This document contains a federal specification section outlining requirements for low-voltage motors to be used on a federal construction project. The specification details motor design standards including efficiency levels in accordance with DOE guidelines. Motors must be rated for continuous operation at 104 degrees Fahrenheit with Class B or higher insulation. Enclosures are to be totally enclosed fan-cooled with hinged access for vibration monitoring. Factory and site testing requirements are specified, include vibration analysis of bearing housing collection points. Motors over 25 horsepower must have alignment jack bolts, and final alignment settings must be reported. The related federal contract opportunity is to construct a Latrine Annex Building at Fort Eustis in accordance with provided specifications, drawings and statements of work.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UFGS
SECTION 26 60 13 Page 1
SECTION 26 60 13.00 40
LOW-VOLTAGE MOTORS
08/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN BEARING MANUFACTURERS ASSOCIATION (ABMA)
ABMA 11 (1990; R 1999) Load Ratings and Fatigue Life for Roller Bearings
ABMA 9 (1990; R 2000) Load Ratings and Fatigue Life for Ball Bearings
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE Std 112 (2004) Standard Test Procedure for Polyphase
Induction Motors and Generators
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ACCEPT (2003) The NETA Acceptance Testing
Specifications
NETA MAINT (2005) Maintenance Testing Specifications for
Electric Power Distribution Equipment and
Systems
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ISO 1940-1 (2003; Corrigendum 2005) Mechanical Vibration
- Balance Quality Requirements for Rotors in a Constant (Rigid) State - Part 1:
Specification and Verification of Balance
Tolerance - International Restrictions
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA MG 1 (2007) Standard for Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2007) National Electrical Code - 2008
Edition
U.S. DEPARTMENT OF ENERGY (DOE)
DOE CI-1 (2001) How to Buy a Premium Energy-Efficient
Electric Motor
SECTION 26 60 13 Page 2
1.2 GENERAL REQUIREMENTS
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Outline drawings for Motors shall indicate overall physical features, dimensions, ratings, service requirements, and weights of equipment.
SD-03 Product Data
Equipment and performance data shall be submitted for Motors consisting of use life, system functional flows, safety features, and mechanical automated details. Curves indicating tested and certified equipment response and performance characteristics shall also be submitted.
Submit Manufacturer's Catalog Data in accordance with paragraph entitled, "Equipment," of this section
For Electric Motors rated over 20 hp and those specified to meet a special vibration class in accordance with NEMA MG 1 indicates number of:
Rotor Bars
Stator Slots
Rotational Speed
Cooling Fan Blades
Bearing Manufacturer
Bearing Style
Bearing Type
Balls/Elements
Commutator Bars
Commutator Brushes
SCR Firing Frequencies (for variable speed motors)
SD-07 Certificates
Certificates shall be submitted for the following tests showing conformance with the referenced standards contained in this section. Certified copies of previous test reports on identical motors may be submitted in lieu of factory test reports.
Factory Test Results
Efficiency
Power-Factor
../26%2000%2000.00%2020.doc ../01%2033%2000.doc
SECTION 26 60 13 Page 3
Service Factor
Temperature Rating
Noise
Full-Load
Locked-Rotor
Insulation Resistance
Winding Resistance
High-Potential Tests
SD-08 Manufacturer's Instructions
Manufacturer's Instructions shall be submitted for Motors including special provisions required to install equipment components and system packages. Special notices shall detail impedances, hazards and safety precautions.
1.4 DESIGN REQUIREMENTS
The following motor design data shall be provided prior to final turnover-number of motor rotor bars, Stator slots, rotational speed; number of cooling fan blades; RPM of motor; bearing manufacturer, bearing type, bearing style and number of balls/elements; number of commutator bars and commutator brushes; and SCR firing frequencies.
PART 2 PRODUCTS
2.1 EQUIPMENT
Submit manufacturer's catalog data for motors and enclosures.
Design, fabrication, testing, and performance of motors shall be in accordance with NEMA MG 1 and ISO 1940-1 and shall meet or exceed the requirements as specified herein.
Testing and performance of polyphase induction motors shall be in accordance with IEEE Std 112, Method B.
Efficiency labeling shall be in accordance with NEMA MG 1.
Allowable balance limits shall be in accordance with ISO 1940-1, Table 1
2.1.1 Efficiency
Metric motor sizes shall be converted to English units by multiplying the kilowatt rating by 1.34 to determine the horsepower equivalent. The result shall be compared to the motor sizes listed in DOE CI-1 and the closest size listed to the horsepower equivalent shall be used for determining efficiencies.
