S02 Sol R0036 AttE SOW.Att16_578-25-003 Basis of Design Existing Condition Photos 2024.11.04.pdf
PDF 5 MB Posted
- Attached to
- Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
- Solicitation number
- 36C25225R0036_3
About this file
This document is a photographic basis of design report detailing existing conditions for elevator renovation at the Edward Hines Jr. VA Medical Center. The report comprehensively documents the current state of eight traction elevators (P1-P5 and S6-S8), capturing detailed images and observations across multiple systems including controllers, machine rooms, hoistways, car interiors, and electrical infrastructure.
Key findings include recommendations for multiple equipment replacements and upgrades, such as replacing controllers (some dating from 2005), upgrading electrical disconnects, replacing car panels and accessories, refurbishing compensation sheaves and buffers, and addressing fire protection and lighting standards. The photographs and accompanying notes highlight issues like outdated technology (12-pulse drive systems), potential accessibility improvements, and the need for LED lighting upgrades to meet federal sustainability guidelines. The document provides a thorough visual and technical assessment to support a comprehensive elevator renovation project in Building 200 at the VA Medical Center.
View the file
Other files
Show 40 more
Latest 50 of 73 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Scope of Work: Investigate and review existing eight (8) traction elevators: P1, P2, P3, P4, P5, S6, S7 and S8.
B.1 - Work in Progress / General Observations:
a. Continuous maintenance of elevators, specifically P2 and S7 were inoperable.
b. Elevator attendant present in elevator S6.
c. On-going demolition of floor 15.
d. Main electrical room upgrades located within basement level.
2. B.2 - Items Observed / Discussed Requiring Action:
a. Elevator Disconnect: Each elevator must be provided with a separate disconnect and surge suppressor in the machine room Per PG-18-10 – Elevator Design Manual Section 12.A. Although each elevator is provided with a separate disconnect, presence of surge suppressors were not evident within the Elevator Machine room (Penthouse Floor 17).
Recommended Solution: Provide surge suppressor on each (8) safety disconnect switch servicing the elevators.
b. Elevator Em. Power: Emergency power supply must have the capacity to operate a minimum of one elevator per group in healthcare facilities and meet the requirements found within VA Electrical Design Manual and Elevator Design Manual Section.
Currently, each elevator is protected by a shunt trip breaker fed from Panel PMRA >
1600A ATS-ELEV > Switchgear B1 > Switchgear GD-A (Building 226) > Five (5)
Parallel 750 kVA Generators (Building 226). During an event of emergency only two
(2) elevators are fully operable, all other elevators report to the nearest floor. It was discussed that the local VA would like to have all eight (8) elevators fully operable in an emergency. HVAC supporting elevator machine/control room appears to be fed from Emergency Power and is fed from Panel HVAC-PH > CMCC-PHA > ATS-
CMCC-PHA > Switchgear B1 > Switchgear GD-A (Building 226) > Five (5) Parallel
750 kVA Generators (Building 226).
RENOVATE ELEVATORS IN BUILDING 200
Edward Hines Jr. VAMC VA Project #: 578-25-003
November 4, 2024
Recommended Solution: Due to the equipment being at or nearing the end of its useful life, engineer recommends replacement of panel boards and other equipment associated with the elevator power circuits. Refer to “VA Hines Building 200 – Facility Condition Assessment” table below on pages 14-17.
a. Fire Alarm and Protection: Per PG-18-10 – Elevator Design Manual Section 12.C, FA initiating devices, heat detectors and sprinklers must be installed as required by ASME A17.1, IBC, NFPA 13, NFPA 70, NFPA 72, and NFPA 101. The Elevator machine/control room is provided with smoke/heat detectors and sprinklers throughout with smoke detectors present within elevator lobbies on each floor. In addition, the top of each elevator shaft appears to be provided with heat detectors.
The bottom of the elevator hoistway for elevators ‘S1-S3’ is provided with a sidewall sprinkler, while no sidewall sprinkler is provided at the bottom of the elevator shaft for elevators P1-P3. Per NFPA 13 Section 9.3.6.2, “the sprinkler required at the bottom of the elevator hoistway shall not be required for enclosed, noncombustible elevator shafts that do not contain combustible hydraulic fluids.”
The top of each elevator hoistway does not contain sprinklers. Per NFPA 13 Section 9.3.6.6 and VA PG18-10 – Fire Design Manual – Table 7.4, “the sprinkler at the top of the elevator hoistway shall not be required where the hoistway for elevators is noncombustible or limited-combustible and the car enclosure materials meet the requirements of ASME A17.1.”
Fire Alarm and protection appears to be in adequate condition with useful life remaining. However, the assistance of the building’s fire alarm maintenance personnel will be needed to make final judgment on reusing or replacing the fire alarm devices.
