FSB2020-270-00 - WI-ANG - 3-Bay Hangar - Addendum 002 Combined Drawings.pdf
PDF 9 MB Posted
- Attached to
- F-35 THREE BAY SPECIALIZED HANGAR
- Solicitation number
- W50S9F-22-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This federal contract opportunity document announces an unrestricted invitation for bid to construct a new three-bay hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. Key details include:
-
The project scope includes demolishing an existing 19,875 square foot building and constructing a new 31,000 square foot three-bay hangar with associated shop and administrative spaces to support fuel cell operations, indoor wash requirements, squadron-level surface coating operations, and weapons load training.
-
The base award contract line items are anticipated to include construction of the three-bay hangar base bid, with optional line items for a paint/mix addition and aircraft-rated pavement.
-
The contract duration is 550 days from issuance of the notice to proceed.
-
The North American Industry Classification code is 236220 for commercial and institutional building construction, with a size standard of $39.5 million. The construction value is estimated between $25-100 million.
-
The solicitation allows for a brand name justification and will be awarded to the responsive and responsible lowest bidder. The pre-bid conference and site visit will be held at Truax Field, and bids are to be submitted through the System for Award Management website.
View the file
Other files
Show 40 more
Latest 50 of 147 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEANS OF EGRESS REQUIREMENTS - 2018 NFPA 101 (U.N.O.)
SPECIAL PURPOSE INDUSTRIAL
(AIRCRAFT HANGARS)
OCCUPANT LOAD
FACTOR
BUSINESS USE
GENERAL PURPOSE
INDUSTRIAL USE
STORAGE/ MECHANICAL
USE
MAX. PROBABLE # OF
OCCUPANTS PRESENT
AT ANY TIME PER NFPA
101, TABLE 7.3.1.2
150 GROSS
(TABLE 7.3.1.2)
100 GROSS
(TABLE 7.3.1.2)
500 GROSS
(TABLE 7.3.1.2)
COMMON PATH
OF TRAVEL
100'
(TABLE 40.2.5.1)
100' (38.2.5.3.1)
100' (40.2.5)
100' (42.2.5)
MAXIMUM TRAVEL
DISTANCE TO EXITS
EXTERIOR INTERVAL
150' (40.6.2.2)
300' (38.2.6.3)
250'
(TABLE 40.2.6.1)
400'
(TABLE 42.2.6)
MINIMUM EXIT ACCESS
CORRIDOR WIDTH
44" (38.2.3.2)
36" (7.3.4.1)
36" (7.3.4.1)
50' (40.6.4)
50' (38.2.5.2.1)
50'
(TABLE 40.2.5.1)
100'
(TABLE 42.2.5)
MAXIMUM DEAD END
CORRIDOR LENGTH
MINIMUM NUMBER
OF EXITS
(40.6.2.1)
PER OCCUPANT
LOAD
(40.2.4.1.1)
CODE SUMMARY
OCCUPANCIES (IBC 2018)
ITEM 2018 IBC REQUIREMENT (U.N.O.)
GENERAL
BUSINESS, GROUP B (304.1) - OFFICE AREAS, ACCESSORY AREAS
HIGH HAZARD GROUP H-2 - SUPPORT SHOP (ALTERNATE BID)
STORAGE, GROUP S-1 (311.2) - MECHANICAL, ELECTRICAL AND
STORAGE AREAS.
STORAGE, GROUP S-2 (311.3) - LAUNDRY ROOMS
OCCUPANCIES (NFPA 101, 2018) BUSINESS (6.1.11) - OFFICE AREAS
SPECIAL PURPOSE INDUSTRIAL, SPI (40.1.2.1.2) - HANGAR AREAS
CONSTRUCTION TYPE TYPE II-B (IBC, TABLE 601)
ALLOWABLE HEIGHT/STORIES UNLIMITED HEIGHT (UFC, 4-211-01, 3-3.1.7)/3 STORIES (IBC, TABLE 504.4)
ALLOWABLE AREA UNLIMITED ONE STORY (IBC 507.4)
ADAAG FULLY COMPLIANT
FIRE PROTECTION SYSTEMS
AIRCRAFT SERVICING AREA WET PIPE SPRINKLER SYSTEM (UFC 3-600-01 FIRE PROTECTION)
ADMINISTRATION AND SHOPS WET PIPE SPRINKLER SYSTEM (UFC 3-600-01 FIRE PROTECTION)
FIRE RESISTANCE REQUIREMENTS
BOILER ROOMS, FURNACE
ROOMS, AND GENERAL
STORAGE ROOMS OVER 100 SF
1 HOUR OR AUTOMATIC FIRE EXTINGUISHING SYSTEM
(TABLE 509)
NON-LOADBEARING EXTERIOR
WALLS
0 HOUR (TABLE 602)
HANGAR COLUMNS 0 HOUR (UFC 4-211-01, 3-3.1.2)
FLOOR CONSTRUCTION 0 HOUR (TABLE 601)
ROOF CONSTRUCTION 0 HOUR (TABLE 601)
FIRE SEPARATION REQUIREMENTS
BUILDING DATA
BUILDING AREA
GROUND FLOOR
HANGAR BAYS
ADMINISTRATIVE AREAS
ACCESSORY STO AND MECH
16,574 SQUARE FEET
2,838 SQUARE FEET
3,559 SQUARE FEET
BUILDING CODES AND STANDARDS
INTERNATIONAL MECHANICAL CODE 2018
INTERNATIONAL BUILDING CODE 2018
NATIONAL ELECTRICAL CODE 2020
NFPA 101 LIFE SAFETY CODE 2018
MINIMUM EGRESS WIDTH 0.2" PER OCCUPANT (NFPA 101, TABLE 7.3.3.1)
EXIT ENCLOSURES 1 HOUR (NFPA 101, 7.1.3.2.1), 1 HOUR DOORS (NFPA 101, 8.3.2.2)
BETWEEN AIRCRAFT SERVICING
AREAS AND ALL OTHER OPERATIONS
1 HOUR (UFC 04-211-01, 3-3.1.2)
DRAFT CURTAINS RECTANGULAR ROOF POCKETS, MAX. 7,500 SF (UFC 4-211-01, 3-3.1.10)
BETWEEN ALL OTHER OCCUPANCIES NOT REQUIRED - MIXED USE NONSEPARATED PER 508.3.2
TOTAL (GROSS SQUARE FEET) 22,968 SQUARE FEET
NFPA 409, STANDARD FOR AIRCRAFT HANGARS 2016
NATIONAL FIRE CODES (NFPA) LATEST EDITIONS
ICC/ANSI A117.1 2003
UNIFORM FEDERAL ACCESSIBILITY STANDARD (UFAS)
UFC 3-600-01, FIRE PROT. ENGINEERING FOR FACILITIES
UFC 1-200-01, GENERAL BUILDING REQUIREMENTS
UFC 4-010-01, MINIMUM ANTI-TERRORISM STANDARDS
ADDITIONAL UNIFIED FACILITY CRITERIA
ACCESSIBILITY FOR FIREFIGHTING
ALL WEATHER ACCESS MUST BE PAVED TO WITHIN 10M
(33 FT) FROM THE BUILDING (UFC 4-211-01, 3-3.1.11)
FIRE DEPARTMENT ACCESS ROADS
MUST COMPLY WITH NFPA 1 (18.2.3.5.1) ACCESS
ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF
NOT LESS THAN 20 FT.
PORTABLE FIRE EXTINGUISHERS - 2018 NFPA 10 (U.N.O.)
