S02 Sol R0036 AttE SOW.Att15b_578-25-003 100 perc DWGS_Part 2of5 2025.01.24.pdf
PDF 2 MB Posted
- Attached to
- Z1DA--578-25-003 Renovate Elevators B200 (Construction) at the Hines VA Hospital in Hines, IL
- Solicitation number
- 36C25225R0036_3
About this file
These are 100% bid documents for an elevator replacement project at the Hines VA Hospital in Hines, Illinois, dated January 24, 2025. The comprehensive electrical design drawings cover a multi-phase renovation of elevator electrical systems in Building 200, including detailed plans for demolition, power distribution, and electrical upgrades. The project involves replacing electrical components for eight elevators (200-P1 through P5 and 200-S6 through S8), including new transfer switches (ATS-ELEV-1 and ATS-ELEV-2), panels (200-PMRA-1 and 200-PMRA-2), and associated electrical infrastructure. The phased approach is designed to minimize disruption, with specific sequence of operations outlined to maintain elevator functionality throughout the renovation process.
The electrical documents include detailed technical specifications, such as feeder schedules showing conductor sizes, voltage drop calculations, and equipment ratings. Key components include new 1600A and 600A automatic transfer switches, panels with surge protection, and modifications to existing electrical distribution systems. The project involves coordinating with VA Contracting Officer Representatives (COR), maintaining existing fire alarm systems, and ensuring compliance with National Electrical Code (NEC) and VA specifications. The electrical design supports the overall elevator replacement project, with careful attention to power continuity, safety, and minimal operational disruption during the renovation.
View the file
Other files
Show 40 more
Latest 50 of 73 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XX
LV 4
R
P
R
T
H
B
S
C
F
DH
C
S
ES
DC
CR
K
MD
N
C
B
T
FS
TS
DD
S
D
F
OS
OS VS
DS
LR
RC
J
D
M
S
H
M
S
SDS
D
SA SA
C
A CA
H
D HD
S
H SH
C
D CD
S
S
DI
D
ND
Z
TR
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
(E) EXISTING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
ELECTRICAL ABBREVIATIONS LIST
CONDUIT AND WIRING
BRANCH CIRCUIT RUN CONCEALED
HOME RUN TO PANEL 2A SPACES 1, 3, & 5,
REFER TO PANEL SCHEDULES
SYMBOLSYMBOL SYMBOL
ELECTRICAL SYMBOL LEGEND
DESCRIPTION DESCRIPTION DESCRIPTION
HORN (80" AFF)
PROGRAM BELL (80 AFF)
BELL/STROBE LIGHT COMBINATION (80" AFF)
CHIME/FLASH COMBINATION (80" AFF)
TIME CLOCK (REFER TO PLANS)
RELAY
POWER POLE (OPEN OFFICE STYLE)
PUSH BUTTON
MANUAL PULL STATION (46" AFF)
MAGNETIC DOOR HOLDER (72" AFF)
2A-1, 3, 5
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SW
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
(N) NEW
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
(R) REPLACE
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
EXIT LIGHT, WALL-MOUNTED, SHADING
AND ARROWS INDICATE FACES AND
DIRECTION
SELF CONTAINED EMERGENCY LIGHTING
UNIT - TYPE AS SPECIFIED
2X4 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
4' LINEAR INDUSTRIAL STRIP FIXTURE - TYPE
AS SPECIFIED
EXIT LIGHT, CEILING-MOUNTED, SHADING
AND ARROWS INDICATE FACES AND
DIRECTION
FLOW SWITCH
TAMPER SWITCH
DUCT DETECTOR
SPEAKER/STROBE COMBINATION (80" AFF)
2X4 CRITICAL BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS
SPECIFIED
2X4 LIFE SAFETY BRANCH FIXTURE -
RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
2X2 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
2X2 CRITICAL BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS
SPECIFIED
2X2 LIFE SAFETY BRANCH FIXTURE -
RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
1X4 FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - TYPE AS SPECIFIED
1X4 CRITICAL BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS
SPECIFIED
1X4 LIFE SAFETY BRANCH FIXTURE -
RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
4' CRITICAL BRANCH LINEAR INDUSTRIAL
STRIP FIXTURE - TYPE AS SPECIFIED
4' LIFE SAFETY BRANCH LINEAR INDUSTRIAL
STRIP FIXTURE - TYPE AS SPECIFIED
RECESSED CAN LIGHT - TYPE AS SPECIFIED
RECESSED CAN LIGHT - TYPE AS SPECIFIED
LIGHTING FIXTURE - PENDANT MOUNTED -
TYPE AS SPECIFIED
CRITICAL BRANCH LIGHTING FIXTURE -
PENDANT MOUNTED - TYPE AS SPECIFIED
WALL SCONCE LIGHTING FIXTURE - SURFACE
MOUNTED - TYPE AS SPECIFIED
CRITICAL BRANCH WALL SCONCE LIGHTING
FIXTURE - SURFACE MOUNTED - TYPE AS
SPECIFIED
EXTERIOR POLE MOUNTED FIXTURE - TYPE
AS SPECIFIED
EXTERIOR POST TOP MOUNTED FIXTURE -
TYPE AS SPECIFIED
COMBINATION EXIT SIGN & SELF CONTAINED
EMERGENCY LIGHTING UNIT - TYPE AS
SPECIFIED
SINGLE-POLE, LOW VOLTAGE, 3-WAY AND
4-WAY SWITCHES (48" AFF)
LOCAL WALL DIMMER SWITCH (48" AFF)
FAN SWITCH (48" AFF)
WALL MOUNTED OCCUPANCY SENSOR
SWITCH; DUAL TECHNOLOGY (PASSIVE
INFRARED/ULTRASONIC)
CEILING MOUNTED OCCUPANCY/VACANCY
SENSOR; DUAL TECHNOLOGY (PASSIVE
INFRARED/ULTRASONIC)
DAYLIGHT SENSOR
ROOM CONTROLLER (REFER TO PLANS)
LIGHTING RELAY
(UL924 GENERATOR TRANSFER DEVICE)
BRANCH CIRCUIT RUN UNDER FLOOR
SIMPLEX RECEPTACLE (18" AFF, UON)
DUPLEX RECEPTACLE (18" AFF, UON)
DOUBLE DUPLEX RECEPTACLE (18" AFF,
UON)
TOP SWITCHED OUTLET, AS NOTED ON PLANS
FIRE ALARM SYMBOLS
TOP AND BOTTOM SWITCHED OUTLET, AS
NOTED ON PLANS
DUPLEX RECEPTACE 6" ABOVE COUNTER
BACKSPLASH OR 48" AFF
DUPLEX RECEPACLE - FLOOR MOUNTED
DUPLEX RECEPACLE - CEILING MOUNTED
JUNCTION BOX
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE
AS NOTED ON PLANS (18" AFF, UON)
DOUBLE DUPLEX RECEPTACE 6" ABOVE
COUNTER BACKSPLASH OR 48" AFF
DOUBLE DUPLEX RECEPACLE - FLOOR
MOUNTED
DOUBLE DUPLEX RECEPACLE - CEILING
MOUNTED
RETRACTABLE CORD REEL WITH DUPLEX
NEMA 5-20 RECEPTACLE. PROVIDE WITH 30'
OF RETRACTABLE S.O. CORD.
