4.1.
5.
6.
7.
8.
NO LARGE POWER TRANSFORMERS OR MOTORS SHOULD BE LOCATED WITHIN 50 FEET OF AV
EQUIPMENT SPACES. / ENTRO 50 PIEDI DALLE ATTREZZATURE AV NON DOVRANNO ESSERE PRESENTI
MOTORI ELETTRICI O TRASFORMATORI DI GRANDI DIMENSIONI.
ALL AV CABLING THAT IS RUN OPEN-WIRE SHALL BE SUPPORTED FROM J-HOOKS NO GREATER THAN 3 FEET APART. NO CABLE IS TO BE UNSUPPORTED OR LAID OVER CEILING TILES, BLACK IRON, OR OTHER CEILING MEMBERS. / TUTTI I CABLAGGI AV IN CUI I CAVI SONO ESPOSTI DEVONO ESSERE SOSTENUTI DA GANCI A J A UNA DISTANZA TRA LORO NON MAGGIORE DI 3 PIEDI. NESSUN CAVO DEVE RIMANERE SENZA SUPPORTO O APPOGGIATO SUI PANNELLI DEL SOFFITTO, SU ELEMENTI IN METALLI O ALTRE PARTI DEL
SOFFITTO.
THE METHOD OF INSTALLATION OF BOXES IN WALLS, AND THE METHOD OF PASSAGE OF CONDUITS AND
WIREWAYS THROUGH ACOUSTICALLY SENSITIVE WALLS SHALL BE COORDINATED WITH THE
ACOUSTICAL CONSULTANT. IL METODO DI INSTALLAZIONE DELLE SCATOLE NEI MURI E IL METODO PER IL PASSAGGIO DELLE CONDOTTE E DELLE CANALINE ATTRAVERSO PARETI CON RILEVANZA ACUSTICA
DEV’ESSERE DEFINITO INSIEME AL CONSULENTE PER L'ACUSTICA.
INSTALL FIRESTOP TO ALL SLAB AND WALL PENETRATIONS PROVIDED FOR THE INSTALLATION OF CABLE AND CONDUIT AS REQUIRED TO MAINTAIN FIRE RATING OF SLAB OR WALL. REVIEW ARCHITECT'S PLANS FOR PARTITION TYPES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE FIRE RATING OF ALL WALLS AND FLOORS HAVING CABLING PENETRATIONS, COORDINATE SEALANT INSTALLATION WITH WORK OF OTHER TRADES. REFER TO ELECTRICAL SPECIFICATIONS FOR MATERIAL AND INSTALLATION PARAMETERS. / PREVEDERE MATERIALE IGNIFUGO PER TUTTE LE PENETRAZIONI DI PARETI O PANNELLI NECESSARIE PER L’INSTALLAZIONE DI CAVI E CONDOTTE, COME RICHIESTO PER GARANTIRE LA RESISTENZA AL FUOCO DEL PANNELLO O DELLA PARETE. VERIFICARE I PIANI DELL’ARCHITETTO PER LE TIPOLOGIE DI TRAMEZZATURA. L'APPALTATORE È TENUTO A VERIFICARE IL LIVELLO DI RESISTENZA AL FUOCO DI TUTTI I PAVIMENTI E LE PARETI ATTRAVERSATI DAI CAVI, COORDINARE L’APPLICAZIONE DI SIGILLANTE CON IL LAVORO DEGLI ALTRI SOGGETTI COINVOLTI. FARE RIFERIMENTO ALLE SPECIFICHE
ELETTRICHE PER I PARAMETRI DI INSTALLAZIONE E I MATERIALI.
ALL POWER, WIREWAYS, AND JUNCTION BOXES ARE TO BE REVIEWED BY ELECTRICAL ENGINEER FOR CODE AND SAFETY COMPLIANCE. / IL CODICE E LA CONFORMITÀ DI SICUREZZA DI TUTTE LE SCATOLE DI DERIVAZIONE, CANALINE E LINEE ELETTRICHE DEVONO ESSERE VERIFICATI DALL’INGEGNERE ELETTRICO.
DRAWING LIST (LISTA DESIGNI): AUDIOVISUAL FLOOR MOUNTED SYMBOLS (SIMBOLI INSTALLAZIONE AUDIOVISIVI
SU PAVIMENTO):
AUDIOVISUAL WALL MOUNTED SYMBOLS (CONT.) (SIMBOLI INSTALLAZIONE
AUDIOVISIVI A PARETE (CONT.))
JUNCTION BOX, 6" x 6" x 4" DEEP, UON, WITH COVER PLATE FOR AV RECEPTACLES. FLUSH MOUNTED IN FINISHED FLOOR OR SURFACE MOUNTED TO SLAB BELOW RAISED FLOOR. / SCATOLA DI DERIVAZIONE, 6” x 6” X 4” PROF., UON, CON SPORTELLO PER PRESE AV. MONTATA A FILO SU PAVIMENTO FINITO O
MONTATA SULLA SUPERFICIE DELLA LASTRA AL DI SOTTO DEI PAVIMENTI SOPRAELEVATI.
FLOOR BOX WITH DIVIDED COMPARTMENTS FOR AV, DATA AND POWER. FLUSH MOUNTED IN FINISHED FLOOR WITH HINGED SCRUB WATER RATED COVER PLATE AND CARPET FLANGE, OoN (VERIFY FINISH PLATE COLOR WITH ARCHITECT). SEE DETAIL. LEGRAND FLOOR BOX MODEL TBD, UON. REFER TO ELECTRICAL PLANS FOR POWER AND DATA REQUIREMENTS. / SCATOLA DA PAVIMENTO CON SPAZI SEPARATI PER AV, DATI E ALIMENTAZIONE ELETTRICA. MONTATA A FILO NEL PAVIMENTO FINITO CON SPORTELLO INCERNIERATO A TENUTA D’ACQUA E FLANGIA PER MOQUETTE, OoN (VERIFICARE COLORE
PIASTRA DEFINITIVO CON ARCHITETTO). VEDI DETTAGLIO. SCATOLA DA PAVIMENTO LEGRAND
MODELLO TBD, UON. FARE RIFERIMENTO AI DISEGNI ELETTRICI PER I REQUISITI DI ALIMENTAZIONE E
DATI.
CONDUIT STUB-UP INTO FURNITURE. / TRONCO DI LINEA NEGLI ARREDI.
POWER RECEPTACLE, DUPLEX, 120 VAC, 15 AMP CIRCUIT, UON. FLUSH MOUNTED IN FINISHED FLOOR
OR SURFACE MOUNTED TO SLAB BELOW RAISED FLOOR. REFER TO AV NOTES FOR ADDITIONAL
INFORMATION. / PRESA DI ALIMENTAZIONE, DUPLEX, 120 V CA, CIRCUITO 15 AMP, UON. MONTATA A FILO SU PAVIMENTO FINITO O MONTATA SULLA SUPERFICIE DELLA LASTRA AL DI SOTTO DEI PAVIMENTI
SOPRAELEVATI. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV.
POWER RECEPTACLE, QUAD, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT. MOUNTED IN FINISHED
FLOOR OR SURFACE MOUNTED TO SLAB BELOW RAISED FLOOR. REFER TO AV NOTES FOR
ADDITIONAL INFORMATION. (* = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI
ALIMENTAZIONE QUADRUPLA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP. MONTATA SU
PAVIMENTO FINITO O MONTATA SULLA SUPERFICIE DELLA LASTRA AL DI SOTTO DEI PAVIMENTI SOPRAELEVATI. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (* = NUMERO DI CIRCUITI
ELETTRICI DEDICATI)
JUNCTION BOX FOR POWER, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT BY THE ELECTRICAL ENGINEER. FLUSH MOUNTED IN FINISHED FLOOR OR SURFACE MOUNTED TO SLAB BELOW RAISED FLOOR. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (* = NUMBER OF DEDICATED POWER CIRCUITS) / SCATOLA DI DERIVAZIONE PER ALIMENTAZIONE ELETTRICA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP DEFINITO DA INGEGNERE ELETTRICO. MONTATA A FILO SU PAVIMENTO FINITO O MONTATA SULLA SUPERFICIE DELLA LASTRA AL DI SOTTO DEI PAVIMENTI SOPRAELEVATI. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (* = NUMERO DI CIRCUITI ELETTRICI DEDICATI)
STANDARD DATA OUTLET FLUSH MOUNTED IN FINISHED FLOOR, FLOOR BOX OR SURFACE MOUNTED IN FINISHED FLOOR, FLOOR BOX OR SURFACE MOUNTED TO SLAB BELOW RAISED FLOOR. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA DATI STANDARD MONTATA A FILO SU PAVIMENTO FINITO, SCATOLA DA PAVIMENTO O MONTATA SU SUPERFICIE NEL PAVIMENTO FINITO, SCATOLA DA PAVIMENTO O MONTATA SU SUPERFICIE SULLA LASTRA SOTTO AL PAVIMENTO RIALZATO. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI
DI DATI)
FB
J
P
ST
FLOOR BOX MOUNTED UNDER RAISED FLOOR TITLE WITH DIVIDED COMPARTMENTS FOR AV, DATA AND POWER. FLUSH MOUNTED IN FINISHED FLOOR WITH HINGED SCRUB WATER RATED COVER PLATE AND CARPET FLANGE, OoN (VERIFY FINISH PLATE COLOR WITH ARCHITECT). SEE DETAIL. LEGRAND FLOOR
BOX MODEL TBD, UON. REFER TO ELECTRICAL PLANS FOR POWER AND DATA REQUIREMENTS. /
SCATOLA DA PAVIMENTO MONTATA SOTTO AL PAVIMENTO SOPRAELEVATO CON SPAZI SEPARATI PER AV, DATI E ALIMENTAZIONE ELETTRICA. MONTATA A FILO NEL PAVIMENTO FINITO CON SPORTELLO INCERNIERATO A TENUTA D’ACQUA E FLANGIA PER MOQUETTE, OoN (VERIFICARE COLORE PIASTRA DEFINITIVO CON ARCHITETTO). VEDI DETTAGLIO. SCATOLA DA PAVIMENTO LEGRAND MODELLO TBD, UON. FARE RIFERIMENTO AI DISEGNI ELETTRICI PER I REQUISITI DI ALIMENTAZIONE E DATI.