EXTINGUISHER SELECTION
MAX TRAVEL DISTANCE
CLASSIFICATION OF
HAZARD
EXTRA (HIGH) 5.4.1.3 HANGAR
BAY
ORDINARY (MODERATE) 5.4.1.2 -
STORAGE, SUPPORT SHOP
4A:60B:C
B: 50 FEET (TABLE 6.3.1.1)
LIGHT (LOW) 5.4.1.1
OFFICE AREAS
20A:120B:C
B: 50 FEET (TABLE 6.3.1.1)
4A:60B:C
B: 50 FEET (TABLE 6.3.1.1)
FIRE PROTECTION ROOM 1 HOUR (UFC 4-211-01, 3-6.7)
INTERNATIONAL PLUMBING CODE 2018
UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION
SYSTEMS
PER OCCUPANT
LOAD
ADJACENT BETWEEN AIRCRAFT
MAINTENANCE BAYS 2 HOURS FIGURE 3.1
PLUMBING MATRIX
WATER CLOSETS/URINALS
(MALE)
B
WATER CLOSETS (FEMALE)
LAVATORIES (MALE)
LAVATORIES (FEMALE)
1.4
0.38
0.93
0.23
S
0.35
0.22
0.35
0.22
1.75
0.60
1.28
0.45
REQUIRED PROVIDED
TOTAL PLUMBING FIXTURES
SERVICE SINKS
DRINKING FOUNTAINS
1 1 1 2
0.45 0.02 0.47 1
WATER CLOSETS (UNISEX)
LAVATORIES (UNISEX)
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
C :\U sers\gaz\D o cum ents\M y R evit\02700_Arch_G ZalabakZ5W
7D .rvt
6/8/2022 10:26: 55 AM
CODE SUMMARY
G-102
JBC
JRT/JBC
MP
OCCUPANCY AREA SCHEDULE
IBC Occupancy Classification
NFPA
Occupancy
Classification
ROOM
AREA
IBC Occupant Load Factor
NFPA
Occupant
Load Factor
IBC
Occupant
Load
NFPA
Occupant
Load REMARKSNUMBER NAME
B BUSINESS
B BUSINESS Business 102 VEST 50 SF 150 SF 150 SF 0.33 0.36 B BUSINESS Business 103 SHARED OFFICE 300 SF 150 SF 150 SF 2.00 1.88 B BUSINESS Business 104 FUEL OPEN
OFFICE
509 SF 150 SF 150 SF 3.40 3.35
B BUSINESS Business 105 VEST 120 SF 150 SF 150 SF 0.80 0.84 B BUSINESS Business 106 CORR 826 SF 150 SF 150 SF 5.50 5.27 B BUSINESS Business 107 CLASSROOM 602 SF 150 SF 150 SF 4.01 3.99 B BUSINESS Business 108 OFFICE 117 SF 150 SF 150 SF 0.78 0.78 B BUSINESS Business 109 RR W 164 SF 150 SF 150 SF 1.09 0.89 B BUSINESS Business 110 WING WEAPONS
MGR
125 SF 150 SF 150 SF 0.83 0.82
B BUSINESS Business 111 RR M 164 SF 150 SF 150 SF 1.09 0.95 B BUSINESS Business 112 FUEL SUPERVISOR 135 SF 150 SF 150 SF 0.90 0.81 B BUSINESS Business 113 BREAK/ TRAINING 551 SF 150 SF 150 SF 3.67 3.47 B BUSINESS Business 114 VEST 159 SF 150 SF 150 SF 1.06 1 B BUSINESS Business 115 OFFICE 125 SF 150 SF 150 SF 0.83 0.85 B BUSINESS Business 116 VINYL OPEN
OFFICE
492 SF 150 SF 150 SF 3.28 3.24
B BUSINESS Business 120A VEST 73 SF 150 SF 150 SF 0.48 0.58 B BUSINESS Business 120B CORR 717 SF 150 SF 150 SF 4.78 5.46 B BUSINESS Business 121 ELEC 78 SF 150 SF 150 SF 0.52 0.38 B BUSINESS Business 127 VEST 98 SF 150 SF 150 SF 0.66 0.64 B BUSINESS Business 130 CLEAN M RR 286 SF 150 SF 150 SF 1.90 1.93 B BUSINESS Business 131 CLEAN M LR 88 SF 150 SF 150 SF 0.59 0.58 B BUSINESS Business 132 CLEAN SHOWER M 51 SF 150 SF 150 SF 0.34 0.34 B BUSINESS Business 133 DIRTY SHOWER M 57 SF 150 SF 150 SF 0.38 0.38 B BUSINESS Business 134 DIRTY LR M 179 SF 150 SF 150 SF 1.19 1.19 B BUSINESS Business 135 DIRTY SHOWER M 56 SF 150 SF 150 SF 0.37 0.37 B BUSINESS Business 136 CLEAN W RR 254 SF 150 SF 150 SF 1.69 1.68 B BUSINESS Business 137 CLEAN W LR 88 SF 150 SF 150 SF 0.58 0.36 B BUSINESS Business 138 CLEAN SHOWER W 56 SF 150 SF 150 SF 0.37 0.37 B BUSINESS Business 139 DIRTY LR W 102 SF 150 SF 150 SF 0.68 0.68 B BUSINESS Business 140 DIRTY SHOWER W 61 SF 150 SF 150 SF 0.41 0.41 B BUSINESS Business 141 DIRTY RR UNISEX 49 SF 150 SF 150 SF 0.33 0.33 B BUSINESS Business 142 DIRTY VEST 247 SF 150 SF 150 SF 1.64 1.64
B BUSINESS: 32 6,976 SF 46.51 45.82
S-1 STORAGE
S-1 STORAGE Industrial 101 WEAPONS
TRAINING
6,314 SF 500 SF 500 SF 12.63 13.17
S-1 STORAGE Storage 117A MOTHER'S ROOM 83 SF 300 SF 0.28 S-1 STORAGE Storage 117B JAN 66 SF 300 SF 0.22 S-1 STORAGE Storage 118 FUEL MAINT.
GENERAL
STORAGE
275 SF 300 SF 0.92
S-1 STORAGE Industrial 119 FUEL CELL 4,782 SF 500 SF 500 SF 9.56 9.96 S-1 STORAGE Storage 124 MECH 709 SF 300 SF 2.36 S-1 STORAGE Storage 125 FIRE 730 SF 300 SF 2.43 S-1 STORAGE Storage 126 TOOLS 916 SF 300 SF 3.05 S-1 STORAGE Industrial 128 WASH BAY 4,878 SF 500 SF 500 SF 9.76 9.97 S-1 STORAGE Storage 129 JAN. 300 SF S-1 STORAGE Storage 143 MASK WASHING 30 SF 300 SF 0.10 S-1 STORAGE Storage 145 ELEC 309 SF 300 SF 1.03 S-1 STORAGE Storage 146 COMM 209 SF 300 SF 0.70
S-1 STORAGE: 13 19,301 SF 43.04 33.1
S-2 STORAGE
S-2 STORAGE Storage 122 FUEL 91 SF 300 SF 300 SF 0.30 0.23 S-2 STORAGE Storage 123 WASH 89 SF 300 SF 300 SF 0.30 0.23
S-2 STORAGE: 2 180 SF 0.60 0.46
TOTAL: 47 26,457 SF 90.15 79.38
1 ADDENDUM 1 04/22/2022
2 ADDENDUM 2 06/08/2022
W
IS C O NS IN
A R C H I T E C T
JASON T.
HOLUBY
A-13101
OKLAHOMA CITY
OK
SS
SS
EEEEE
E
E
EEE
E E
E E E E
E E E E E E E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E
E
E
GGGGGGGGG
G
G G
G
G
G G
GG
G
G G
G
G
G
G
G
G
G
G
G
G G
G
G
G
G
G
G G
G
SAN
SAN
SAN
SAN
SA
N
SAN
SAN
SAN
SAN
SAN
SAN SAN SAN SAN SAN SAN
SAN
SAN
SAN
SAN
SAN
SANSAN
SAN
SAN
SAN SAN
SAN
SAN
SAN
SA
N
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
T
T
T
T T
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
W W W W W W W W W W
W
W
W
W
W
W
W
W
W
W W
W W
W W
W
W W
W
W
W
W
W W
W
W
W
W
W
WWWWW WV
WV
WV
WVWV WV
WV
TEL
WV
TEL
TEL
WV
UT
UT
UT
UT
WV
TEL
WV
UT
UT
UT
GV
GVGTST
WV
TEL
WV
SAN
SAN
WV
A/C A/C EL
SAN
SAN
AG
WV
AG
UT
BLDG
BLDG
BLDG
SIGN
SIGN
AG
AG
AG
UT
BLDG
UT
SAN
SAN
SAN
SAN
SAN
BLDG
BLDG
BLDG
BLDG
BLDG
SAN
GTST
WV
SS
WV
WV
WVWV
SAN
SAN
VENT
UT UT
A/C
UT
DOCK DOCK
TEL
A/C
BORE
AG
E
E
E
SS
SS
SS
SS
W W
W W
W
W
W
W
W
W
W
W
W
W W W
W
W
W
EXISTING PCC
PAVEMENT
EXISTING
BUILDING 414
EXISTING
BITUMINOUS
PAVEMENT
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
STRUCTURE TO
BE RELOCATED
BY THE
GOVERNMENT
PRIOR TO
CONSTRUCTION
CONTRACTOR STAGING AREA,
RESTORE AT PROJECT
COMPLETION.
MITCHELL ST.
PROJECT LIMITS
0 15' 30' 60' N
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
-B ay S pe ci al iz ed H an ga r M ad is on , W is co ns in
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
LDH
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
1525 S. 6th Street Springfield, IL 62703 phone: 217-788-2450 fax: 217-788-2503
ACCESS PLAN
C-101
LDH
HLE
1 06/08/2022ADDENDUM 2
SS
EEEEE
EEE
E E
E E E E
E E E E E E E E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E
E
GGGGGGGGG
G
G G
G
G
G
G G
GG
G
G G
G
G
G
G
G
G
G
G
G
G G
G
G
G
G
SAN SAN SAN SAN SAN SAN
SAN
SAN
SAN
SAN
SAN
SANSAN
SAN
SAN
SAN SAN SAN
SAN
SAN
SAN
SAN
SA
N
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
W W W W W W W W W W
W
W
W
W
W
W
W
W
W
W W
W W
W
W
W
W W
W W
W
W
W
W W
W
W
W
W
W
W
WWWWW WV
WV
WVWV WV
WV
TEL
WV
TEL
TEL
TEL
MWEL
WV
UT
UT
UT
WV
TEL
WV
MWEL
MWEL
UT
UT
MWEL
MWEL
UT
MWEL
MWEL
GV
GVGTST
WV
TEL
WV
MWEL
WV
A/C A/C EL
MWEL
SAN
AG
WV
AG
UT
BLDG
BLDG
BLDG
AG
AG
AG
UT
BLDG
UT
MWEL
MWEL
SAN
SAN
BLDG
BLDG
BLDG
BLDG
BLDG
MWEL
SAN
MWEL
GTST
WV
SS
WV
WV
WVWV
SAN
SAN
VENT
UT UT
A/C
UT
DOCK DOCK
TEL
A/C
BORE
AG
SS
SS
SSSSSSSS
EXISTING 18" RCP TO REMAIN
SS
SS
SS
SS
W W
W W
W
W
W
W
W
W
W
W
W
W W W
SS
SSEX
IS
TI
N G
2"
R C
P
TO
R
EM
AI
N
W
W
REMOVE BITUMINOUS
PAVEMENT (TYP.), 5,036 S.Y.
REMOVE PCC PAVEMENT,
1,447 S.Y.
REMOVE COMMUNICATION LINE,
202 L.F.
EXISTING WALL TO BE
REMOVED TO PROPOSED
PCC PAVEMENT LIMIT.
92 L.F.
REMOVE BITUMINOUS
PAVEMENT (OLI 2), 692 S.Y.
REMOVE ELECTRICAL,
COORDINATE WITH MADISON
GAS AND ELECTRIC
REMOVE FENCE, 317 L.F.
REMOVE GAS LINE, 129 L.F.
REMOVE MONITORING
WELL, 3 EACH.
REMOVE EXISTING SANITARY (TYP.),
540 L.F. AND 6 STRUCTURES.
REMOVE SIDEWALK,
2,454 S.F. (TYP.)
REMOVE STORM (TYP.), 773
L.F. AND 11 STRUCTURES.
REMOVE WATER LINE,
32 L.F. AND HYDRANT
EXISTING PCC
PAVEMENT
EXISTING
BUILDING TO BE
REMOVED
EXISTING
BITUMINOUS
PAVEMENT
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING PCC
PAVEMENT
EXISTING
STRUCTURE TO
BE RELOCATED
BY THE
GOVERNMENT
PRIOR TO
CONSTRUCTION
REMOVE ELECTRICAL,
COORDINATE WITH MADISON
GAS AND ELECTRIC
REMOVE HYDRANT
REMOVE HYDRANT
REMOVE EXISTING UNDERGROUND
FUEL OIL, USED OIL, USED SOLVENT,
AND DETERGENT STORAGE TANKS.