RANGE RECEPTACLE, 4" AFF TO CENTER.
120/240V, 1 PHASE, 3 WIRE PLUS GROUND, 50
AMPS NEMA 14-50.
DRYER RECEPTACLE, 48" AFF TO CENTER.
120/240V, 1 PHASE, 3 WIRE PLUS GROUND, 30
AMPS NEMA 14-30.
RETRACTABLE CORD REEL WITH DOUBLE
DUPLEX NEMA 5-20 RECEPTACLES. PROVIDE
WITH 30' OF RETRACTABLE S.O. CORD.
TRANSFORMER
MOTOR CONNECTION - HORSE POWER AS
NOTED
DISCONNECT SWITCH - MOTOR/STARTER
COMBINATION NEMA SIZE TO MATCH HP
SHOWN ON PLANS AT THE SPECIFIED
VOLTAGE, HEAVY DUTY
DISCONNECT SWITCH - NON-FUSED -
FRAME/FUSE/POLES/NEMA AS NOTED ON
PLANS, ALL DISCONNECTS SHALL BE
HEAVY DUTY AND NEMA TYPE 1 U.O.N.
30/2/3R
DISCONNECT SWITCH - FUSED -
FRAME/FUSE/POLES/NEMA AS NOTED ON
PLANS, ALL DISCONNECTS SHALL BE
HEAVY DUTY AND NEMA TYPE 1 U.O.N.
30/15/2/3R
MOTOR RATED SWITCH WITH THERMAL
OVERLOADS FOR FRACTIONAL
HORSEPOWER MOTORS
USB RECEPTACLE COMBINATION
STROBE LIGHT (80" AFF)
HORN/STROBE LIGHT COMBINATION (80" AFF)
MINI HORN (80" AFF)
SPEAKER (80" AFF)
SMOKE DETECTOR TIED TO FACP - WALL MOUNTED; CEILING MOUNTED
STANDALONE SMOKE ALARM - WALL MOUNTED; CEILING MOUNTED
STANDALONE COMBO SMOKE/CARBON MONOXIDE ALARM - WALL MOUNTED;
CEILING MOUNTED
HEAT DETECTOR TIED TO FACP - WALL MOUNTED; CEILING MOUNTED
COMBINATION SMOKE/HEAT DETECTOR TIED TO FACP - WALL MOUNTED;
CEILING MOUNTED
COMBO SMOKE/CARBON MONOXIDE DETECTOR TIED TO FACP - WALL
MOUNTED; CEILING MOUNTED
FIRE ALARM CONTROL PANEL SURFACE OR RECESSED
DATA OUTLET (18" AFF U.O.N.)
ABOVE COUNTER DATA OUTLET (6" ABOVE
COUNTER BACKSPASH OR 48" AFF)
DATA OUTLET - CEILING MOUNTED
DATA OUTLET - RECESSED FLOOR BOX OR
POKE THRU
CABLE TV OUTLET (18" AFF U.O.N.);
PROVIDE 1 F-TYPE CONNECTOR
COMMUNICATION CABLE TRAY MOUNTED
ABOVE SUSPENDED CEILING - SIZE AS
NOTED ON PLANS
8" CEILING MOUNTED PAGING SPEAKER;
PROVIDED WITH BAFFLE, GRILLE AND
MATCHING TRANSFORMER
8" WALL MOUNTED PAGING SPEAKER;
PROVIDED WITH BAFFLE, GRILLE AND
MATCHING TRANSFORMER
CARD READER. FLUSHED MOUNTED AT 42"
AFF.
DOOR CONTACT
ELECTRIC DOOR STRIKE
KEY PAD
MOTION DETECTOR
PUSH PLATE
(MOUNTING HEIGH TO CENTER LINE OF BOX, UNLESS NOTED OTHERWISE)
CCTV CAMERA - FIXED
CCTV CAMERA - PAN, TILT, ZOOM
NURSE STATION (46" AFF U.O.N.)
CODE BLUE STATION (46" AFF U.O.N.)
BED NURSE CALL (46" AFF U.O.N.)
TOILET NURSE CALL (46" AFF U.O.N.)
SHOWER NURSE CALL (46" AFF U.O.N.)
DOCTOR DICTATION (46" AFF U.O.N.)
DOCTOR PAGE (46" AFF U.O.N.)
DUTY STATION (46" AFF U.O.N.)
NURSE CALL MASTER
NURSE CALL DOME LIGHT (CEILING)
NURSE CALL ZONE LIGHT (CEILING)
NURSE CALL TERMINAL CABINET
NCT
CONDUIT AND WIRING
NEW SCOPE OF WORK
DEMOLITION SCOPE OF WORK
EXISTING SCOPE OF WORK
LOW VOLTAGE TRANSFORMER
1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS
FOR REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT
APPEAR ON THE FOLLOWING DRAWINGS.
2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON
EXISTING UTILITIES WITH VA COR, WITH A MINIMUM OF THREE WEEKS
NOTICE, IN ORDER TO MINIMIZE IMPACT TO OTHER AREAS.
3. PERFORM ALL WORK IN COMPLIANCE WITH VA HINES SPECIFICATION
REQUIREMENTS, NEC, ALL APPLICABLE FEDERAL, STATE, AND LOCAL
CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY
HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING
DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL
GOVERN. REFER TO ELECTRICAL SPECIFICATIONS FOR THE LATEST
VERSION OF THE NFPA 70, 72, 101 AND IBC APPLICABLE.
4. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE
STARTING THE WORK THE CONTRACTOR SHALL REVIEW ALL OTHER
DISCIPLINE DRAWINGS AND VERIFY FIELD CONDITIONS AND SHALL MAKE
ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE
OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE
ATTENTION OF THE VA COR.
5. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY
THE CONTRACTOR UNLESS NOTED OTHERWISE.
6. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER
EQUIPMENT AND DEVICE MANUFACTURER RECOMMENDATIONS.
7. CONTRACTOR SHALL PROVIDE SUBMITTALS TO VA COR FOR REVIEW AND
APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN
THE SUBMITTAL REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS,
DIMENSIONS, WIRING DIAGRAMS, ACCESSORIES, OPERATION MANUALS, AND
ALL NECESSARY INFORMATION FOR REVIEWER TO MAKE A SOUND
EVALUATION.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET
OF RECORD DRAWINGS TO THE VA AT THE END OF THE CONSTRUCTION.
9. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND
FREE OF DEFECTS. ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) STANDARDS
AND SHALL BE UL LABELED. ALL ELECTRICAL EQUIPMENT AND MATERIALS
SHALL BE INSTALLED IN A WORKMANLIKE MANNER.
10. ALL ELEVATOR CONTROLS MUST REPORT TO THE EXISTING FIRE ALARM OF
THE BUILDING.
11. REFER TO ARCHITECTURAL SET SHEET G1C101 FOR STATEMENT OF BIDS.
12. FOR ALL NEW EQUIPMENT, PROVIDE NAMEPLATE OF PANEL AND CIRCUIT
NUMBER DEVICES IS BEING FED FROM.
GENERAL PROJECT NOTES
1. FIRE ALARM DEVICES ARE SHOWN FOR REFERENCE ONLY AND NOT IN
PROJECT SCOPE. ALL DEVICES ARE EXISTING TO REMAIN AND NOT TO BE
DISTURBED. THE FIRE ALARM SHALL REMAIN FULLY FUNCTIONAL DURING
THE RENOVATION OF THE PROJECT. EXISTING FIRE ALARM SYSTEM IS
SIMPLEX - 4100U.
FIRE ALARM NOTES
ELECTRICAL SHEET INDEX
SHEET DESCRIPTION
E001 ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS
ED100 BASEMENT DEMOLITION POWER PLAN - OVERALL
ED100.1 BASEMENT DEMOLITION ELECTRICAL PLAN
ED101.1 FIRST - FOURTEENTH FLOOR DEMOLITION ELECTRICAL PLAN
ED115 FIFTEENTH LEVEL DEMOLITION ELECTRICAL PLAN
ED116 MACHINE ROOM DEMOLITION ELECTRICAL PLAN
ELD116 MACHINE ROOM DEMOLITION LIGHTING PLAN
E100 BASEMENT POWER PLAN - OVERALL
E100.1 BASEMENT POWER PLAN
E101.1 FIRST - FOURTEENTH FLOOR ELECTRICAL PLAN (TYP)
E115 FIFTEENTH FLOOR ELECTRICAL PLAN
E116 MACHINE ROOM ELECTRICAL PLAN
ELE116 MACHINE ROOM LIGHTING PLAN
E-500 ELECTRICAL DETAILS
E-600 DEMOLITION PARTIAL ELECTRICAL ONE-LINE DIAGRAM
E-601 DEMOLITION PARTIAL ELECTRICAL ONE-LINE DIAGRAM
E-602 RENOVATION PARTIAL ELECTRICAL ONE-LINE DIAGRAM
E-603 RENOVATION PARTIAL ELECTRICAL ONE-LINE DIAGRAM
E-700 ELECTRICAL SCHEDULES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:4
A
M
E001
ELECTRICAL LEGEND, NOTES AND
ABBREVIATIONSGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
FIRE RATING LEGEND
1 HOUR FIRE WALL
2 HOUR FIRE WALL
Revisions: Date:
01/24/2025
3 3
SDSD
SD SD SD
SD
SD
SD
ENGINEERING ELECTRICAL
CLOSET
C014
ENGINEERING ELECTRICAL
CLOSET
C017
NOT IS SCOPE
ELEVATOR P1ELEVATOR P2ELEVATOR P3
ELEVATOR P5ELEVATOR P4
ELEVATOR S8
ELEVATOR S7
ELEVATOR S6
ED100
ENGINEERING ELECTRICAL
CLOSET
C022
A
B C D E F G H I J K L M N O P Q
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL
REMAIN OPERATIONAL DURING CONSTRUCTION.
I. FIRE ALARM DEVICES SHALL REMAIN UNLESS NOTED BY THE COR OR VA. IF
FIRE ALARM DEVICES ARE REQUIRED TO BE TEMPORARILY REMOVED, THE
CONTRACTOR SHALL PROVIDE A FIRE WATCH UPON COMPLETION OF WORK.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
200-B1 (E)
200-A1 (E)
(E)
(E)(E)(E)
(D)
(E)
(E)
(E)
(E)
(E)
(E)
1600A ATS-ELEV (D)
ENGINEERING ELECTRICAL
CLOSET
C014
F G
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:1
A
M
ED100
BASEMENT DEMOLITION POWER
PLAN - OVERALLGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"ED100
1 BASEMENT DEMOLITION POWER PLAN - OVERALL
KEYNOTES
1 APPROXIMATE LOCATION FOR SWITCHGEAR GD-A (BUILDING 226) -
(5) PARALLEL 750 kVA GENERATORS.
2 BUILDING 200.
3 LOCATION OF EXISTING MAIN SWITCHBOARD 200-MB-B IN ROOM
C022.
4 LOCATION OF EXISTING MAIN SWITCHBOARD 200-MB-A IN ROOM
C022.
5 EXISTING ATS-ELEV SHALL BE DEMOLISHED. REMOVE EXISTING
FEEDERS AND CONDUIT IN THEIR ENTIRETY BACK TO POINT OF
ORIGIN. REFER TO SHEETS E-600-E-603 FOR PHASING NOTES AND
ADDITIONAL INFORMATION.