(Motors shall have efficiencies in accordance with the recommended levels specified in DOE CI-1.)
2.2 MOTOR TYPES
Motor shall be marked to show the index letter, which shall be the letter shown or a letter that indicates a higher efficiency.
SECTION 26 60 13 Page 4
Motors shall be of the following types:
250 watt rating (1/3 HP) and smaller, single phase - capacitor start
375 watt (1/2 HP) and larger, three-phase - induction squirrel-cage type, NEMA Design B, having normal starting torque and low starting current
Motors shall be designed for across-the-line starting and shall be designed with torque characteristics to carry the specified rated starting load.
Motors shall have factory-sealed ball bearings with an L-10 rated life of not less than 50,000 hours in accordance with ABMA 9 or ABMA 11.
2.3 SIZES OF MOTORS
2.3.1 Motors
Motors shall be of a sufficient size for the duty to be performed and shall not exceed the full-load rating when the driven equipment is operating at specified capacity under the most severe loading conditions.
2.3.2 Electrically Driven Equipment
When electrically driven equipment differs from that indicated, adjustments shall be made to the motor size, wiring and conduit systems disconnect devices, and circuit protection to accommodate the equipment actually installed, at no additional cost to the Government. Control and protective devices shall be in accordance with Section 26 05 73.00 40 OVERCURRENT
PROTECTIVE DEVICES.
2.4 VOLTAGE RATINGS
Motors shall have the following minimum voltage ratings:
MOTOR SIZE MOTOR
MOTOR TYPE HORSEPOWER SERVICE VOLTAGE RATING
Fractional 1/3 and 120/208-volt, 115-volt, Horsepower, smaller 3-phase, 60-hertz
Single-Phase 4-wire
Fractional 1/2 and 120/208-volt, 200-volt, And Integral larger 3-phase, 3-phase
Horsepower, 4-wire 60-hertz
3-Phase
Fractional 1/2 and 480-volt, 230/460-volt, And Integral larger 3-phase, 3-phase, Horsepower, 3-wire 60-hertz
3-Phase
2.5 TEMPERATURE RATING AND INSULATION
Motors shall be designed for continuous operation at the rated full load in an ambient temperature of 104 degrees F.
../26%2005%2073.00%2040.doc
SECTION 26 60 13 Page 5
Insulation level shall be at least Class B.
2.6 MOTOR HOUSINGS
The motor housing shall have a smooth surface in the vertical, horizontal, and axial directions at each bearing housing for attaching a magnet mounted accelerometer in order to monitor the motor vibration. The surface shall be on the bearing housing. The axial surface will be as close to the motor centerline as possible. The surface will have a finish of 63 micro-inch minimum. Diameter of finished surface shall be 2 inch minimum and must be corrosion resistant. As an option sound disks can be used to meet the smooth surface requirement. Disk shall have a minimum thickness of 3/8 inch.
Surface shall be level within 1 degree or 0.001 inch.
The smooth surface shall be identified (using a label or plate) "Vibration data collection point - Do Not Paint"
2.7 MOTOR ENCLOSURES
Motors installed in indoor, nonhazardous locations where it is necessary to protect the motor from dirt, moisture, chemical fumes, or other harmful ingredients in the surrounding atmosphere shall be the totally enclosed type, with either of the following:
Totally enclosed fan-cooled enclosures for exterior cooling by means of a fan or fans integral with the machine but external to the enclosing parts. Enclosures shall have a hinged access cover at each vibration collection point. Cover must be large enough to enable the placement of a magnet/accelerometer data collection instrument.
2.8 SERVICE FACTOR
Service factor of general purpose and other open ac motors shall be in accordance with NEMA MG 1.
Totally enclosed ac motors shall have a service factor of 1.15.
2.9 FACTORY TESTS
Factory test all motors in accordance with the requirements of NEMA MG 1.
Polyphase induction motors shall be factory-tested in accordance with IEEE
Std 112, Method B. Tests shall consist of measurements of voltage, frequency, speed, and current under no-load conditions; voltage, frequency, and current under locked-rotor conditions; and efficiency, noise, power factor, and thermal protection. Routine tests on wound-rotor induction motors shall include the measurement of wound-rotor open-circuit voltage across the slip rings under locked-rotor conditions. Electrical tests shall consist of winding resistance, insulation resistance, and high-potential tests. Submit certified copies of factory test results for approval prior to shipment from the factory. Previous test reports on identical motors are not acceptable for these tests.