AV
AUDIOVISUAL WALL MOUNTED SYMBOLS: (SIMBOLI INSTALLAZIONE AUDIOVISIVI A
PARETE:)
JUNCTION BOX, 2.5" DEEP, FOR AV RECEPTACLES. SINGLE GANG, UON. MOUNT FLUSH WITH FINISHED WALL TREATMENT AT BUILDING STANDARD BASE OUTLET HEIGHT, UON. (# = NUMBER OF GANGS) / SCATOLA DI DERIVAZIONE, 2,5” PROF., PER PRESE AV. PER DISPOSITIVO SINGOLO, UON. MONTAGGIO A FILO CON PARETE FINITA ALL’ALTEZZA DELLE PRESE STANDARD DELL’EDIFICIO, UON. (N. = NUMERO DI
DISPOSITIVI POSSIBILI)
FLAT PANEL DISPLAY JUNCTION BOX WITH SEPARATE COMPARTMENTS FOR AV, DATA, AND POWER.
SEE DETAIL. CHIEF WALL BOX MODEL PAC526/527 SERIES (4.0" DEEP), UON. MOUNT FLUSH WITH
FINISHED WALL TREATMENT. SEE ELEVATION. AT 60" AFF, UON. REFER TO POWER AND DATA
DESCRIPTIONS FOR RELATED REQUIREMENTS. (# = NUMBER OF DATA DROPS), (* = NUMBER OF POWER OUTLETS) / SCATOLA DI DERIVAZIONE CON PANNELLO DISPLAY PIATTO E SPAZI SEPARATI PER AV, DATI E ALIMENTAZIONE ELETTRICA. VEDI DETTAGLIO. SCATOLA DA MURO CHIEF MODELLO PAC526/SERIE 527 (PROF. 4”), UON. MONTAGGIO A FILO CON PARETE FINITA. VEDI ALTEZZA. A 60” SU PAV FINITO, UON.
FARE RIFERIMENTO A DESCRIZIONI DATI E ALIMENTAZIONE PER REQUISITI RELATIVI. (N. = NUMERO DI
CALI DI DATI) (* = NUMERO DI PRESE ELETTRICHE)
SCREW COVER BOX FOR AV SIGNAL CABLE AND CONDUIT TERMINATION. SIZED BY ELECTRICAL
ENGINEER. MOUNT FLUSH WITH FINISHED WALL TREATMENT AT STANDARD BASE OUTLET HEIGHT, UON. / SCATOLA CON COPERCHIO AVVITATO PER TERMINAZIONE TUBO E CAVO SEGNALE AV.
DIMENSIONI DEFINITE DA INGEGNERE ELETTRICO. MONTAGGIO A FILO CON PARETE FINITA
ALL’ALTEZZA STANDARD DELLE PRESE, UON.
WALL BOX TYPE 1, 6" x 6" x 4" DEEP, FOR AV RECEPTACLES. MOUNT FLUSH WITH FINISHED WALL TREATMENT AT BUILDING STANDARD BASE OUTLET HEIGHT, UON. / SCATOLA DA PARETE TIPO 1, 6” x 6” x 4” PROF., PER PRESE AV. MONTAGGIO A FILO CON PARETE FINITA ALL’ALTEZZA STANDARD DELLE
PRESE DELL’EDIFICIO, UON.
WALL BOX TYPE 2, 12" x 12" x 4" DEEP, FOR AV RECEPTACLES. MOUNT FLUSH WITH FINISHED WALL TREATMENT AT BUILDING STANDARD BASE OUTLET HEIGHT, UON. / SCATOLA DA PARETE TIPO 2, 12” x 12” x 4” PROF., PER PRESE AV. MONTAGGIO A FILO CON PARETE FINITA ALL’ALTEZZA STANDARD
DELLE PRESE DELL’EDIFICIO, UON.
WALL SWITCH FOR RAISE/LOWER/STOP OF PROJECTION SCREEN AND/OR FOR VIDEO PROJECTOR
LIFT. MOUNT AT STANDARD SWITCH HEIGHT, UON. / INTERRUTTORE DA PARETE PER
SOLLEVARE/ABBASSARE/FERMARE LO SCHERMO E/O PER SOLLEVARE IL PROIETTORE VIDEO.
MONTARE AD ALTEZZA STANDARD DEGLI INTERRUTTORI, UON.
POWER RECEPTACLE, DUPLEX, 120 VAC, 15 AMP CIRCUIT. MOUNT AT BUILDING STANDARD BASE
ELECTRICAL HEIGHT, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. / PRESA DI
ALIMENTAZIONE, DUPLEX, 120 V CA, CIRCUITO 15 AMP. MONTARE AD ALTEZZA STANDARD DELLE
PRESE DELL’EDIFICIO, UON. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV.
POWER RECEPTACLE, QUAD, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT. MOUNT AT BUILDING STANDARD BASE ELECTRICAL HEIGHT, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION.
(* = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI ALIMENTAZIONE QUADRUPLA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP. MONTARE AD ALTEZZA STANDARD DELLE PRESE DELL’EDIFICIO, UON. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (* = NUMERO DI CIRCUITI ELETTRICI
DEDICATI)
POWER RECEPTACLE, 208 VAC, SINGLE DEDICATED 30 AMP CIRCUIT. MOUNT AT BUILDING STANDARD BASE ELECTRICAL HEIGHT, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. / PRESA DI ALIMENTAZIONE, 208 V CA, CIRCUITO SINGOLO DEDICATO 30 AMP. MONTARE AD ALTEZZA STANDARD DELLE PRESE DELL’EDIFICIO, UON. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV.
JUNCTION BOX FOR POWER, 120 VAC, 20 AMP, SIZED BY THE ELECTRICAL ENGINEER. MOUNT AT
BUILDING STANDARD BASE ELECTRICAL HEIGHT, UON. REFER TO AV NOTES FOR ADDITIONAL
INFORMATION. (* = NUMBER OF DEDICATED CIRCUITS) / SCATOLA DI DERIVAZIONE PER
ALIMENTAZIONE ELETTRICA, 120 V CA, 20 AMP, DIMENSIONE DEFINITA DA INGEGNERE ELETTRICO.
MONTARE AD ALTEZZA STANDARD DELLE PRESE DELL’EDIFICIO, UON. PER ULTERIORI
INFORMAZIONI CONSULTARE LE NOTE AV. (* = NUMERO DI CIRCUITI DEDICATI)
FP
RL
SC
W1
W2
J#
P
STANDARD INFORMATION OUTLET. MOUNT AT BUILDING STANDARD BASE ELECTRICAL HEIGHT, UON.
REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA INFO STANDARD. MONTARE AD ALTEZZA STANDARD DELLE PRESE DELL’EDIFICIO, UON. PER ULTERIORI
INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI DI DATI)
AUDIOVISUAL CONTROL PANEL OUTLET. REFER TO DETAIL. TRIPLE-GANG BOX WITH DOUBLE GANG REDUCTION RING AND SINGLE POE DATA DROP, UON. MOUNT AT 48" AFF, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA PANNELLO DI CONTROLLO AUDIOVISIVO.
FARE RIFERIMENTO A DETTAGLIO. SCATOLA PER TRE DISPOSITIVI CON ANELLO DI RIDUZIONE DOPPIO E CALO DATI POE SINGOLO, UON. MONTATO A 48” SU PAV FINITO, UON. PER ULTERIORI INFORMAZIONI
CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI DI DATI)
AUDIOVISUAL ROOM SCHEDULRE OUTLET. REFER TO DETAIL. DOUBLE-GANG BOX WITH SINGLE GANG REDUCTION RING AND SINGLE POE DATA DROP, UON. MOUNT AT 48" AFF, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA COME DA SCHEMA SALA AUDIOVISIVI.
FARE RIFERIMENTO A DETTAGLIO. SCATOLA PER DUE DISPOSITIVI CON ANELLO DI RIDUZIONE SINGOLO E CALO DATI POE SINGOLO, UON. MONTATO A 48” SU PAV FINITO, UON. PER ULTERIORI INFORMAZIONI
CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI DI DATI)
DATA OUTLET FOR AUDIO NETWORK. PROVIDE DROPS WITH NEUTRIK ETHERCON CHASSIS CONNECTORS.
MOUNT AT BUILDING STANDARD BASE ELECTRICAL HEIGHT, UON. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. REFER TO DETAIL. (# = NUMBER OF DATA DROPS) / PRESA DATI PER RETE AUDIO.
PREVEDERE USCITE CON CONNETTORI TELAIO ETHERCON NEUTRIK. MONTARE AD ALTEZZA STANDARD DELLE PRESE DELL’EDIFICIO, UON. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. FARE
RIFERIMENTO A DETTAGLIO. (N. = NUMERO DI CALI DI DATI)
RS232 INTERFACE FOR LIGHTING AND SHADES. MOUNT AT BUILDING STANDARD BASE OUTLET HEIGHT, UON.
REFER TO ELECTRICAL DRAWINGS FOR LIGHTING AND SHADE CONTROL SPECIFICATIONS. / INTERFACCIA
RS232 PER ILLUMINAZIONE E OSCURAMENTO. MONTARE AD ALTEZZA STANDARD DELLE PRESE
DELL’EDIFICIO, UON. FARE RIFERIMENTO AI DISEGNI ELETTRICI PER LE SPECIFICHE DI COMANDO DI
ILLUMINAZIONE E OSCURAMENTO.
CATV OUTLET WITH A SINGLE RF DROP, UON. MOUNT AT BUILDING STANDARD BASE OUTLET HEIGHT, UON.
