S06 36C25225R0036 006_Att05 Physical Access Control Clarifications.pdf
PDF 118 KB Posted
- Attached to
- Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
- Solicitation number
- 36C25225R0036_3
About this file
This document is an Amendment (P0006 - Attachment 5) for Solicitation 36C25225R0036, detailing Physical Access Control System requirements for the 578-25-003 Renovate Elevators project in Building 200. The specification mandates installing security cameras (AXIS M3086-V or equal) in elevator cabs and card readers (Signo PIV 40, 40HNKS-03-0059X or equal) in each elevator lobby, with all data routed to Building 200 Telecom Room 1459 on the 14th floor. The new security system must integrate with existing systems, using Milestone Software for cameras and Lenel OnGuard for PIV readers.
The project requires one new workstation and monitor with a split screen to view all eight elevators, to be installed in the Police SOC, Building 1 – Room F108. Specific technical requirements include meeting Physical Security System specifications outlined in project documents, providing necessary power and data connections, and ensuring compatibility with existing security infrastructure. No biometric security or direct data connections between Room 1459 and the Police SOC are required.
View the file
Other files
Show 40 more
Latest 50 of 73 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
578-25-003 Renovate Elevators in Building 200
Physical Access Control System
- The new elevators shall meet the Physical Security System requirements as outlined in the project Specifications.
- This includes security cameras in the elevator cabs and card readers in each elevator lobby, along with the associated power and data connections. All data from the elevator penthouse to be run to Building 200 Telecom Room 1459 – 14th floor.
- Basis of Design o Security cameras - AXIS M3086-V or equal o Card readers – Signo PIV 40, 40HNKS-03-0059X or equal
- The new security system should integrate with the existing system o Cameras use Milestone Software o PIV Readers use Lenel OnGuard
- Only one (1) new workstation and one (1) new monitor is necessary, with a split screen to view all eight elevators. To be installed in the Police SOC, Building 1 – Room F108.
- No data connections between 1459 and the Police SOC are required.
- No biometric security is required.
Solicitation 36C25225R0036 Project 578-25-003 Renovate Elevators in Bldg 200 Amendment P0006 - Attachment 5