6 CONTRACTOR SHALL CAPTURE EXISTING PRE-TRANSFER SIGNAL
FROM PARALLEL GENERATOR TO ATS-ELEV (D). PROVIDE WIRE,
JUNCTION BOXES, CONDUIT, ETC. ABOVE EXISTING ATS-ELEV AS
REQUIRED TO MAINTAIN CONTINUITY FOR NEW ATS-ELEV-1 AND ATS
ELEV-2 TO BE LOCATED ON OPPOSING WALL IN EXISTING
ELECTRICAL CLOSET C014.
7 DEMOLISH EXISTING ATS EQUIPMENT. REMOVE ALL EXISTING
FEEDS AND CONDUIT BACK TO SOURCE.
N
SCALE: 1/4" = 1'-0"ED100
2 BASEMENT ENLARGED PLAN - ENGINEERING ELECTRICAL CLOSET C014 DEMO
SDSD
SD SD SD
SD
SD
SD
ELEVATOR P1ELEVATOR P2ELEVATOR P3
ELEVATOR P5ELEVATOR P4
ELEVATOR S8
ELEVATOR S7
ELEVATOR S6
(TYP)
(TYP)
(D)(D)(E) (E)
(E)(D)(E)
(D)
(E)
(E) (D)
(E) (E) (E)
(E)(E)
(E)
(E)
(E)
F G H I J K L
NOT IN SCOPE
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL
REMAIN OPERATIONAL DURING CONSTRUCTION.
I. FIRE ALARM DEVICES SHALL REMAIN UNLESS NOTED BY THE COR OR VA. IF
FIRE ALARM DEVICES ARE REQUIRED TO BE TEMPORARILY REMOVED, THE
CONTRACTOR SHALL PROVIDE A FIRE WATCH UPON COMPLETION OF WORK.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:2
A
M
ED100.1
BASEMENT DEMOLITION
ELECTRICAL PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"ED100.1
1 BASEMENT DEMOLITION ELECTRICAL PLAN
N
KEYNOTES
1 DEMOLISH LIGHTING FIXTURES IN SCOPE OF WORK. EXISTING
LIGHTING CIRCUITS AND LIGHTING CONTROLS TO REMAIN AND BE
REUSED.
SDSD
SD SD SD
SD
SD
SD
SDSD
SD SD SD
SD
SD
SD
ELEVATOR P1ELEVATOR P2ELEVATOR P3
ELEVATOR P5ELEVATOR P4
ELEVATOR S8
ELEVATOR S7
ELEVATOR S6
(TYP)
(TYP)
(D)(D)
(D)
(D)
(E)
(E) (D)
(E) (E) (E)
(E)(E)
(E)
(E)
(E)
NOT IN SCOPE
F G H I J K L
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL
REMAIN OPERATIONAL DURING CONSTRUCTION.
I. FIRE ALARM DEVICES SHALL REMAIN UNLESS NOTED BY THE COR OR VA. IF
FIRE ALARM DEVICES ARE REQUIRED TO BE TEMPORARILY REMOVED, THE
CONTRACTOR SHALL PROVIDE A FIRE WATCH UPON COMPLETION OF WORK.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
H I J K
NOT IN SCOPE
(E)
(E) (E)
(E)
(E)
(E)
(E)
(E)
ELEVATOR
P1
ELEVATOR
P2
ELEVATOR
P3
ELEVATOR
P5
ELEVATOR
P4
ELEVATOR
S8
ELEVATOR
S7
ELEVATOR
S6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:2
A
M
ED101.1
FIRST - FOURTEENTH FLOOR
DEMOLITION ELECTRICAL PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"ED101.1
1 FIRST - FOURTEENTH FLOOR DEMOLITION ELECTRICAL PLAN (TYPICAL)
N
KEYNOTES
1 DEMOLISH LIGHTING FIXTURES IN SCOPE OF WORK. EXISTING
LIGHTING CIRCUITS AND LIGHTING CONTROLS TO REMAIN AND BE
REUSED.
2 EXISTING ABANDONED SIMPLEX FIRE ALARM PANEL UNDER
PREVIOUS RENOVATION TO BE REMOVED. PREP AREA FOR NEW
FIRE COMMAND STATION. RE-USE EXISTING CIRCUIT FOR NEW FIRE
ALARM CONTROL PANEL FOR FIRE COMMAND STATION. REFER TO
SHEET E101.1 FOR ADDITIONAL INFORMATION.
3 EXISTING FIRE ALARM CONTROL ROOM.
SCALE: 3/32" = 1'-0"ED101.1
2 FIRST FLOOR DEMOLITION ELECTRICAL PARTIAL PLAN - EXISTING FIRE ALARM CONTROL ROOM N
SDSD
SD SD SD
SD
SD
SD
SD
SD
SD
HD
HD
HD
SD
HD
SD
HD
SD
HD
SD
HD
SD
HD
ELEVATOR P1ELEVATOR P2ELEVATOR P3
ELEVATOR P5ELEVATOR P4
ELEVATOR S8
ELEVATOR S7
ELEVATOR S6
(TYP)
(TYP)
(D)(D)
(E)(D)(E)
(D)
(E)
(E) (D)
(E) (E) (E)
(E)(E)
(E)
(E)
(E)
(E) (E)
NOT IN SCOPE
F G H I J K L
(E)
(E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL
REMAIN OPERATIONAL DURING CONSTRUCTION.
I. FIRE ALARM DEVICES SHALL REMAIN UNLESS NOTED BY THE COR OR VA. IF
FIRE ALARM DEVICES ARE REQUIRED TO BE TEMPORARILY REMOVED, THE
CONTRACTOR SHALL PROVIDE A FIRE WATCH UPON COMPLETION OF WORK.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:3
A
M
ED115
FIFTEENTH LEVEL DEMOLITION
ELECTRICAL PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"ED115
1 FIFTEENTH LEVEL DEMOLITION ELECTRICAL PLAN
N
KEYNOTES
1 DEMOLISH LIGHTING FIXTURES IN SCOPE OF WORK. EXISTING
LIGHTING CIRCUITS AND LIGHTING CONTROLS TO REMAIN AND BE
REUSED.
HD
S
HD
HD
HD
HD
HD HD
HD
HD
HD
HD
HD
HD
HD
HD
HD
J
J J
HD
EXISTING PANEL
200-EL(D)
(D) 200-T-EL
ELEVATOR
CONTROL
CAB S6
(D) EXISTING 200
ATS-E3
(D) EXISTING PANEL
200-E3
(D) EXISTING PANEL
200-PMRA
(D) EXISTING PANEL
200-HVAC-PH
(D)AHU-AS1
GT S6
(D)
GT S7
GT S8
ELEVATOR
CONTROL
CAB S7
(D)
ELEVATOR
CONTROL
CAB S8
(D)
200-S6, DISC.