(# = NUMBER OF CATV DROPS) / PRESA CATV CON RIDUZIONE RF SINGOLA, UON. MONTARE AD ALTEZZA
STANDARD DELLE PRESE DELL’EDIFICIO, UON. (N. = NUMERO DI USCITE DATI)
CP#
RS#
AN#
LS
TV
AUDIOVISUAL CEILING MOUNTED SYMBOLS: (SIMBOLI INSTALLAZIONE AUDIOVISIVI A
SOFFITTO:)
JUNCTION BOX, 2.5" DEEP, FOR AV RECEPTACLES SINGLE GANG, UON. FLUSH MOUNTED IN INISHED
CEILING. (# = NUMBER OF GANGS) / SCATOLA DI DERIVAZIONE, 2,5” PROF., PER PRESE AV. DISPOSITIVO SINGOLO, UON. MONTATA A FILO SU SOFFITTO FINITO. (N. = NUMERO DISPOSITIVI POSSIBILI)
JUNCTION BOX, 2.5" DEEP, PROVIDE DOUBLE-GANG BOX, UON, FOR AV RECEPTACLES. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. (# = NUMBER OF GANGS) / SCATOLA DI DERIVAZIONE, 2,5” PROF., PREVEDERE SCATOLA PER DUE DISPOSITIVI, UON, PER PRESE AV. MONTATA SU SUPERFICIE
SOPRA AL SOFFITTO FINITO. (N. = NUMERO DISPOSITIVI POSSIBILI)
SCREW COVER BOX FOR AV SIGNAL CABLE AND CONDUIT TERMINATION. SIZED BY ELECTRICAL
ENGINEER. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. / SCATOLA CON COPERCHIO AVVITATO PER TERMINAZIONE TUBO E CAVO SEGNALE AV. DIMENSIONI DEFINITE DA INGEGNERE
ELETTRICO. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO.
12" x 4", UON, CABLE TRAY. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. / 12" x 4”, UON, PASSERELLA PORTA-CAVI. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV.
LOW VOLTAGE CONTROLLER FOR PROJECTION SCREEN OR SHADE CONTROL. SUPPLIED WITH SCREEN.
SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. ACCESS PANEL TO CONTROLLER MUST BE
PROVIDED FOR MAINTENANCE. / DISPOSITIVO DI CONTROLLO BASSA TENSIONE PER COMANDO
OSCURAMENTO O SCHERMO DI PROIEZIONE. DOTATO DI SCHERMO. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. A FINI DI MANUTENZIONE, DEV’ESSERE PREVISTO UN PANNELLO DI ACCESSO AL
DISPOSITIVO DI CONTROLLO.
POWER RECEPTACLE, DUPLEX, 120 VAC, 15 AMP, UON. FLUSH MOUNTED IN FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI ALIMENTAZIONE, DUPLEX, 120 V CA, 15 AMP, UON. MONTATA A FILO SU SOFFITTO FINITO. PER ULTERIORI
INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CIRCUITI ELETTRICI DEDICATI)
POWER RECEPTACLE, QUAD, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT. FLUSH MOUNTED IN FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI ALIMENTAZIONE QUADRUPLA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP.
MONTATA A FILO SU SOFFITTO FINITO. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (N. =
NUMERO DI CIRCUITI ELETTRICI DEDICATI)
POWER RECEPTACLE, 208 VAC, SINGLE DEDICATED 30 AMP CIRCUIT. FLUSH MOUNTED IN FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. / PRESA DI ALIMENTAZIONE, 208 V CA, CIRCUITO SINGOLO DEDICATO 30 AMP. MONTATA A FILO SU SOFFITTO FINITO. PER ULTERIORI
INFORMAZIONI CONSULTARE LE NOTE AV.
POWER RECEPTACLE, DUPLEX, 120 VAC, 20 AMP, UON. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI ALIMENTAZIONE, DUPLEX, 120 V CA, 20 AMP, UON. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CIRCUITI
ELETTRICI DEDICATI)
POWER RECEPTACLE, QUAD, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DEDICATED POWER CIRCUITS) / PRESA DI ALIMENTAZIONE QUADRUPLA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. PER ULTERIORI INFORMAZIONI
CONSULTARE LE NOTE AV. (N. = NUMERO DI CIRCUITI ELETTRICI DEDICATI
JUNCTION BOX FOR POWER, 120 VAC, SINGLE DEDICATED 20 AMP CIRCUIT, SIZED BY THE ELECTRICAL
ENGINEER. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. REFER TO AV NOTES FOR
ADDITIONAL INFORMATION. (# = NUMBER OF DEDICATED POWER CIRCUITS) / SCATOLA DI DERIVAZIONE PER ALIMENTAZIONE ELETTRICA, 120 V CA, CIRCUITO SINGOLO DEDICATO 20 AMP, DIMENSIONE DEFINITA DA INGEGNERE ELETTRICO. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. PER ULTERIORI
INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CIRCUITI ELETTRICI DEDICATI)
DATA OUTLET FLUSH MOUNTED IN FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL
INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA DATI MONTATA A FILO SU SOFFITTO FINITO. PER
ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI DI DATI)
DATA OUTLET SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. REFER TO AV NOTES FOR ADDITIONAL INFORMATION. (# = NUMBER OF DATA DROPS) / PRESA DATI MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. PER ULTERIORI INFORMAZIONI CONSULTARE LE NOTE AV. (N. = NUMERO DI CALI DI
DATI)
RS232 INTERFACE FOR LIGHTING AND SHADES. SURFACE MOUNTED TO SLAB ABOVE FINISHED CEILING. / INTERFACCIA RS232 PER ILLUMINAZIONE E OSCURAMENTO. MONTATA SU SUPERFICIE SOPRA AL SOFFITTO
FINITO.
J
SC
LVC
P
LS
J
CATV OUTLET WITH A SINGLE RF DROP, UON. SURFACE MOUNTED TO SLAB ABOVE FINISHED
CEILING. (# = NUMBER OF CATV DROPS) / PRESA CATV CON RIDUZIONE RF SINGOLA, UON.
MONTATA SU SUPERFICIE SOPRA AL SOFFITTO FINITO. (N. = NUMERO DI USCITE DATI)
SPEAKER LOCATION, SINGLE ZONE, OON. SEE DETAIL. SHOWN FOR COORDINATION PURPOSES
ONLY. (* = SPEAKER ZONE) / UBICAZIONE DIFFUSORE, ZONA SINGOLA, OON. VEDI DETTAGLIO. A
MERO FINE DI COORDINAMENTO. (* = ZONA DIFFUSORE)
S1
ZONE*#
S2
TV
NOTES: (NOTE:)
SPEAKER BACK BOX TYPE 1. FLUSH MOUNTED IN FINISHED CEILING, UON. SEE DETAIL. FOR
REFERENCE ONLY. SPEAKER DRIVER SEPARATE, TO BE INSTALLED AT LATER DATE. SEE
DIVISION OF RESPONSIBILITIES. / CORPO DEL DIFFUSORE TIPO 1. MONTATA A FILO SU SOFFITTO
FINITO, UON. VEDI DETTAGLIO. SOLO PER RIFERIMENTO. DRIVER DIFFUSORE SEPARATO, DA
INSTALLARE SUCCESSIVAMENTE. VEDI SUDDIVISIONE DELLE RESPONSABILITÀ.
SPEAKER LOCATION, LOUDSPEAKER, UON. SEE DETAIL. SHOWN FOR COORDINATION PURPOSES
ONLY. / UBICAZIONE DIFFUSORE, ALTOPARLANTE, UON. VEDI DETTAGLIO. A MERO FINE DI
COORDINAMENTO.
SB1
CELING CAMERA TYPE [1] MOUNTED TO FINISHED CEILING. SEE DETAIL. / TELECAMERA A
SOFFITTO DI TIPO [1] MONTATA SU SOFFITTO FINITO. VEDI DETTAGLIO.
C1
PROJECTION SCREEN OR SHADE MOTOR. SEE DETAIL. / MOTORE OSCURAMENTO O SCHERMO DI
PROIEZIONE. VEDI DETTAGLIO.
J COORDINATION FOR CIELING MOUNTED CAMERA. / COORDINAMENTO PER TELECAMERA
MONTATA A SOFFITTO.
AUDIOVISUAL CEILING MOUNTED SYMBOLS: (SIMBOLI INSTALLAZIONE
AUDIOVISIVI A SOFFITTO:)
1.
2.
3.
4.
MINIMUM ACCEPTABLE DISTANCE BETWEEN PARALLEL AV AND POWER CONDUITS /
DISTANZA MINIMA ACCETTABILE TRA CONDOTTE DI POTENZA E AV PARALLELE
AV CONDUIT /
CONDOTTA AV
POWER
CONDUIT /
CONDOTTO
ELETTRICO
COMBINED AMPACITY OF ALL PHASE
CONDUCTORS IN POWER CONDUIT / CAPACITÀ IN AMPERE COMBINATA
DI TUTTI I CONDUTTORI DI FASE NELLA CONDOTTA DI POTENZA
UNDER
60A/MENO DI
60A
60A 120A 240A 400A
EMT EMT 2 FT. 3 FT. 4 FT. NA/ND NA/ND
EMT
RIGID
STEEL/ACCIAIO
RIGIDO
4 IN. 8 IN. 1 FT. 2 FT. 4 FT.
1 IN. 2 IN. 4 IN. 8 IN. 16 IN.
POWER AND DATA REQUIREMENTS SHOWN FOR REFERENCE ONLY AND ARE NOT FOR CONSTRUCTION.
COORDINATE WITH ELECTRICAL ENGINEER, ARCHITECT AND TELECOM DESIGNER DRAWINGS FOR
LOCATION OF ALL OUTLETS IN THIS DRAWING SET. / REQUISITI DATI E ALIMENTAZIONI INDICATI SOLO PER RIFERIMENTO E DA NON UTILIZZARE PER LA COSTRUZIONE. COORDINARE CON INGEGNERE ELETTRICO, ARCHITETTO E PROGETTISTA TELECOMUNICAZIONI L’UBICAZIONE DI TUTTE LE PRESE IN QUESTA SERIE DI
DISEGNI.
WHERE POWER CIRCUITS ARE SHOWN TERMINATING IN JUNCTION BOXES WITHOUT RECEPTACLES, THE WIRES SHALL BE TAPED AND THE BOXES COVERED. THESE CIRCUITS WILL BE CONNECTED BY OTHERS DURING INSTALLATION OF THE AV SYSTEMS EQUIPMENT. / LADDOVE I CIRCUITI DI POTENZA RISULTANO TERMINARE IN SCATOLE DI DERIVAZIONE SENZA PRESE, È NECESSARIO ISOLARE I FILI CON NASTRO E COPRIRE LA SCATOLA. QUESTI CIRCUITI SARANNO COLLEGATI AD ALTRI DURANTE L’INSTALLAZIONE DELLE
APPARECCHIATURE AV.