INTRUSION DETECTION CABLES
AND GAP SENSORS TO BE
REMOVED AND REPLACED,
SPLICING WILL NOT BE ALLOWED.
WORK TO BE COORDINATED WITH
ADVANTOR.
REMOVE ELECTRICAL, COORDINATE
WITH MADISON GAS AND ELECTRIC
REMOVE CONCRETE
CURB AND GUTTER,
364 L.F.
REMOVE WATER LINE, 72 L.F. AND
CAP EXISTING LINE TO REMAIN
REMOVE TELEPHONE
PEDESTAL AND
PULLBOX
REMOVE EXISTING
BUILDING STRUCTURE, 10
BOLLARDS, AGGREGATE
BASE AND SIGN
FEDERAL AVIATION
ADMINISTRATION CABLE IN THIS
AREA, APPROXIMATELY 24" DEEP.
THIS CABLE CANNOT BE SPLICED
IF CUT AND WOULD NEED
REPLACED ITS ENTIRE LENGTH.
REMOVE
BITUMINOUS
PAVEMENT (OLI 2),
3,060 S.Y.
REMOVE MONITORING
WELL (OLI 2)
GAS TEST STATION TO
BE ADJUSTED (OLI 2)
SANITARY STRUCTURE
TO BE ADJUSTED (OLI 2)
ADDITIONAL PAVEMENT TO BE
REMOVED FOR UTILITY
REMOVAL OR INSTALLATION
SHALL BE REPLACED IN KIND,
SEE TYPICAL SECTIONS.
0 15' 30' 60'
N
PROPOSED
REMOVAL LEGEND
BITUMINOUS PAVEMENT
PCC PAVEMENT
SIDEWALK
WALL
CONCRETE CURB AND GUTTER
ELECTRICAL LINE
STORM DRAIN
WATER LINE
GAS LINE
COMMUNICATION LINE
SANITARY LINE
FENCE LINE
MONITORING WELL
WATER/SANITARY STRUCTURE
STORM STRUCTURE
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
-B ay S pe ci al iz ed H an ga r M ad is on , W is co ns in
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
LDH
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
1525 S. 6th Street Springfield, IL 62703 phone: 217-788-2450 fax: 217-788-2503
REMOVAL PLAN
C-301
LDH
HLE
EXISTING CONDITIONS ARE BASED ON SURVEY
PERFORMED BY KL ENGINEERING, INC. ON 06/2020.
OLI - OPTIONAL LINE ITEM
ADDENDUM 21 06/08/2022
SS
EEEEE
EEE
E E
E E E E
E E E E E E E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E
E
FO
FO
GGGGGGGGG
G
G G
G
G
G
G G
GG
G
G G
G
G
G
G
G
G
G
G
G G
G
G
G
G
SAN SAN SAN SAN SAN SAN
SAN
SAN
SAN
SAN
SAN
SANSAN
SAN
SAN
SAN SAN
SAN
SAN
SA
N
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
W W W W W W W W W W
W
W
W
W
W
W
W
W
W
W W
W W
W
W
W
W W
W
W
W
W
W W
W
W
W
W
W
WWWWW WV
WV
WVWV WV
WV
TEL
WV
TEL
TEL
TEL
WV WV
WV
UT
UT
UT
WV
TEL
WV
UT
UT
UT
GV
GVGTST
WV
TEL
WV
WV
A/C A/C EL
SAN
AG
WV
AG
UT
UT
UT
SAN
SAN
SAN
GTST
WV
WV
WV
WVWV
SAN
SAN
VENT
UT UT
A/C
UT
DOCK DOCK
TEL
A/C
BORE
AG
SSSSSSSS
EXISTING 18" RCP TO REMAIN
SS
SS
W W
W W
W
W
W
W
W
W
W
W
W
W W W
SS
SSEX
IS
TI
N G
2"
R C
P
TO
R
EM
AI
N
W
W
PROPOSED PCC
PAVEMENT,
1,468 S.Y.
EXISTING PCC
PAVEMENT
F-35 3-BAY
SPECIALIZED
HANGAR
PROPOSED
AIRSIDE
BITUMINOUS
PAVEMENT (OLI 2),
1413 S.Y.
EXISTING
BITUMINOUS
PAVEMENT
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING
BUILDING
EXISTING PCC
PAVEMENT
PROPOSED LANDSIDE
BITUMINOUS
PAVEMENT, 2,218 S.Y.
PROPOSED MARKING,
80 L.F.
PROPOSED 10' CHAIN
LINK FENCE WITH
VISUAL SLATS, 197 L.F.
PROPOSED DROP BEAM
BARRIER WITH KEYPAD AND
REMOTE ACROSS MITCHELL ST.
PROPOSED
SIDEWALK,
544 S.F.
PROPOSED LANDSIDE
BITUMINOUS PAVEMENT,
(OLI 1), 259 S.Y.
PROPOSED LANDSIDE
BITUMINOUS PAVEMENT, 175 S.Y.
PROPOSED LANDSIDE
BITUMINOUS PAVEMENT, 112 S.Y.
PROPOSED DOUBLE
SWING GATE 20 L.F.
OPENING
INTRUSION DETECTION CABLES
AND GAP SENSORS TO BE
REMOVED AND REPLACED,
SPLICING WILL NOT BE ALLOWED.
WORK TO BE COORDINATED WITH
ADVANTOR.
PROPOSED LANDSIDE
BITUMINOUS PAVEMENT,
143 S.Y.
PROPOSED 10' POST
AND PANEL WALL,
3 - 12' SECTIONS = 36 L.F.
PROPOSED 2' MOW
STRIP, TYP.
5'x5'
STOOP
5'x5'
STOOP
5'x5'
STOOP
PROPOSED
SIDEWALK, 1,087 S.F.
5'x8'
STOOP
(BASE BID)
PROPOSED SIDEWALK
(OLI 1), 141 S.F.
6'-10" x 10'-11"
MECHANICAL
PAD
2' MOW STRIP (BASE
BID), REMOVE FOR OLI 1
2' MOW STRIP (BASE
BID), REMOVE FOR OLI 1
2' MOW STRIP (OLI 1)
PAINT
BOOTH
(O
LI
1)1
4546 47
52 53
58 59 60
77 78
FEDERAL AVIATION
ADMINISTRATION CABLE IN THIS
AREA, APPROXIMATELY 24" DEEP.
THIS CABLE CANNOT BE SPLICED
IF CUT AND WOULD NEED
REPLACED ITS ENTIRE LENGTH.
PROPOSED
LANDSIDE
BITUMINOUS
PAVEMENT (OLI 2),
3,060 S.Y.
0 15' 30' 60' N
EXISTING PROPOSED LEGEND
BITUMINOUS PAVEMENT
PCC PAVEMENT
PCC SIDEWALK
WATER
ELECTRIC
GAS
COMMUNICATION
STORM
FENCE
STORM/SANITARY STRUCTURE
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
-B ay S pe ci al iz ed H an ga r M ad is on , W is co ns in
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
LDH
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
1525 S. 6th Street Springfield, IL 62703 phone: 217-788-2450 fax: 217-788-2503
PROPOSED PLAN
C-401
LDH
HLE
SS
ADDENDUM 2 06/08/20221
OLI - OPTIONAL LINE ITEM
AutoCAD SHX Text
SEE UTILITY PLAN FOR PROPOSED UTILITY INFORMATION
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
-B ay S pe ci al iz ed H an ga r M ad is on , W is co ns in
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
LDH
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
1525 S. 6th Street Springfield, IL 62703 phone: 217-788-2450 fax: 217-788-2503
TYPICAL SECTION AND
PAVEMENT DETAILS
HLE
LDH
C-402
ADDENDUM 2 06/08/20221
AutoCAD SHX Text
VARIES (SEE STAKING PLAN)
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL APRON SECTION
AutoCAD SHX Text
1. PROPOSED 12 INCH PCC PAVEMENT PROPOSED 12 INCH PCC PAVEMENT 2. PROPOSED 12 INCH STONE PROPOSED 12 INCH STONE 3. PROPOSED COMPACTED SUBGRADE OR FILL MATERIALPROPOSED COMPACTED SUBGRADE OR FILL MATERIAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
%%U SIDEWALK/STOOP/MOW STRIP CROSS SECTION DETAIL
AutoCAD SHX Text
VARIES
AutoCAD SHX Text x
AutoCAD SHX Text
VARIES
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text
VARIES
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text WITH 6x6-2.9x2.9 W.W.F.
AutoCAD SHX Text
PROPOSED CONCRETE SIDEWALK
AutoCAD SHX Text
%%UNOTES
AutoCAD SHX Text
1. JOINTS SHALL BE SPACED AT 6' MAX SPACING OR AS SPECIFIED. JOINTS SHALL BE SPACED AT 6' MAX SPACING OR AS SPECIFIED. 2. JOINTS SHALL BE CONTRACTION JOINTS. EXPANSION JOINTS WITH 1/2" PREFORMED JOINTS SHALL BE CONTRACTION JOINTS. EXPANSION JOINTS WITH 1/2" PREFORMED EXPANSION MATERIAL SHALL BE SPACED AT 36' MAX. INTERVALS. 3. 1/2" PREFORMED JOINT FILLER TO BE USED IN ALL LOCATIONS WHERE 1/2" PREFORMED JOINT FILLER TO BE USED IN ALL LOCATIONS WHERE SIDEWALK IS ADJACENT TO EXISTING PAVEMENT.
AutoCAD SHX Text
6 INCH AGGREGATE BASE COURSE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text POLYETHYLENE OR POLYESTER TAPE (3 MIL. MIN.) OR MARKING TAPE, RUBBER TAPE, 1/8" WIDER THAN WIDTH OF JOINT.
