Amendment 0004.pdf
PDF 145 KB Posted
- Attached to
- P242 Combat Rescue Helicopter Simulator Facility Federal contract opportunity
- Solicitation number
- N6247023R0003
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
MILCON P242 COMBAT RESCUE HELICOPTER SIMULATOR FACILITY, AVIANO, ITALY
Please see Block 14 Continuation Page
1. CONTRACT ID CODE PAGE OF PAGES
J 1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 31-May-2023
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N6247023R0003
X 9B. DATED (SEE ITEM 11)
29-Mar-2023
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
31-May-2023
CODE
COMNAVFACSYSCOM ATLANTIC
6506 HAMPTON BLVD
NORFOLK VA 23508-1278
N62470 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N6247023R0003
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)
The following have been added by full text:
AMENDMENT 0004
The purpose of this amendment is to provide the following:
1. Respond to Pre-Proposal Inquiries (PPIs)
1. Pre-Proposal Inquiry (PPI) Responses
31. Inquiry: (Reference Section 09 097 13.00 40) Fire rating protection of new Steel Roof structures.
In drawing S-001 a new fire rating treatment is required to protect the Steel trusses. In particular in point 8.3 an intumescent Paint is request to guarantee the required fire rating shown in fire protection drawings. On fire protection drawings we cannot find this request.On the architectural drawings the varius compartimentations are illustrated, for exemple in AR111; 60 minutes is required between the “OFT Simulator Bay” and other rooms. On the tech. Specs. Section 09 097 13.00 40 C.3.1.3 we cannot find the fire rating request. What is the required fire protection degree for the Steel trusses?
Response: As indicated on G-111 and A-111, provide 1-hour rating for the steel trusses in the
Simulator Bay such that it matches the wall ratings between the Simulator Bay and adjacent spaces.
Sheet S-001 states to provide fire protection paint for steel elements. S-512 provides critical temperatures for each element to determine thickness of required intumescent paint.
32. Inquiry: Most of the suppliers and subcontractors in Italy are very busy with ongoing Governmental projects. Accordingly, we kindly request to extend the proposal due date by at least 15 days allowing enough time to receive and evaluate the offers and provide the Government with the most competitive offer.
Response: See Amendment 0003.
33. Inquiry: Inquiry 2 para a) did not clarify if Gantt Schedule of max 4 pages is included within the 10 pages of Factor 4 - Project Specific Requirements. Please clarify
Response: The Gantt schedule is not included in the page limit stated for the narrative.
34. Inquiry: (Reference Dwg P-601 WC-01) Request clarification of the water conditioner as it seems needed to provide cold water to the sanitary system. Please clarify
Response: The water conditioner consists of a reverse polarity system which will serve to the domestic cold water network to the building.
35. Inquiry: (Reference Dwg M-606 Water Chemical) Within the AHU schedule water is foreseen while in the scheme 5 chemial agents dosing pot must be provided. Please clarify if such system is required due the quite signifant amount/cost of such system.
Response: Each closed loop piping system for heating and cooling must be provided with a chemical pot feeder. Current design is provided with one chemical pot in the heating loop, which is required.
N6247023R0003
For the chilled water, each chiller loop is provided with 2 chemical pots, one in the supply and one on the return, to make the treatment in the buffer tanks easier.
--End of Amendment--