200/150/3/1
200-S7, DISC.
200/200/3/1
200-S8, DISC.
200/200/3/1
(D)
(D)
(D)
(D)
(D)
(D)
(E)(E)
ELEVATOR
CONTROL
CAB P1
(D)
200-P1, DISC.
200/150/3/1
ELEVATOR
CONTROL
CAB P3
(D)
(D)
ELEVATOR
CONTROL
CAB P2
(D)
(D)
(D)
200-P2, DISC.
200/150/3/1
200-P3, DISC.
200/150/3/1
GT P3 GT P2 GT P1
(D)AHU-A2F DISC.
(D)(D)
(D)
GT P4 GT P5
200-P4, DISC.
200/150/3/1
200-P5, DISC.
200/150/3/1
ELEVATOR
CONTROL
CAB P5
ELEVATOR
CONTROL
CAB P4
(D) (D)
(D)(D) (D) (D)
(D) (D) (D)
(D)(D)
200-P1, DISC.
200/200/3/1
200-P2, DISC.
200/200/3/1
200-P3, DISC.
200/200/3/1
200-P4, DISC.
200/200/3/1
200-P5, DISC.
200/200/3/1
200-S8, DISC.
225/225/3/1
200-S7, DISC.
225/225/3/1
200-S6, DISC.
225/225/3/1
(D)
(D)
(D)
(D)
(D)AHU-A3F
(D) EXISTING
AHU-A1F
(D)AHU-AS2
ENGINEERING MECHANICAL
ROOM
(D)EF-7
(D)SF-EL1
(D)EF-12
(D)AHU-S3
(E)
(E)
(E)(E)
(E) (E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)(E)
(E)
(E)
2 3
(TYP)
(TYP)
(D) (D) (D) (D) 7
(TYP)
H I J
(E)
(TYP)
(TYP)
(E)
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL
REMAIN OPERATIONAL DURING CONSTRUCTION.
I. FIRE ALARM DEVICES SHALL REMAIN UNLESS NOTED BY THE COR OR VA. IF
FIRE ALARM DEVICES ARE REQUIRED TO BE TEMPORARILY REMOVED, THE
CONTRACTOR SHALL PROVIDE A FIRE WATCH UPON COMPLETION OF WORK.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
A. CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE
DEMOLITION/RENOVATION PLANS AND IDENTIFY ALL OLD AND NEW GEAR
ENSURING EXISTING INSTALLATION ARE NOT DISTURBED. ELEVATORS
WITHIN SOW ARE 200-P1-P5 AND 200-S6-S8. THE CONTRACTOR SHALL
ENSURE ALL PREP WORK ARE COMPLETED PRIOR TO MOVING TO PHASE 1.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PROVIDING A FIRE
WATCH DURING ANY SHUT DOWN OF ELEVATORS OR ANY MODIFICATIONS
TO THE EXISTING FIRE ALARM SYSTEM. CONTRACTOR IS RESPONSIBLE TO
VERIFY IF EXISTING CONDUIT SHALL BE ABONDONED OR REUSED FOR
PROJECT SCOPE.
B. DURING THE CHANGE OVER OF UPGRADING THE EXISTING 1600A ATS-
ELEVATORS (INTO TWO SEPARATE ATS) A NEW 1600A 200-ATS-ELEV-1 SHALL
BE INSTALLED ON THE OPPOSING WALL IN ELEC CLOSET C014. THE INTENT
IS TO TEMPORARY POWER ALL ELEVATORS ON NEW PANEL 200-PMRA-1
(LOCATED ON NORTH WALL OF ELEVATOR MACHINE ROOM) FROM THE NEW
200-ATS-ELEV-1. A NEW 600A 200-ATS-ELEV-2 SHALL BE INSTALLED IN
EXISTING ELECTRICAL ROOM B0-31A AND SHALL FEED NEW PANEL 200-
PMRA-2 WHICH SHALL POWER ONLY SERVICE ELEVATORS 200-S6-S8. ONCE
200-PMRA-2 IS READY FOR SERVICE; 200-PMRA-1 SHALL POWER ONLY
ELEVATORS 200-P1-P5. THE CONTRACTOR SHALL COORDINATE WITH THE
COR AT LEAST 3 WEEKS IN ADVANCE PRIOR TO DISTURBING SERVICES TO
THE ELEVATORS. PROVIDE SUFFICIENT STAFFS ONSITE TO ENSURE ALL
WORK TO BE COMPLETED WITHIN THE ALOTTED TIME GIVEN BY THE VA AND
MUST NOT EXCEED THAT TIME PERIOD.
C. THE CONTRACTOR SHALL COORDINATE ALL GEAR STAGING, ROUTING,
PLACEMENT/FITMENT ON SITE AND COORDINATE LEAD-TIMES. ENSURE
PROJECT IS PROGRESSING IN A TIMERLY MANNER, MEETING THE
EXPECTATION OF THE VA.
SEQUENCE OF OPERATIONS - PHASE 0
A. PREP AREA AND INSTALL NEW 600A ATS, LABELED AS 200-ATS-ELEV-2
LOCATED IN EXISTING ELECTRICAL CLOSET C014 TO SERVICE NEW PANEL
200-PMRA-2 LOCATED IN THE MACHINE ROOM; NEW PANEL 200-PMRA-2
SERVES ELEVATORS 200-S6-S8.
1. UPON ACTIVATION OF NEW 200-PMRA-1 SERVICING ALL
ELEVATORS, CONTRACTOR SHAL INSTALL NEW 600A CIRCUIT
BREAKER WITHIN EXISTING SWITCHBOARD 200-MB-B AND LABEL AS
200-ATS-ELEV-2. ENSURE CIRCUIT BREAKER IS IN THE “OFF”
POSITION.
2. RUN NEW CONDUIT AND CONDUCTORS OVERHEAD FROM EXISTING
SWITCHBOARD 200-MB-B TO NEW 200-ATS-ELEV-2. MAKE
TERMINATIONS.