EMPTY CONDUIT RUNS ON THESE DRAWINGS SHOW ONLY INTERCONNECTION BETWEEN TERMINATION POINTS. THE EXACT PATH OF CONDUIT IS TO BE DETERMINED BY THE COORDINATE PATHWAYS FOR ALL
AV RELATED DEVICES WITH ARCHITECTURAL AND ELECTRICAL PLANS. / LE CONDOTTE VUOTE
RAPPRESENTATE SU QUESTI DISEGNI MOSTRANO SOLAMENTE LE INTERCONNESSIONI TRA I PUNTI TERMINALI. IL PERCORSO ESATTO DELLE CONDOTTE DEV'ESSERE DEFINITO SULLA BASE DEI PERCORSI
COORDINATI TRA TUTTI I DISPOSITIVI AV E I DISEGNI ELETTRICI ED ARCHITETTONICI.
HIGH LEVEL/HIGH CURRENT FEEDS (SUCH AS FOR POWER DISTRIBUTION PANELS, LIGHTING, AND BRANCH CIRCUITS,) ARE NOT TO BE RUN PARALLEL WITH AUDIO/VIDEO CONDUITS OR CABLING. IF HIGH LEVEL/HIGH CURRENT FEEDS MUST RUN PARALLEL TO AUDIO/VIDEO CONDUITS OR CABLING, MINIMUM SEPARATION MUST BE MAINTAINED ACCORDING TO THE FOLLOWING TABLE. "NA" INDICATES THAT THE USE SHOULD BE AVOIDED. SPACINGS ASSUME THAT POWER CONDUCTORS WILL NOT BE TWISTED PAIRS.
CLOSER SPACINGS CAN BE USED IF POWER CONDUCTORS ARE TWSITED PAIRS. / LE LINEE A LIVELLO
ELEVATO/CORRENTE ELEVATA (COME QUELLE PER I PANNELLI DI DISTRIBUZIONE ELETTRICA,
ILLUMINAZIONE E CIRCUITI DERIVATI) NON DEVONO CORRERE PARALLELAMENTE A CABLAGGI O CONDOTTE AUDIO/VIDEO. NEL CASO IN CUI LE LINEE A LIVELLO ELEVATO/CORRENTE ELEVATA DEBBANO
CORRERE PARALLELE A CABLAGGI O CONDOTTE AUDIO/VIDEO, È NECESSARIO MANTENERE UNA
SEPARAZIONE MINIMA, COME PREVISTO DALLA TABELLA SEGUENTE. “NA” INDICA CHE SE NE DOVREBBE EVITARE L’USO. LE SPAZIATURE PRESUPPONGONO CHE I CONDUTTORI DI POTENZA NON SIANO DOPPINI RITORTI. È POSSIBILE AVERE SPAZI PIÙ RISTRETTI QUANDO I CONDUTTORI DI POTENZA SONO DOPPINI
RITORTI.
RIGID
STEEL/ACCIAIO
RIGIDO
RIGID
STEEL/ACCIAIO
RIGIDO
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
1684614
07/11/22
Richard Tyler, PE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
100 AIRSIDE DRIVE
MOON TOWNSHIP, PA 15108
A V
IA
N
O A
IR
B
A S
E
A V
IA
N
O
IT
A
L Y
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
SS
IF
IE
D
FI
LE
N
AM
E:
PL
O
TT
ED
LMM / BTN
FIRE PROTECTION DPS
F
A D
A L C
O M
B A
T R
E S
C U
E H
E
LI
C O
P T
R
IM
U
LA
T
O R
F A
C
IL
IT
Y
P
2)
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N O
R F
O L
K , V
A A
T
LA
N T
IC
D
E S
IG
N
A N
D C
O N
S T
R U
C T
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
TE
M
S C
O M
M A
N D
A T
LA
N
TI
C
DRAWFORM REVISION: 12 APRIL 2018
ISSUED FOR CONSTRUCTION – 10 MAR 2023
AS NOTED
B
IM
0:
//1
P
S im ul at or /B
LD
G
P
2-
4- T
.r vt
/8
/2
:1
4:
A M
A U
D
IO
V
IS
U A
L L
E G
E N
D
REWSHJACM
TA001
A U
D O
V
IS
IV
I
L E
G G
E N
D A
14125592
KMC
AUDIOVISUAL SHEET LIST (LISTA SCHEDE AUDIOVISIVI)
Sheet Number/Num ero Foglio Sheet Name / Nome Foglio
Approved by CDR Jonathan Horner, ROICC, via SAT-TO form
AFC AT FINISHED CEILING/A SOFFITTO
FINITO
AFF ABOVE FINISHED FLOOR/SOPRA AL
PAVIMENTO FINITO
AFP ABOVE FINISHED PLATFORM OR RAISED
FLOOR/SOPRA ALLA PIATTAFORMA
FINITA O PAVIMENTO SOPRAELEVATO
AS ABOVE SLAB / SOPRA A LASTRA
ATS ABOVE TABLE SURFACE/SOPRA A
SUPERFICIE DEL TAVOLO
AV AUDIOVISUAL / AUDIOVISIVO
CLG CEILING / SOFFITTO
EMT
FP FLAT PANEL / PANNELLO PIATTO
GND GROUND / TERRA
ID INSIDE DIAMETER / DIAMETRO INTERNO
IDF INTERMEDIATE DISTRIBUTION FRAME /
QUADRO DISTRIBUZIONE INTERMEDIO
LAN LOCAL AREA NETWORK / RETE LOCALE
MAX MAXIMUM / MASSIMO
MDF MAIN DISTRIBUTION FRAME / QUADRO DISTRIBUZIONE PRINCIPALE
MIN MINIMUM / MINIMO
MM MULTIMODE / MULTIMODO
MTD MOUNTED / MONTATO
MTER MAIN TELECOMMUNICATIONS EQUIPMENT ROOM /
SALA APPARECCHIATURE DI TELECOMMUNICAZIONE PRINCIPALI
NIC NOT IN CONTRACT / ESCLUSO DALL'APPALTO
NTS NOT TO SCALE / NON IN SCALA
OD OUTSIDE DIAMETER / DIAMETRO ESTERNO
OFE OWNER FURNISHED EQUIPMENT /
ATTREZZATURE FORNITE DAL PROPRIETARIO
OSP OUTSIDE PLANT / INOIANTO ESTERNO
PB PULLBOX / CASSETTA PULLBOX
SM SINGLE MODE / MODO SINGOLO
ST STRAND / FILO
STP SHIELDED TWISTED PAIR /
DOPPINO SCHERMATO
TBD TO BE DETERMINED / DA DEFINIRE
TEMP TEMPORARY / TEMPORANEO
TGB TELECOMMUNICATIONS
GROUND BAR / BARRA DI MESSA
A TERRA DELLE
TELECOMUNICAZIONI
TR TELECOMMUNICATIONS ROOM /
SALA TELECOMUNICAZIONI
TSER TELECOMMUNICATIONS
SERVICE ENTRANCE ROOM/SALA
INGRESSO SERVIZIO
TELECOMUNICAZIONI
TYP TYPICAL / TIPICO
UON UNLESS OTHERWISE NOTED/SE
NON SCHERMATO
UPS UNINTERRUPTIBLE POWER
SUPPLY/GRUPPO DI CONTINUITÁ
UTP UNSHIELDED TWISTED
PAIR/DOPPINO NON SCHERMATO
VIF VERIFY IN FIELD/VERIFICA IN
CAMPO
VOIP VOICE OVER INTERNET PROTOCOL
/VOCE DA PROTOCOLLO INTERNET
WAN WIDE AREA NETWORK / RETE AD
AMPIA AREA
WAP WIRELESS ACCESS POINT / PUNTO
DI ACCESSO WIRELESS
WP WATERPROOF / IMPERMEABILE
WW WIREWAY / CANALINA
SCOPE OF WORK (PORTATA DEL LAVORO)
FURNISH/
FORNITURA
INSTALL/
INSTALLAZI
ONE
IN-WALL BLOCKING SUPPORT FOR AV MOUNTS/SUPPORTO DI
BLOCCO NELLA PARETE PER SISTEMI DI MONTAGGIO AV
GC
MOTORIZED PROJECTION SCREENS/SCHERMI DI PROIEZIONE
MOTORIZZATI
AV
FURNITURE CUTOUTS FOR AV EQUIPMENT (UNLESS PROVIDED BY
FURNITURE PROVIDER)/INTAGLI NEGLI ARREDI PER
APPARECCHIATURE AV (SE NON REALIZZATI DAL FORNITORE DEGLI
ARREDI)
MOTORIZED LIFTS/SOLLEVATORI MOTORIZZATI EC
UNISTRUT AND/OR BLACK IRON AS REQ'D FOR CEILING MOUNTED
AV DEVICES/PROFILI UNISTRUT E/O IN FERRO NERO, COME
RICHIESTO PER I DISPOSITIVI AV MONTATI A SOFFITTO
CABLE CONTAINMENT INCLUDING:/CONTENIMENTO CAVI,
COMPRESO QUANTO SEGUE:
- CONDUIT WITH MEASURED PULLSTRINGS, CABLETRAY,
LADDERTRAY, WIREWAYS, JUNCTION BOXES, PULL BOXES, AND
BACKBOXES. / CONDOTTA CON CORDICELLE, PASSERELLE CAVI,
PASSERELLE A SCALA, CANALINE, SCATOLE DI DERIVAZIONE,
CASSETTE PULLBOX E BACKBOX MISURATE.
