07 21 16 Mineral Fiber Blanket Insul.pdf
PDF 56 KB Posted
- Attached to
- Construct Latrine Annex Building
- Solicitation number
- W911SF-20-B-0001
About this file
This document contains technical specifications for mineral fiber blanket insulation and vapor retarders for use in an annex addition project. Key details include:
-
Mineral fiber blanket insulation is specified to meet ASTM C665 Type I, II, or III standards with various Class A or B flame/smoke ratings. Thermal resistance values and installation methods are defined. Recycled material content is required.
-
Other materials such as sill sealer insulation, blocking, and vapor retarders made of polyethylene sheeting or membrane are also specified. Pressure sensitive tape and accessories are identified.
-
Submittal requirements, product data, manufacturer instructions, delivery and storage procedures, safety precautions for installers, and installation methods are outlined in detail. Special installation considerations are given for areas like ceilings, floors, around heat sources, and with or without affixed vapor retarders.
The related federal contract opportunity is to construct a latrine annex building in accordance with the attached statement of work, drawings, and technical specifications, suggesting this document provides specifications for the insulation and vapor retarder materials to be used on that project for the annex addition.
View the file
Other files
Show 40 more
Latest 50 of 72 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annex Addition to B3010
SECTION 07 21 16 Page 1
SECTION 07 21 16
MINERAL FIBER BLANKET INSULATION
PART 1 GENERAL
1.1 REFERENCES
See Scope of Work for additional information.
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C 665 (2006) Mineral-Fiber Blanket Thermal
Insulation for Light Frame Construction and Manufactured Housing
ASTM C 930 (2005) Potential Health and Safety Concerns
Associated with Thermal Insulation Materials and Accessories
ASTM D 3833/D 3833M (1996; R 2006) Water Vapor Transmission of
Pressure-Sensitive Tapes
ASTM D 4397 (2002) Standard Specification for
Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications
ASTM D 828 (1997; R 2002) Tensile Properties of Paper and Paperboard Using Constant-Rate-of- Elongation Apparatus
ASTM E 136 (2004) Behavior of Materials in a Vertical
Tube Furnace at 750 Degrees C
ASTM E 84 (2008a) Standard Test Method for Surface
Burning Characteristics of Building Materials
ASTM E 96/E 96M (2005) Standard Test Methods for Water Vapor
Transmission of Materials
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 211 (2006) Chimneys, Fireplaces, Vents, and Solid
Fuel-Burning Appliances
NFPA 31 (2006; Errata 2006; Errata 2007) Installation of Oil Burning Equipment
NFPA 54 (2006) National Fuel Gas Code
NFPA 70 (2007) National Electrical Code - 2008
Edition
SECTION 07 21 16 Page 2
TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)
TAPPI T803 OM (2006) Puncture Test of Container Board
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.134 Respiratory Protection
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control approval.for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] The following shall be submitted in accordance with Section 01
33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Blanket insulation
Sill sealer insulation
Vapor retarder
Pressure sensitive tape
Accessories
SD-08 Manufacturer's Instructions
Insulation
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow.
Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.3.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.
1.4 SAFETY PRECAUTIONS
SECTION 07 21 16 Page 3
1.4.1 Respirators
Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134.
1.4.2 Smoking
Do not smoke during installation of blanket thermal insulation.
1.4.3 Other Safety Concerns
Consider other safety concerns and measures as outlined in ASTM C 930.
PART 2 PRODUCTS
2.1 BLANKET INSULATION
ASTM C 665, Type I, blankets without membrane coverings and II, blankets with non-reflecting coverings and III, blankets with reflective coverings;
Class A, membrane-faced surface with a flame spread of 25 or less B, membrane-faced surface with a flame propagation resistance; critical radiant flux of 0.12 W/m2( 0.11 Btu/ft2) or greater, except a flame spread rating of 25 or less and a smoke developed rating of 150 or less when tested in accordance with ASTM E 84.
2.1.1 Thermal Resistance Value (R-VALUE)
As indicated
2.1.2 Recycled Materials
Provide Thermal Insulation containing recycled materials to the extent practicable, provided the material meets all other requirements of this section. The minimum required recycled materials content by weight are:
Rock Wool: 75 percent slag Fiberglass: 20 to 25 percent glass cullet
2.1.3 Prohibited Materials
Do not provide asbestos-containing materials.
2.2 SILL SEALER INSULATION
ASTM C 665, Type I.
2.3 BLOCKING
Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C 665, Type I, or other approved materials. Use only non-combustible materials meeting the requirements of ASTM E 136 for blocking around chimneys and heat producing devices.
SECTION 07 21 16 Page 4
2.4 VAPOR RETARDER
a. 0.15 mm( 6 mil) thick polyethylene sheeting conforming to ASTM D 4397 and having a water vapor permeance of 5.72 x 10-8g/Pa.s.m2( 1 perm) or less when tested in accordance with ASTM E 96/E 96M.
b. Membrane with the following properties:
Water Vapor Permeance: ASTM E 96/E 96M: 5.72 x 10-8 g/Pa.s.m2 (1 perm) Maximum Flame Spread: ASTM E 84: 25 Combustion Characteristics: Passing ASTM E 136] Puncture Resistance: TAPPI T803 OM: 50 Tensile Strength: ASTM D 828: 35
]2.5 PRESSURE SENSITIVE TAPE
As recommended by the vapor retarder manufacturer and having a water vapor permeance rating of 5.72 x 10-8 g/Pa.s.m2( one perm) or less when tested in accordance with ASTM D 3833/D 3833M.
