This technical specification outlines requirements for plumbing piping insulation for a federal construction project. Insulation materials must meet standards for composition, thermal properties, fire resistance, and vapor barriers. Requirements are specified for various pipe sizes and insulation Types T-1 through T-10, covering mineral fiber, cellular elastomer, and cellular glass insulation with jackets. Application methods are defined for each insulation Type, including surface preparation, joining materials, fitting covers, and finishing. Jacketing must utilize aluminum, vapor-barrier coatings, or PVC. Insulation contractors must submit product data and installation instructions for review and approval.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Latrine Annex Building has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 22 07 19.00 40
PLUMBING PIPING INSULATION
08/16
PART 1 GENERAL
Section 22 00 00 PLUMBING, GENERAL PURPOSE applies to work specified in this section.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A240/A240M (2018) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B209M (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)
ASTM C195 (2007; R 2013) Standard Specification for Mineral Fiber Thermal Insulating Cement
ASTM C449 (2007; R 2013) Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement
ASTM C533 (2017) Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation
ASTM C534/C534M (2016) Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form
ASTM C547 (2017) Standard Specification for Mineral Fiber Pipe Insulation
ASTM C552 (2017; E 2018) Standard Specification for Cellular Glass Thermal Insulation
ASTM C553 (2013) Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
ASTM C591 (20172019) Standard Specification for Unfaced Preformed Rigid Cellular
Polyisocyanurate Thermal Insulation
ASTM C592 (2016) Standard Specification for Mineral Fiber Blanket Insulation and Blanket-Type Pipe Insulation (Metal-Mesh Covered) (Industrial Type)
ASTM C647 (2008; R 2013) Properties and Tests of Mastics and Coating Finishes for Thermal Insulation
ASTM C795 (2008; R 2018) Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel
ASTM C916 (2014) Standard Specification for Adhesives for Duct Thermal Insulation
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM C921 (2010) Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation
ASTM C1136 (2017a) Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D579/D579M (2015) Standard Specification for Greige Woven Glass Fabrics
ASTM D5590 (2000; R 2010; E 2012) Standard Test Method for Determining the Resistance of Paint Films and Related Coatings to Fungal Defacement by Accelerated Four-Week Agar Plate Assay
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E96/E96M (2016) Standard Test Methods for Water Vapor Transmission of Materials
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 220 (2018) Standard on Types of Building Construction
NFPA 255 (2006; Errata 2006) Standard Method of Test of Surface Burning Characteristics of Building Materials
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE AMS 3779 (2016; Rev B) Tape Adhesive, Pressure Sensitive Thermal Radiation Resistant, Aluminum Foil/Glass Cloth
SAE AMS-STD-595A (2017) Colors used in Government Procurement
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-A-3316 (1987; Rev C; Am 2 1990) Adhesives, Fire-Resistant, Thermal Insulation
MIL-PRF-19565 (1988; Rev C) Coating Compounds, Thermal Insulation, Fire- and Water-Resistant, Vapor-Barrier
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Adhesives; G
Coatings; G
Insulating Cement; G
Insulation Materials; G
Jacketing; G
Tape; G
SD-08 Manufacturer's Instructions
Installation Manual; G
SD-11 Closeout Submittals
Record Drawings
1.3 QUALITY CONTROL
1.3.1 Recycled Materials
Provide thermal insulation containing recycled materials to the extent practicable, provided that the material meets all other requirements of this section. The minimum recycled material content of the following insulation types are:
a. Rock Wool - 75 percent slag by weight
b. Fiberglass - 20-25 percent glass cullet by weight
c. Plastic Rigid Foam - 9 percent recovered material
d. Polyisocyanurate/Polyurethane - 9 percent recovered material
e. Rigid Foam - 9 percent recovered material
Submit recycled materials documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product.
Indicate relative dollar value of recycled content products to total dollar value of products included in project.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.1.1 Performance Requirements
Provide noncombustible thermal-insulation system materials, as defined by NFPA 220. Provide adhesives, coatings, sealants, facings, jackets, and thermal-insulation materials, except cellular elastomers, with a flame-spread classification (FSC) of 25 or less, and a smoke-developed classification (SDC) of 50 or less. Determine these maximum values in accordance with NFPA 255. Provide coatings and sealants that are nonflammable in their wet state.
Provide adhesives, coatings, and sealants with published or certified temperature ratings suitable for the entire range of working temperatures normal for the surfaces to which they are to be applied.
2.2 COMPONENTS
2.2.1 Insulation
2.2.1.1 Mineral Fiber Insulation
Provide mineral fiber insulation conforming to ASTM C553 and suitable for surface temperatures up to 188 degrees C 370 degrees F. Provide insulation with a density not less than 4-pound per cubic foot and with thermal conductivity not greater than 0.26 Btu-inch per hour per square foot per degree F at 66 degrees C 150 degrees F mean.
2.2.1.2 Cellular Elastomer Insulation
Provide cellular elastomer insulation conforming to ASTM C534/C534M.
Ensure the water vapor permeability does not exceed 0.30 grain per foot per inch per hour per square foot mercury pressure difference for 25 millimeter 1-inch thickness of cellular elastomer.
2.2.1.3 Cellular Glass Insulation
Conform to ASTM C552, Type II, Grade 2, pipe covering for Cellular Glass.
Substitutions for this material are not permitted. Ensure minimum thickness is not less than 38 mm 1-1/2 inches.
2.2.1.4 Omitted
2.2.1.5 Fiberglass Insulation
Conform to ASTM C547. Ensure the apparent thermal conductivity does not exceed 0.54 Btu-inch per hour per square foot per degree F at 93 degrees C 200 degrees F mean.
Fiber glass pipe insulation having an insulating efficiency not less than that of the specified thickness of mineral fiber pipe insulation may be provided in lieu of mineral fiber pipe insulation for aboveground piping.
2.2.1.6 Polyisocyanurate Pipe Insulation
Conform to ASTM C591 for polyisocyanurate, minimum density of 1.7 pounds per cubic foot.
2.2.1.7 Pipe Barrel
For temperatures up to and including 650 degrees C 1200 degrees F, use pipe barrel insulation Type II, Molded, Grade A or Type III, Precision V-Groove, Grade A.
2.2.1.8 Pipe Fittings
Provide molded pipe fitting insulation covering for use at temperatures up to and including 650 degrees C 1200 degrees F.
2.2.1.9 Omitted
2.2.2 Adhesives
2.2.2.1 Lagging Adhesive
Lagging is the material used for thermal insulation, especially around a cylindrical object. This may include the insulation as well as the cloth/material covering the insulation. To resist mold/mildew, ensure lagging adhesive conforms to ASTM D5590 with 0 growth rating. Provide nonflammable and fire-resistant lagging adhesives with a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Adhesive are MIL-A-3316, Class 1, pigmented white and suitable for bonding fibrous glass cloth to faced and unfaced fibrous glass insulation board; for bonding cotton brattice cloth to faced and unfaced fibrous glass insulation board; for sealing edges of and bonding glass tape to joints of fibrous glass board; for bonding lagging cloth to thermal insulation; or Class 2 for attaching fibrous glass insulation to metal surfaces. Apply lagging adhesives in strict accordance with the manufacturer's recommendations for pipe and duct insulation.
2.2.2.2 Vapor-Barrier Material Adhesives
Ensure adhesives conform to the requirements of ASTM C916, Type I, when attaching fibrous-glass insulation to metal surfaces or attaching insulation to itself, to metal, and to various other substrates.
2.2.2.3 Cellular Elastomer Insulation Adhesive
For cellular elastomer insulation adhesive, provide a solvent cutback chloroprene elastomer conforming to ASTM C916, Type I, and is approved by the manufacturer of the cellular elastomer for the intended use.
2.2.3 Insulating Cement
2.2.3.1 General Purpose Insulating Cement
Provide general purpose insulating cement, mineral fiber, conforming to ASTM C195. Ensure composite is rated for 1800 degrees F service, with a thermal-conductivity maximum of 0.85 Btu per inch per hour per square foot for each degree F temperature differential at 93 degrees C 200 degrees F mean temperature for a 1 inch thickness.
2.2.3.2 Finishing Insulating Cement
Provide finishing insulating cement of a mineral-fiber, hydraulic-setting type conforming to ASTM C449.
2.2.4 Caulk
Provide elastomeric joint sealant in accordance with ASTM C920, Type S, Grade NS, Class 25, Use A.