- FLOOR BOXES (COORDINATED WITH AV/TC/EC)/SCATOLE A
PAVIMENTO (COORDINATE CON AV/TC/EC)
POWER OUTLETS / PRESE DI ALIMENTAZIONE
AV CABLING (LOW VOLTAGE) / CABLAGGI AV (BASSA TENSIONE)
AV DEVICE POWER / ALIMENTAZIONE DISPOSITIVI AV
CUSTOM ENGRAVED AV COVER PLATES / COPERCHI AV CON
INCISIONI PERSONALIZZATE
VOICE/DATA NETWORK CABLING (FIBER AND TWISTED PAIR) - FOR
AV DEVICES / CABLAGGI RETE DATI/VOCE (DOPPINI E FIBRA) - PER
DISPOSITIVI AV
ALL CABLE INSTALLATION, TERMINATION AND TESTING SHALL BE IN ACCORDANCE.
REFER TO AV DETAIL SHEETS FOR ADDITIONAL SCOPE DELINEATION AND INFORMATION.
* EC OR AV DEPENDING ON LINE VOLTAGE LEVEL
TUTTE LE INSTALLAZIONI, TERMINAZIONI E TEST DEI CAVI DEVONO ESSERE CONFORMI. FARE RIFERIMENTO ALLE
SCHEDE DI DETTAGLIO AV PER ULTERIORI DEFINIZIONI E INFORMAZIONI SULLA PORTATA.
* EC O AV, A SECONDA DEL LIVELLO DI TENSIONE SULLA LINEA
DEFINITION OF TERMS / DEFINIZIONE DEI TERMINI
LEGEND FOR SCOPE OF WORK BETWEEN TRADES:
LEGENDA DELLA PORTATA DEL LAVORO TRA I SOGGETTI COINVOLTI:
GC = GENERAL CONTRACTOR (APPALTATORE GENERALE)
EC = ELECTRICAL CONTRACTOR (APPALTATORE ELETTRICO)
AV = AUDIOVISUAL CONTRACTOR (APPALTATORE AUDIOVISIVI)
O = OWNER (PROPRIETARIO)
ST = STRUCTURED CABLING, OR TELECOMMUNICATIONS CONTRACTOR (CABLAGGIO
STRUTTURATO, O APPALTATORE TELECOMUNICAZIONI)
FURNISH - TO PURCHASE AND DELIVER TO THE PROJECT SITE COMPLETE WITH EVERY NECESSARY APPURTENANCE AND SUPPORT. PURCHASING SHALL INCLUDE PAYMENT OF ALL SALES TAXES AND OTHER SURCHARGES AS MAY BE REQUIRED TO ASSURE THAT PURCHASED ITEMS ARE FREE OF ALL LIENS. CLAIMS, OR ENCUMBRANCES.
FORNITURA - ACQUISTARE E CONSEGNARE AL SITO DEL PROGETTO, INSIEME A TUTTI GLI ACCESSORI E I SUPPORTI NECESSARI. L’ACQUISTO DEVE INCLUDERE IL PAGAMENTO DI TUTTE LE IMPOSTE DI VENDITA E ALTRI SUPPLEMENTI NECESSARI A GARANTIRE CHE TUTTI GLI ARTICOLI ACQUISTATI SIANO LIBERI DA VINCOLI, RIVENDICAZIONI O GRAVAMI.
INSTALL - TO UNLOAD AT THE DELIVERY POINT AT THE SITE AND PERFORM EVERY OPERATION NECESSARY TO ESTABLISH SECURE MOUNTING AND CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT, ALL AS
PART OF THE WORK.
INSTALLAZIONE - SCARICARE AL PUNTO DI CONSEGNA SUL SITO ED ESEGUIRE LE OPERAZIONI NECESSARIE PER IL MONTAGGIO SICURO E IL CORRETTO FUNZIONAMENTO ALLA GIUSTA UBICAZIONE PREVISTA DAL PROGETTO, IL TUTTO NELL’AMBITO DEL LAVORO.
PROVIDE - TO FURNISH AND INSTALL
PREVEDERE - FORNIRE E INSTALLARE
ABBREVIATIONS: (ABBREVIAZIONI:) SCOPE OF WORK BETWEEN TRADES: (PORTATA DEL LAVORO TRA I SOGGETTI
COINVOLTI:)
EC
ELECTRICAL METALLIC TUBING (WITH
PULL STRING) / TUBATURA METALLICA
ELETTRICA (CON CORDICELLA)
EMPTY CONDUIT / CONDOTTO
GC
AV
GC
EC
EC
DEDICATED DISTRUBTION PANELS AND DIMMERS
PANNELLI DI DISTRIBUZIONE DEDICATI E REGOLATORI
AV DEVICE WALL MOUNTS / SISTEMI DI MONTAGGIO A PARETE
DISPOSITIVI AV
EC EC
EC EC
AV AV
EC EC
AV EC/AV*
AV EC
ST ST
AV DEVICES (AS DESCRIBED IN THE AV BID DOCUMENTS)
DISPOSITIVI AV (COME DESCRITTI NEI DOCUMENTI DI OFFERTA AV)
AV EC/AV*
A AMPERES / AMPERE
AC ABOVE COUNTER/SOPRA A PIANO DI
LAVORO
AWG AMERICAN WIRE GAGE/MISURA CAVO
AMERICANA
C CONDUIT / CONDOTTA
CAT-3 TIA/EIA CATEGORY 3 RATED
CLASSIFICATO CATEGORIA 3 TIA/EIA
CAT-5E TIA/EIA CATEGORY 5 E RATED
CLASSIFICATO CATEGORIA 5 E TIA/EIA
CAT-6A TIA/EIA CATEGORY 6A RATED
CLASSIFICATO CATEGORIA 6A TIA/EIA
CAT-6E TIA/EIA CATEGORY 6 E RATED
CLASSIFICATO CATEGORIA 6 E TIA/EIA
CB CEILING BOX / SCATOLA A SOFFITTO
CCTV CLOSED CIRCUIT TELEVISION /
TELEVISIONE A CIRCUITO CHIUSO
CKT CIRCUIT / CIRCUITO
COAX COAXIAL CABLE /CAVO COASSIALE
CL CENTER LINE / LINEA CENTRALE
COND CONDUCTOR / CONDUTTORE
EM EMERGENCY / EMERGENZA
CP CONSOLIDATION POINT /
PUNTO DI CONSOLIDAMENTO
CU COPPER / RAME
DVR DIGITAL VIDEO RECORDER /
REGISTRATORE VIDEO DIGITALE
DWG DRAWING / DISEGNO
EC CONDUCTOR / CONDUTTORE
EX EXISTING / PREESISTENTE
F/UTP
FOILED/UNSHIELDED TWISTED PAIR /
DOPPINO NON SCHERAMATO/FODERATO
VP VAPOR PROOF /IMPERMEABILE
AL VAPORE
W WATTS / WATT
WM WIRE MANAGEMENT/GESTIONE
CAVI
WS WORKSTATION / POSTAZIONE DI
LAVORO
WT WATER TIGHT / A TENUTA
STAGNA
XFRM TRANSFORMER /
TRASFORMATORE
TV TELEVISION / TELEVISIONE
VA VOLT/AMPERS /VOLT/AMPERE
VM VOLTMETER / VOLTMETRO
TS TAMPER SWITCH / INTERRUTTORE
DI ARRESTO
SP SPEAKER / DIFFUSORE
SB SPEAKER BACK BOX / CORPO
DEL DIFFUSORE
PR PAIR / PAIO/COPPIA
PNL PANEL / PANNELLO
POE POWER OVER ETHERNET / POWER OVER ETHERNET
PRJ PROJECTOR / PROIETTORE
PTZ PAN/TILT/ZOOM / PANORAMICA, INCLINAZIONE, ZOOM
RM ROOM / LOCALE/SALA
RW RACEWAY / PISTA
SC SCREW COVER BOX / SCATOLA
CON COPERCHIO AVVITATO
PBX PRIVATE BRANCH EXCHANGE / CENTRALINO PRIVATO
PP PATCH PANEL / PANNELLO PATCH
PA PUBLIC ADDRESS / INDIRIZZO PUBBLICO
NO NORMALLY OPEN / NORMALMENTE APERTO
NO. NUMBER / NUMERO
NID NETWORK INTERFACE DEVICE / DISPOSITIVO DI INTERFACCIA DI RETE
N NEUTRAL / NEUTRO
NC NORMALLY CLOSED / NORMALMENTE CHIUSO
MH MANHOLE / POZZETTO
MER MECHANICAL EQUIPMENT ROOM /
LOCALE APPARECCHIATURE MECCANICHE
MC MAIN CROSS CONNECT/CENTRO STELLA DI COMPRENSORIO
MIC MICROPHONE / MICROFONO
LV LOW VOLTAGE / BASSA TENSIONE
HC HUNG CEILING / SOFFITTO SOSPESO
HZ HERTZ / HERTZ
FA FIRE ALARM / ALLARME ANTINCENDIO
FACP FIRE ALARM CONTROL PANEL /
PANNELLO DI CONTROLLO ALLARME ANTINCENDIO
FB FLOOR BOX / SCATOLA A PAVIMENTO
FO FIBER OPTIC / FIBRA OTTICA
EC
SPECIFY/
SPECIFICARE
AV
AV
AV
AV/EC
AV
AV
AV
AV
AV
GC
GC
GC
EC
EC
AV
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
ALL OVERHEAD RIGGING REQUIREMENTS ARE TO BE REVIEWED AND STAMPED FOR
APPROVAL BY LICENSED STRUCTURAL ENGINEER FOR CODE AND SAFETY COMPLIANCE. /
TUTTI I REQUISITI PER GLI ELEMENTI SOSPESI DEVONO ESSERE VERIFICATI E APPROVATI
DA UN INGEGNERE STRUTTURALE CERTIFICATO IN TERMINI DI CODICE E CONFORMITÀ DI
SICUREZZA.
POWER BREAKER AND DISTRIBUTION PANELS ARE SIZED AND SPECIFIED BY THE
ELECTRICAL ENGINEER. / L’INTERRUTTORE E I PANNELLI DI DISTRIBUZIONE SONO
DIMENSIONATI E SPECIFICATI DALL’INGEGNERE ELETTRICO.
ALL CABLE TRAY THAT IS SURFACE-MOUNTED ON SLAB BELOW RAISED FLOOR OR ABOVE
EQUIPMENT RACKS SHALL BE SECURELY FASTENED AND LEFT OPEN FOR CABLE ACCESS.