2.6 ACCESSORIES
2.6.1 Adhesive
As recommended by the insulation manufacturer.
2.6.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
2.6.3 Wire Mesh
Corrosion resistant and as recommended by the insulation manufacturer.
PART 3 EXECUTION
3.1 EXISTING CONDITIONS
Before installing insulation, ensure that areas that will be in contact with the insulation are dry and free of projections which could cause voids, compressed insulation, or punctured vapor retarders. If moisture or other conditions are found that do not allow the workmanlike installation of the insulation, do not proceed but notify Contracting Officer of such conditions.
3.2 PREPARATION
3.2.1 Blocking at Attic Vents and Access Doors
Prior to installation of insulation, install permanent blocking to prevent insulation from slipping over, clogging, or restricting air flow through soffit vents at eaves. Install permanent blocking around attic trap doors.
Install permanent blocking to maintain accessibility to equipment or controls that require maintenance or adjustment.
3.2.2 Blocking Around Heat Producing Devices
SECTION 07 21 16 Page 5
Install non-combustible blocking around heat producing devices to provide the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless these are certified by the manufacturer for installation surrounded by insulation: 75 mm( 3 inches) from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is to be placed above fixture or device, 600 mm( 24 inches) above fixture.
b. Masonry chimneys or masonry enclosing a flue: 50 mm( 2 inches) from outside face of masonry. Masonry chimneys for medium and high heat operating appliances: Minimum clearances required by NFPA 211.
c. Vents and vent connectors used for venting the products of combustion, flues, and chimneys other than masonry chimneys:
Minimum clearances as required by NFPA 211.
f. Gas Fired Appliances: Clearances as required in NFPA 54.
g. Oil Fired Appliances: Clearances as required in NFPA 31.
Blocking around flues and chimneys is not required when insulation blanket, including any attached vapor retarder, passed ASTM E 136, in addition to meeting all other requirements stipulated in Part 2. Blocking is also not required if the chimneys are certified by the manufacturer for use in contact with insulating materials.
3.3 INSTALLATION
3.3.1 Insulation
Install and handle insulation in accordance with manufacturer's instructions. Keep material dry and free of extraneous materials. Ensure personal protective clothing and respiratory equipment is used as required.
Observe safe work practices.
3.3.1.1 Electrical wiring
Do not install insulation in a manner that would sandwich electrical wiring between two layers of insulation.
3.3.1.2 Continuity of Insulation
Install blanket insulation to butt tightly against adjoining blankets and to studs, rafters, joists, sill plates, headers and any obstructions. Where insulation required is thicker than depth of joist, provide full width blankets to cover across top of joists. Provide continuity and integrity of insulation at corners, wall to ceiling joints, roof, and floor. Avoid creating thermal bridges.
3.3.1.3 Installation at Bridging and Cross Bracing
Insulate at bridging and cross bracing by splitting blanket vertically at center and packing one half into each opening. Butt insulation at bridging and cross bracing; fill in bridged area with loose or scrap insulation.
SECTION 07 21 16 Page 6
3.3.1.4 Cold Climate Requirement
Place insulation to the outside of pipes.
3.3.1.5 Insulation Blanket with Affixed Vapor Retarder
Locate vapor retarder as indicated. Do not install blankets with affixed vapor retarders unless so specified. Unless the insulation manufacturer's instructions specifically recommend not to staple the flanges of the vapor retarder facing, staple flanges of vapor retarder at 150 mm( 6 inch) intervals flush with face or set in the side of truss, joist, or stud.
Avoid gaps and bulges in insulation and "fishmouth" in vapor retarders.
Overlap both flanges when using face method. Seal joints and edges of vapor retarder with pressure sensitive tape. Stuff pieces of insulation into small cracks between trusses, joists, studs and other framing, such as at attic access doors, door and window heads, jambs, and sills, band joists, and headers. Cover these insulated cracks with vapor retarder material and tape all joints with pressure sensitive tape to provide air and vapor tightness.
3.3.1.6 Insulation without Affixed Vapor Retarder
Provide snug friction fit to hold insulation in place. Stuff pieces of insulation into cracks between trusses, joists, studs and other framing, such as at attic access doors, door and window heads, jambs, and sills, band joists, and headers.
3.3.1.7 Sizing of Blankets
Provide only full width blankets when insulating between trusses, joists, or studs. Size width of blankets for a snug fit where trusses, joists or studs are irregularly spaced.
3.3.1.8 Special Requirements for Ceilings
Place insulation under electrical wiring occurring across joists. Pack insulation into narrowly spaced framing. Do not block flow of air through soffit vents. [Attach insulation to attic door by adhesive or staples.]
3.3.1.9 Installation of Sill Sealer
Size sill sealer insulation and place insulation over top of masonry or concrete perimeter walls or concrete perimeter floor slab on grade. Fasten sill plate over insulation.
3.3.1.10 Special Requirements for Floors
Hold insulation in place with corrosion resistant wire mesh, wire fasteners, or wire lacing.
3.3.1.11 Access Panels and Doors
Affix blanket insulation to access panels greater than one square foot and access doors in insulated floors and ceilings. Use insulation with same R- Value as that for floor or ceiling.
SECTION 07 21 16 Page 7
3.3.2 Installation of Separate Vapor Retarder
Apply continuous vapor retarder as indicated. Overlap joints at least 150 mm( 6 inches) and seal with pressure sensitive tape. Seal at sill, header, windows, doors and utility penetrations. Repair punctures or tears with pressure sensitive tape.
-- End of Section --