. The product marking shall include the following:
a. An ICBO number.
b. Manufacturer's identification.
c. Minimum delivered uncoated steel thickness.
d. Protective coating designator.
e. Minimum yield strength.
SECTION 05 40 00 Page 5
2.3 CONNECTIONS
Screws for steel-to-steel connections shall be self-drilling tapping in compliance with SAE J78 of the type, size, and location as shown on the drawings. Electroplated screws shall have a Type II coating in accordance with ASTM B 633. Screws, bolts, and anchors shall be hot-dipped galvanized in accordance with ASTM A 123/A 123M or ASTM A 153/A 153M as appropriate.
Screws bolts, and anchors shall be hot dipped galvanized in accordance with ASTM A 123/A 123M or ASTM A 153/A 153M as appropriate.
[2.4 PAINT
Ungalvanized steel, if used, shall be thoroughly cleaned, phosphate treated, and coated with corrosion-inhibiting primer, SSPC Paint 25.
]2.5 PLASTIC GROMMETS
Supply plastic grommets, recommended by stud manufacturer, to protect electrical wires. Prevent metal to metal contact for plumbing pipes.
PART 3 EXECUTION
3.1 FASTENING
Fasten framing members together by welding or by using self-drilling or self-tapping screws. Electrodes and screw connections shall be as required and indicated in the design calculations.
3.1.1 Welds
All welding shall be performed in accordance with AWS D1.3/D1.3M, as modified by AISI SG02-1. All welders, welding operations, and welding procedures shall be qualified according to AWS D1.3/D1.3M. All welds shall be cleaned and coated with rust inhibitive galvanizing paint. Do not field weld materials lighter than 1.2 mm( 18 gage).
3.1.2 Screws
Screws shall be [of the] [self-drilling self-tapping]type, size, and location shown on the drawings. Screw penetration through joined materials shall not be less than three exposed threads. Minimum spacings and edge distances for screws shall be as specified in AISI SG02-1. Screws covered by sheathing materials shall have low profile heads.
3.1.3 Anchors
Anchors shall be of the type, size, and location shown on the drawings.
3.2 INSTALLATION
3.2.1 Tracks
Provide accurately aligned runners at top and bottom of partitions. Anchor tracks as indicated in design calculations. Butt weld joints in tracks or splice with stud inserts. Fasteners shall be at least 75 mm( 3 inches) from the edge of concrete slabs.
SECTION 05 40 00 Page 6
3.2.2 Studs
Cut studs square and set with firm bearing against webs of top and bottom tracks. Position studs vertically in tracks and space as indicated in design. Do not splice studs. Provide at least two studs at jambs of doors and other openings 600 mm( 2 feet) wide or larger. Provide jack studs over openings, as necessary, to maintain indicated stud spacing. Provide tripled studs at corners, positioned to receive interior and exterior finishes.
Fasten studs to top and bottom tracks by welding or screwing both flanges to the tracks. Framed wall openings shall include headers and supporting components as shown on the drawings. Headers shall be installed in all openings that are larger than the stud spacing in a wall. In curtain wall construction, provide for vertical movement where studs connect to the structural frame. Provide horizontal bracing in accordance with the design calculations and AISI SG03-3, consisting of, as a minimum, runner channel cut to fit between and welded to the studs or hot- or cold-rolled steel channels inserted through cutouts in web of each stud and secured to studs with welded clip angles. Bracing shall be not less than the following:
LOAD HEIGHT BRACING
Wind load only Up to 3000 mm One row at mid-height Over 3000 mm Rows 1500 mm o.c. maximum
Axial load Up to 3000 mm Two rows at 1/3 points Over 3000 mm Rows 900 mm o.c. maximum
LOAD HEIGHT BRACING
Wind load only Up to 10 feet One row at mid-height Over 10 feet Rows 5'-0" o.c. maximum
Axial load Up to 10 feet Two rows at 1/3 points Over 10 feet Rows 3'-4" o.c. maximum
3.2.3 Joists and Trusses
Locate each joist or truss directly above a stud. Provide doubled joists under parallel partitions wherever partition length exceeds 1/2 of joist span. Joists shall have at least 60 mm( 2.50 inches) of bearing on steel, 100 mm( 4 inches) on masonry, and shall be reinforced over bearings where required to prevent web crippling. Splice joists over bearings only. Lap and weld splices as indicated. Provide manufacturer's standard bridging which shall not be less than the following:
CLEAR SPAN BRIDGING
Up to 4200 mm One row near center 4200 mm to 6000 mm Two rows at 1/3 points 6000 mm to 7800 mm Three rows at 1/4 points 7800 mm to 10600 mm Four rows at 1/5 points
CLEAR SPAN BRIDGING
Up to 14 feet One row near center 14 to 20 feet Two rows at 1/3 points 20 to 26 feet Three rows at 1/4 points
SECTION 05 40 00 Page 7
26 to 32 feet Four rows at 1/5 points Temporary bracing shall be provided and remain in place until work is permanently stabilized.
3.2.4 Erection Tolerances
a. Framing members which will be covered by finishes such as wallboard, plaster, or ceramic tile set in a mortar setting bed, shall be within the following limits:
(1) Layout of walls and partitions: 6 mm( 1/4 inch) from intended position;
(2) Plates and runners: 6 mm in 2400 mm( 1/4 inch in 8 feet) from a straight line;
(3) Studs: 6 mm in 2400 mm( 1/4 inch in 8 feet) out of plumb, not cumulative; and
(4) Face of framing members: 6 mm in 2400 mm( 1/4 inch in 8 feet) from a true plane.
b. Framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive shall be within the following limits:
(1) Layout of walls and partitions: 6 mm( 1/4 inch) from intended position;
(2) Plates and runners: 3 mm in 2400 mm( 1/8 inch in 8 feet) from a straight line;
(3) Studs: 3 mm in 2400 mm( 1/8 inch in 8 feet) out of plumb, not cumulative; and
(4) Face of framing members: 3 mm in 2400 mm( 1/8 inch in 8 feet) from a true plane.
3.2.5 Special Inspection and Testing for Seismic-Resisting Systems
Special inspections and testing for seismic-resisting systems and components shall be done in accordance with Section 01 45 35 SPECIAL INSPECTION FOR
SEISMIC-RESISTING SYSTEMS.
-- End of Section --
File details come from the government source that posted it. Updated .