/ TUTTE LE PASSERELLE PORTA-CAVI MONTATE SULLA SUPERFICIE DELLA LASTRA SOTTO
AL PAVIMENTO SOPRAELEVATO O SOPRA AI RACK DELLE APPARECCHIATURE DEVONO
ESSERE SALDAMENTE FISSATE E LASCIATE APERTE IN MODO CHE I CAVI SIANO
ACCESSIBILI.
POWER FOR AV AND RELATED SYSTEMS SHALL USE AN EIA/TIA 607 COMPLIANT
GROUNDING SYSTEM, DESIGNED BY THE ELECTRICAL ENGINEER. REFER TO AV DETAIL
SHEETS FOR ADDITIONAL GROUNDING REQUIREMENTS IF APPLICABLE. / L’ALIMENTAZIONE
ELETTRICA PER AV E RELATIVI IMPIANTI DEVE INCLUDERE UN IMPIANTO DI MESSA A TERRA
CONFORME EIA/TIA 607, PROGETTATO DALL’INGEGNERE ELETTRICO. FARE RIFERIMENTO
ALLE SCHEDE DI DETTAGLIO AV PER ULTERIORI REQUISITI DI MESSA A TERRA, LADDOVE
APPLICABILI.
ALL AV-RELATED EMPTY CONDUIT SHALL BE REAMED, CLEANED, CAPPED (WHERE
APPROPRIATE), TAGGED, AND FURNISHED WITH PULL WIRES. / TUTTE LE CONDOTTE
VUOTE RELATIVE ALL’AV DEVONO ESSERE RIPULITE E TAPPATE (LADDOVE APPROPRIATO),
ETICHETTATE E DOTATE DI FUNE.
WHERE EXACT DIMENSIONS ARE NOT INDICATED, THE SCALE OF THIS DRAWING IS
SUFFICIENTLY ACCURATE FOR DETERMINING THE LOCATION OF EQUIPMENT, JUNCTION
BOXES, OUTLET BOXES, WIREWAYS, PANELS, ETC. WHERE EXACT DIMENSIONS ARE
INDICATED, THE REFERENCE SURFACE SHALL BE THE FINAL FINISHED SURFACE INCLUDING
ANY ACOUSTICAL TREATMENT. ROOM DIMENSIONS ON THE DRAWINGS HAVE BEEN TAKEN
FROM PRELIMINARY ARCHITECTURAL DRAWINGS. ALL DIMENSIONS MUST BE VERIFIED
AND ANY DEVIATIONS CAUSING CHANGES MUST BE COORDINATED WITH AECOM. /
LADDOVE LE DIMENSIONI ESATTE NON SIANO INDICATE, LA SCALA DI QUESTO DISEGNO È
SUFFICIENTEMENTE PRECISA DA POTER DETERMINARE L’UBICAZIONE DI
APPARECCHIATURE, SCATOLE DI DERIVAZIONE, CASSETTE CON PRESE, CANALINE,
PANNELLI, ECC. SE LE DIMENSIONI ESATTE SONO INDICATE, LA SUPERFICIE DI RIFERIMENTO
DEV'ESSERE LA SUPERFICIE FINITA, EVENTUALI TRATTAMENTI ACUSTICI COMPRESI. LE
DIMENSIONI DELLA SALA SUI DISEGNI SONO TRATTE DAI DISEGNI ARCHITETTONICI
PRELIMINARI. TUTTE LE MISURE DEVONO ESSERE VERIFICATE ED EVENTUALI DIFFERENZE
CHE COMPORTANO MODIFICHE DEVONO ESSERE ACCORDATE CON AECOM.
NOTIFY OWNER'S REPRESENTATIVES OF ANY DISCREPANCIES BETWEEN THE EXISTING
CONDITIONS AND THE AV DRAWINGS. OBTAIN CLARIFICATION BEFORE PROCEEDING WITH
WORK. / COMUNICARE AI RAPPRESENTANTI DEL PROPRIETARIO EVENTUALI DISCREPANZE
TRA LE CONDIZIONI ESISTENTI E I DISEGNI AV. ATTENDERE CHIARIMENTI PRIMA DI
PROCEDERE CON I LAVORI.
ALL AV DEVICES SHALL BE SECURELY MOUNTED PLUMB AND STRAIGHT TO WALLS,
FLOORS, OR RACKS PER THE MANUFACTURER'S RECOMMENDED MOUNTING PRACTICE. /
TUTTI I DISPOSITIVI AV DEVONO ESSERE CORRETTAMENTE MONTATI A PIOMBO E DRITTI
RISPETTO A PARETI, PAVIMENTI O RACK, COME DA PRATICA DI MONTAGGIO
RACCOMANDATA DAL PRODUTTORE.
THERE SHALL BE A MINIMUM OF ONE PULL BOX FOR EVERY 100' OF STRAIGHT EMPTY AV-
RELATED CONDUIT AND ONE PULL BOX WHERE THERE ARE MORE THAN TWO 90° BENDS
OR LESSER BENDS TOTALING 180° IN A CONDUIT RUN. / È NECESSARIO PREDISPORRE
ALMENO UNA CASSETTA PULLBOX OGNI 100’ DI CONDOTTA VUOTA DRITTA PER L’IMPIANTO
AV E UNA CASSETTA PULLBOX SE SONO PRESENTI PIÙ DI DUE CURVE A 90° O CURVE
MINORI PER UN TOTALE DI 180° NELLO STESSO PERCORSO DELLA CONDOTTA.
MAINTAIN MINIMUM BEND RADIUS OF 10X OD FOR ALL AV-RELATED CONDUITS. / TENERE
UN RAGGIO DI CURVATURA MIN DI 10X D.E. PER TUTTE LE CONDOTTE DELL’IMPIANTO AV.
LIGHTING DESIGNER TO PROVIDE LIGHTING ON A SEPARATE DIMMING ZONE (OR SWITCH IF
NO DIMMING) AT THE SCREEN/DISPLAY DEVICE TO ENSURE GOOD CONTRAST AND IMAGE
SHARPNESS. / IL PROGETTISTA DELL’ILLUMINAZIONE DEVE PREVEDERE L’ILLUMINAZIONE IN
UNA DIVERSA ZONA IN CUI LA LUCE VIENE ABBASSATA (O UN INTERRUTTORE IN CASO DI
MANCANZA DI REGOLAZIONE) NEI PRESSI DEL DISPOSITIVO DI VISUALIZZAZIONE/SCHERMO
PER GARANTIRE UN BUON CONTRASTO E LA NITIDEZZA DELL’IMMAGINE.
AV CONTRACTOR SHALL RESTORE CEILINGS, WALLS AND ANY OTHER SURFACES
AFFECTED BY THEIR WORK PRIOR TO COMPLETION OF WORK WITH LIKE MATERIALS TO
MATCH EXISTING CONSTRUCTION. / L’APPALTATORE DELL’AV È TENUTO A RIPRISTINARE
SOFFITTI, PARETI E ALTRE SUPERFICI ALTERATE DAL SUO LAVORO PRIMA DI CONCLUDERE
IL SUO INTERVENTO, UTILIZZANDO MATERIALI SIMILI A QUELLI DELLA COSTRUZIONE
ESISTENTE.
REFER TO AV ELECTRICAL PLANS AND/OR RISER DIAGRAMS FOR EMPTY CONDUIT SIZING.
/ FARE RIFERIMENTO AI DISEGNI ELETTRICI E/O AI DIAGRAMMI DELLA COLONNA MONTANTE
DELL’AV PER IL DIMENSIONAMENTO DELLE CONDOTTE VUOTE.
ALL POWER CIRCUITS INDICATED IN THIS DRAWING SET TO BE PROVIDED BY DEDICATED
BREAKER PANEL(S). NO NON-AV CIRCUITS TO BE FED FROM DEDICATED AV BREAKER
PANEL(S). / TUTTI I CIRCUITI ELETTRICI INDICATI IN QUESTA SERIE DI DISEGNI DEVONO
ESSERE DOTATI DI PANNELLO/I CON INTERRUTTORI DEDICATO/I. NESSUN CIRCUITO NON
APPARTENENTE ALL’AV DOVRÀ ESSERE ALIMENTATO DA QUESTO/I PANNELLO/I DI
INTERRUTTORI DEDICATO/I.
POWER FOR ALL AV SERVICES IN EACH DESIGNATED SPACE SHALL BE ON THE SAME
ELECTRICAL PHASE, AND THIS PHASE SHALL NOT INCLUDE MOTORS, APPLIANCES, OR
ANY OTHER SOURCE THAT CAN CAUSE SIGNAL INTERFERENCE. / L’ALIMENTAZIONE
ELETTRICA PER TUTTI I SERVIZI AV IN CIASCUNO SPAZIO DESIGNATO DOVRÀ ESSERE
SULLA STESSA FASE E SU TALE FASE NON DOVRANNO ESSERCI MOTORI,
APPARECCHIATURE O ALTRE POTENZIALI FONTI DI INTERFERENZE PER I SEGNALI.
GROUNDING: GROUND COMMUNICATIONS SYSTEMS AND EQUIPMENT IN ACCORDANCE
WITH ANSI/TIA/EIA-807 GROUNDING STANDARDS AND APPLICABLE NEC REQUIREMENTS
EXCEPT WHERE DRAWINGS OR SPECIFICATIONS EXCEED NEC REQUIREMENTS. ALL
RACKS, METALLIC BACKBOARDS, CABLE SHEATHS, CABLE TRAYS, ETC. ENTERING OR
RESIDING IN TECHNICAL EQUIPMENT SPACES SHALL BE GROUNDED TO THEIR
RESPECTIVE GROUND SYSTEM USING A MINIMUM OF #6 AWG STRANDED COPPER
BONDING CONDUCTOR AND COMPRESSOR CONNECTORS. ALL WIRES USED FOR
TECHNICAL POWER SYSTEMS OR IDENTIFIED AT EACH TERMINATION POINT WITH A WRAP
OF GREEN TAPE. ALL CABLES AND BUS BARS SHALL BE IDENTIFIED AND LABELED TAPE.
