This document provides specifications for gypsum board and related materials for use in the construction of a latrine annex building. Key details include requirements for gypsum board, water-resistant gypsum board, joint treatment materials, fasteners, and accessories. The specifications define material standards, sustainable design criteria, submittal requirements, delivery and storage instructions, and installation methods. They also address environmental conditions, qualifications, scheduling, fire resistance, patching, and waste management. The related federal contract opportunity is to construct the latrine annex building in accordance with the attached statement of work, drawings, and these gypsum board specifications issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort Eustis.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annex Addition to B3010
SECTION 09 29 00 Page 1
SECTION 09 29 00
GYPSUM BOARD
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992) Interior Installation of Cementitious
Backer Units
ANSI/CTI A108/A118/A136.1 (2005) Specification for the Installation of
Ceramic Tile
ASTM INTERNATIONAL (ASTM)
ASTM C 1002 (2007) Standard Specification for Steel Self-
Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1047 (2005) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C 1177/C 1177M (2006) Standard Specification for Glass Mat
Gypsum Substrate for Use as Sheathing
ASTM C 1178/C 1178M (2006) Standard Specification for Glass Mat
Water-Resistant Gypsum Backing Panel
ASTM C 1396/C 1396M (2006a) Standard Specification for Gypsum
Board
ASTM C 36/C 36M (2003e1) Gypsum Wallboard
ASTM C 442/C 442M (2004e1) Gypsum Backing Board, Gypsum
Coreboard, and Gypsum Shaftliner Board
ASTM C 475/C 475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C 514 (2004) Standard Specification for Nails for the Application of Gypsum Board
ASTM C 557 (2003e1) Adhesives for Fastening Gypsum
Wallboard to Wood Framing
ASTM C 630/C 630M (2003e1) Water-Resistant Gypsum Backing Board
SECTION 09 29 00 Page 2
ASTM C 79/C 79M (2004a) Treated Core and Nontreated Core Gypsum Sheathing Board
ASTM C 840 (2007) Application and Finishing of Gypsum
ASTM C 954 (2007) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
ASTM C 960/C 960M (2004) Predecorated Gypsum Board
ASTM D 1037 (2006a) Evaluating Properties of Wood-Base
Fiber and Particle Panel Materials
ASTM D 1149 (2007) Standard Test Method for Rubber
Deterioration - Surface Ozone Cracking in a Chamber
ASTM D 226 (2006) Standard Specification for Asphalt-
Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D 2394 (2005e1) Simulated Service Testing of Wood and Wood-Base Finish Flooring
ASTM D 412 (2006a) Standard Test Methods for Vulcanized
Rubber and Thermoplastic Elastomers - Tension
ASTM D 5420 (2004) Impact Resistance of Flat, Rigid
Plastic Specimen by Means of a Strike Impacted by a Falling Weight (Gardner Impact)
ASTM D 624 (2000; R 2007) Tear Strength of Conventional
Vulcanized Rubber and Thermoplastic Elastomers
ASTM E 2129 (2005) Standard Practice for Data Collection for Sustainability Assessment of Building Products
ASTM E 695 (2003) Measuring Relative Resistance of
Wall, Floor, and Roof Construction to Impact Loading
ASTM E 84 (2008a) Standard Test Method for Surface
Burning Characteristics of Building Materials
GYPSUM ASSOCIATION (GA)
GA 214 (1996) Recommended Levels of Gypsum Board
Finish
GA 216 (2004) Application and Finishing of Gypsum
SECTION 09 29 00 Page 3
GA 224 (1997) Installation of Predecorated Gypsum
GA 253 (1999) Application of Gypsum Sheathing
GA 600 (2003) Fire Resistance Design Manual
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED (2002; R 2005) Leadership in Energy and
Environmental Design(tm) Green Building Rating System for New Construction (LEED-NC)
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2008) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Product Data
Glass Mat Water-Resistant Gypsum Tile Backing Board
Glass Mat Covered or Reinforced Gypsum Sheathing
Glass Mat Covered or Reinforced Gypsum Sheathing Sealant
Impact Resistant Gypsum Board
Accessories
Submit for each type of gypsum board and for cementitious backer units.
Gypsum Board; (LEED)
Submit documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.
Adhesives; (LEED)
Joint Treatment Materials
Submit manufacturer's product data, indicating VOC content.
Local/Regional Materials; (LEED)
SECTION 09 29 00 Page 4
Documentation indicating distance between manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included in project.]
Environmental Data
SD-02 Certificates
Asbestos Free Materials; G
Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.
SD-03 Manufacturer's Instructions
Material Safety Data Sheets
SD-04 Operation and Maintenance Data
Manufacturer maintenance instructions
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.3.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range.
Gypsum wallboard shall not be stored with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives.
1.3.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Temperature
SECTION 09 29 00 Page 5
Maintain a uniform temperature of not less than 10 degrees C( 50 degrees F) in the structure for at least 48 hours prior to, during, and following the application of gypsum board, cementitious backer units, and joint treatment materials, or the bonding of adhesives.
1.4.2 Exposure to Weather
Protect gypsum board and cementitious backer unit products from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
1.4.3 Temporary Ventilation
Provide temporary ventilation for work of this section.
1.5 SUSTAINABLE DESIGN REQUIREMENTS
1.5.1 Local/Regional Materials
Use materials or products extracted, harvested, or recovered, as well as manufactured, within a (500 mile ) 800 kilometer radius from the project site, if available from a minimum of three sources. See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total local material requirements.
Gypsum board materials may be locally available.
1.5.2 Environmental Data
Submit Table 1 of ASTM E 2129 for the following products:
1.6 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
1.7 SCHEDULING
The gypsum wall board shall be taped, spackled and primed before the installation of the highly-emitting materials. Gypsum wallboard shall be installed after the installation and ventilation period of the highly-emitting materials.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only.
Submit Material Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Gypsum Board
ASTM C 36/C 36M and ASTM C 1396/C 1396M. Gypsum board shall contain a minimum of 5 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content. No Paper facings. Gypsum cores shall contain a minimum of 95 percent post-industrial recycled gypsum content. See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total
SECTION 09 29 00 Page 6 recycled content requirements. Gypsum board may contain post-consumer or post-industrial recycled content.
2.1.1.1 Regular
(48 inch) wide,(5/8 inch) thick, tapered edges.
2.1.1.2 Type X (Special Fire-Resistant)
(48 inch )wide,(5/8 inch) thick, tapered edges.
2.1.2 Gypsum Backing Board
ASTM C 442/C 442M, gypsum backing board shall be used as a base in a multilayer system.
2.1.3 Water-Resistant Gypsum Backing Board
ASTM C 630/C 630M
2.1.3.1 Regular
(48 inch )wide, ( 5/8 inch) thick, tapered edges.
2.1.3.2 Type X (Special Fire-Resistant)
(48 inch )wide,(5/8 inch) thick, tapered edges.
2.1.4 Joint Treatment Materials
ASTM C 475/C 475M. Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound. Pre-mixed compounds shall be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds.
2.1.4.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.4.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.4.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
2.1.4.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.4.5 Joint Tape
SECTION 09 29 00 Page 7
Use cross-laminated or tapered edge tape recommended by the manufacturer.
Paper and fiberglass joint tape are not permitted.
2.1.5 Fasteners
2.1.5.1 Nails
ASTM C 514. For predecorated gypsum board provide special nails with factory coated heads of color to match wall covering materials as recommended by the predecorated gypsum board manufacturer.
2.1.5.2 Screws
ASTM C 1002, Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.84 mm( 0.033 inch) thick. ASTM C 954 steel drill screws for fastening gypsum board to steel framing members 0.84 to 2.84 mm( 0.033 to
0.112 inch) thick. Provide cementitious backer unit screws with a polymer coating.
2.1.6 Adhesives
Do not use adhesive containing benzene, carbon tetrachloride, or trichloroethylene. Adhesive shall contain a maximum VOC content of 50 grams per liter. Adhesive must meet the requirements of LEED low emitting materials credit.
2.1.6.1 Adhesive for Fastening Gypsum Board to Wood Framing
Not permitted.ASTM C 557.
2.1.6.2 Adhesive for Laminating
Not permitted. Adhesive attachment is not permitted for multi-layer gypsum boards. For laminating gypsum studs to face panels, provide adhesive recommended by gypsum board manufacturer.
2.1.7 Accessories
ASTM C 1047. Fabricate from corrosion protected steel or plastic designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials. For predecorated gypsum board provide prefinished metal or plastic trim to match predecorated gypsum board.
2.1.8 Asphalt Impregnated Building Felt
Provide a 6.7 kg( 15 lb) asphalt moisture barrier over gypsum sheating.
Conforming to ASTM D 226 Type 1 (No. 15) for asphalt impregnated building felt.
2.1.9 Water
SECTION 09 29 00 Page 8
Provide clean, fresh, and potable water.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Gypsum Board and Framing
Verify that surfaces of gypsum board and framing to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Masonry, Plaster and Concrete Walls
Verify that surfaces of masonry and concrete walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.2 APPLICATION OF GLASS MAT COVERED OR FIBER REINFORCED GYPSUM
Apply gypsum board to framing and furring members in accordance with ASTM C 840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints. Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible.
Surfaces of gypsum board and substrate members may not be bonded together with an adhesive, except where prohibited by fire rating(s). Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer. Minimize framing by floating corners with single studs and drywall clips. Install (5/8 inch )16 mm gypsum or (1/2 inch )13 mm ceiling board over framing at (24 inches )610 mm on center. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Semi-Solid Gypsum Board Partitions
Provide in accordance with ASTM C 840, System IV or GA 216 .
3.2.2 Solid Gypsum Board Partitions
SECTION 09 29 00 Page 9
Provide in accordance with ASTM C 840, System V or GA 216.
3.2.3 Adhesive Application to Interior Masonry or Concrete Walls
Apply in accordance with ASTM C 840, System VI or GA 216.
3.2.4 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C 840, System VIII or GA 216.
3.2.5 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
In dry areas (areas other than tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply glass mat water-resistant gypsum tile backing board in accordance with ASTM C 840, System X or GA 216.
3.2.6 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing
Apply gypsum sheathing in accordance to gypsum association publications GA
253. Follow gypsum sheathing manufacturer's requirements of design details for joints and fasteners and be properly installed to protect the substrate from moisture intrusion. Do not leave exposed surfaces of the gypsum sheathing beyond the manufacturer's recommendation without a weather barrier cladding. Provide continuous asphalt impregnated building felt over sheathing surface in single fashion with edges and ends lapped a minimum of 150 mm( 6 inch). Property flash the openings. Seal all joints, seams, and penetrations with a compatible silicone sealant.
3.2.7 Floating Interior Angles
Minimize framing by floating corners with single studs and drywall clips.
Locate the attachment fasteners adjacent to ceiling and wall intersections in accordance with ASTM C 840, System XII or GA 216, for single-ply and two-ply applications of gypsum board to wood framing.
3.2.8 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C 840, System XIII or GA 216. Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.
3.2.9 Application of Impact Resistant Gypsum Board
Apply in accordance with applicable system of ASTM C 840 as specified or GA
216. Follow manufacturers written instructions on how to cut, drill and attach board.
3.3 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C 840, GA 214 and GA
216. Finish plenum areas above ceilings to Level 1 in accordance with GA
214. Finish water resistant gypsum backing board, ASTM C 630/C 630M, to receive ceramic tile to Level 2 in accordance with GA 214. Finish walls and
SECTION 09 29 00 Page 10 ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214. Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with GA 214. Finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214.
Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.3.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.4 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07920 JOINT SEALANTS Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.4.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing
Apply silicone sealant in a 9.5 mm( 3/8 inch) bead to all joints and trowel flat. Apply enough of the same sealant to all fasteners penetrating through the glass mat gypsum board surface to completely cover the penetration when troweled flat. Do not place [construction and materials behind sheathing until a visual inspection of sealed joints during daylight hours has been completed by Contracting Officer.]
3.5 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and ceiling framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated, or GA 600 for the File Number(s) indicated]. Joints of fire-rated gypsum board enclosures shall be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.6 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes. Remove predecorated gypsum board which cannot be restored to like-new condition. Provide new predecorated gypsum board.
3.7 WASTE MANAGEMENT
SECTION 09 29 00 Page 11
Separate clean waste gypsum products from contaminants. Do not include wood, plastic, metal, asphalt-impregnated gypsum board, or any gypsum board coated with glass fiber, vinyl, decorative paper, or other finish. Place in designated area and protect from moisture and contamination. Coordinate with Section 32 05 33 LANDSCAPE ESTABLISHMENT to identify requirements for gypsum soil amendment and to prepare scrap gypsum board for use as soil amendment.
Identify manufacturer's policy for collection or return of remaining construction scrap, unused material, demolition scrap, and packaging material. Institute demolition and construction recycling to take advantage of manufacturer's programs. When such a service is not available, seek local recyclers to reclaim the materials.
-- End of Section --