3. INSTALL NEW 600A CIRCUIT BREAKER WITHIN EXISTING
SWITCHBOARD 200-B1 AND LABEL AS 200-ATS-ELEV-2. ENSURE
CIRCUIT BREAKER IS IN THE “OFF” POSITION.
4. RUN NEW CONDUIT AND CONDUCTORS BELOW BASEMENT IN
INTERSTITIAL SPACE FROM EXISTING SWITCHBOARD 200-B1 TO
NEW 200-ATS-ELEV-2. MAKE TERMINATIONS.
5. RUN NEW CONDUIT AND CONDUCTORS BELOW BASEMENT IN
INTERSTITIAL SPACE TO SHAFT LOCATED NEAR ELEVATORS P4-P5
FROM NEW 200-ATS-ELEV-2 TO NEW PANEL 200-PMRA-2 LOCATION.
SEQUENCE OF OPERATIONS - PHASE 1
A. PREP AREA AND INSTALL NEW 1600A ATS, LABELED AS 200-ATS-ELEV-1
SERVICING NEW PANEL 200-PMRA-1 LOCATED IN THE MACHINE ROOM; NEW
PANEL 200-PMRA-1 TEMPORARILY SERVES ELEVATORS 200-P1-P5 AND 200-
S6-S8.
B. CONTRACTOR SHALL INSTALL A 1000AT 277/480V, 3P, 4W CIRCUIT BREAKER
IN THE EXISTING SPARE 8-B IN EXISTING 200-B1 SWITCHGEAR.
C. PREP AREA AND INSTALL THE NEW PANEL 200-PMRA-1 LOCATED IN THE
MACHINE ROOM; NEW PANEL WILL TEMPORARY SERVE ELEVATORS 200-P1-
P5, 200-S6-S8 BUT WILL PERMANATELY SERVE 200-P1-P5.
D. RUN NEW CONDUIT AND CONDUCTORS FROM NEW 200-ATS-ELEV-1 TO NEW
PANEL 200-PMRA-1. ROUTING SHALL BE FED BELOW BASEMENT TO
ADJACENT SHAFT BY ELEVATORS P4 AND P5 UP TO ELEVATOR MACHINE
ROOM. MAKE TERMINATIONS.
E. INSTALL NEW JUNCTION BOX OVERHEAD OF EXISTING 1600A ATS-
ELEVATORS IN THE BASEMENT. SIZE NEW JUNCTION BOX PER NEC IN
PREPERATIONS FOR CONNECTIONS OF INCOMING AND OUTGOING POWER.
F. INSTALL NEW JUNCTION BOX OVERHEAD OF EXISTING PANEL 200-PMRA IN
THE MACHINE ROOM. SIZE NEW JUNCTION BOX PER NEC IN PREPERATIONS
FOR CONNECTIONS OF ELEVATOR POWER.
G. RUN NEW CONDUITS AND CONDUCTORS OVERHEAD FROM NEW JUNCTION
BOX UNDER PHASE 1, F, TO NEW 1600A PANEL 200-PMRA-1 FOR ELEVATOR
POWER. PROVIDE ENOUGH CONDUCTOR SLACK IN NEW JUNCTION BOX TO
TERMINATE CONNECTIONS WITH EXISTING ELEVATOR CONDUCTORS.
H. ALL ELEVATORS WILL BE OPERABLE.
SEQUENCE OF OPERATIONS - PHASE 2
A. SAFELY SWITCH OVER CIRCUIT BREAKERS SERVICING 1600A ATS-
ELEVATORS ON THE EMERGENCY AND NORMAL SIDE IN THE “OFF” POSITION
TO DE-ENERGIZE 1600A ATS-ELEVATORS; EXISTING BREAKER ON
EMERGENCY IS LOCATED WITHIN SWITCHBOARD 200-B1 AND EXISTING
BREAKER ON NORMAL IS LOCATED WITHIN SWITCHBOARD 200-MB-B.
B. ONCE DE-ENERGIZED, REMOVE EMERGENCY AND NORMAL CONDUCTORS
FROM 1600A ATS-ELEVATORS AND PROVIDE CONNECTIONS WITHIN THE NEW
JUNCTION BOX OVERHEAD AS DESCRIBED IN PHASE 1, E. EXTEND CONDUIT
AND CONDUCTORS AS NEEDED FOR PRE TRANSFER SWITCH TO ATS RELAY
FROM GENERATOR. AT THIS POINT NEW 1600A 200-ATS-ELEV-1 IN EXISTING
ELECTRICAL CLOSET C014 WILL BE CONNECTED TO THE EMERGENCY AND
NORMAL PANELS.
C. CONTRACTOR SHALL REPLACE EXISTING 1000A CIRCUIT BREAKERS IN 200-
B1 AND 200-MB-B WITH 600A 277/480V, 3P, 4W CIRCUIT BREAKER (MATCH
EXISTING AIC RATING) FOR NEW 200-ATS-ELEV-2, LOCATED IN EXISTING
ELECTRICAL ROOM B0-31A.
D. ALL ELEVATORS WILL OPERABLE.
SEQUENCE OF OPERATIONS - PHASE 3
A. REMOVE EXISTING 1600A ATS-ELEVATORS AND EXISTING PANEL 200-PMRA.
B. PREP AREA AND INSTALL NEW PANEL 200-PMRA-2 IN THE SAME LOCATION
AS EXISTING PANEL 200-PMRA; NEW PANEL 200-PMRA-2 SERVES ELEVATORS
200-S6-S8.
C. MAKE CONNECTIONS FROM NEW 200-ATS-ELEV-2 TO NEW PANEL 200-
PMRA-2. TEST ALL CONNECTIONS. AT THIS POINT, NEW PANEL 200-PMRA-2 IS
READY FOR FINAL SWITCH OVER TO SERVICE ELEVATORS 200-S6-S8 AS
DESCRIBED IN THE FOLLOWING STEPS. PRIOR TO MOVING TO PHASE 4, D
ENSURE NEW PANEL 200-PMRA-2 IS DE-ENERGIZED.
D. SAFELY SWITCH OVER CIRCUIT BREAKERS SERVICING ELEVATORS 200-S6-
S8 IN THE “OFF” POSITION WITHIN NEW PANEL 200-PMRA-1. SPLICE
CONDUCTORS SERVICING ELEVATORS 200-S6-S8 WITHIN NEW JUNCTION
BOX IN PHASE 1, F AND EXTEND CONDUIT AND CONDUCTORS TO NEW PANEL
200-PMRA-2.