ALL CABLES AND BUS BARS SHALL BE IDENTIFIED AND LABELED "TECHNICAL POWER
SYSTEM GROUND". / MESSA A TERRA: COLLEGARE A TERRA GLI IMPIANTI E LE
APPARECCHIATURE DI COMUNICAZIONE COME PREVISTO DALLE NORME PER LA MESSA A
TERRA ANSI/TIA/EIA-807 E DAI REQUISITI NEC APPLICABILI, SALVO IL CASO IN CUI I DISEGNI
O LE SPECIFICHE SUPERINO I REQUISITI NEC. TUTTI I RACK, PANNELLI POSTERIORI
METALLICI, GUAINE DEI CAVI, PASSERELLE PORTA-CAVI, ECC. L’INGRESSO O LA
PERMANENZA NEI LOCALI DELLE APPARECCHIATURE TECNICHE DEVE PREVEDERE LA
MESSA A TERRA CON IL RELATIVO IMPIANTO, UTILIZZANDO ALMENO 6 CONDUTTORI A
TREFOLI IN RAME AWG E CONNETTORI A COMPRESSIONE. TUTTI I FILI IMPIEGATI PER GLI
IMPIANTI DI POTENZA TECNICI SONO IDENTIFICATI A OGNI PUNTO TERMINALE CON UN
GIRO DI NASTRO VERDE. TUTTI I CAVI E LE BLINDOSBARRE DEVONO ESSERE IDENTIFICATI
ED ETICHETTATI “MESSA A TERRA IMPIANTO DI POTENZA TECNICO”.
CONDUIT STUBS: PROVIDE NYLON BUSHING ON ALL CONDUIT STUBS AND NON-
TERMINATING CONDUIT ENDS TO PROTECT WIRE PULLS. / TRONCHI DI LINEA CONDOTTA:
PREVEDERE BOCCOLE IN NYLON SU TUTTI I TRONCHI DI LINEA DELLE CONDOTTE E LE
ESTREMITÀ SENZA MORSETTO TERMINALE A FINI DI PROTEZIONE.
JUNCTION BOX COVERS: UNLESS OTHERWISE NOTED, ALL JUNCTION BOXES MUST BE
PROVIDED WITH A COVER. WHERE RAISED DEVICE COVERS ARE SPECIFIED, MATCH
COVER DEPTH TO WALL THICKNESS. WHERE JUNCTION BOXES ARE MOUNTED AT OR
ABOVE FINISHED CEILING HEIGHT, INSTALL JUNCTION BOXES WITH OPEN SIDE FACING
DOWN. / COPERCHI SCATOLE DI DERIVAZIONE: SE NON DIVERSAMENTE INDICATO, TUTTE
LE SCATOLE DI DERIVAZIONE DEVONO ESSERE DOTATE DI COPERCHIO. LADDOVE
VENGANO RICHIESTI COPERCHI SOPRAELEVATI, FAR CORRISPONDERE LA PROFONDITÀ
DEL COPERCHIO CON LO SPESSORE DELLA PARETE. SE LE SCATOLE DI DERIVAZIONE
SONO MONTATE A LIVELLO OD OLTRE L'ALTEZZA DEL SOFFITTO FINITO, INSTALLARE
SCATOLE DI DERIVAZIONE CON IL LATO APERTO RIVOLTO VERSO IL BASSO.
POWER RECEPTICALS: TECHNICAL POWER RECEPTICALS, INCLUDING BE PROVIDED BY
THE BUIDING CONTRACTOR AND APPEAR ON THE ELECTRICAL DRAWINGS. TECHNICAL
POWER RECEPTACLES IN RELATION TO TECHNOLOGY INFRASTRUCTURE IS CRITICAL.
REFER TO THE ELECTRICAL DRAWINGS FOR COMPLETE POWER LAYOUTS AND
CIRCUITING DETAILS. / PRESE DI ALIMENTAZIONE: LE PRESE DI ALIMENTAZIONE TECNICHE
DEVONO ESSERE FORNITE DALL’APPALTATORE EDILE E RAPPRESENTATE SUI DISEGNI
ELETTRICI. LE PRESE DI ALIMENTAZIONE TECNICHE RELATIVE ALL’INFRASTRUTTURA
TECNOLOGICA SONO FONDAMENTALI. FARE RIFERIMENTO AI DISEGNI ELETTRICI PER LA
DISPOSIZIONE COMPLESSIVA DELL'ALIMENTAZIONE E I DETTAGLI DEI CIRCUITI.
NETWORK OUTLETS FOR AUDIOVISUAL SYSTEMS: ALL NETWORK OUTLETS SHALL APPEAR
ON THE NETWORK DRAWINGS. NETWORK SERVICES APPEARING ON THE AUDIOVISUAL
DRAWINGS ARE REPRESENTATIVE OF NETWORK CONNECTIVITY REQUIREMENTS IN
SUPPORT OF AUDIOVISUAL SYSTEMS, AS THE LOCATION OF NETWORK SERVICES IN
RELATION TO TECHNOLOGY INFRASTRUCTURE IS CRITICAL. REFER TO THE STRUCTURED
CABLING SYSTEM SPECIFICATIONS AND DRAWINGS FOR ADDITIONAL INFORMATION. /
PRESE DI RETE PER GLI IMPIANTI AUDIOVISIVI: TUTTE LE PRESE DI RETE DEVONO ESSERE
RAPPRESENTATE SUI DISEGNI DELLE RETI. I SERVIZI DI RETE INCLUSI NEI DISEGNI
AUDIOVISIVI SONO RAPPRESENTATIVI DEI REQUISITI DI CONNETTIVITÀ DELLA RETE IN
SOSTEGNO DEGLI IMPIANTI AUDIOVISIVI, DAL MOMENTO CHE L’UBICAZIONE DEI SERVIZI DI
RETE RELATIVI ALL’INFRASTRUTTURA TECNOLOGICA È FONDAMENTALE. FAR RIFERIMENTO
A DISEGNI E SPECIFICHE DEL SISTEMA DI CABLAGGIO STRUTTURATO PER MAGGIORI
INFORMAZIONI.
NOTES: (NOTE:)
22.
23.
24.
25.
26.
27.
28.
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
1684614
07/11/22
Richard Tyler, PE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
100 AIRSIDE DRIVE
MOON TOWNSHIP, PA 15108
A V
IA
N
O A
IR
B
A
IA
N
O
IT
A
L Y
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
SS
IF
IE
D
FI
LE
N
AM
E:
PL
O
TT
ED
LMM / BTN
FIRE PROTECTION DPS
F
A D
A L C
O M
B A
T R
E S
C U
E H
E
LI
C O
P T
U
LA
T
O R
F A
C
IL
IT
Y
P
2)
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N O
R F
O L
K , V
A A
T
LA
N T
IC
D
E S
IG
N
A N
D C
O N
S T
R U
C T
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
TE
M
S C
O M
M A
N D
A T
LA
N
TI
C
DRAWFORM REVISION: 12 APRIL 2018
ISSUED FOR CONSTRUCTION – 10 MAR 2023
AS NOTED
B
IM
0:
//1
P
S im ul at or /B
LD
G
P
2-
4- T
.r vt
/8
/2
:1
4:
A M
A U
D
IO
V
IS
U A
L L
E G
E N
D
TA002
A U
D O
V
IS
IV
I
L E
G G
E N
D A
14125593
KMC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
1684614
07/11/22
Richard Tyler, PE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
100 AIRSIDE DRIVE
MOON TOWNSHIP, PA 15108
A V
IA
N
O A
IR
B
A
IA
N
O
IT
A
L Y
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
SS
IF
IE
D
FI
LE
N
AM
E:
PL
O
TT
ED
LMM / BTN
FIRE PROTECTION DPS
F
A D
A L C
O M
B A
T R
E S
C U
E H
E
LI
C O
P T
U
LA
T
O R
F A
C
IL
IT
Y
P
2)
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N O
R F
O L
K , V
A A
T
LA
N T
IC
D
E S
IG
N
A N
D C
O N
S T
R U
C T
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
TE
M
S C
O M
M A
N D
A T
LA
N
TI
C
DRAWFORM REVISION: 12 APRIL 2018
ISSUED FOR CONSTRUCTION – 10 MAR 2023
AS NOTED
B
IM
0:
//1
P
S im ul at or /B
LD
G
P
2-
4- T
.r vt
/8
/2
:1
4:
A M
A U
D
IO
V
IS
U A
L D
E V
IC
E
S C
H E
D U
L
TA003
A U
D
IO
V
IS
IV
I
A B
A C
O D
IS
P
O S
IT
IV
I
14125594
KMC
AUDIOVISUAL DEVICE SCHEDULE/SCHEMA DISPOSITIVI AUDIOVISIVI
DEVICE ID/ID
DISPOSITIVO DESCRIPTION/DESCRIZIONE
COUNT/CONTEGG
IO
BL-01 WALL MOUNTED BLUE LIGHT SIGNAL - 24 VAC/24VDC (SEGNALE A LUCE BLU MONTATO A PARETE - 24VCA/24VDC) 3 CAM-01 PTZ CAMERA, WALL MOUNTED, 40X UHD /w ONELINK BRIDGE SYSTEM (TELECAMERA PTZ, MONTATA A PARETE, 40X UHD CON SISTEMA ONELINK BRIDGE) 1 CP-01 10" WALL MOUNT TOUCH CONTROL PANEL (PANNELLO DI CONTROLLO TATTILE MONTATO A PARETE 10") 2 CP-02 10" TABLE TOP TOUCH CONTROL PANEL (PANNELLO DI CONTROLLO TATTILE DA TAVOLO 10") 1
CRK-01 THERMOLATED TRIPLE THICK REFINED MDF FINISHING KIT (AGED CHERRY)_1.125" TOP, 1" SIDES, .50" KICK PLATE -TRADITIONAL STYLE WITH THREE .75" SMOKED PLEXI FRONT DOORS (KIT FINITURA MDF TRIPLO SPESSORE THERMOLATE (AGED CHERRY)_TOP 1.125”, LATI 1”, ZOCCOLO 50” - STILE TRADIZIONALE CON TRE SPORTELLI FRONTALI SMOKED PLEXI DA 75”)
FM-01 TV MOUNT - WALL FULL SWING / SUPPORTO TV A PARETE INCLINAZIONE REGOLABILE 1 FM-02 X-LARGE FUSION MICRO-ADJUSTABLE TILTING WALL DISPLAY MOUNT / SUPPORTO PER DISPLAY A PARETE INCLINABILE REGOLABILE FUSION XL 2
FPD-01 86" FLAT PANEL DISPLAY, 4K, IP5, NON-GLARE-DISPLAY PANNELLO PIATTO 86", 4K, IP5, ANTIRIFLESSO 1 FPD-02 98" FLAT PANEL DISPLAY, 4K, IP5, NON-GLARE-DISPLAY PANNELLO PIATTO 98", 4K, IP5, ANTIRIFLESSO 2
