This document summarizes an invitation for bid for construction services. The 115th Fighter Wing at Dane County Regional Airport -Truax Field in Madison, WI is soliciting bids to construct a new three-bay hangar facility compatible with F-35 operations. The scope of work includes demolishing an existing building and constructing a 31,000 square foot hangar with three bays, administrative and shop spaces, and support systems like HVAC, electrical power, and fire suppression. The project also requires installation of a lightning protection system, fall protection, and an Advantor security system. Two options are included for additional paint/mix and aircraft pavement work. Brand name justification is provided for several specified systems. The bid opening will be conducted according to FAR Subpart 14.4. Interested contractors must register in SAM and check the site regularly for amendments. The response window closes in 550 days and the project value is estimated between $25-100 million.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 THREE BAY SPECIALIZED HANGAR, newest first.
File Type Posted
02_ITEM 01.2-2_ADD 04_Section 04 20 00.pdf PDF
04_ITEM 01.2-4_ADD 04_Section 07 24 00.pdf PDF
10_ITEM 01.2-10_ADD 04_Section 32 13 14.13.pdf PDF
15_ITEM 01.3-5_ADD 04_02700SF105.pdf PDF
17_ITEM 01.3-7_ADD 04_02700SF503.pdf PDF
23_ITEM 01.3-13_ADD 04_02700A-503.pdf PDF
25_ITEM 01.3-15_ADD 04_02700ES101.pdf PDF
26_ITEM 01.3-16_ADD 04_02700EP102.pdf PDF
27_ITEM 01.3-17_ADD 04_02700EP701.pdf PDF
03_ITEM 01.2-3_ADD 03_Section 05 50 13.pdf PDF
09_ITEM 01.2-9_ADD 03_Section 26 05 26.00 40.pdf PDF
11_ITEM 01.3-1_ADD 03_02700G-002.pdf PDF
13_ITEM 01.3-3_ADD 03_02700C-401.pdf PDF
15_ITEM 01.3-5_ADD 03_02700C-404.pdf PDF
16_ITEM 01.3-6_ADD 03_02700C-601.pdf PDF
18_ITEM 01.3-8_ADD 03_02700SF103.pdf PDF
33_ITEM 01.3-23_ADD 03_02700IG-500.pdf PDF
34_ITEM 01.3-24_ADD 03_02700FX102.pdf PDF
36_ITEM 01.3-26_ADD 03_02700FA102.pdf PDF
MAT MGMT PPLAN_Approval for 3-Bay Hangar.pdf PDF
W50S9F22B0001 Solicitation - Ammend 0001.pdf PDF
Questions and Answers 1.pdf PDF
01_FSB2020-270-00_WI-ANG_3-Bay_ADD NO. 02_2022.06.08_Narrative.pdf PDF
05_ITEM 01.2-4_ADD 02_Section 03 30 00.pdf PDF
06_ITEM 01.2-5_ADD 02_Section 04 20 00.pdf PDF
09_ITEM 01.2-10_ADD 02_Section 09 06 00.pdf PDF
10_ITEM 01.2-11_ADD 02_Section 11 94 10.pdf PDF
14_ITEM 01.2-15_ADD 02_Section 32 13 14.13.pdf PDF
15_ITEM 01.3-1_ADD 02_02700G-102.pdf PDF
16_ITEM 01.3-2_ADD 02_02700C-101.pdf PDF
19_ITEM 01.3-5_ADD 02_02700C-402.pdf PDF
20_ITEM 01.3-6_ADD 02_02700S-001.pdf PDF
28_ITEM 01.3-14_ADD 02_02700SF210.pdf PDF
29_ITEM 01.3-15_ADD 02_02700SF502.pdf PDF
30_ITEM 01.3-16_ADD 02_02700AD-101.pdf PDF
35_ITEM 01.3-21_ADD 02_02700A-402.pdf PDF
36_ITEM 01.3-22_ADD 02_02700A-500.pdf PDF
37_ITEM 01.3-23_ADD 02_02700A-501.pdf PDF
38_ITEM 01.3-24_ADD 02_02700A-702.pdf PDF
42_ITEM 01.3-28_ADD 02_02700ES101.pdf PDF
43_ITEM 01.3-29_ADD 02_02700EG101.pdf PDF
04_ITEM 01.2-3_ADD 02_Section 01 78 00.pdf PDF
F-35 3-Bay Hangar Site Visit Attendance.pdf PDF
Supplemental Site Visit Instructions.pdf PDF
ATTACHMENT 2 - Volume 4 - WI ANG F-35 3-Bay CD Specs ADD 01 (1 of 2).pdf PDF
ATTACHMENT 6 - 20220208 Single Source Determination - Marshall Best - Redacted.pdf PDF
ATTACHMENT 1a - FSB2020-270-00 - WI-ANG - 3-Bay Hangar - ADD 01 COMBINED DRAWINGS (1 of 2).pdf PDF
ATTACHMENT 1b - FSB2020-270-00 - WI-ANG - 3-Bay Hangar - ADD 01 COMBINED DRAWINGS (2 of 2).pdf PDF
ATTACHMENT 3 - Volume 4 - WI ANG F-35 3-Bay CD Specs ADD 01 (2 of 2).pdf PDF
ATTACHMENT 5 - 20220208 Single Source Determination - Andover - Redacted.pdf PDF
Show all 50