Edward Hines Jr. VAMC
b. Elevator car lights, alarm, GFCI receptacles, hoist way lights, and elevator pits:
During site investigation Emergency Panel 200-EL appears to be providing power to elevator misc. devices, equipment, and accessories as some of the breakers are labeled and others were not, however, it is difficult to determine/confirm.
Further investigation with the assistance of the VA will be required.
Emergency Panel 200-EL > T-EL 15KVA > 200-E3 > ATS-E3 > GDP (Building
226) > Switchgear GD-A (Building 226) > Five (5) Parallel 750 kVA Generators (Building 226).
Elevator pits do not contain GFCI receptacles and sump pumps, however, drains were present in existing elevator pits. Per 2022 ASME A17.1 Section 2.2.2.5, “…a drain OR sump pump shall be provided in elevator pit.” Elevator hoist way lights were found at each landing/opening; none found at top of the shaft. It can also be noted that the top exterior of each existing elevator car does have a maintenance light and receptacle. Although adequate lighting is provided within the elevator pit, hoist way and top it is recommended to replace the existing CFL fixtures to LED’s to help promote/meet the “Executive Order on Catalyzing Clean Energy Industries and Jobs Through Federal Sustainability” Section 208. By switching over to LED’s these have the lowest cost of ownership through the extra-long life of the LED diodes (50,000 hours+), near more than 75% energy use reduction compared to fluorescent with equivalent light output (4-32W bulbs - 128W total to deliver the same light as a 5000 lumen 40 watt LED fixture). Current industry standards have
RENOVATE ELEVATORS IN BUILDING 200
Edward Hines Jr. VAMC trended to 100% use of LED fixtures in government owned facilities, and most private industries are using 100% LED fixtures for their lighting needs as well.
Edward Hines Jr. VAMC
c. Penthouse Clearance Issues: Elevator P1’s and AHU-A2F’s safety disconnect switch does not have the proper 3’ clearance.
Recommended Solution: Relocate safety disconnect switches services Elevator P1 and AHU-A2F.
d. Penthouse lighting Issues: All lighting fixtures are CFL and with one lighting fixture appears to be inoperable.
Recommended Solution: Engineer’s recommendation is to replace all CFL lighting fixtures within Penthouse to LED and upgrade controls system to help promote/meet the “Executive Order on Catalyzing Clean Energy Industries and Jobs Through Federal Sustainability” Section 208. By switching over to LED’s these have the lowest cost of ownership through the extra-long life of the LED diodes (50,000 hours+), near more than 75% energy use reduction compared to fluorescent with equivalent light output (4-32W bulbs - 128W total to deliver the same light as a 5000 lumen 40 watt LED fixture). Current industry standards have trended to 100% use of LED fixtures in government owned facilities, and most private industries are using 100% LED fixtures for their lighting needs as well.
Edward Hines Jr. VAMC
e. Penthouse unprotected conductors: Conductors are exposed/unprotected and are subject to physical damage.
Recommended Solution: Run exposed conductors within conduit to limit physical damage.
f. 1600A ATS-ELEV and 200A ATS-ELEV: Both Automatic Transfer Switch servicing either the Elevator power and the misc. elevator equipment/devices are not conforming to VA TIL Standards to be Bypass Isolation.
Edward Hines Jr. VAMC
C.5 – SUPPORTING PHOTOGRAPHS
1. Cars P1-P5 - existing controllers will be replaced. 2. Cars P1-P5 – controller data tag from 2005.
3. Cars P1-P5 – older 12 pulse drive technology. 4. Cars P1-P5 – dispatch controller and monitor in machine room.
Edward Hines Jr. VAMC
5. Cars P1-P5 – Gearless hoist machines. Typical for all 8 elevators.
6. Cars P1-P5 – GE machine data tag.
7. Cars P1-P5 – disconnects. 8. Cars P1-P5 – machine room has smoke detectors and sprinklers. Sprinklers will require a shunt trip.
Edward Hines Jr. VAMC
9. Cars P1-P5 – machine room lighting. 10. Cars P1-P5 – AC units must be dedicated to the machine room. Older units should be serviced or replaced.
11. Cars P1-P5 – stairs and railing down to elevator secondary. 12. Cars P1-P5 – secondary equipment (deflector sheave, rope gripper and governor)
Edward Hines Jr. VAMC
13. Cars P1-P5 – Age of deflector sheaves is unknown. New machines will pull this sheave into the machine room.
Deflector sheaves function in conjunction with the machines.
14. Cars P1-P5 – safety governor will be replaced.
15. Cars P1-P5 – smoke detectors are present at the top of hoistways.
16. Cars P1-P5 – crosshead data tag does not show an installation date.
Edward Hines Jr. VAMC
17. Cars P1-P5 – MAC operators will be replaced with a new door operator.
18. Cars P1-P5 – existing roller guide assemblies will be replaced.
19. Cars P1-P5 – some pit equipment will be reused/refurbished.
20. Cars P1-P5 – buffers will be refurbished. Compensation sheaves will be refurbished.
Edward Hines Jr. VAMC
21. Cars P1-P5 – First floor entrance. Frames and doors will be reused. Hall fixtures will be replaced.
22. Cars P1-P5 - First floor entrance. Frames and doors will be reused. Hall fixtures will be replaced.
23. Cars P1-P5 – buttons are close to accessibility standards which will reduce occurrences of cutting and patching walls.
24. Cars P1-P5 – lantern/position indicators will be replaced.
Back boxes can be reused to reduce amount of cutting and patching. Voice annunciators can be located in each fixture at each landing.
Edward Hines Jr. VAMC
25. Cars P1-P5 – car panels will be replaced with new. 26. Cars P1-P5 – existing car panel with plastic buttons which are susceptible to breaking/cracking.
27. Cars P1-P5 – Auxiliary car panels will be replaced. 28. Cars P1-P5 - car sills can be reused. Car doors are showing signs of wear/abuse. Cab flooring can be replaced if cabs are upgraded.
Edward Hines Jr. VAMC
29. Cars S6-S8 – Motion Control Engineering controller. 30. Cars S6-S8 – MCE controller data tag from 2005.
31. Cars S6-S8 – dispatch controller and monitor. 32. Cars S6-S8 – gearless hoist machines.
Edward Hines Jr. VAMC
33. Cars S6-S8 – rope gripper added to the machines. A new AC machine will have the code required redundant brake integrated into the machine.
34. Cars S6-S8 – disconnects will be upgraded.
35. Cars S6-S8 – Miscellaneous cabinets, some with unknown functions. Non elevator related components will need to be relocated or separated from elevator mechanicals.
36. Cars S6-S8 - Miscellaneous cabinets, some with unknown functions. Non elevator related components will need to be relocated or separated from elevator mechanicals. Arrow pointing to service elevator group controller.
Edward Hines Jr. VAMC
37. Cars S6-S8 – mechanicals by S6-S8 will need to be separated by a fire rated partition.
38. Cars S6-S8 - mechanicals by S6-S8 will need to be separated by a fire rated partition.
39. Cars S6-S8 – hoisting hatch. 40. Evidence of leaks in the ceiling. These need to be addressed prior to new controllers being installed.
Edward Hines Jr. VAMC
41. Cars S6-S8 – access to secondary. 42. Cars S6-S8 – deflector sheaves in secondary. Age unknow.
43. Cars S6-S8 – governors in the secondary. Duct is running through the secondary in back of car S6 governor.
44. Cars S6-S8 – smoke detectors at top of hoistway.
Edward Hines Jr. VAMC
45. Cars S6-S8 – car top equipment. 46. Cars S6-S8 – roller guides and tape selector will be
47. Cars S6-S8 – door equipment will be upgraded.
Mechanical restrictors (black angle) will be reused.
48. Hoistway switches will be replaced for all eight elevators
Edward Hines Jr. VAMC
49. Cars S6-S8 – counterweight frames can be reused, providing cars are properly counterbalanced.
50. Cars S6-S8 – compensation sheaves will be refurbished.
51. Cars S6-S8 – governor tail sheaves will be replaced. 52. Cars S6-S8 – buffers will be refurbished.
Edward Hines Jr. VAMC
53. Cars S6-S8 – additional pit equipment. 54. Cars S6-S8 – pit drain in middle right. Drain must have a trap.
55. Cars S6-S8 – typical lobby configuration. 56. Cars S6-S8 – buttons are close to accessibility standards which will reduce occurrences of cutting and patching walls.
Edward Hines Jr. VAMC
57. Cars S6-S8 - lantern/position indicators will be replaced.
Back boxes can be reused to reduce amount of cutting and patching.
58. Cars S6-S8 – main car panels will be replaced. VA:
Telephone handset utilized for code blue may be replaced.
59. Cars S6-S8 – Code blue card reader not currently active. 60. Cars S6-S8 – Auxiliary car panel in side wall will be
Edward Hines Jr. VAMC
61. Cars S6-S8 – “dog house” in back of cab to move long pieces of equipment.
62. Cars S6-S8 - “dog house” in back of cab to move long pieces of equipment. Position indicator on back wall will be replaced with new.
Edward Hines Jr. VAMC
File details come from the government source that posted it. Updated .