PART 3 EXECUTION
3.1 INSTALLATION
SECTION 26 60 13 Page 6
Motors shall be installed, aligned, and connected in accordance with the equipment manufacturer's instructions.
Motors shall be bolt mounted. Motor feet shall be coplanar within 0.001 inch. Base mounting points shall be accessible and adjustable to enable machine alignment. Motors over 25 hp shall have alignment jack bolts installed to enable alignment.
Alignment of motors shall be rechecked and adjusted as required after the motor has been in operation for not less than 48 hours.
3.2 ALIGNMENT
Before attempting alignment, the contractor will demonstrate that the load does not have any load/force imposed by the piping system. Minimum alignment values (below) are for motor and load at normal running temperatures. Values must be compensated for thermal growth. Limited movement of the motor or load (commonly known as bolt-bound) must be corrected to ensure alignment capability. Hold down bolts shall not be undercut in order to perform adjustment.
Shims shall be commercially die-cut, without seams or folds, and be made of corrosion resistant stainless steel. No more than four shims shall be used at any single point.
Motor and load shall be aligned to the following minimum specifications:
Speed(RPM) Close-Coupled Close-Coupled Spool Piece Angle
Offset (mils) Angle(mils/in.) (mils/in. @ coupling pt.)
600 6.0 2.0 3.0
900 5.0 1.5 2.0
1200 4.0 1.0 1.5
1800 3.0 0.5 1.0
3600 1.5 0.4 0.5
7200 1.0 0.3 0.4
Motor/load alignment shall be performed under the direction of the manufacturer's representative.
Final alignment settings shall be provided as part of the final test data.
3.3 ELECTRICAL TESTS
Perform continuity test on all phases.
Perform insulation resistance and polarization index test on each phase of motor. Insulation tests on 480-volt and 600-volt motors shall be conducted using a 1000-volt insulation test set. Insulation tests on motors rated less than 480-volts shall be conducted using 500-volt insulation test set.
Test data shall include the location and identification of motors and megohm readings versus time. Test data shall be recorded at 15, 30, 45 seconds, and in 1 minute increments thereafter up to 10 minutes. Megohm readings shall not be less than 25 megohms for each phase and each phase reading shall be within 10 percent of the other two.
SECTION 26 60 13 Page 7
Perform inspections and test procedures on all motors in accordance with
NETA ACCEPT and NETA MAINT 7.15.1 for rotating machinery, AC motors.
Calculate the polarization index of each phase by dividing the 10 minute reading by the 1 minute reading. The polarization index shall be greater than 1.25. Any values lower shall be rejected and the motor returned to the factory.
3.4 VIBRATION TESTS
3.4.1 Vibration Analyzer
Contractor shall use a Fast Fourier Transformer (FFT) analyzer to measure vibration levels. It shall have the following characteristics: A dynamic range greater than 70 dB; a minimum of 400 line resolution; a frequency response range of 5 Hz-10 KHz (300-600000 cpm); the capacity to perform ensemble averaging, the capability to use a Hanning window; auto-ranging frequency amplitude; a minimum amplitude accuracy over the selected frequency range of plus or minus 20 percent or plus or minus 1.5 dB.
An accelerometer, either stud-mounted or mounted using a rare earth, low mass magnet and sound disk (or finished surface) shall be used with the FFT analyzer to collect data. The mass of the accelerometer and its mounting shall have minimal influence on the frequency response of the system over the selected measurement range.
3.4.2 Vibration Data
Vibration data shall be collected in the axial, vertical, and horizontal direction for each motor bearing.
Two narrowband spectra for each data collection point shall be obtained in the following manner: For all machines regardless of operating speed, a 5 to
500 Hz spectrum with a minimum of 400 lines of resolution shall be obtained.
An additional spectrum of 5 to 2500 or 5 to 5000 Hz shall be acquired for machines operating at or below 1800 RPM or greater than 1800 RPM, respectively.
Vibration limits shall conform to the following:
Frequency Range (CPM) Vibration limit (inch/sec)
0.3xRPM to 0.8xRPM 0.04
0.8xRPM to 1.2xRPM 0.75
1.2xRPM to 3.5xRPM 0.04
3.5xRPM to 120,000cpm 0.03
Final test reports shall be provided to the Contracting Officer. Reports shall have a cover letter/sheet clearly marked with the System name, Date, and the words "Final Test Reports - Forward to the Systems
<NED/>Engineer/Condition Monitoring Office/Predictive Testing Group for inclusion in the Maintenance Database."
-- End of Section