F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PARTITION TYPE NOTES

A. STUD GAUGE IN PARTITION SCHEDULE IS A

MINIMUM.

B. STUD SPACING IN PARTITION SCHEDULE IS

MAXIMUM.

C. ALL GYPSUM BOARD SHALL BE 5/8" TYPE 'X' UNLESS

NOTED OTHERWISE OR REQUIRED FOR ACOUSTIC

ASSEMBLY.

D. PROVIDE CONTINUOUS 20 GAUGE DEFLECTION

TRACK (2 1/2" DEEP LEG TRACK) AND 20 GAUGE

UPPER HORIZONTAL SPACER BARS AT ALL

INTERIOR PARTITIONS EXTENDED TO DECK.

E. SUBSTITUTE 5/8" TYPE 'X' FIRE RESISTANT TILE

BACK BOARD AT ALL LOCATIONS SCHEDULED TO

RECEIVE WALL TILE.

F. ALL GYPSUM WALL BOARD SHALL BE CUT TIGHT TO

FIT AND SEALED COMPLETELY AIRTIGHT WITH

REQUIRED SEALANT FOR EITHER FIRE RATING OR

SOUND ATTENUATION AT ALL MEP PENETRATIONS

THRU INTERIOR PARTITIONS SCHEDULED TO DECK.

G. FILL ALL PERIMETER VOIDS AND HEAD OF WALL

METAL DECK FLUTES WITH FIRESAFING INSULATION

AT ALL FIRE RATED WALLS TO ACHIEVE COMPLETE

CLOSURE AND SEAL BOTH SIDES WITH ELASTIC

FIRESTOPPING SPRAY MASTIC.

H. ALL SOUND ATTENUATION BATTS SHALL BE

UNFACED, 2.5 PCF, INSTALLED CONTINUOUS

VERTICALLY, CUT TIGHT TO FIT AND FILL THE STUD

CAVITY.

I. PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT

THE FOLLOWING LOCATIONS:

a. MECHANICAL ROOMS

b. PLUMBING WET WALLS AT JANITOR ROOMS AND

RESTROOMS

c. LOADING DOCK AND RELATED CORRIDOR

J. PROVIDE IMPACT RESISTANT GYPSUM BOARD AT

ALL CORRIDOR WALLS, UP TO 8'-0" AFF.

K. 'S' IN PARTITION SCHEDULE INDICATES SOUND

BATTS ARE TO BE PROVIDED BUT A MINIMUM STC IS

NOT SPECIFIED.

L. THE TERM "TO DECK" IN THE PARTITION SCHEDULE

REFERS TO THE ENTIRE WALL ASSEMBLY

CONTINUING TO THE DECK ABOVE. WHEN THIS IS

MARKED "NO" THEN THE WALL IS TO STOP 6" ABOVE

THE CEILING UNLESS NOTED OTHERWISE. OTHER

HEAD OF WALL CONDITIONS WILL BE NOTED IN THE

PARTITION SCHEDULE - TYPE COMMENTS OR ON

THE PLANS.

M. THE ASSEMBLY CODES IN THE TYPE COMMENTS

ARE USED AS A BASIS OF DESIGN AND NOT THE

ONLY METHOD OF ACHIEVING THE DESIRED

PERFORMANCE CRITERIA OF A WALL ASSEMBLY.

"A" SERIES - ACOUSTIC PARTITION

STC IS A PRIORITY. MAY OR MAY NOT NEED FIRE

RATING.

"B" SERIES - SCIF WALL

STC IS A PRIORITY. MAY OR MAY NOT NEED FIRE

RATING.

"C" SERIES - CHASE

"D" SERIES - DOUBLE STUD

STC OR WRAPPING AN ITEM IS PRIORITY. MAY OR

MAY NOT NEED FIRE RATING.

"F" SERIES - FURRING

"G" SERIES - GENERIC

"H" SERIES - HAT CHANNEL

"I" SERIES - INTERIOR PARTITION

NO FIRE RATING, NO STC RATING.

"M" SERIES - MASONRY - FIRE RATED

FIRE RATING IS PRIORITY. MAY OR MAY NOT NEED

STC.

"N" SERIES - MASONRY - NOT RATED

NO FIRE RATING. MAY OR MAY NOT NEED STC.

"P" SERIES - PARTIAL HEIGHT

NO FIRE RATING, NO STC RATING.

"R" SERIES - RATED INTERIOR PARTITION

"S" SERIES - SHAFT WALL

"U" SERIES - USER DEFINED

CREATE UNIQUE WALLS AS NEEDED.

"V" SERIES - VAULT WALL

TYPICALLY FOR CASINOS

"W" SERIES - FIRE WALL / AREA SEPARATION

PROTECTED ON BOTH SIDES OF AN EXPANSION

JOINT WHEN DOUBLE STUD.

"Z" SERIES - SOUND PARTITION WITH Z-CLIPS

STC IS A PRIORITY. MAY OR MAY NOT NEED FIRE

RATING.

WALL SERIES LEGEND

STANDARD PARTITION

BATT INSULATION

1-HOUR FIRE RATING

2-HOUR FIRE RATING

3-HOUR FIRE RATING

4-HOURS FIRE RATING

1-HOUR FIRE/SMOKE

CONCRETE MASONRY UNIT - HOLLOW

CONCRETE MASONRY UNIT - GROUT FILLED

CONCRETE MASONRY UNIT - SAND FILLED

DOUBLE STUD PARTITION

PARTITION TYPES LEGEND

A1*

"*" DENOTES WALL IS

TO DECK ABOVE

DENOTES GENERIC

SIZE OF STRUCTURAL

ELEMENT

WALL SERIES. SEE

LEGEND ON THIS

SHEET

1 HR. RATED PARTITION WITH 8" CMU

IBC TABLE 720.1, MATERIAL 3

2 HR. RATED PARTITION WITH 8" CMU

IBC TABLE 720.1, MATERIAL 3

1 HR. RATED PARTITION WITH 12" CMU

IBC TABLE 720.1, MATERIAL 3

A3

NON-RATED PARTITION AS SHOWN ABOVE

WITH UNFACED ACOUSTICAL BATTS AND

EXTENDING GYPSUM BOARD TO DECK

FINISH

FLOOR

5/8" GYP BD

SCHEDULED CLG

STEEL RUNNER

CHANNEL

1-5/8" STUDS

AT 16" OC

NON-RATED FURRING

PARTITION

C1

C6

NON-RATED FURRING

PARTITION WITH 6" STUDS AND

UNFACED ACOUSTICAL BATTS IN

LIEU OF 1-5/8" STUDS

CMU WALL

5/8" GYP BD

(BOTH SIDES)

FINISH

FLOOR

DECK

SLOTTED

DEFL TRACK

SCHEDULED CLG

STEEL RUNNER

CHANNEL

6" M

IN

BASE AS

SCHEDULED

BASE AS

SCHEDULED

3-5/8" STUDS

AT 16" OC

M8

M8A

M12C

STEEL

RUNNER

CHANNEL

A6

NON-RATED PARTITION AS SHOWN

ABOVE WITH 6" STUDS IN LIEU OF

3-5/8" STUDS

FINISH

FLOOR

DECK

SCHEDULED CLG

8" CMU

PROVIDE UL ASSEMBLY

HW-D-0042 TO DECK

BASE AS

SCHEDULED

6" M

IN

FINISHED FLOOR

FINISH

FLOOR

5/8" GYP BD

SCHEDULED CLG

STEEL RUNNER

CHANNEL

1-5/8" STUDS

AT 16" OC

NON-RATED FURRING

PARTITION

F1

F2

NON-RATED FURRING

PARTITION WITH 2-1/2" STUDS IN

LIEU OF 1-5/8" STUDS

6" M

IN

BASE AS

SCHEDULED

STEEL

RUNNER

CHANNEL

F3

NON-RATED FURRING

PARTITION WITH 3-5/8" STUDS IN

LIEU OF 1-5/8" STUDS

F6

NON-RATED FURRING

PARTITION WITH 6" STUDS IN

LIEU OF 1-5/8" STUDS

I3 NON-RATED PARTITION AS SHOWN ABOVE

5/8" GYP BD

(BOTH SIDES)