E. SAFELY SWITCH OVER MAIN CIRCUIT BREAKER IN NEW PANEL 200-PMRA-2 IN
THE “ON” POSITION TO ENERGIZE THE NEW PANEL AND SERVICE TO
ELEVATORS 200-S6-S8.
F. ALL ELEVATORS WILL BE OPERABLE.
SEQUENCE OF OPERATIONS - PHASE 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:3
A
M
ED116
MACHINE ROOM DEMOLITION
ELECTRICAL PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"ED116
1 MACHINE ROOM DEMOLITION FLOOR ELECTRICAL PLAN
N
KEYNOTES
1 CONTRACTOR SHALL FOLLOW SEQUENCE OF OPERATIONS AND
PHASING DURING DEMOLITION OF PANEL 200-PMRA.
2 CONTRACTOR SHALL REPLACE DEMOLISHED EQUIPMENT WITH
NEW. USE EXISTING FEEDS FOR RECONNECTION OF NEW
EQUIPMENT.
3 REMOVE EXISTING ELECTRICAL DEVICE AND BRANCH CIRCUITS AND
FEEDERS IN THEIR ENTIRETY BACK TO POINT OF ORIGIN.
4 CONTRACTOR SHALL PROVIDE WIRE, JUNCTION BOXES, CONDUIT,
ETC. AS REQUIRED TO MAINTAIN CONTINUITY TO EXISTING TO
REMAIN EQUIPMENT, SYSTEMS DEVICES, ETC. REFER TO
SEQUENCE OF OPERATIONS AND PHASING
5 ALL ELEVATOR EQUIPMENT, DISCONNECTS, CONTROLS AND GEAR
SHALL BE DEMOLISHED AND REPLACED WITH NEW.
6 CONTRACTOR SHALL DEMOLISH ALL EXISTING EQUIPMENT,
DISCONNECTS, FEEDERS, CONDUIT OR JUNCTION BOXES FOR
ELEVATORS 200-P1-P5 TO SOURCE.
7 FOR ELEVATORS 200-S6-S8, CONTRACTOR SHALL PROVIDE
JUNCTION BOX ABOVE ELEVATOR CONTROLS AND MAINTAIN FEED
TO EQUIPMENT. EXISTING PANEL PMRA WILL BE DEMOLISHED AND
EXISTING FEEDS FOR 200-S6-S8 SHALL BE DEMOLISHED TO NEW
JUNCTION BOX PROVIDED. REFER TO SEQUENCE OF OPERATIONS
AND PHASING.
8 CONTRACTOR SHALL DEMOLISH ALL EXISTING EQUIPMENT,
DISCONNECTS, FEEDERS, CONDUIT OR JUNCTION BOXES FOR
ELEVATORS 200-S6-S8 TO SOURCE.
1 2
(TYP) (TYP)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)(D)
(D)
(D) (D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D) (D)
(D)
(D)
(D)
(D)
(E)
(E)
(E) (D)
(D)
(E)
ENGINEERING MECHANICAL
ROOM
H I J
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN THESE
DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE VA/COR.
C. REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT, BRANCH CIRCUITS
AND FEEDERS THAT ARE INDICATED FOR DEMOLITION IN THEIR ENTIRETY
BACK TO POINT OF ORIGIN UNLESS OTHERWISE INDICATED. TURN OFF AND
LABEL CIRCUIT BREAKERS AS SPARES FOR NEW WORK WHERE APPLICABLE.
D. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS, OFFSETS, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, VA AND
MANUFACTURER RECOMMENDATIONS.
E. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS
AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL
EQUIPMENT SHOWN TO BE DEMOLISHED.
F. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING.
G. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
H. ALL EXISTING LIFE SAFETY LIGHTING LOCATED IN AREAS THAT ARE
EXISTING TO REMAIN, SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
CONSTRUCTION.
I. THE DESIGN INTENT IS TO REPLACE ALL EXISTING LIGHT FIXTURES AND RE-
USE EXISTING LIGHTING CONTROLS WITHIN SCOPE OF WORK. EXISTING
LIGHTING CIRCUIT/S SHALL BE REUSED DURING RENOVATION.
J. PRIOR TO THE REMOVAL OF DEVICES (INTENDED TO BE REINSTALLED AND
REUSED), THE GENERAL CONTRACTOR SHALL TEST AND VERIFY THAT THE
DEVICES ARE FULLY FUNCTIONAL. IN THE CASE THAT THEY ARE FOUND
NON-FUNCTIONAL, THE GENERAL CONTRACTOR SHALL INCLUDE IN BID THE
MEANS AND METHODS TO REINSTATE DEVICES BACK TO FUNCTIONAL.
ELECTRICAL DEMOLITION GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:3
A
M
ELD116
MACHINE ROOM DEMOLITION
LIGHTING PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"ELD116
1 MACHINE ROOM DEMOLITION FLOOR LIGHTING PLAN
KEYNOTES
1 DEMOLISH LIGHTING FIXTURES AND LIGHTING CONTROLS IN SCOPE
OF WORK. EXISTING LIGHTING CIRCUITS TO REMAIN AND BE
REUSED.
2 CONTRACTOR SHALL TRACE CIRCUITS BACK TO SOURCE PRIOR TO
DEMOLITION AND VERIFY PANEL SCHEDULES INFORMATION IS
ACCURATE. EXISTING CIRCUITS THAT SHARE FEEDS OUT OF SCOPE
OF WORK SHALL RETAIN CONTINUITY.
N
CR
C R
J J
ENGINEERING ELECTRICAL
CLOSET
C014
ENGINEERING ELECTRICAL
CLOSET
C017
NOT IS SCOPE
ELEVATOR P1ELEVATOR P2ELEVATOR P3
ELEVATOR P5ELEVATOR P4
ELEVATOR S8
ELEVATOR S7
ELEVATOR S6
E100
3 4
A
B C D E F G H I J K L M N O P Q
10 (TYP)
A. EXISTING CONDITIONS BASED ON FIELD OBSERVATION. ELECTRICAL
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND REPORT
DISCREPANCIES TO VA/COR PRIOR TO DISTURBING EXISTING
INSTALLATIONS.
B. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF WORK, ELECTRICAL
EQUIPMENT SHALL BE LOCATED SO THAT THE CODE REQUIRED MINIMUM
WORKING CLEARANCE AND DEDICATED ELECTRICAL SPACE ARE
MAINTAINED.
C. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE SCOPE
OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY RACEWAY
ROUTING, BENDS OFFSETS, PULL BOXES, AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH THE CODE VA, AND
MANUFACTURER RECOMMENDATIONS.
D. FINAL MOUNTING HEIGHTS AND LOCATION OF BOXES, JUNCTION BOXES
RECEPTACLES, AND DATA CONNECTIONS SHALL BE VERIFIED WITH THE VA
PRIOR TO CONSTRUCTION.
E. ALL JUNCTION BOXES SHALL BE RIGIDLY ATTACHED TO STRUCTURE OR
MILLWORK.
F. COORDINATE FINAL POWER REQUIREMENTS OF ALL EQUIPMENT IN THE
BUILDING WITH VENDOR AND VA PRIOR TO CONSTRUCTION. ALL
ELECTRICAL INSTALLATIONS SHALL COMPLY WITH NEC REQUIREMENTS.
G. ALL RECEPTACLES COVER PLATES SHALL HAVE THE DEVICE'S CIRCUIT
(PANEL AND CIRCUIT NUMBER) AFFIXED ACROSS THE TOP OF THE PLATE
WITH 3/16" HEIGHT BLACK TEXT ON CLEAR SELF-ADHESIVE TAPE.
H. ALL 120V 20A RECEPTACLES INSTALLED WITHIN THE BUILDING EXCEPT
THOSE INSTALLED FOR FIXED APPLIANCES AND EQUIPMENT SHALL BE
TAMPER RESISTANT TYPE.
I. LIGHTING FIXTURES CONNECTED TO THE LIFE SAFETY CIRCUITS AND EXIT
SIGNS SHALL HAVE A 24/7 OPERATION.
J. PROVIDE ALL MOUNTING AND SUPPORT HARDWARE FOR LIGHT FIXTURES
TO MEET SPECIFIED MOUNTING HEIGHTS AND REQUIREMENTS.
K. REFER TO ASME A17.1 2.14.7 FOR ILLUMINATION OF CARS AND LIGHTING
FIXTURES.
L. CONTRACTOR SHALL INCLUDE IN BID FOR ALL WORK REQUIRED TO BE
PERFORMED IN CEILING SPACES. ALL CONDUIT SHALL BE RAN FROM
SOURCE LOCATION. COORDINATE WITH VA FOR ACCESS TO SPACES IN
ADVANCE NOTICE PRIOR TO WORK.
M. EXISTING FIRE ALARM SYSTEM IS SIMPLEX - 4100U. GENERAL CONTRACTOR
SHALL VERIFY IN FIELD PRIOR ANY SOFTWARE UPDATES. GENERAL
CONTRACTOR TO PROVIDE ALL FIRE ALARM DEVICES, WIRING, TESTING AND
PROGRAMMING NEEDED TO SUCCESSFULLY INTERCONNECT THE
ELEVATORS TO THE EXISTING FIRE ALARM NOTIFICATION SYSTEM.
ELECTRICAL GENERAL NOTES
ENGINEERING ELECTRICAL
CLOSET
C014
200-B1 (E)
200-A1 (E)
(E)
(E)(E)(E)
(E)
(E)
(E)
(E)
(E)
(E)
ENGINEERING ELECTRICAL
CLOSET
C014
F G
1600A
200-ATS-ELEV-1 (N)
600A 200-ATS-ELEV-2
(N)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Architect:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP Engineer: Elevator Consultant:
MES GROUP LERCH BATES
550 N. REO STREET SUITE 203
TAMPA, FL 33609
813.289.4700
216 S. JEFFERSON STREET
SUITE LL2
CHICAGO, IL 60661
312.256.1010
30% SCHEMATIC DESIGN 06/20/2024
60% DESIGN DEVELOPMENT 08/12/2024
KEY PLAN
NO SCALE
N
90% QAQC REVIEW 09/23/2024
90% CONSTRUCTION DOCUMENTS 10/02/2024
100% QAQC REVIEW 10/25/2024
100% BID DOCUMENTS 01/20/2025
100% BID DOCUMENTS - REVISED BASE BID 01/24/2025
A u to d e s k D o c s /1
.6
.1
V A
H in e s E le v a to r
R e p la c e m e n t/
.6
.1
H in e s E le v a to rs M
E P
R
.r v t
/2
/2
:3
:0
A
M
E100
BASEMENT POWER PLAN -
OVERALLGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
ELEVATOR REPLACEMENT
5000 5TH AVE, HINES, IL 60141
578-25-003
01/24/2025 SAR SMY
100% BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/16" = 1'-0"E100
1 BASEMENT POWER PLAN - OVERALL
KEYNOTES
1 APPROXIMATE LOCATION FOR SWITCHGEAR GD-A (BUILDING 226) -
(5) PARALLEL 750 kVA GENERATORS.
2 BUILDING 200.
3 LOCATION OF EXISTING MAIN SWITCHBOARD 200-MB-A IN ROOM
C022.
4 LOCATION OF EXISTING MAIN SWITCHBOARD 200-MB-B IN ROOM
C022.
5 CONTRACTOR SHALL EXTEND EXISTING PRE-TRANSFER SIGNAL
FROM PARALLEL GENERATOR TO NEW ATS-ELEV-1 AND ATS-ELEV-2.
PROVIDE WIRE, JUNCTION BOXES, CONDUIT, ETC. AS REQUIRED TO
MAINTAIN CONTINUITY TO EQUIPMENT RELOCATED ON OPPOSING
WALL IN EXISTING ELEC ROOM C014.
6 CONTRACTOR SHALL INSTALL NEW 1600A, 480/277V, 3P, 4W, NEMA 1
ISOLATION-BYPASS TRANSFER SWITCH (BASIS OF DESIGN: ASCO)
FOR ATS-ELEV-1 IN EXISTING ELECTRICAL CLOSET C014. REFER TO
SHEETS E-600-E-603 FOR PHASING NOTES AND ADDITIONAL
INFORMATION. REFER TO SHEET E-700 FOR FEEDER SIZE AND
QUANTITY.
7 PULLBOX LOCATIONS SHOWN FOR REFERENCE. CONTRACTOR
SHALL FIELD COORDINATE…