S06 36C25225R0036 006_Att02 25-0725 Supplemental Sketches.pdf
PDF 1 MB Posted
- Attached to
- Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
- Solicitation number
- 36C25225R0036_3
About this file
This document contains two Request for Information (RFI) pages related to a federal contract for renovating elevators in Building 200, Solicitation 36C25225R0036, Project 578-25-003.
RFI 7.4 requests clarification on constructing a wall separating passenger and service elevators, specifically noting that Drawing GC102 shows construction details but does not specify the wall's height. RFI 12.3 seeks details for a new concrete slab, specifying that the slab thickness should be a minimum of 5" at the high portion of the flute, with final thickness determined based on finishing elevation and adjacent slab conditions. The concrete slab drawing includes technical specifications such as using a 2" 20 GA galvanized composite steel floor deck, welding requirements, and mechanical fastening instructions. The document is part of Amendment P0006, Attachment 2, and provides technical details to support the elevator renovation project.
View the file
Other files
Show 40 more
Latest 50 of 73 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI 7.4:
Part of CLIN II states “construct a wall separating the passenger and service elevators”. Drawing GC102 shows the wall construction details but does not show a height. Please provide more details for the wall separating the passenger and service elevators.
Solicitation 36C25225R0036 Project 578-25-003 Renovate Elevators in Bldg 200 Amendment P0006 - Attachment 2 Page 1 of 2
RFI 12.3:
Please provide details for the new concrete slab for the drawing above. (Dwg AE100)
Slab Thickness to be a minimum of 5" at the high portion of the flute, but shall be determined based upon finishing to match the elevation of the adjacent slab. Verify conditions in field and verify with Architect prior to slab installation.
Solicitation 36C25225R0036 Project 578-25-003 Renovate Elevators in Bldg 200 Amendment P0006 - Attachment 2 Page 2 of 2