FINISH

FLOOR

DECK

SLOTTED

DEFL TRACK

SCHEDULED CLG

STEEL RUNNER

CHANNEL

BASE AS

SCHEDULED

3-5/8" STUDS

AT 16" OC

I6

NON-RATED PARTITION AS SHOWN

ABOVE WITH 6" STUDS IN LIEU OF

3-5/8" STUDS

6" M

IN

FINISHED FLOOR

NON RATED PARTITION WITH 8" CMU

IBC TABLE 720.1, MATERIAL 3

N8

FINISH

FLOOR

DECK

SCHEDULED CLG

8" CMU

PROVIDE UL ASSEMBLY

HW-D-0042 TO DECK

BASE AS

SCHEDULED

8" CMU

2HR RATED PARTITION WITH 8" CMU

IBC TABLE 720.1, MATERIAL 3 UP TO

11' - 4" AFF WITH 6" CH STUD ON TOP

WITH 2 LAYERS OF GYP BD ON

HANGAR SIDE

S6

FINISH

FLOOR

DECK

8" CMU

PROVIDE UL ASSEMBLY

HW-D-0042 TO DECK

BASE AS

SCHEDULED

SLOTTED

DEFLECTION

TRACK

FIRE SEALANT

5/8" GYP BD

(2 LAYERS)

1" SHAFT

LINER

6" CH STUD

10' - 0" AFF

T.O. CMU

REF STRUCTURAL

FOR DISTANCE

BELOW FINISH FLOOR

5/8" GYP BD

(BOTH SIDES)

FINISH

FLOOR

DECK

SLOTTED

DEFL TRACK

SCHEDULED CLG

STEEL RUNNER

CHANNEL

BASE AS

SCHEDULED

6" STUDS AT

16" OC

Z6

1HR RATED PARTITION WITH 6" CH

STUD, 1/2" RESILIENT CHANNEL,

5/8" ACOUSTIC GYP BD ON BOTH

SIDES - 1HR W/BATTS.

6" BATT

INSULATION

PROVIDE UL ASSEMBLY

HW-D-0042 TO DECK

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

FSB2020-270-00

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

NWC / JBC

F-

3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin

Ai r N at io na l G ua rd

C

B

A

D

C

B

A

54321

DECEMBER 23, 2021

C :\U sers\gaz\D o cum ents\M y R evit\02700_Arch_G ZalabakZ5W

7D .rvt

6/28/2022 2:12: 22 PM

PARTITION TYPES

A-002

JBC

JRT/JBC

MP

INTERIOR PARTITION SCHEDULE

MARK

FIRE

RATING UL NO.

WALL

STC

SOUND

BATTS TYPE

TO

DECK

STUD

GAUGE

STUD

SPACING TYPE COMMENTS

A3 -- -- 45 Yes (A3) 3 5/8" STUDS, 5/8" ACOUSTIC GYP BD BOTH SIDES-0HR W/BATTS Yes 20 GA 16" OC NGC 2013005 A6 -- -- 45 Yes (A6) 6" STUDS, 5/8" GYP BD BOTH SIDES-0HR W/BATTS No 20 GA 16" OC NGC 2013023 C1 -- -- -- No (C1) 1 5/8" STUDS, 5/8" GYP BD ONE SIDE-0HR No 20 GA 16" OC -- C6 -- -- 55 Yes (C6) 6" STUDS, 5/8" GYP BD ONE SIDE-0HR W/BATTS Yes 20 GA 16" OC NGC 2013021 F1 -- -- -- No (F1) 1 5/8" STUDS, 5/8" GYP BD ONE SIDE-0HR No 20 GA 16" OC -- F2 -- -- -- No (F2) 2 1/2" STUDS, 5/8" GYP BD ONE SIDE-0HR No 20 GA 16" OC -- F3 -- -- -- No (F3) 3 5/8" STUDS, 5/8" GYP BD ONE SIDE-0HR No 20 GA 16" OC -- F6 -- -- -- No (F6) 6" STUDS, 5/8" GYP BD ONE SIDE-0HR No 20 GA 16" OC -- I3 -- -- -- No (I3) 3 5/8" STUDS, 5/8" GYP BD BOTH SIDES-0HR No 20 GA 16" OC -- I6 -- -- -- No (I6) 6" STUDS, 5/8" GYP BD BOTH SIDES-0HR Yes 20 GA 16" OC -- M8 1 U906 -- No (M8) 8" CMU BLOCK-1HR Yes -- -- --

M12C 1 U906 -- No (M12) 12" CMU BLOCK-1HR Yes -- -- -- N8 -- -- 55 No (N8) 8" CMU BLOCK, GROUT FILLED-0HR Yes -- -- GROUT FILLED S6 2 Yes

SCALE: NTS

PARTITION TAG LEGENDD1

SCALE: NTS

PARTITION TYPES1

1 ADDENDUM 3 06/14/2022

2 ADDENDUM 4 06/28/2022

W

IS C O NS IN

A R C H I T E C T

JASON T.

HOLUBY

A-13101

OKLAHOMA CITY

OK

File details come from the government source that posted it. Updated .