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
NEW PCC PAVEMENT
AutoCAD SHX Text
NEW PCC SIDEWALK
AutoCAD SHX Text
SEE SEALANT DETAIL 1
AutoCAD SHX Text
AGGREGATE BASE COURSE
AutoCAD SHX Text
%%UDETAIL 1 - SEALANT
AutoCAD SHX Text
1/4" MAX. BELOW PAVEMENT
AutoCAD SHX Text
1/4" RADIUS OR CHAMFER
AutoCAD SHX Text
SILICONE SEALANT 1 ± 1/8" DEPTH
AutoCAD SHX Text
PREFORMED JOINT FILLER, ASTM 1751
AutoCAD SHX Text
BOND BREAKER
AutoCAD SHX Text
2.0% AND VARIES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PAVEMENT SECTION - ASPHALT - AIRSIDE
AutoCAD SHX Text
1. PROPOSED 2" BITUMINOUS SURFACE COURSE 2. PROPOSED TACK COAT 3. PROPOSED 3" BITUMINOUS BASE COURSE 4. PROPOSED BITUMINOUS PRIME COAT 5. PROPOSED 12" AGGREGATE BASE COURSE 6. PROPOSED COMPACTED SUBGRADE OR FILL MATERIAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2.0% AND VARIES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PAVEMENT SECTION - ASPHALT - LANDSIDE
AutoCAD SHX Text
1. PROPOSED 2" BITUMINOUS SURFACE COURSE 2. PROPOSED TACK COAT 3. PROPOSED 2" BITUMINOUS BASE COURSE 4. PROPOSED BITUMINOUS PRIME COAT 5. PROPOSED 12" AGGREGATE BASE COURSE 6. PROPOSED COMPACTED SUBGRADE OR FILL MATERIAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING MITCHELL STREET PAVEMENT SECTION
AutoCAD SHX Text
1. 4" ASPHALT PAVEMENT 4" ASPHALT PAVEMENT 2. 15" AGGREGATE BASE COURSE15" AGGREGATE BASE COURSE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING BID OPTION 2 ASPHALT PAVEMENT SECTION
AutoCAD SHX Text
1. 5" ASPHALT PAVEMENT 5" ASPHALT PAVEMENT 2. 12" AGGREGATE BASE COURSE12" AGGREGATE BASE COURSE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXISTING PCC APRON PAVEMENT SECTION
AutoCAD SHX Text
1. 12" PCC PAVEMENT 12" PCC PAVEMENT 2. 12" AGGREGATE BASE COURSE12" AGGREGATE BASE COURSE
AutoCAD SHX Text
ACI AMERICAN CONCRETE INSTITUTE
ADD'L ADDITIONAL
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ANCH ANCHOR
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AT/FP ANTI-TERRORISM FORCE PROTECTION
AWS AMERICAN WELDING SOCIETY
BM BEAM
BO BOTTOM OF
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BASE PLATE
BR BRACING
BRG BEARING
BTWN BETWEEN
CFMF COLD FORMED METAL FRAMING
CJ CONSTRUCTION JOINT
CENTER LINE
CL CENTER LINE
CL COLLATERAL LOAD
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONNX CONNECTION
CONT CONTINUOUS
COORD COORDINATE
CR CENTER OF RADIUS
DBA DEFORMED BAR ANCHOR
DBE DECK BEARING ELEVATION
DEG DEGREE
db DIAMETER BAR
DIA DIAMETER
DL DEAD LOAD
DN DOWN
DWLS DOWELS
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATION
EQ EQUAL
EQUIV EQUIVALENT
EW EACH WAY
EXP EXPANSION
ºF/C DEGREES FAHRENHEIT/CELSIUS
FF FINISH FLOOR
FFE FINISHED FLOOR ELEVATION
FIN FINISH
FLR FLOOR
FLG FLANGE
FND FOUNDATION
FT FOOT/FEET
FTG FOOTING
FS FAR SIDE
GA GAGE
GALV GALVANIZED
GB GRADE BEAM
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING CODE
IMWP INSULATED METAL WALL PANEL
IN INCH/INCHES
JB JOIST BEARING
JST JOIST
JT JOINT
LBS POUNDS
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LSH LONG SIDE HORIZONTAL
LSSH LONG SLOTTED HOLES
MBM METAL BUILDING MANUFACTURER
MFR MANUFACTURER
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MPH MILES PER HOUR
NS NEAR SIDE
NSG NON-SHRINK GROUT
NTS NOT TO SCALE
OC ON CENTER
OH OPPOSITE HAND
OPNG OPENING
OVS OVERSIZED
PERIM PERIMETER
PL PLATE
± PLUS/MINUS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
REF REFER
REINF REINFORCE/REINFORCING
REQ'D REQUIRED
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SF SQUARE FEET
SIM SIMILAR
SJ SAWCUT JOINT
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SSLT SHORT SLOTTED HOLES
SSMA STEEL STUD MANUFACTURERS
ASSOCIATION
STD STANDARD
STIFF STIFFENER
TC TENSION CONTROL
TO TOP OF
TOF TOP OF FOUNDATION/FOOTING
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WL WIND LOAD
WP WORKING POINT
WWF WELDED WIRE FABRIC
WWR WELDED WIRE REINFORCEMENT
ABBREVIATIONS DESIGN CRITERIA:
GOVERNING BUILDING CODE: IBC 2018
BUILDING RISK CATEGORY: III
DESIGN LOADS:
DEAD LOADS:
ROOF SYSTEM ...................................................... 20 PSF SUPERIMPOSED
FUTURE PHOTOVOLTAIC PANELS ...................... 10 PSF
FRAMING................................................................. ACTUAL WEIGHT OF MATERIALS, UNLESS NOTED OTHERWISE
INSULATION............................................................ 1 PSF
CEILING COLLATERAL........................................... 3 PSF
MISCELLANEOUS .................................................. 5 PSF
MECHANICAL/ELECTRICAL/PLUMB...................... 5 PSF
LIVE LOADS:
ROOF (NON-REDUCIBLE)....................................... 20 PSF
TRAFFIC LOAD AT HANGAR ................................. F-35 (70400 LBS)
SNOW LOAD: (ASCE 7-16 AND WBDG WEBSITE)
BASIC GROUND SNOW LOAD, (Pg)....................... 30 PSF
TERRAIN CATEGORY............................................. C
ROOF EXPOSURE................................................... PARTIAL
EXPOSURE FACTOR, (Ce)...................................... 1.0 THERMAL FACTOR, (Ct).......................................... 1.0 SLOPE FACTOR, (Cs).............................................. 1.0 IMPORTANCE FACTOR, (Is).................................... 1.10 FLAT ROOF SNOW, (Ps).......................................... 23.1 PSF
WIND LOAD: (ASCE 7-16 AND WBDG WEBSITE)
BUILDING DESIGN:
BASIC WIND SPEED................................................. 115 MPH
EXPOSURE CATEGORY........................................... C
TOPOGRAPHIC FACTOR, (Kzt)............................... 1.0
BUILDING ENCLOSURE CATEGORY....................... ENCLOSED ADMIN
PARTIALLY ENCLOSED HANGARS
SEISMIC DESIGN DATA: (ASCE 7-16 AND WBDG WEBSITE)
SHORT PERIOD ACCELERATION, Ss ................... 0.074 g LONG PERIOD ACCELERATION, S1...................... 0.048 g
SOIL SITE CLASS ................................................... D
SITE COEFFICIENT, Fa .......................................... 1.6 SITE COEFFICIENT, Fv .......................................... 2.4 DESIGN SPECTRAL ACCELERATION, SDs .......... 0.079 g DESIGN SPECTRAL ACCELERATION, SD1 .......... 0.077 g
SEISMIC DESIGN CATEGORY .............................. B
ANALYSIS METHOD................................................ EQUIVALENT LATERAL FORCE
SEISMIC FORCE RESISTING SYSTEM.................. STEEL SYSTEMS NOT SPECIFICALLY
DETAILED FOR SEISMIC RESISTANCE
(HANGARS)
INTERMEDIATE REINFORCED
MASONRY SHEAR WALLS
(LOW ROOF AREA)
DESIGN BASE SHEAR............................................ 50 kips (LOW ROOF AREA) 16 kips (SINGLE BAY HANGAR) 20 kips (TWO BAY HANGAR)
R=3.0, Ω=3.0, Cd=3.0, I=1.25, Cs=0.033 (HANGARS) R=3.5, Ω=2.5, Cd=2.25, I=1.25, Cs=0.028 (LOW ROOF AREA)
TEMPERATURE:
STRUCTURE SHALL BE ANALYZED FOR T = +37,-53 °F (90 °F TOTAL ΔT )
MATERIAL DESIGN VALUES:
CONCRETE
ALL FOUNDATIONS AND NON HANGAR BAY SLABS ON GRADE
MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS
AND NORMAL WEIGHT CONCRETE ...................... 4,000 PSI
HANGAR BAY PAVEMENTS
FLEXURAL STRENGTH AT 90 DAYS .........................650 PSI
CONCRETE REINFORCEMENT(MINIMUM YIELD STRENGTH)
ALL DEFORMED BARS, UNLESS NOTED OTHERWISE.
(ASTM A615, GRADE 60)................................................ Fy = 60,000 PSI WELDED WIRE FABRIC (ASTM A185).......................... Fy = 60,000 PSI SMOOTH BARS (ASTM A82).......................................... Fy = 70,000 PSI DEFORMED BAR ANCHORS (ASTM A706)................... Fy = 60,000 PSI
STRUCTURAL STEEL (MINIMUM YIELD STRENGTH)
WIDE FLANGES (ASTM A992 OR A572, GR. 50).......... Fy = 50,000 PSI PIPES (ASTM A500, GRADE B)...................................... Fy = 42,000 PSI TUBES (ASTM A500, GRADE B)..................................... Fy = 46,000 PSI
ALL OTHER SHAPES AND PLATES
UNLESS NOTED OTHERWISE (ASTM A36)............. Fy = 36,000 PSI
ANCHOR RODS
(ASTM F 1554, WELDABLE GRADE 55).................... Fy = 55,000 PSI COLD FORMED STRUCTURAL SHAPES...................... Fy = 33,000 PSI (MIN)
MISCELLANEOUS NOTES:
1. REFERENCE DATUM ELEVATION 100'-0" IS EQUAL TO THE ACTUAL
FINISH FLOOR ELEVATION PROVIDED BY CIVIL. REFERENCED
ELEVATIONS ARE BASED ON THIS DATUM ELEVATION.
2. GENERAL NOTES AND TYPICAL DETAILS APPLY TO THE ENTIRE
PROJECT AND CONVEY ENGINEERING INTENT. SPECIFIC
DETAILS ARE NOT DRAWN FOR EVERY CONDITION OF
CONSTRUCTION OR ASSEMBLY. MANY CONDITIONS SIMILAR TO
THOSE DEPICTED EXIST AND THOSE SIMILAR CONDITIONS ARE
INCLUDED IN THE CONTRACT SCOPE OF WORK. THE
CONTRACTOR SHALL INCLUDE COST OF THE WORK FOR THESE
SIMILAR CONDITIONS. FUTURE CLARIFICATION OF DETAILS
SHALL NOT BE THE BASIS OF ADDITIONAL COMPENSATION FOR
THE CONTRACTOR.
CONSTRUCTION NOTES:
1. ALL INTERFERING PIPES, UTILITIES, AND FIXTURES WILL BE
RELOCATED BY CONTRACTOR AS REQUIRED.
2. THE CONTRACTOR IS HELD RESPONSIBLE FOR PROTECTION OF
PERSONNEL AND EQUIPMENT DURING THE COURSE OF
OPERATIONS ACCORDING TO CURRENT SAFETY REGULATIONS.
3. THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER COPIES OF
ALL SHOP DRAWINGS OF NEW WORK FOR APPROVAL.
4. THE CONTRACTOR SHALL REPAIR ALL EXISTING WORK WHICH
HAS BEEN DAMAGED BY HIS CONSTRUCTION OPERATIONS AND
REMOVE ALL DEBRIS FROM THE SITE AFTER COMPLETION OF
THE PROJECT.
SOILS/FOUNDATION NOTES:
1. FOUNDATION RECOMMENDATIONS ARE BASED ON THE
GEOTECHNICAL REPORT PREPARED BY GESTRA DATED
SEPTEMBER 10, 2020 FOR PROPOSED AIR NATIONAL GUARD
F-35 HANGAR FACILITY, TRUAX FIELD, MADISON, WISCONSIN,
PROJECT NO.: M20046-10.
2. THE ALLOWABLE SOIL BEARING PRESSURE IS 1500 PSF.
SHALLOW FOOTINGS SHALL BEAR AT LEAST 48 INCHES BELOW
FINAL GRADE FOR FROST PROTECTION AND SHALL HAVE A
MINIMUM WIDTH OF 18 INCHES FOR CONTINUOUS FOOTINGS AND
24 INCHES FOR SPREAD FOOTINGS.
3. SHALLOW GROUNDWATER (4-5 FEET BELOW THE SURFACE AT
THE TIME OF THE GEOTECHNICAL INVESTIGATION DRILLING) IS A
CONCERN. SEASONAL VARIATIONS IN GROUNDWATER
ELEVATION AND THE NEED TO PLACE FOUNDATIONS AT LEAST
48 INCHES BELOW FINISH GRADE MAY REQUIRE DEWATERING
DURING CONSTRUCTION. FOR EXCAVATIONS EXTENDING BELOW
THE GROUND WATER TABLE A FORMAL DEWATERING PLAN IS
REQUIRED TO LOWER THE GROUND WATER AT LEAST 2 FEET
BELOW THE BOTTOM OF THE EXCAVATION. EXCAVATIONS FOR
SHALLOW FOUNDATIONS MAY ALSO REQUIRE ADDITIONAL
EXCAVATION AND REPLACEMENT WITH OPEN GRADED
GRANULAR FILL OVERLYING A GEOTEXTILE TO PROVIDE A
STABLE WORKING SURFACE.
4. AFTER EXCAVATING, FOOTINGS SHOULD BE INSPECTED AND
CONCRETE PLACED AS QUICKLY AS POSSIBLE TO AVOID
EXPOSURE TO WETTING AND DRYING.
5. WATER SHOULD NOT BE ALLOWED TO COLLECT IN THE
EXCAVATIONS OR NEAR THE FOUNDATIONS AND FLOOR SLAB
AREAS OF THE BUILDINGS DURING CONSTRUCTION.
6. ALL VEGETATION, TOPSOIL, SOFT OR LOOSE SOIL, CONCRETE,
ASPHALT, OLD FOUNDATIONS AND DELETERIOUS MATERIALS
SHALL BE STRIPPED FROM THE BUILDING SITE. STRIPPING AND
UNDERCUTTING SHALL EXTEND A MINIMUM OF 5 FEET BEYOND
THE BUILDING PERIMETER AND THE DEPTH SHALL BE AS
DETERMINED BY THE GEOTECHNICAL ENGINEER.
7. AFTER STRIPPING THE SITE BUT PRIOR TO PLACING FILL THE
SITE SHALL BE COMPACTED. ANY AREAS OF SIGNIFICANT
DEFLECTION DURING COMPACTION MAY BE DISKED, DRIED, AND
RE-COMPACTED IF WEATHER PERMITS, OR REMOVED AND
REPLACED WITH ENGINEERED FILL. AFTER THE INITIAL
COMPACTION THE SITE SHALL BE PROOF ROLLED WITH A 20 TON
TANDEM AXLE DUEL WHEEL DUMP TRUCK. A GEOTECHNICAL
ENGINEER OR THEIR DESIGNATED REPRESENTATIVE SHOULD BE
PRESENT DURING THE PROOF ROLLING PROCESS IN ORDER TO
IDENTIFY SOFT OR UNSTABLE AREAS, IF ANY, AND
SUBSEQUENTLY RECOMMEND REMEDIATION PROCEDURES.
SOFT AREAS OF SUBGRADE THAT DEFLECT MORE THAN 1 INCH
OR SHOW PERMANENT DEFORMATION GREATER THAN 1 INCH
SHALL BE REMEDIATED. WHERE SUBGRADE REMEDIATION IS
NEEDED THE TYPE OF REMEDIATION AND THE DEPTH NEEDED
SHOULD BE DETERMINED AT THE TIME OF CONSTRUCTION
BASED ON DRAINAGE, WEATHER AND SOIL CONDITIONS. REFER
TO THE GEOTECHNICAL REPORT FOR REMEDIATION OPTIONS.
8. AFTER PROOF ROLLING AND ANY REQUIRED REMEDIATION THE
SUBGRADE SOILS SHALL BE SCARIFIED TO A DEPTH OF 8
INCHES, MOISTURE CONTENT ADJUSTED TO WITHIN (+/-) 2
PERCENT THE OPTIMUM MOISTURE CONTENT, AND COMPACTED
TO 95 PERCENT OF THE MODIFIED PROCTOR MAXIMUM DRY
DENSITY.
9. AFTER INSPECTION OF THE SUBGRADE, STRUCTURAL FILL
MATERIAL SHALL BE PLACED IN LIFTS BETWEEN 6 AND 12
INCHES. EACH LIFT OF STRUCTURAL FILL MATERIAL SHALL HAVE
THE MOISTURE CONTENT ADJUSTED TO WITHIN (+/-) 2 PERCENT
OF THE OPTIMUM MOISTURE CONTENT, AND COMPACTED TO 95
PERCENT OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY.
10. THE GEOTECHNICAL ENGINEER SHALL PROVIDE
RECOMMENDATIONS FOR SUITABLE TYPES OF ENGINEERED
FILL. WHERE UNSUITABLE SOILS ARE ENCOUNTERED AT THE
BASE OF THE FOUNDATIONS, SOIL CORRECTION SHOULD
CONSIST OF ADDITIONAL EXCAVATION TO REMOVE THE
UNSUITABLE SOILS TO A DEPTH AS DETERMINED BY THE
GEOTECHNICAL ENGINEER. THESE OVER EXCAVATIONS SHALL
BE FILLED WITH ENGINEERED FILL AS GIVEN IN NOTE 9.
ALTERNATELY A LEAN CONCRETE WITH A MINIMUM
COMPRESSIVE STRENGTH OF 500 PSI CAN BE USED TO FILL THE
OVER-EXCAVATION TO THE BOTTOM OF THE FOUNDATION.
CONCRETE CONSTRUCTION NOTES:
1. ALL DETAILING, FABRICATION AND PLACING OF REINFORCING
BARS, UNLESS NOTED OTHERWISE, SHALL FOLLOW THE LATEST
EDITION ACI DETAILING MANUAL, DETAILS AND DETAILING OF
CONCRETE REINFORCEMENT, ACI MANUAL OF ENGINEERING
AND PLACING DRAWINGS FOR REINFORCED CONCRETE
STRUCTURES, ACI SPECIFICATIONS FOR STRUCTURAL
CONCRETE FOR BUILDINGS AND THE PROVISIONS OF ACI
"BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE"
(ACI 318-APPLICABLE EDITION).
2. UNLESS NOTED OTHERWISE, LAP SPLICES OR EMBEDMENT
LENGTHS SHALL CONFORM TO ACI REQUIREMENTS FOR CLASS B
SPLICES. REFER TO CONCRETE REINFORCEMENT LAP LENGTH
SCHEDULE.
3. UNLESS NOTED OTHERWISE, CONCRETE COVER OVER STEEL
REINFORCEMENT SHALL CONFORM TO MINIMUM REQUIRED BY
ACI 318-APPLICABLE EDITION.
4. AT INTERSECTING FOUNDATIONS AND CURBS EXTEND ALL
HORIZONTAL REINFORCING OF THE INTERSECTING MEMBER
BEYOND THE POINT OF INTERSECTION TO THE OPPOSITE FACE
AND BEND TO A STANDARD 90 DEGREE HOOK, OR PROVIDE
BENT DOWELS OF EQUAL SIZE AND SPACING AND LAP AS
REQUIRED BY NOTE 2 (BUT NOT LESS THAN 24") IN EACH
DIRECTION.
5. AT FOUNDATION AND CURB CORNERS, PROVIDE TOP AND
BOTTOM CORNER BARS. NUMBER, SIZE AND SPACING OF
CORNER BARS SHALL BE EQUAL TO NUMBER, SIZE AND SPACING
OF HORIZONTAL REINFORCING WITH WHICH THEY LAP AND
SHALL EXTEND 40 BAR DIAMETERS IN EACH DIRECTION. IF
REINFORCING MEETING AT THE CORNER IS OF DIFFERENT SIZE,
CORNER BAR SHALL MATCH THE LARGER OF THE BARS. BOTH
LEGS OF CORNER BARS SHALL BE EQUAL LENGTH.
6. TOP AND BOTTOM STEEL REINFORCING OF CONTINUOUS
FOOTINGS SHALL PASS THROUGH THE CONFINED CORE OF THE
COLUMN FOOTINGS. CONTINUOUS FOOTING TIE/STIRRUPS
SHALL START WITHIN 3" OF FACE OF COLUMN FOOTING.
7. ALL REINFORCING SHALL BE SUPPORTED FROM THE INTERIOR
OF THE CONCRETE ELEMENTS. PROVIDE ALL STANDS
REQUIRED TO ADEQUATELY HOLD REINFORCEMENT IN PLACE
DURING CONCRETE PLACEMENT.
8. PROVIDE SLEEVES IN SLABS AND FOUNDATION FOR ALL
PENETRATIONS (DO NOT DRILL). LOCATIONS MUST BE
APPROVED BY ARCHITECT-ENGINEER. REFER TO DETAIL
FOR PIPE PENETRATIONS THROUGH GRADE BEAMS.
9. UNLESS NOTED OTHERWISE ON ARCHITECTURAL DRAWINGS,
PROVIDE 3/4" CHAMFER ON ALL EXPOSED CONCRETE EDGES.
10. PROVIDE CONCRETE EQUIPMENT PADS OF SIZE REQUIRED FOR
EQUIPMENT FURNISHED. SEE MECHANICAL AND ELECTRICAL
DRAWINGS FOR NUMBER, SIZE AND LOCATION OF SUCH PADS
ON THE FLOOR SLAB UNLESS OTHERWISE SHOWN. REFER TO
DETAIL FOR REINFORCEMENT INFORMATION.
11. THE SIZE AND LOCATION OF ALL EQUIPMENT PADS, FLOOR PITS,
TRENCH DRAINS AND OPENINGS FOR ALL DUCTS AND PIPES
THROUGH FLOOR SLABS AND FOOTINGS SHALL BE VERIFIED
WITH THE MECHANICAL AND ELECTRICAL CONTRACTORS
REQUIREMENTS PRIOR TO PLACEMENT.
12. ALL CONCRETE SLAB ACCESSORIES (TRENCHES, GRATING,
EMBEDDED ITEMS, ETC.) SHALL BE DESIGNED FOR THE UNIFORM
AND CONCENTRATED LIVE LOADS ON THIS SHEET.
13. LOCALLY SLOPE THE SLAB TO FLOOR DRAINS WITH AN 18"
RADIUS AROUND THE DRAIN BODY. REFER PLUMBING FOR
ADDITIONAL FLOOR DRAIN INFORMATION.
14. REFER TO THE PLUMBING SPECIFICATIONS FOR THE USE OF
SLEEVES AND SEALANTS AT PLUMBING PENETRATIONS
THROUGH THE SLAB ON GRADE AND GRADE BEAM.
15. PROVIDE BOLLARDS AS REQUIRED BY ARCHITECTURAL SHEETS.
REFER TO DETAIL FOR ADDITIONAL INFORMATION.
B3 / S-003
D3 / S-003
B1 / S-003
REINFORCED MASONRY NOTES:
1. ALL CMU SHALL BE 1 OR 2-CELL BLOCK.
2. MASONRY DESIGN STRENGTH, F’m = 2,000 PSI.
3. MINIMUM MORTAR COMPRESSIVE STRENGTH SHALL BE 2,000 PSI
AT 28 DAYS.
4. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL
ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED
CONTINUOUS VERTICAL CELL NOT LESS THAN 2 INCHES BY 3
INCHES IN PLAN DIMENSION.
5. SLAB DOWELS SHALL BE INSTALLED PER THE CMU DETAILS.
POST-INSTALLED BARS WITH EPOXY ARE ALLOWED.
CONTRACTOR TO PROVIDE PRODUCT DATA. EMBEDMENT OF
BAR WITH EPOXY TO DEVELOP 125% OF NOMINAL YIELD STRESS
OF BAR.
6. LOCATION OF CONTROL JOINTS SHALL BE AS SHOWN ON CMU
ELEVATION SHEETS AND DETAILS OF CONTROL JOINTS SHALL
BE AS SHOWN, REFER TO TYPICAL MASONRY DETAILS.
7. REFER TO ARCHITECTURAL DRAWINGS FOR ALL CMU WALL
INFORMATION NOT SHOWN IN STRUCTURAL.
8. AN ADDITIONAL VERTICAL BAR OF THE SAME SIZE AND LENGTH
AS THE NORMAL REINFORCING BAR SHALL BE PLACED:
A. ON EACH SIDE OF CONTROL JOINTS
B. AT ALL WALL INTERSECTIONS OF EXTERIOR WALLS
C. AT ALL DISCONTINUOUS EDGES
D. AT ALL DOOR AND WINDOW JAMS
E. AS SHOWN ON STRUCTURAL DRAWINGS
9. CMU LINTELS SHALL USE THE BARS AS REQUIRED PER TYPICAL
CMU WALL OPENING DETAIL AND CMU LINTEL TYPES, UNLESS
NOTED OTHERWISE. ALL OPENINGS GREATER THAN 2 FEET
SHALL HAVE A LINTEL.
10. CELLS WHICH CONTAIN REINFORCING STEEL SHALL BE FILLED
SOLIDLY WITH 2,000 PSI COARSE GROUT MEETING THE
REQUIREMENTS OF ASTM C476.
11. PROVIDE BOND BEAMS AT ELEVATION 98'-8", 99'-4", 103'-4",
107'-4", EVERY 6TH COURSE UNLESS AT TOP OF WALL. IF AT TOP
OF WALL PROVIDE TOP TWO COURSES AS BOND BEAMS.
REINFORCE 8" CMU BOND BEAMS WITH (1) #5 CONT AND 12" CMU
BOND BEAMS WITH (2) #5 CONT.
STEEL CONSTRUCTION NOTES:
1. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND
ERECTED IN ACCORDANCE WITH THE APPLICABLE EDITIONS OF
THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS
AND BRIDGES" AND THE AISC "SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS", AND AS SUPPLEMENTED BY THESE GENERAL
NOTES IN ADDITION TO THE PROJECT SPECIFICATIONS.
2. THE STEEL CONTRACTOR SHALL FURNISH ERECTION BOLTS AS
REQUIRED FOR FIELD CONNECTIONS.
3. ALL BEAMS THAT ARE REQUIRED TO HAVE CAMBER SHALL BE
FABRICATED WITH CAMBERS UPWARD. BEAMS WITHOUT
SPECIFIED CAMBER SHALL BE FABRICATED SUCH THAT AFTER
ERECTION ANY CAMBER DUE TO ROLLING OR SHOP
FABRICATION IS UPWARD.
4. ALL SHOP AND FIELD WELDS SHALL BE MADE IN ACCORDANCE
WITH THE ANSI/AWS "D1.1 STRUCTURAL WELDING CODE -
STEEL", APPLICABLE EDITION.
5. UNLESS NOTED OTHERWISE, ALL BOLTS SHALL BE ASTM A325-N
WITH SUITABLE WASHERS AND NUTS.
6. SUBSTITUTION OF EXPANSION ANCHORS FOR EMBEDDED
ANCHORS SHOWN ON THE DRAWING WILL NOT BE PERMITTED.
7. CUTS, HOLES, COPING, ETC. REQUIRED FOR WORK OF OTHER
TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE
IN THE SHOP. CUTS OR BURNING OF HOLES IN STRUCTURAL
STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED.
8. THE ERECTION CONTRACTOR SHALL SURVEY ANCHOR RODS
AND REPORT ANY DISCREPANCIES FROM THE CONTRACT
DOCUMENTS TO THE ARCHITECT-ENGINEER. ALL CORRECTIONS
TO WORK MUST BE APPROVED IN WRITING BY THE ARCHITECT-
ENGINEER PRIOR TO THE START OF ERECTION.
9. REFER TO ARCHITECTURE FOR ADDITIONAL MISCELLANEOUS
STEEL NOT SHOWN IN THE STRUCTURAL DRAWINGS.
10. ALL ADDITIONAL FRAMING REQUIRED TO SUPPORT OR BRACE
MECHANICAL OR ELECTRICAL EQUIPMENT OR PIPING NOT
SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE SUPPLIED
BY THE MECHANICAL OR ELECTRICAL CONTRACTOR AT NO
ADDITIONAL COST TO THE OWNER. CONTRACTOR TO CAREFULLY
COORDINATE AND DESIGN BRACING AND SUPPORT STRUCTURES
TO NOT OVERLOAD THE FRAMING SHOWN IN THESE
DOCUMENTS.
STEEL DECK NOTES:
1. ALL STEEL DECK SHALL SPAN A MINIMUM OF (3) SPANS IN THE
DIRECTION SHOWN ON THE FRAMING PLANS.
2. FOR DECK TYPE ORIENTATION AND FASTENER PATTERN REFER
TO THE COMPOSITE ROOF FRAMING PLAN.
3. PIPES, CONDUITS, DUCTS AND OTHERS ITEMS HANGING FROM
ROOF SHALL BE ATTACHED TO THE BOTTOM FLANGE OF A BEAM.
HANGING FROM THE BOTTOM OF DECK IS NOT PERMITTED.
PROVIDE KICKERS FOR SUSPENDED MECHANICAL EQUIPMENT.
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
C :\U sers\ich\D o cum ents\M y R evit\02700_Stru_ih ortonXV Z5D
.rvt 6/7/2022 9:10:2 1 A
M
GENERAL NOTES
S-001
TJD
ICH
ICH
1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
GENE O.
BROWN
E-47748
SUPPORTING MEMBER
OPENING
SUPPORTING MEMBER
L4x3x1/4 LLV FOR SPANS ≤ TO 4'-0" L5x3x1/4 LLV FOR SPANS > 4'-0" < 6'-0"
L6x4x3/8 LLV FOR SPANS > 5'-0" < 8'-0" L5x3x1/4 LLV FOR SPANS ≤ TO 5'-0"
NOTES:
1. DECK TO BE FASTENED TO ALL ANGLES.
2. PROVIDE ANGLE FRAME FOR ALL
OPENINGS LARGER THAN 6" IN ANY
DIRECTION.
L3x3x1/4x0'-4"
(WELD TO SUPPORTING MEMBER)
WELD ALL EXPOSED SURFACES
TYPICAL FOR ROOF OPENING
FRAMES INSTALLED AFTER
STEEL DECK IS IN PLACE
TYP FOR ROOF OPENING
FRAMES INSTALLED BEFORE
STEEL DECK IS IN PLACE 3/16
3/16
TYP
3/16 3/16
TYP
1/4
J
J
G
G
F
F
E
E
C
C
M
M
K
K
L
L
H
H
23'-10" 22'-0" 22'-6"
'-4
'-6
'-6
'-6
'-6
'-4
A4
SF210
A1
SF210
W14X22
(ABOVE)
W14X22
(ABOVE)
B4
SF210
'-4
'-4
'-4
'-4
B1
SF210
'-0
'-0
15'-2" 38'-0"
28'-4" 28'-4"
C4
SF210
C1
SF210
C4
SF210
16'-5" 38'-0"
'-2
'-0
18'-0" 18'-0"
18'-0" 18'-0"
'-9
'-0
7' -0
'-1 0"
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
W14X22
(ABOVE)
TYP
0"
5/16
FALL ARREST PROTECTION
SYSTEM AT ROOF
ROOF FRAMING
(REF PLAN)
1' -5
" M
IN
4" ROUND PIPE MAX
REFER HIGH ROOF FRAMING PLAN
L4X4X1/4
2-1/2X2-1/2X1/4
STIFFENER TYP
1 3/16
3 SIDES
TYP
1/
2"
3/4" DIA BOLT
TYP
SELF-LOCKING
CARABINER W/ 3/4" GATE
OPENING
ULTRA-LOCK SELF
RETRACTING LIFELINE (SRL)
25 FT
TROLLEY ANCHORAGE
CONNECTOR
W12X45 FALL ARREST
SUPPORT
BOS
125'-0"
" M
AX
D
EP
TH
3"
W BEAM (REF PLAN)
W12X45 FALL ARREST BEAM
HSS4X4X1/4 POST
3/8"X5"X8" PL W/ (2)
3/4" DIA BOLT A325-N
L2-1/2X2-1/2X1/4 KICKER
1/4" PL W/ (1) 3/4" DIA BOLT TYP
VA
R
IE
S
1/4
1/4 1/4
1/4 1/4
1/4 1/4
2 1/2" 1 1/2" 1 1/2"
2 1/2"
2"
7" 3"
1/
2"
1/4 6 1/4 6
TYP
3/8"X6"X9 1/2" PL
NOTE: ADJUST DIMENSION
OF THE 3/8" PL AT SLOPED
W BEAM MEMBERS
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
C :\U sers\ich\D o cum ents\M y R evit\02700_Stru_ih ortonXV Z5D
.rvt 6/7/2022 9:10:2 0 A
M
FALL ARREST DIAGRAM
S-002
TJD
ICH
ICH
SCALE: NTS
ROOF FRAMED OPENINGA3SCALE: NTS
FALL ARREST DIAGRAMA1
SCALE: NTS
FALL ARREST PROTECTION SYSTEM AT ROOFB3
SCALE: NTS
FALL ARREST SECTIONC3
SCALE: NTS
FALL ARREST POST DETAILD4
1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
GENE O.
BROWN
E-47748
A
J
GFEC
CB
MK LD
H
A.3
C.2 G.6F.7B.7
4.3
10'-10" 45'-1 1/2" 23'-10" 22'-0" 22'-6" 9'-0"
3' -1
0"
9' -9
'-7
7' -3
/8
'-0
/8
'-6
'-6
'-1
1/
8"
9' -6
/8
'-6
'-6
/4
8' -9
/4
'-6
'-0
'-1
0"
'-4
/4
9' -0
'-0
/8
'-8
/8
'-4
'-4
35'-10 3/8" 14'-2 3/8" 5'-10 3/4"
2'-8 1/4"
10'-10 5/8" 25'-8 1/8" 35'-2 3/4"
2'-11" 20'-6" 20'-8" 20'-6"
BRACING
BR
AC
IN
G
BR
AC
IN
G
BRACING
BRACING
BRACING
BR
AC
IN
G
BR
AC
IN
G
MATCHLINE
0'
-2
1. PROVIDE BOTTOM FLANGE BRACES ON ALL PERIMETER ROOF
BEAMS AS SHOWN ON DETAILS.
2. ALL SUSPENDED MECHANICAL, ELECTRICAL AND FIRE
PROTECTION PIPES OR EQUIPMENT SHALL BE SUPPORTED BY
BEAMS. PROVIDE KICKERS AS NEEDED. ATTACHMENT TO
METAL DECK FROM BELOW IS NOT ALLOWED.
3. LOCATION AND WEIGHTS OF MECHANICAL EQUIPMENT SHOWN
ON PLAN ARE BASIS OF DESIGN. VERIFY WITH MECHANICAL
FOR ADDITIONAL INFORMATION. GC TO COORDINATE FINAL
LOCATION AND WEIGHT WITH SUPPORT REQUIREMENTS.
LOW ROOF FRAMING PLAN NOTES
2 MECHANICAL ROOF TOP UNIT OR MAKE UP AIR UNIT. REFER
TO MECHANICAL FOR UNIT SCHEDULING. GC TO COORD
FINAL LOCATION OF THE W8X18 SUPPLEMENTARY STEEL TO
SUPPORT UNIT CURBS ONCE FINAL UNITS HAVE BEEN
SELECTED. GC TO COORDINATE OPENINGS THRU ROOF OR
WALL AND PROVIDE ANGLE FRAMING FOR ROOF OPENING
AND COLD FORMED FRAMING AT WALL OPENINGS.
MECHANICAL EXHAUST FAN. REFER TO MECHANICAL
DRAWINGS FOR FAN SCHEDULING. PROVIDE ANGLE FRAME
AT EXHAUST FAN TO SUPPORT DUCT PENETRATION IN THE
DECK AND THE EXHAUST FAN CURB PER DETAIL .
GC TO COORD LOCATION OF ANGLE FRAME ONCE FINAL
UNIT SIZE AND LOCATION HAVE BEEN SELECTED.
A3 / S-002
1 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 20" OC.
4 PCA UNITS. PROVIDE STEEL FRAMING AS SHOWN ON
DETAIL . REFER TO MECHANICAL DRAWINGS
FOR UNIT SCHEDULING.
5 SKYLIGHTS AND SKYLIGHT OPENING FRAMING
6 CMU WALL BELOW. REFER TO FOUNDATION PLAN.
A1 / SF508
7 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 6" OC.
8 EXPANSION JOINT ALONG WALL
9 MECHANICAL GAS PIPE ANCHOR. REFER TO DETAIL
A4/SF101.
COORDINATE FINAL LOCATION AND HEIGHT WITH THE
MECHANICAL CONTRACTOR.
C O
O R
D W
/ M
EC
H
AS
R
EQ
U
IR
ED
1/
4"
3/
4"
3/ 4"
1/
4"
4"
8"
CAP PLATE PLAN VIEW
1/4
TYP
1/4
TYP
(2) 3/8" "U" BOLTS
MECH PIPING
HSS3X0.25 POST
ROOFING BOOT JACK
REFER ARCH
6" RIGID INSULATION
REFER ARCH
ROOF DECK
REFER PLAN
ROOF BEAM
REFER PLAN
1/4" CAP PLATE
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021N
N
PROJECT
KEYPLAN
A
PLAN TRUE
C :\U sers\ich\D o cum ents\M y R evit\02700_Stru_ih ortonXV Z5D
.rvt 6/7/2022 9:10:2 3 A
M
LOW ROOF FRAMING PLAN -
COMPOSITE
SF101
TJD
CTW
CTW
SCALE: 1/16" = 1'-0"
LOW ROOF FRAMING PLAN - COMPOSITEA1
0 8' 16' 32'
1/16" = 1'-0"
0 6" 1' 2'
1" = 1'-0"
SCALE: 1" = 1'-0"
TYPICAL MECHANICAL ROOF PIPE ANCHOR DETAILA4 1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
GENE O.
BROWN
E-47748
J
GFEC
C
B
B
MK LD
H
8C1
SF209
D1
SF210
W
X3
W18X35 W18X40
W18X35
W
X4
W18X35 W21X44
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X2
W
X4
W
X4
W
X4
W12X14
W 10X22
W10X12
14'-2 3/8" 5'-10 3/4" 2'-8 1/4"
10'-10 5/8" 25'-8 1/8" 35'-2 3/4" 2'-11"
20'-6" 20'-8" 20'-6"
3' -1
0"
9' -9
'-7
'-6
'-0
'-1
0"
'-4
/4
9' -0
'-0
/8
C1
SF202
C1
SF207
C1
SF206
C1
SF208
C4
SF402
W16X26
W
X2
W
X2
W
X2
W
X2
W
X2
W16X26
W
X2
W
X2
4'-0" 5'-0" 5'-0" 5'-0" 5'-0" 4'-0" 5'-0" 5'-0" 4'-9 1/4"
4'-0 1/8"
5'-0" 3'-9" 3'-9 1/4"
1'-7 1/4"
2'-11"
W
X2
W
X4
W
X4
W
X4
W
X4
W
X4
W
X4
W
X4
W
X4
W
X4
W
X4
W
X5
W
X1
W
X1
W
X1
W18X35
3'-8" 5'-0" 5'-0" 5'-3 1/2" 4'-3 1/2"
5'-2" 5'-3" 4'-0" 5'-0"
1'-3 1/8" 3'-8 7/8"
5'-0" 5'-0" 4'-0"
4'-3 1/8" 8 7/8" 5'-0" 4'-9 5/8"
3'-11 3/4"
3'-4 3/8" 4'-7 3/8" 4'-2 1/2"
4'-9 1/2"
2'-10 1/4"
3' -6
/8
7' -8
/2
7'
-9
/2
4 1/4"
C.2 G.6F.7B.7
4.3
3/4"
1 1/2"
2' -3
/2
3'
-6
3' -6
1/ 2"
4'-1 3/8"
4 1/2"
4'-6" 4'-6"
1'-6 1/8"
HVU-1
1500 LBS
RTU
2670 LBS
EF
72 LBS
2'-11"
W
X2
1'-4 5/8"
1'-1 3/8"
W16X26
W16X26 W16X26
W16X26
W
X3
BRACING
BR
AC
IN
G
BR
AC
IN
G
MATCHLINE
SEE A1 /
SF103
MATCHLINE
SEE A1 /
SF103
A1
SF206
A1
SF208
A1
SF207
A1
SF209
W
X2
CMU
WALL
STEEL
FRAMING
W
X2 21' -0
SF504
A3
SF502
C1
TYP
SF502
C2
TYP
SF507
A1
SF507
B5
TYP
PIPE RACK
(REFER ELEV)
GIRTS TYP
(REFER ELEV)
20'-1 1/8" 23'-10" 22'-0" 22'-6" 9'-0"
4'-9 1/4"
4'-0 1/8"
5'-0"
AT GRID 6
SF507
D5
SIM
W
X3
SF507
B3
SIM
SF507
B43 1/2"
DECK BRG
116'-8 1/8"
DECK BRG
116'-8 1/8"
1. PROVIDE BOTTOM FLANGE BRACES ON ALL PERIMETER ROOF
BEAMS AS SHOWN ON DETAILS.
2. ALL SUSPENDED MECHANICAL, ELECTRICAL AND FIRE
PROTECTION PIPES OR EQUIPMENT SHALL BE SUPPORTED BY
BEAMS. PROVIDE KICKERS AS NEEDED. ATTACHMENT TO
METAL DECK FROM BELOW IS NOT ALLOWED.
3. LOCATION AND WEIGHTS OF MECHANICAL EQUIPMENT SHOWN
ON PLAN ARE BASIS OF DESIGN. VERIFY WITH MECHANICAL
FOR ADDITIONAL INFORMATION. GC TO COORDINATE FINAL
LOCATION AND WEIGHT WITH SUPPORT REQUIREMENTS.
LOW ROOF FRAMING PLAN NOTES
2 MECHANICAL ROOF TOP UNIT OR MAKE UP AIR UNIT. REFER
TO MECHANICAL FOR UNIT SCHEDULING. GC TO COORD
FINAL LOCATION OF THE W8X18 SUPPLEMENTARY STEEL TO
SUPPORT UNIT CURBS ONCE FINAL UNITS HAVE BEEN
SELECTED. GC TO COORDINATE OPENINGS THRU ROOF OR
WALL AND PROVIDE ANGLE FRAMING FOR ROOF OPENING
AND COLD FORMED FRAMING AT WALL OPENINGS.
MECHANICAL EXHAUST FAN. REFER TO MECHANICAL
DRAWINGS FOR FAN SCHEDULING. PROVIDE ANGLE FRAME
AT EXHAUST FAN TO SUPPORT DUCT PENETRATION IN THE
DECK AND THE EXHAUST FAN CURB PER DETAIL .
GC TO COORD LOCATION OF ANGLE FRAME ONCE FINAL
UNIT SIZE AND LOCATION HAVE BEEN SELECTED.
A3 / S-002
1 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 20" OC.
4 PCA UNITS. PROVIDE STEEL FRAMING AS SHOWN ON
DETAIL . REFER TO MECHANICAL DRAWINGS
FOR UNIT SCHEDULING.
5 SKYLIGHTS AND SKYLIGHT OPENING FRAMING
6 CMU WALL BELOW. REFER TO FOUNDATION PLAN.
A1 / SF508
7 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 6" OC.
8 EXPANSION JOINT ALONG WALL
9 MECHANICAL GAS PIPE ANCHOR. REFER TO DETAIL
A4/SF101.
COORDINATE FINAL LOCATION AND HEIGHT WITH THE
MECHANICAL CONTRACTOR.
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021N
N
PROJECT
KEYPLAN
A
PLAN TRUE
C :\U sers\ich\D o cum ents\M y R evit\02700_Stru_ih ortonXV Z5D
.rvt 6/7/2022 9:10:2 4 A
M
LOW ROOF FRAMING PLAN -
SECTOR ONE
SF102
TJD
GMR
GMR
SCALE: 1/8" = 1'-0"
LOW ROOF FRAMING PLAN - SECTOR ONEA1
0 4' 8' 16'
1/8" = 1'-0"
1 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
GENE O.
BROWN
E-47748
A G
G
F
F
E
E
C
CB
H
H
C1
SF205D3
SF210
W
X3
W
X3
W
X3
W
X3
W
X3
W12X26
W
X1
W12X26
W24X55
W
X3
W
X3
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22
C8X11.5
C8X11.5
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22
W10X22 W10X22
W10X12
W10X12
7' -3
/8
'-0
/8
'-6
'-6
'-1
1/
8" 9'
-6
/8
'-6
'-6
/4
8' -9
/4
10'-10" 45'-1 1/2" 23'-10" 22'-0" 22'-6" 9'-0"
C1
SF201
C1
SF202
C1
SF204
A1
SF203
W24X55
W24X55
W24X55
W24X55
W24X55 W24X55
W16X26
W16X26
W16X26
W
X3
W16X26
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
W24X55
A.3
A.3
DOAS
1805 LBS
MAU
6065 LBS CCU
1830 LBS
HUM
800 LBS
HUM
1000 LBS
PCA
3500 LBS
PCA
3500 LBS
CCU
1825 LBS
HUM
800 LBS
MAU
6065 LBS
HUM
800 LBS
2' -9
/8
4' -6
3' -2
/2
4' -6
5'
-0
4' -6
4'
-6
5' -0
5'
-0
4' -6
4'
-6
5' -0
5'
-0
4' -1
7/
8"
4' -0
/8
4'
-3
/2
4' -0
5'
-0
5' -0
5'
-0
5' -0
5'
-0
5' -0
1' -0
/8
2'
-1
1/ 8"
4' -0
4'
-7
/8
4'-1"
A1
SF508
A1
SF508
SIM
BRACING
BR
AC
IN
G
BR
AC
IN
G
BRACING
BRACING
W
X3
6 6
MATCHLINE
SEE A1 /
SF102
MATCHLINE
SEE A1 /
SF102
ABOVE
ABOVE
AB
O
VE
A
N D
BE
LO
W
A1
SF201
A1
SF202
A1
SF205
W
X3
CMU
WALL
ELEV
STEEL
FRAMING
ELEV
A1
SF203
OH
SF502
C2
SF502
C1
SF504
A3
SF507
B5
TYP
TYP
TYP
TYP
SF507
B5 TYP
SF504
B3
SF504
B5
PIPE RACKS
(REFER ELEV)
PIPE RACKS
(REFER ELEV)
PIPE RACKS
(REFER ELEV)
PIPE RACKS
(REFER ELEV)
GIRTS (REFER ELEV)
A1
SF211
'-4
'-4
SF502
A3
A1
SF210
1'-0"
1'-0"SF507
D5
SF507
B3
TYP
SF507
D5
SIM
SF507
C3
SF507
C4 TYP
UNO
SF507
C3SIM
SF507
D5 SIM
SF507
D5 SIM
D E
C K
BR
G
4'
-5
/8
D E
C K
BR
G
6'
-8
/8
DECK BRG
114'-7 1/4"
DECK BRG
116'-8 1/8"
MAU
690 LBS 2
SF-01 75 LBS
1. PROVIDE BOTTOM FLANGE BRACES ON ALL PERIMETER ROOF
BEAMS AS SHOWN ON DETAILS.
2. ALL SUSPENDED MECHANICAL, ELECTRICAL AND FIRE
PROTECTION PIPES OR EQUIPMENT SHALL BE SUPPORTED BY
BEAMS. PROVIDE KICKERS AS NEEDED. ATTACHMENT TO
METAL DECK FROM BELOW IS NOT ALLOWED.
3. LOCATION AND WEIGHTS OF MECHANICAL EQUIPMENT SHOWN
ON PLAN ARE BASIS OF DESIGN. VERIFY WITH MECHANICAL
FOR ADDITIONAL INFORMATION. GC TO COORDINATE FINAL
LOCATION AND WEIGHT WITH SUPPORT REQUIREMENTS.
LOW ROOF FRAMING PLAN NOTES
2 MECHANICAL ROOF TOP UNIT OR MAKE UP AIR UNIT. REFER
TO MECHANICAL FOR UNIT SCHEDULING. GC TO COORD
FINAL LOCATION OF THE W8X18 SUPPLEMENTARY STEEL TO
SUPPORT UNIT CURBS ONCE FINAL UNITS HAVE BEEN
SELECTED. GC TO COORDINATE OPENINGS THRU ROOF OR
WALL AND PROVIDE ANGLE FRAMING FOR ROOF OPENING
AND COLD FORMED FRAMING AT WALL OPENINGS.
MECHANICAL EXHAUST FAN. REFER TO MECHANICAL
DRAWINGS FOR FAN SCHEDULING. PROVIDE ANGLE FRAME
AT EXHAUST FAN TO SUPPORT DUCT PENETRATION IN THE
DECK AND THE EXHAUST FAN CURB PER DETAIL .
GC TO COORD LOCATION OF ANGLE FRAME ONCE FINAL
UNIT SIZE AND LOCATION HAVE BEEN SELECTED.
A3 / S-002
1 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 20" OC.
4 PCA UNITS. PROVIDE STEEL FRAMING AS SHOWN ON
DETAIL . REFER TO MECHANICAL DRAWINGS
FOR UNIT SCHEDULING.
5 SKYLIGHTS AND SKYLIGHT OPENING FRAMING
6 CMU WALL BELOW. REFER TO FOUNDATION PLAN.
A1 / SF508
7 ROOF DECKING
1.5B 20GA GALV ROOF DECK (33 KSI MIN) ATTACHED
WITH 36/7 PATTERN OF 5/8" DIA PUDDLE WELDS AT ALL
SUPPORTS AND AT PERIMETER. PROVIDE #10 TEK LAP
FASTENERS 6" OC.
8 EXPANSION JOINT ALONG WALL
9 MECHANICAL GAS PIPE ANCHOR. REFER TO DETAIL
A4/SF101.
COORDINATE FINAL LOCATION AND HEIGHT WITH THE
MECHA…