2.2.5 Corner Angles
Provide a nominal 0.41 millimeter 0.016 inch thick aluminum 25 by 25 millimeter 1 by 1 inch corner angle piping insulation with factory applied kraft backing. Ensure aluminum conforms to ASTM B209M ASTM B209, Alloy 3003.
2.2.6 Jacketing
2.2.6.1 Aluminum Jacket
Provide aluminum jackets conforming ASTM B209M ASTM B209, Temper H14, minimum thickness of 0.41 mm 0.016 inch, with factory-applied polyethylene and kraft paper moisture barrier on the inside surface. Provide smooth surface jackets for jacket outside diameters less than 200 mm 8 inches.
Provide corrugated surface jackets for jacket outside diameters 200 mm 8 inches and larger. Provide stainless steel bands, minimum width of 13 mm
0.5 inch. Provide factory prefabricated aluminum covers for insulation on fittings, valves, and flanges.[ Provide aboveground jackets and bands with factory-applied baked-on semi-gloss brown color conforming to Federal Standard SAE AMS-STD-595A, "Colors," color chip number 20062.]
2.2.6.2 Omitted
2.2.6.3 Omitted
2.2.6.4 Omitted
2.2.6.5 PVC Jacket
Provide 0.25 millimeter 0.010 inch thick, factory-premolded polyvinylchloride, pipe-barrel sheeting vapor-barrier jacketing that is self-extinguishing, with high-impact strength and moderate chemical resistance. Ensure jacket has a permeability rating of 0.574 nanogram per pascal per second per square meter 0.01 grain per hour per square foot per inch of mercury pressure difference, determined in accordance with ASTM E96/E96M. Provide manufacturer's standard solvent-weld type vapor-barrier joint adhesive.
Ensure conformance to ASTM C1136 for, Type I, low-vapor transmission, high-puncture resistance vapor barriers.
2.2.7 Coatings
2.2.7.1 Outdoor Vapor-Barrier Finishing
Provide a nonasphaltic, hydrocarbon polymer, mastic coating. Ensure the coating conforms to the requirements of ASTM C1136 and ASTM C921.
2.2.7.2 Indoor Vapor-Barrier Finishing
Provide a pigmented resin and solvent compound coatings conforming to ASTM C1136, Type II.
2.2.7.3 Outdoor and Indoor Nonvapor-Barrier Finishing (NBF)
Provide a pigmented polymer-emulsion as recommended by the insulation material manufacturer for the surface to be coated.
2.2.7.4 Vapor Retarder
The vapor retarder coating shall be fire and water resistant and appropriately selected for either outdoor or indoor service. Color shall be white. The water vapor permeance of the compound shall be 0.013 perms or less at 1 mm 43 mils dry film thickness as determined according to procedure B of ASTM E96/E96M utilizing apparatus described in ASTM E96/E96M.
The coating shall be nonflammable, fire resistant type. [To resist mold/mildew, coating shall meet ASTM D5590 with 0 growth rating. ]Coating shall meet MIL-PRF-19565 Type II (if selected for indoor service) and be Qualified Products Database listed. All other application and service properties shall be in accordance with ASTM C647.
2.2.7.5 Cellular-Elastomer Finishing
Provide a polyvinylchloride lacquer coating recommended by the manufacturer of the cellular elastomer finish.
2.2.7.6 Coating Color
Blend with background of surrounding area for the coating color.
2.2.8 Tape
Provide a knitted elastic cloth glass lagging specifically suitable for continuous spiral wrapping of insulated pipe bends and fittings that produces a smooth, tight, wrinkle-free surface. Conform to requirements of SAE AMS 3779, ASTM D579/D579M, and ASTM C921 for tape, weighing not less than 10 ounces per square yard.
2.3 MATERIALS
Submit manufacturer's catalog data for the following items:
a. Adhesives
b. Coatings
c. Insulating Cement
d. Insulation Materials
e. Jacketing
f. Tape
Provide compatible materials that do not contribute to corrosion, soften, or otherwise attack surfaces to which applied, in either the wet or dry state. Meet ASTM C795 requirements for materials to be used on stainless steel surfaces. Provide materials that are asbestos free.
PART 3 EXECUTION
Apply insulation only to the system or component surfaces that have previously been tested and approved by the Contracting Officer.
3.1 PREPARATION
Submit installation drawings for pipe insulation, conforming with the adhesive manufacturer's written instructions for installation. Submit installation manual clearly stating the manufacturer's instructions for insulation materials.
Clean surfaces to remove oil and grease before insulation adhesives or mastics are applied. Provide solvent cleaning required to bring metal surfaces to such condition.
3.2 INSTALLATION OF INSULATION SYSTEMS
Apply materials in conformance with the recommendations of the manufacturer.
Install smooth and continuous contours on exposed work. Smoothly and securely paste down cemented laps, flaps, bands, and tapes. Apply adhesives on a full-coverage basis.
Install insulation lengths tightly butted against each other at joints.
Where lengths are cut, provide smooth and square and without breakage of end surfaces. Where insulation terminates, neatly taper and effectively seal ends, or finish as specified. Direct longitudinal seams of exposed insulation away from normal view.
Use insulation meeting maximum value conductance as tested at any point, do not use an average. Meet or exceed the specified maximum conductance by adding additional insulation thickness.
3.2.1 Dual-Temperature (Hot- and Chilled-) Water Piping (Exposed Handicaped)
Install a mineral fiber with vapor barrier jacket, Type T-1 insulation, with a thickness of not less than 1/2-inch. Insulate aboveground pipes, valve bodies, fittings, unions, and flanges.
3.2.2 Omitted
3.2.3 Cold-Water and Condensate-Drain Piping
Insulate aboveground pipes, valve bodies, fittings, unions, flanges, and miscellaneous surfaces.
Provide flexible cellular-elastomeric thermal insulation for cold water piping, Type T-3, with a thickness of 1/2 inch. Use expanded, closed-cell pipe insulation only aboveground, not for underground piping.
3.2.4 Omitted
3.2.5 Omitted
3.2.6 Omitted
3.2.7 Omitted
3.2.8 Omitted
3.2.9 Omitted
3.2.10 Omitted
3.3 APPLICATION
3.3.1 Type T-1, Mineral Fiber with Vapor-Barrier Jacket
Apply factory and field attached vapor barrier jacket to piping insulated with mineral fiber. Maintain vapor seal. Securely cement jackets, jacket laps, flaps, and bands in place with vapor-barrier adhesive. Provide jacket overlaps not less than 1-1/2 inches and jacketing bands for butt joints 75 millimeter 3-inches in width.
Insulate exposed-to-view fittings and valve bodies with preformed mineral-fiber of the same thickness as the pipe-barrel insulation.
Temporarily secure fitting insulation in place with light cord ties. Apply a 1.52 millimeter 60-mil coating of white indoor vapor-barrier coating and, while still wet, wrap with glass lagging tape with 50 percent overlap, and smoothly blend into the adjacent jacketing. Apply additional coating as needed with rubber-gloved hands to smooth fillets or contour coating.
Allow to fully cure before the finish coating is applied. Field fabricate and install insulation for concealed fittings and special configurations.
Build up insulation from mineral fiber and a special mastic consisting of a mixture of insulating cement and lagging adhesive diluted with 3 parts water. Where standard vapor-barrier jacketing cannot be used, make the surfaces vapor tight by using coating and glass lagging cloth or tape as previously specified.
In lieu of materials and methods previously specified, fittings may be wrapped with a twine-secured, mineral-wool blanket to the required thickness and covered with premolded polyvinylchloride jackets. Make seams vapor tight with a double bead of manufacturer's standard vapor-barrier adhesive applied in accordance with the manufacturer's instructions. Hold all jacket ends in place with AISI 300 series corrosion-resistant steel straps, 15-mils thick by 1/2-inch wide.
Do not use staples as a means to apply insulation. Install continuous vapor-barrier materials over all surfaces, including areas inside pipe sleeves, hangers, and other concealment.
Provide piping insulation at hangers consisting of 208 kilogram per cubic meter 13-pounds per cubic foot density; fibrous-glass inserts or expanded, rigid, closed-cell, polyvinylchloride. Where required, seal junctions with vapor-barrier jacket, glass-cloth mesh tape, and vapor-barrier coating.
Expose white-bleached kraft paper side of the jacketing to view.
Finish exposed-to-view insulation with not less than a 6-mil dry-film thickness of nonvapor-barrier coating suitable for painting.
3.3.2 Omitted
3.3.3 Type T-3, Cellular Elastomer
Cover piping-system surfaces with flexible cellular-elastomer sheet or preformed insulation. Maintain vapor seal. Cement insulation into continuous material using a solvent cutback chloroprene adhesive recommended by the manufacturer for the specific purpose. Apply adhesive to both of the contact surfaces on a 100-percent coverage basis to a minimum thickness of 0.254 millimeter 10-mils wet or approximately 4 square meter per liter 150 square feet per gallon of undiluted adhesive.
Set cold water piping insulation into an outdoor vapor-barrier coating applied intermittently over a minimum length of 6 inches at maximum intervals of 12 feet. At piping supports, ensure insulation is continuous by using outside-carrying type clevis hangers with insulation shield.
Install [Cork] [Wood dowel] load-bearing inserts between the pipe and insulation shields to prevent insulation compression.
Insulate hot-water, cold-water, and condensate drain pipes to the extent shown with nominal 1/2-inch thick, fire retardant (FR), cellular elastomer, preformed pipe insulation. Seal joints with adhesive.
At pipe hangers or supports where the insulation rests on the pipe hanger strap, cut the insulation with a brass cork borer and insert a [No. 3] superior grade cork. Seal seams with approved adhesive. Insulate sweat fitting with miter-cut pieces of cellular elastomer insulation of the same nominal pipe size and thickness as the insulation on the adjacent piping or tubing. Join miter-cut pieces with approved adhesive. Slit and snap covers over the fitting, and seal joints with approved adhesive.
Insulate screwed fittings with sleeve-type covers formed from miter-cut pieces of cellular elastomer thermal insulation having an inside diameter large enough to overlap adjacent pipe insulation. Lap pipe insulation against fittings, and overlap not less than 1 inch. Use adhesive to join cover pieces and cement the cover to the pipe insulation.
Finish surfaces exposed to view or ultraviolet light with not less than a 2 mil minimum dry-film thickness application of a polyvinylchloride lacquer recommended by the manufacturer. Apply in not less than two coats.
3.3.4 Type T-4, Cellular Glass with Vapor-Barrier Jacket
Apply factory and field attached vapor barrier jacket to piping insulated with cellular glass. Maintain vapor seal. Securely cement jackets, jacket laps, flaps, and bands in place with vapor-barrier adhesive. Provide jacket overlaps not less than 1-1/2 inches. Provide jacket bands for butt joints of not less than 3 inches width. Provide insulation continuous through hangers. Bed insulation in an outdoor vapor-barrier coating applied to all piping surfaces.
Insulate flanges, unions, valves, anchors, and fittings with factory premolded or prefabricated or field fabricated segments of insulation of the same material and thickness as the adjoining pipe insulation. When segments of insulation are used, provide elbows with not less than three segments. For other fittings and valves, cut segments to the required curvature or nesting size.
Secure segments of the insulation in place with twine or copper wire.
After the insulation segments are firmly in place, apply a vapor-barrier coating over the insulation in two coats with glass tape imbedded between coats. Vary the tint of the first coat from the expected white color of the second coat to ensure the complete application of the two coats. Apply coatings to a total dry-film thickness of 1/16 inch minimum. Overlap glass tape seams not less than 1inch and tape ends not less than 4inches.
In lieu of materials and methods specified above, fittings may be wrapped with 10 millimeter 3/8-inch thick, vapor-barrier, adhesive-coated strips of cellular elastomer insulation. Install insulation under tension, compressed to 25 percent of original thickness, and wrapped until overall thickness is equal to adjacent insulation. Secure cellular elastomer in place with twine and sealed with vapor-barrier coating applied to produce not less than 1/16-inch dry-film thickness. Cover fittings with premolded polyvinylchloride jackets. Make seams vapor-tight with a double bead of manufacturer's standard vapor-barrier adhesive applied in accordance with the manufacturer's instructions. Hold jacket ends in place with AISI 300 series corrosion-resistant steel straps, 15-mils thick by 1/2-inch wide.
To prevent condensation, insulate anchors secured directly to piping for not less than 6 inches from the surface of the pipe insulation.
Install white-bleached kraft paper side of jacket exposed to view.
Finish exposed-to-view insulation with not less than a 6-mil dry-film thickness of nonvapor-barrier coating suitable for painting.
3.3.5 Omitted
3.3.6 Type T-6, Mineral Fiber with Aluminum Jacket
Apply factory or field attached aluminum jacket to piping insulated with mineral fiber.
Insulate fittings and valve bodies with preformed mineral-fiber of the same thickness as the pipe-barrel insulation. Temporarily secure fitting insulation in place with light cord ties. Apply a 1.52 millimeter 60-mil coating of vapor-barrier mastic, and while still tacky, wrap with glass lagging tape.
Apply additional mastic as needed using rubber-gloved hands to smooth fillets or contour coatings. Field fabricate and install insulation for special configurations. Build up insulation from mineral fiber and a mixture of insulating cement and lagging adhesive diluted with 3 parts water. Only where standard aluminum jacketing cannot be used, make the surfaces vapor-tight by using mastic and glass lagging cloth or tape as specified above with an added finish coat of mastic.
Set pipe insulation into outdoor vapor-barrier coating applied intermittently over a minimum length of 6-inches with a maximum coating application of 12-foot. Seal ends of the insulation to the jacketing with the same coating material to provide effective vapor barrier stops.
Install continuous vapor barrier over all surfaces, including areas inside pipe sleeves, hangers, and other concealment.
Apply piping insulation to both sides of pipe hangers. Insulate junctions with a special mastic mixture, glass cloth mesh tape, and mastic as previously specified.
Securely cement jacket laps, flaps, and bands in place with aluminum jacket sealant. Provide 6 inch wide minimum jacketing bands for butt joints.
Wherever possible, lap joints against the weather so that the water runs off the lower edge and in accordance with the pipe drainage pitch. Locate longitudinal laps on horizontal lines 45 degrees below the horizontal centerline and alternately staggered 25 millimeter 1 inch. Lap jacketing material a minimum of 2 inches, circumferentially sealed with mastic, and strapped to provide a waterproof covering throughout. Locate straps 8 inches on center and pull up tight to hold jacketing securely in place.
Use screws in addition to straps when necessary to obtain a waterproof covering. Place extra straps on each side of supporting devices and at openings. Where flanging access occurs, strap a chamfer sheet to the pipe at jacketing.
Stiffen exposed longitudinal edges of aluminum jacketing by bending a 25 millimeter 1 inch hem on one edge.
Provide expansion joints for maximum and minimum dimensional fluctuations.
To prevent corrosion, do not allow the aluminum jacketing to come in direct contact with other types of metal.
At openings in jacket, apply an outdoor vapor-barrier coating for 2 inches in all directions. Apply jacketing while waterproofing is tacky.
Use screws at each corner of each sheet, at fitting jackets, and as necessary for the service. Place Number 7, 10 millimeter 3/8 inch long, binding-head aluminum sheet metal screws through the mastic seal.
3.3.7 Omitted
3.3.8 Type T-9, Cellular Elastomer
Clean pump surfaces with solvent. Apply not less than 1 inch of general purpose insulating cement, mixed with nonvapor-barrier adhesive diluted with 3 parts water, to achieve smooth surface and configuration contours.
After all water has been removed, cover surfaces with 13 millimeter 1/2 inch thick cellular elastomer insulation, attached and joined into a continuous sheet with an outdoor vapor-barrier coating recommended by the insulation manufacturer for the specific purpose. Apply coating to both of the contact surfaces on a 100-percent coverage basis with a minimum thickness of 10 mils wet. Blend coating into the adjacent flange insulation. Cover joint with a band of cellular elastomer equal to the flange assembly width. Use same coating to seal insulation to the casing at penetrations and terminations. Insulate pumps in a manner that permits insulation to be removed to repair or replace pumps.
Finish insulation with a 2 mil minimum dry-film application of a polyvinylchloride lacquer coating recommended by the manufacturer and applied in not less than two coats.
3.3.9 Type T-10, Mineral-Fiber Fill
Pack voids surrounding pipe with mineral-fiber fill.
3.3.10 Omitted
3.4 CLOSEOUT ACTIVITIES
Final acceptance of the performed work is dependent upon providing Record Drawings details to the Contracting Officer. Include construction details, by building area, the insulation material type, amount, and installation method. An illustration or map of the pipe routing locations may serve this purpose.
-- End of Section --