LEC-01 AUDIOVISUAL TECHNOLOGY LECTERN (LEGGIO TECNOLOGIA AUDIOVISIVA) 1
LED-01 4 TIME ZONE CLOCK - POWER FROM DISPLAY BACK BOX (OROLOGIO 4 FUSI ORARI - ALIMENTATO DA BACK BOX DEL DISPLAY) 3 LS-01 DISPLAY SIDE MOUNTED CUSTOM HEIGHT LOUDSPEAKER, 6 Ohms, 90W-ALTOPARLANTE ALTEZZA PERSONALIZZABILE MONTAGGIO LATERALE DISPLAY, 6 Ohm, 90 W 2 LS-02 DISPLAY SIDE MOUNTED CUSTOM HEIGHT LOUDSPEAKER, 6 Ohms, 90W-ALTOPARLANTE ALTEZZA PERSONALIZZABILE MONTAGGIO LATERALE DISPLAY, 6 Ohm, 90 W 4 MC-01 CEILING RECESSED MULTI ARRAY MICROPHONE, PoE+ (MICROFONO MULTI ARRAY INCASSATO NEL SOFFITTO, PoE+) 1
S1 CEILING RECESSED 6.5" SPEAKER, 70V, COLOR TO BE CONFIRMED (DIFFUSORE INCASSATO NEL SOFFITTO 6.5", 70V, COLORE DA CONFERMARE) 16
AUDIOVISUAL INFRASTRUCTURE DEVICE SCHEDULE/SCHEMA DISPOSITIVI INFRASTRUCTTURA AUDIOVISIVA
DEVICE ID/ID DISPOSITIVO DESCRIPTION/DESCRIZIONE COUNT/CONTEGGIO
DB-01 DISPLAY BACK BOX /W SURGE PROTECT QUAD OUTLET / BACK BOX DISPLAY CON PRESA QUADRUPLA E PROTEZIONE DA SOVRATENSIONE 1 DB-01 DISPLAY BACK BOX /W SURGE PROTECT QUAD OUTLET / BACK BOX DISPLAY CON PRESA QUADRUPLA E PROTEZIONE DA SOVRATENSIONE 1 DB-01 DISPLAY BACK BOX /W SURGE PROTECT QUAD OUTLET / BACK BOX DISPLAY CON PRESA QUADRUPLA E PROTEZIONE DA SOVRATENSIONE 1 FB-01 4-GANG FLOOR BOX WITH QUAD AC OUTLET BY ELEC. CONTRACTOR / SCATOLA A PAVIMENTO PER QUATTRO DISPOSITIVI CON PRESA CA QUADRUPLA DA APPALTATORE ELETTRICO 1 FB-01 4-GANG FLOOR BOX WITH QUAD AC OUTLET BY ELEC. CONTRACTOR / SCATOLA A PAVIMENTO PER QUATTRO DISPOSITIVI CON PRESA CA QUADRUPLA DA APPALTATORE ELETTRICO 1 JB-01 WALL RECESSED SINGLE GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER UN DISPOSITIVO INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-01 WALL RECESSED SINGLE GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER UN DISPOSITIVO INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-01 WALL RECESSED SINGLE GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER UN DISPOSITIVO INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-02 WALL RECESSED TWO GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER DUE DISPOSITIVI INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-02 WALL RECESSED TWO GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER DUE DISPOSITIVI INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-02 WALL RECESSED TWO GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER DUE DISPOSITIVI INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-02 WALL RECESSED TWO GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER DUE DISPOSITIVI INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-02 WALL RECESSED TWO GANG JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE PER DUE DISPOSITIVI INCASSATA A MURO DA APPALTATORE ELETTRICO. 1 JB-03 SLAB MOUNTED JUNCTION BOX BY ELEC. CONTRACTOR / SCATOLA DI DERIVAZIONE MONTATA SU PANNELLO DA APPALTATORE ELETTRICO 1 SC-01 PROVIDED BY ELECTRICAL CONTRACTOR AV PULL BOX, SIZE DETERMINED BY ELEC. CONTRACTOR / FORNITO DA APPALTATORE ELETTRICO PULL BOX AV, MISURA DEFINITA DA APPALTATORE ELETTRICO 1 SC-01 PROVIDED BY ELECTRICAL CONTRACTOR AV PULL BOX, SIZE DETERMINED BY ELEC. CONTRACTOR / FORNITO DA APPALTATORE ELETTRICO PULL BOX AV, MISURA DEFINITA DA APPALTATORE ELETTRICO 1
DN
DN
DN
OFT SIMULATOR BAY /
BAIA SIMULATORE OFT
COMPUTER / IG /
COMPUTER /IG
SIMULATOR MX / TOOL
STORAGE / ICS SUPPORT /
SIMULATORE MX /
MAGAZZINO STRUMENTI /
SUPPORTO ICS
074 MULTI-PURPOSE ROOM B /
SALA MULTIFUNZIONE B
MULTI-PURPOSE ROOM A /
SALA MULTIFUNZIONE A
MISSION PLANNING /
LIBRARY /
PIANIFICAZIONE MISSIONE
/ BIBLIOTECA
SPARES STORAGE ROOM /
LOCALE STOCCAGGIO
RICAMBI
TA401
TA401
TA403
TA403
SCALE: SCALE:
PLAN
NORTH
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
1684614
07/11/22
Richard Tyler, PE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
100 AIRSIDE DRIVE
MOON TOWNSHIP, PA 15108
A V
IA
N
O A
IR
B
A
IA
N
O
IT
A
L Y
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
SS
IF
IE
D
FI
LE
N
AM
E:
PL
O
TT
ED
LMM / BTN
FIRE PROTECTION DPS
F
A D
A L C
O M
B A
T R
E S
C U
E H
E
LI
C O
P T
U
LA
T
O R
F A
C
IL
IT
Y
P
2)
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N O
R F
O L
K , V
A A
T
LA
N T
IC
D
E S
IG
N
A N
D C
O N
S T
R U
C T
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
TE
M
S C
O M
M A
N D
A T
LA
N
TI
C
DRAWFORM REVISION: 12 APRIL 2018
ISSUED FOR CONSTRUCTION – 10 MAR 2023
GRAPHIC SCALE
SCALA GRAFICA
NORTH
NORD AS NOTED
B
IM
0:
//1
P
S im ul at or /B
LD
G
P
2-
4- T
.r vt
/8
/2
:1
4:
A M
A U
D
IO
V
IS
U A
L
G R
O U
N D
F L
O O
R P
L A
N
TA110
A U
D
IO
V
IS
IV
I
P
IA
N
T A
P
IA
N O
T E
R R
A
14125595
KMC
SCALE: 1 : 100
AUDIOVISUAL - FIRST FLOOR PLAN / AUDIOVISIVI - PLANIMETRIA PRIMO PIANO
A1
SCALE:1:100
2 mmM 4 mmM 8 mmM
1 SEE SHEET T-001 FOR TELECOMMUNICATIONS NOTES, SYMBOLS, AND
ABBREVIATIONS. / VEDI SCHEDA T-001 PER LE NOTE DI
TELECOMUNICAZIONE, SIMBOLI E ABBREVIAZIONI.
OFT SIMULATOR BAY /
BAIA SIMULATORE OFT
SIMULATOR MX / TOOL
STORAGE / ICS SUPPORT /
SIMULATORE MX /
MAGAZZINO STRUMENTI /
SUPPORTO ICS
COMPUTER / IG /
COMPUTER /IG
MULTI-PURPOSE ROOM B /
SALA MULTIFUNZIONE B
MULTI-PURPOSE ROOM A /
SALA MULTIFUNZIONE A
SPARES STORAGE ROOM /
LOCALE STOCCAGGIO
RICAMBI
MISSION PLANNING /
LIBRARY /
PIANIFICAZIONE MISSIONE
/ BIBLIOTECA
TA401
TA401
TA403
TA403
SCALE: SCALE:
PLAN
NORTH
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
1684614
07/11/22
Richard Tyler, PE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
100 AIRSIDE DRIVE
MOON TOWNSHIP, PA 15108
A V
IA
N
O A
IR
B
A
IA
N
O
IT
A
L Y
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
SS
IF
IE
D
FI
LE
N
AM
E:
PL
O
TT
ED
LMM / BTN
FIRE PROTECTION DPS
F
A D
A L C
O M
B A
T R
E S
C U
E H
E
LI
C O
P T
U
LA
T
O R
F A
C
IL
IT
Y
P
2)
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
N O
R F
O L
K , V
A A
T
LA
N T
IC
D
E S
IG
N
A N
D C
O N
S T
R U
C T
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
TE
M
S C
O M
M A
N D
A T
LA
N
TI
C
DRAWFORM REVISION: 12 APRIL 2018
ISSUED FOR CONSTRUCTION – 10 MAR 2023
GRAPHIC SCALE
SCALA GRAFICA
NORTH
NORD AS NOTED
B
IM
0:
//1
P
S im ul at or /B
LD
G
P
2-
4- T
.r vt
/8
/2
:1
4:
A M
A U
D
IO
V
IS
U A
L
G R
O U
N D
F L
O O
R R
C P
TA210
A U
D
IO
V
IS
IV
I
P
IA
N
T A
P
IA
N O
T E
R R
A C
O N
T R
O S
O F
F
IT
T I
14125596
KMC
SCALE: 1 : 100
AUDIOCISUAL - FIRST FLOOR RCP /…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .