Attachment K - 1684614dwg2of16.pdf

PDF 1 MB Posted

Attached to
P242 Combat Rescue Helicopter Simulator Facility Federal contract opportunity
Solicitation number
N6247023R0003
Issued by
Department of the Navy Naval Facilities Engineering Command

View the file

Other files for this federal contract opportunity

Other files attached to P242 Combat Rescue Helicopter Simulator Facility, newest first.
File Type Posted
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Attachment K - Civil Drawings - Addendum1_REVISED.pdf PDF
Attachment K - Architecture Drawings - Addendum1_REVISED.pdf PDF
Amendment 0003.pdf PDF
Attachment N -B7300.pdf PDF
Attachment M - Safety and Coordination Plan_ITALIAN.pdf PDF
Attachment L - Safety and Coordination Plan_ENGLISH.pdf PDF
Amendment 0002.pdf PDF
P242 Amendment 0001.pdf PDF
Attachment K - 1684614dwg12of16.pdf PDF
Attachment I - INSTALLATION ACCESS REQUEST.pdf PDF
Attachment F - LRA Commercial Vehicle Inspection Procedures.pdf PDF
P242 Solicitation.pdf PDF
Attachment K - 1684614dwg9of16.pdf PDF
Attachment K - 1684614dwg6of16.pdf PDF
Attachment K - 1684614dwg7of16.pdf PDF
Attachment K - 1684614dwg16of16.pdf PDF
Attachment K - 1684614dwg15of16.pdf PDF
Attachment A - Pre-Proposal Inquiry Form.xls XLS spreadsheet
Attachment K - 1684614dwg4of16.pdf PDF
Attachment K - 1684614dwg8of16.pdf PDF
Attachment K - 1684614dwg14of16.pdf PDF
Attachment K - 1684614dwg11of16.pdf PDF
Attachment K - 1684614dwg1of16.pdf PDF
Attachment B - SEC-NAV_5512_1_11787 Form.pdf PDF
Attachment E - Price Proposal Form.pdf PDF
Attachment C - Construction Experience Project Data Sheet (1).pdf PDF
Attachment J -Specifications.pdf PDF
Attachment K - 1684614dwg5of16.pdf PDF
Attachment K - 1684614dwg13of16.pdf PDF
Attachment K - 1684614dwg10of16.pdf PDF
Attachment K - 1684614dwg3of16.pdf PDF
Attachment D - Past Performance Questionnaire (PPQ).pdf PDF
Attachment H - Informazione Antimafia.pdf PDF
Attachment G - Comunicazione Antimafia.pdf PDF
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. PROJECT NAME, P-242 ADAL COMBAT RESCUE HELICOPTER SIMULATOR FACILITY, AVIANO AIR BASE, ITALY.

2. PROJECT DESCRIPTION

THE FACILITY IS A ONE STORY ADAL COMBAT RESCUE HELICOPTER SIMULATOR FACILITY.

THE FACILITY HAS BEEN ANALYZED FOR LIFE SAFETY AND FIRE PROTECTION REQUIREMENTS USING THE CODES AND STANDARDS LISTED BELOW. THE UNIFIED FACILITIES CRITERIA (UFC), WHICH PROVIDES TECHNICAL CRITERIA FOR NEW AND RENOVATED MILITARY CONSTRUCTION, APPLIES TO THE MILITARY DEPARTMENTS, THE DEFENSE AGENCIES, AND THE DOD FIELD ACTIVITIES.

BASED ON UFC 1-200-01 CHAPTER 2 - MODIFICATIONS TO THE INTERNATIONAL BUILDING CODE (IBC) AND UFC 3-600-01, THE IBC WILL BE USED FOR FIRE RESISTANCE REQUIREMENTS, ALLOWABLE FLOOR AREA, BUILDING HEIGHT LIMITATIONS, BUILDING SEPARATION DISTANCE REQUIREMENTS, BUILDING CONSTRUCTION TYPE, AND OCCUPANCY SEPARATION REQUIREMENTS, EXCEPT AS MODIFIED BY UFC 3-600-01. NFPA 101 WILL BE USED FOR BUILDING CONSTRUCTION RELATED TO EGRESS AND SAFETY TO LIFE AS WELL AS FIRE RESISTANCE RATINGS OF NON-BEARING PARTITIONS. IF ANY CONFLICTS OCCUR BETWEEN NFPA 101 AND IBC RELATED TO FIRE RESISTANCE RATING, NFPA 101 AND APPLICABLE CRITERIA CONTAINED IN UFC 3-600-01 WILL TAKE PRECEDENCE.

OCCUPANCY DEFINITIONS OF NFPA 101 WILL BE USED TO DETERMINE MEANS OF EGRESS REQUIREMENTS ADDITIONALLY TO THOSE

AMENDED BY UFC 3-600-01.

3. APPLICABLE CODES AND STANDARDS

UFC 1-200-01 – GENERAL BUILDING REQUIREMENTS, 8 OCTOBER 2019 WITH CHANGE 1, 1 OCTOBER 2020 UFC 3-600-01 – FIRE PROTECTION ENGINEERING FOR FACILITIES, 8 AUGUST 2016 WITH CHANGE 6, 6 MAY 2021 UFC 4-010-01 – DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 12 DECEMBER 2018 WITH CHANGE 1, 19 AUGUST 2020 UFC 4-021-01 – DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, 9 APRIL 2008 WITH CHANGE 1, JANUARY 2010 AS AMENDED BY

ENGINEERING AND CONSTRUCTION BULLETIN NO. 2018-17

IBC – 2018 EDITION – INTERNATIONAL BUILDING CODE

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 1 FIRE CODE, 2021

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 10 – 2022 EDITION – STANDARD FOR PORTABLE FIRE EXTINGUISHERS NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 24 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE

MAINS AND THEIR APPURTENANCES, 2022

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70 NATIONAL ELECTRIC CODE, 2017

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2020 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 80 STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2022 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING & VENTILATING

SYSTEMS, 2021

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 101 LIFE SAFETY CODE, 2021

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 291 RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF

HYDRANTS, 2022

HN CODES:

DM 10/03/1998 GENERAL CRITERIA FOR FIRE SAFETY AND EMERGENCY MANAGEMENT IN THE WORKPLACE WORKPLACES DM 22/02/2006 APPROVAL OF THE FIRE PREVENTION TECHNICAL REGULATION FOR THE DESIGN, CONSTRUCTION AND OPERATION OF

BUILDINGS AND/OR PREMISES USED AS OFFICES

DM 22/12/2012 TECHNICAL REGULATION ON FIRE PREVENTION FOR ACTIVE FIRE PROTECTION SYSTEMS INSTALLED IN ACTIVITIES

SUBJECT TO FIRE PREVENTION CONTROLS

DM 08/11/2019 APPROVAL OF THE FIRE PREVENTION TECHNICAL REGULATION FOR THE DESIGN, CONSTRUCTION AND OPERATION OF

PLANTS FOR THE PRODUCTION OF HEAT USING GASEOUS FUELS

DM 03/08/2015 FIRE PREVENTION CODE

DPR 151/2011 LIST OF ACTIVITIES SUBJECT TO FIRE BRIGADE CONTROLS

HN REQUIREMENTS:

UNI 10779 FIRE EXTINGUISHING SYSTEMS - HYDRANT NETWORKS - DESIGN, INSTALLATION AND OPERATIONFIRE EXTINGUISHING

SYSTEMS - HYDRANT NETWORKS - DESIGN, INSTALLATION AND OPERATION

UNI 12845 FIXED FIREFIGHTING INSTALLATIONS - AUTOMATIC SPRINKLER SYSTEMS - DESIGN, INSTALLATION AND MAINTENANCE

UNI 11292 ROOMS INTENDED TO HOUSE PUMPING UNITS FOR FIRE-FIGHTING SYSTEMS

UNI 11528 GAS INSTALLATIONS WITH A HEAT INPUT GREATER THAN 35 KW - DESIGN, INSTALLATION AND COMMISSIONING UNI 10435 GAS-FIRED APPLIANCES WITH A RATED THERMAL INPUT GREATER THAN 35 KW - INSPECTION AND MAINTENANCE UNI 9795 FIXED AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS - DESIGN, INSTALLATION AND OPERATION

UNI 9494 SMOKE AND HEAT CONTROL SYSTEMS

4. OCCUPANCY CLASSIFICATION

IBC SECTION 303: ASSEMBLY GROUP A-3 NFPA 101, CHAPTER 13: EXISTING OCCUPANCIES (NOT PART OF ADDITION) IBC SECTION 304: BUSINESS GROUP B NFPA 101, CHAPTERS 37 & 38: BUSINESS OCCUPANCIES IBC SECTION 311: STORAGE GROUP S-1 NFPA 101, CHAPTER 42: STORAGE – ORDINARY HAZARD

5. CONSTRUCTION TYPE (IBC 602.2 AND TABLE 601)

CONSTRUCTION TYPE IIB

6. AREA AND HEIGHT LIMITATIONS (IBC TABLE 504 AND IBC TABLE 506.2)

7. MIXED USE AND OCCUPANCY SEPARATIONS (IBC TABLE 508.4)

THE FACILITY IS CLASSIFIED AS A NON-SEPARATED MIXED USE.

8. FIRE RESISTIVE REQUIREMENTS (IBC TABLE 601 AND 602)

PRIMARY STRUCTURAL FRAME 0 HOUR RATING (TO BE PROTECTED AS REQUIRED BY HN CODES)

EXTERIOR BEARING WALLS 0 HOUR RATING*

INTERIOR BEARING WALLS 0 HOUR RATING (TO BE PROTECTED AS REQUIRED BY HN CODES)

EXTERIOR NON-BEARING WALLS AND PARTITIONS 0 HOUR RATING

INTERIOR NON-BEARING WALLS AND PARTITIONS 0 HOUR RATING (TO BE PROTECTED AS REQUIRED BY HN CODES) FLOOR CONSTRUCTION AND SECONDARY MEMBERS 0 HOUR RATING (TO BE PROTECTED AS REQUIRED BY HN CODES) ROOF CONSTRUCTION AND SECONDARY MEMBERS 0 HOUR RATING (TO BE PROTECTED AS REQUIRED BY HN CODES)

* TAKES INTO ACCOUNT THE FIRE SEPARATION DISTANCE REQUIREMENT OF IBC TABLE 602.

NOTE:

1. ROOM SEPARATION MUST ALSO COMPLY WITH THE HOST NATION CODE. STRUCTURE AND LOAD BEARING ELEMENTS WILL BE PROTECTED BY INTUMESCENT PAINT RATED WITH REQUIRED R AND REI/EI IN ACCORDANCE WITH DM 22/02/2006. MINIMUM R/REI 30 FOR ALL OFFICE BUILDINGS AND R/REI 120 FOR MECHANICAL, BOILER, AND ELECTRICAL ROOMS.

9. PROTECTION FROM HAZARDS (NFPA 101 CHAPTERS 38 AND 42)

PROTECTION FROM ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF THE BUILDING, SUCH AS AREAS USED FOR GENERAL STORAGE, BOILER OR FURNACE ROOMS, OR MAINTENANCE SHOPS MUST BE

PROTECTED IN ACCORDANCE WITH NFPA 101 SECTION 8.7.

MECHANICAL AND BOILER ROOMS MUST BE HAVE A 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH DM 08/11/2019.

ELECTRICAL AND TELECOMMUNICATIONS ROOMS MUSTHAVE A 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH THE

AVIANO FACILITY STANDARDS.

10. OPENING PROTECTION AND PENETRATION REQUIREMENTS (NFPA 101 CHAPTER 8)

PENETRATIONS FOR CABLES, CONDUITS, PIPES, AND SIMILAR ITEMS TO ACCOMMODATE ELECTRICAL, MECHANICAL, PLUMBING, AND COMMUNICATIONS SYSTEMS THAT PASS THROUGH FIRE BARRIERS MUST BE PROTECTED BY APPROVED FIRESTOP SYSTEMS OR

DEVICES TESTED IN ACCORDANCE WITH ASTM E 814 OR ANSI / UL 1479.

DUCT THROUGH PENETRATIONS OF FIRE RATED PARTITIONS MUST HAVE A FIRE DAMPER WITH A FIRE RESISTANCE RATING OF NOT

LESS THAN THE STRUCTURE THROUGH WHICH THE DUCT IS PENETRATING.

FIREBLOCKING AND DRAFTSTOPPING ARE NOT REQUIRED IN NON-COMBUSTIBLE CONSTRUCTION (IBC 718.2, 718.3)

11. STRUCTURAL ELEMENTS SUPPORTING FIRE BARRIER AND EXIT COMPONENTS (NFPA 101, 8.2) A. STRUCTURAL ELEMENTS THAT SUPPORT FIRE BARRIERS MUST BE PERMITTED TO HAVE ONLY THE FIRE RESISTANCE

RATING REQUIRED FOR THE CONSTRUCTION CLASSIFICATION OF THE BUILDING, PROVIDED THAT BOTH OF THE

FOLLOWING CRITERIA ARE MET:

1. SUCH STRUCTURAL ELEMENTS SUPPORT NONBEARING WALL OR PARTITION ASSEMBLIES THAT HAVE A REQUIRED

1-HOUR FIRE RESISTANCE RATING OR LESS.

2. SUCH STRUCTURAL ELEMENTS DO NOT SERVE AS EXIT ENCLOSURES OR PROTECTION FOR VERTICAL OPENING.

B. STRUCTURAL ELEMENTS THAT SUPPORT 1-HOUR FIRE BARRIERS FOR INCIDENTAL USE (IBC TABLE 509) DO NOT REQUIRE TO

BE FIRE RESISTANCE RATED.

12. FIRE BARRIER IDENTIFICATION (IBC 703.7)

IDENTIFY ALL FIRE RATED AND SMOKE WALLS EXCEPT IN STAIRWELLS OR PUBLIC AREAS AS INDICATED BELOW, WITH LABELING STATING THE FOLLOWING: "FIRE AND/OR SMOKE BARRIER – PROTECT ALL OPENINGS" IN ACCORDANCE WITH IBC-2018 SECTION 703.7 AND UFC 3-600-01 7-2. PUBLIC AREAS INCLUDE OFFICES, LOBBIES, CORRIDORS, ETC. THAT DO NOT HAVE DROP CEILINGS. IN AREAS WITH DROP CEILINGS, PAINT NOTIFICATION LABELING ON THE WALL ABOVE THE DROP/FINISHED CEILING. IN MECHANICAL, ELECTRICAL AND OTHER SIMILAR ROOMS, APPLY LABELING AT 2.4 M ABOVE FINISHED FLOOR LEVEL. SPACE STENCILED WALL LABELING WITHIN 4.6 METERS OF THE END OF EACH WALL AND AT MAXIMUM OF 3 METERS INTERVALS. IN ROOMS WITH RAISED FLOORING, PLACE LABELING ON WALLS UNDER THE FLOOR WITH SPACING OF LABELING REDUCED TO 4.6 METERS INTERVALS.

13. INTERIOR FINISH CLASSIFICATION LIMITS (NFPA 101 10.2)

IN ACCORDANCE WITH DM 22/02/2006, CORRIODRS, EXIT ENCLOSURES, AND EXIT PASSAGEWAYS MUST BE PROVIDED WITH A MAXIMUM 50% OF THE SURFACE WITH EUROPEAN CLASS 1 MATERIALS. ALL THE OTHER SURFACES MUST BE PROVIDED WITH MATERIAL CLASS 0. EUROPEAN CLASS 2 IS PERMITTED FOR COATING MATERIALS IF THE BUILDING IS PROTECTED THROUGHOUT BY

AN AUTOMATIC SPRINKLER SYSTEM.

14. INSULATION REQUIREMENTS (UFC 3-600-01 SECTION 8-1)

THERMAL AND ACOUSTICAL INSULATION WITH A FLAME SPREAD (FS) RATING NOT HIGHER THAN 75, AND A SMOKE DEVELOPED (SD) RATING NOT HIGHER THAN 150 MUST BE USED WHEN TESTED IN ACCORDANCE WITH ASTM E84 UNLESS EXCEPTIONS OF SECTION 8-1

ARE MET.

15. MEANS OF EGRESS (NFPA 101)

REFER TO LIFE SAFETY PLANS FOR OCCUPANT LOAD CALCULATIONS, AND EGRESS LIMITATION. BUILDING P-242 IS INTENDED TO BE AN EXTENSION OF THE EXISTING BUILDING. THERE IS ONE MAIN ENTRANCE OR DIRECT ACCESS TO THE INTERIOR OF P-242, OCCUPANTS CAN EGRESS THROUGH THE BUILDING P-242 OR THE EXISTING BUILDING. THEREFORE, THE EXISTING MEANS OF EGRESS ARE CONSIDERED SUPPLEMENTARY TO THE MEANS OF EGRESS OF BUILDING P-242. THE FULLY SPRINKLERED FACILITY (P-242) MUST BE CONNECTED TO THE ADJACENT FULLY SPRINKLERED VIA A COMMON CORRIDOR 065.

HOST NATION CRITERIA WAS DETERMINED IN ACCORDANCE WITH RESPONSE TO RFI 35. IN ACCORDANCE WITH RFI 35, THE OCCUPANT LOAD OF THE ENTIRE BUILDING IS CONSIDERED TO BE 72 PERSONS PLUS 20 PERCENT SAFETY FACTOR FOR A TOTAL OF 87 PERSONS. THE MINIMUM MEASURES REQUIRED BY THE DM 20/02/2006 FOR OFFICE TYPE I ARE BASED ON THIS OCCUPANCY.

DM 22/02/2006 REQUIRES A MINIMUM OF TWO EXITS IN OPPOSITE DIRECTION. THE WIDTH OF EACH EGRESS ROUTE MUST BE NOT LESS THAN 2 MODULES. EACH MODULE MUST BE A MINIMUM OF 600 MM IN WIDTH. THE MINIMUM WIDTH OF EACH EXIT MUST BE AT

LEAST 1200 MM. DOOR MUST OPEN IN THE DIRECTION OF THE EGRESS ROUTE.

THE EXIT CAPACITY MUST BE AS FOLLOWS:

L (M) = (A / 50) * 0.60 WHERE A IS THE TOTAL OCCUPANCY.

L (M) = (176 / 50) * 0.60 = 2.2 M EXIT CAPACITY REQUIRED. 3.6 M OF EXIT CAPACITY IS PROVIDED.

16. DISCHARGE FROM EXITS (NFPA 101)

EXIT DISCHARGE MUST BE IN ACCORDANCE WITH NFPA 101 SECTION 7.7. EXITS MUST TERMINATE DIRECTLY AT A PUBLIC WAY OR AT AN EXTERIOR DISCHARGE. EXITS ARE PERMITTED TO DISCHARGE INTO OPEN COURTS OR YARDS. EACH DOOR TO THE EXTERIOR MUST BE A MINIMUM OF TWO MODULES. THE EXIT WIDTH OF EACH MODULE MUST BE 600 MM IN ACCORDANCE WITH DM 22/02/2006.

THE MINIMUM WIDTH OF BUILDING EXITS MUST BE 1200 MM.

17. ILLUMINATION OF MEANS OF EGRESS (NFPA 101)

MEANS OF EGRESS MUST BE ILLUMINATED IN ACCORDANCE WITH NFPA 101 SECTION 7.8.1.2 THROUGH 7.8.1.5 IN DESIGNATED

CORRIDORS LEADING TO AN EXIT AND/OR PUBLIC WAY.

18. EMERGENCY LIGHTING

EMERGENCY LIGHTING MUST BE PROVIDED IN ACCORDANCE WITH NFPA 101 SECTION 7.9.1.3 AND 7.9.2 IN DESIGNATED CORRIDORS LEADING TO AN EXIT AND/OR PUBLIC WAY. EGRESS ROUTES MUST HAVE A MINIMUM OF 2 HOURS OF LIGHTING AND A MINIMUM OF 5

LUX AT 1 METER FROM THE FLOOR ALONG THE EGRESS ROUTE.

19. MARKINGS OF MEANS OF EGRESS (NFPA 101)

MEANS OF EGRESS, OTHER THAN MAIN EXTERIOR EXIT DOORS THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, MUST HAVE SIGNS AT EXITS THAT ARE READILY VISIBLE FROM ANY DIRECTION OF EXIT ACCESS IN ACCORDANCE WITH NFPA 101 SECTION

7.10. HORIZONTAL COMPONENTS OF THE EGRESS PATH WITHIN AN EXIT ENCLOSURE WHERE THE CONTINUATION OF THE EGRESS

PATH IS NOT OBVIOUS MUST ALSO HAVE SIGNS.

20. ROOF ACCESS (UFC 3-600-01, SECTION 10-4)

FIRE DEPARTMENT ROOF ACCESS IS NOT REQUIRED AS THE BUILDING IS LESS THAN FOUR STORIES.

21. PORTABLE FIRE EXTINGUISHERS (NFPA 10, 6.2.1.2.2)

PROVIDE FIRE EXTINGUISHERS AS REQUIRED BY NFPA 101 AND UFC 3-600-01. DM 10/03/1998 CLASSIFIES THE BUILDING AS A HIGH- RISK ACTIVITY AND THEREFORE REQUIRES A FIRE EXTINGUISHER WITH A MINIMUM CAPACITY OF 34A-144B PER 100 SQUARE METERS.

EXTINGUISHERS ARE LOCATED ALONG EGRESS ROUTES AND THE MAXIMUM DISTANCE TO AN EXTINGUISHER MUST NOT EXCEED 30

METERS.

22. AUTOMATIC SPRINKLERS AND OTHER EXTINGUISHING EQUIPMENT (NFPA 13, AND UFC 3-600-01 CHAPTER 9-7.2) COMPLETE, SUPERVISED, AUTOMATIC WET PIPE SPRINKLER SYSTEMS WILL BE PROVIDED THROUGHOUT THE ADDITION IN ACCORDANCE WITH UFC 3-600-01 AND NFPA 13. SEISMIC PROTECTION IS REQUIRED BECAUSE THE SITE IS CLASSIFIED AS SEISMIC DESIGN CATEGORY D. REFER TO FIRE PROTECTION DRAWINGS FOR ADDITIONAL INFORMATION. HOSE CABINETS MUST BE PROVIDED SUCH THAT THE MAXIMUM DISTANCE TO REACH THE NEAREST HOSE CABINET IS 20 METERS IN ACCORDANCE WITH UNI 10779.

ACCORDING TO UNI 10779, EACH HOSE CABINET IS PERMITTED TO COVER AN AREA EQUAL TO A CIRCLE WITH A RADIUS OF 20

METERS. REFER TO SHEET FX411.

23. FIRE ALARM AND MASS NOTIFICATION SYSTEMS (UFC 3-600-01, UFC 4-021-01 AND NFPA 72) THE ADDITION WILL BE PROVIDED WITH A COMPLETE, SUPERVISED, ADDRESSABLE, COMBINED FIRE ALARM AND MASS NOTIFICATION SYSTEM THROUGHOUT THE ADDITION. THE NEW FIRE ALARM AND MASS NOTIFICATION INITIATING AND NOTIFICATION APPLIANCES WILL BE CONNECTED TO THE EXISTING BUILDING SYSTEM. THE SYSTEM MUST INCLUDE A COMBINED, REMOTE FIRE ALARM AND MASS NOTIFICATION CONTROL PANEL, REMOTE ANNUNCIATORS, LOCAL OPERATING CONSOLES, POWER SUPPLIES, SPRINKLER SYSTEM MONITORING, AHU MONITORING AND SHUT DOWN, INITIATING DEVICES AND SPEAKER/STROBE ANNUNCIATION

DEVICES. REFER TO FIRE ALARM DRAWINGS FOR ADDITIONAL INFORMATION.

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

1684614

07/11/22

Richard Tyler, PE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

100 AIRSIDE DRIVE

MOON TOWNSHIP, PA 15108

A V

IA

N

O A

IR

B

A S

E

A V

IA

N

O

IT

A

L Y

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

SS

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

LMM / BTN

FIRE PROTECTION DPS

F

A

D A

L C

O M

B A

T R

E S

C U

E H

E L

IC

O P

T

R

IM

U L A

T O

R F

A C

IL

IT

Y

P

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

N O

R F

O L

K V

A A

T L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

TE

M

S C

O M

M A

N D

A T

LA

N

TI

C

DRAWFORM REVISION: 12 APRIL 2018

ISSUED FOR CONSTRUCTION – 10 MAR 2023

AS NOTED

B

IM

/1

P

S im u la to r/

B L D

G P

-1

-F

.r v t

/7

/2

:0

:5

P M

L

IF

E S

A F

E T

Y

C O

D E

A N

A L

Y S

IS

ASDMADL

G-101

S

IC

U R

E Z

Z A

A

N A

L

IS

I D

E I

C O

D

IC

I

14125384

KMC

STORAGE, GROUP S-1 6,503

BUSINESS, GROUP B 6,410

ASSEMBLY, GROUP A-3 3,530

870 3,285

OCCUPANCY

ALLOWABLE AREA FOR

SINGLE-STORY SPRINKLERED

BUILDING (SQ. M)

ADDITION AREA

(SQ. M)

FIRST FLOOR TOTAL

AREA (SQ. M)

ALLOWABLE BUILDING AREA FOR CONSTRUCTION TYPE II-B, SNGLE-STORY SPRINKLERED,

NON-SEPARATED MIXED USE FACILITY

FIRE BARRIERS 1 3/4

FIRE BARRIERS 2 1 1/2

COMPONENTS WALLS AND PARTITIONS (HOUR) FIRE DOOR ASSEMBLIES (HOUR)

CLASS A INTERIOR WALL AND CEILING FINISH- FLAME SPREAD INDEX 0-25, SMOKE DEVELOPED 0-450 CLASS B INTERIOR WALL AND CEILING FINISH- FLAME SPREAD INDEX 26-75, SMOKE DEVELOPED 0-450 CLASS C INTERIOR WALL AND CEILING FINISH- FLAME SPREAD INDEX 76-200, SMOKE DEVELOPED 0-450

CLASS I INTERIOR FLOOR FINISH- CRITICAL RADIANT FLUX NOT LESS THAN 0.45 W/CM^2

CLASS II INTERIOR FLOOR FINISH- CRITICAL RADIANT FLUX NOT MORE THAN 0.22 W/CM^2 BUT LESS THAN 0.45 W/CM^2

CLASS I OR II CLASS I OR II N/A

STORAGE

CLASS A, B, OR C CLASS A, B, OR C CLASS A, B, OR C

CLASS I OR II CLASS I OR II N/A

NEW BUSINESS

CLASS A, B, OR C CLASS A OR B CLASS A, B, OR C

OCCUPANCY

EXIT ENCLOSURES AND EXIT

PASSAGEWAYS

CORRIDORS

ROOMS AND ENCLOSED

SPACES

INTERIOR FINISH CLASSIFICATION (SPRINKLERED): NFPA 101 A.10.2.2

IRE-3 600 855 71

IRE-2 600 1,948 162

IRE-1 600 1,948 162

INDIVIDUAL ROOM EXITS

E-3 1,200 1,948 100 E-2 1,200 1,948 162 E-1 1,200 1,948 162

EXITS

MINIMUM CLEAR WIDTH

(MM)

ACTUAL CLEAR WIDTH

(MM)

OCCUPANT CAPACITY

EXIT CAPACITY NFPA 101, 7.2.1.2.3

INDIVIDUAL ROOM EXITS ARE PROVIDED.

EXITS REQUIRED = 2 IRE = 4 EXITS PROVIDED = 3

TOTAL OCCUPANT LOAD 109

MECHANICAL, ELECTRICAL, OTHER

BUILDING EQUIPMENT AND STORAGE

46.5 265 6

MISSION PLANNING/LIBRARY 1.4 26 19

MULTI-PURPOSE ROOM 1.4 70 50

SIMULATOR BAY 14 296 22

BUSINESS 14 160 12

USE

OCCUPANT LOAD FACTOR

(SQ. M/PERSON)

AREA (SQ.M) OCCUPANT LOAD

FIRST FLOOR ADDITION OCCUPANT LOAD CALCULATIONS: NFPA 101, TABLE 7.3.1.2 AND UFC 3-600-01 TABLE 10-1

LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL

MAXIMUM IDENTIFIED

EGRESS DISTANCES

6 15 46

STORAGE, ORDINARY

HAZARD 30 30 122

BUSINESS 15 30 91

OCCUPANCY DEAD END (M) COMMON PATH (M) TRAVEL DISTANCE (M)

EGRESS LIMITATIONS, SPRINKLERED FACILITY

NFPA 101, TABLE A.7.6

DPS

Approved by CDR Jonathan Horner, ROICC, via SAT-TO form

1. NOME DEL PROGETTO, SIMULATORE DI ELICOTTERO DA RICERCA E SOCCORSO IN COMBATTIMENTO P-242 ADAL, BASE AEREA DI

AVIANO, ITALIA.

2. DESCRIZIONE DEL PROGETTO

SI TRATTA DI UNA STRUTTURA A UN PIANO CON SIMULATORE DI ELICOTTERO DA RICERCA E SOCCORSO IN COMBATTIMENTO ADAL.

I REQUISITI DELL’IMPIANTO IN TERMINI DI SICUREZZA VITALE E PROTEZIONE ANTINCENDIO SONO STATI ANALIZZATI SULLA BASE DEI CODICI E DELLE NORME INDICATI IN SEGUITO. GLI UNIFIED FACILITIES CRITERIA (UFC) SONO CRITERI TECNICI PER LE STRUTTURE MILITARI NUOVE E RIQUALIFICATE APPLICABILI AI DIPARTIMENTI MILITARI, ALLE AGENZIA DELLA DIFESA E ALLE ATTIVITÀ SUL CAMPO DEL DIPARTIMENTO DELLA DIFESA. CONFORMEMENTE AGLI UFC 1-200-01 CAPITOLO 2 - MODIFICHE ALL’INTERNATIONAL BUILDING CODE (IBC) E AGLI UFC 3-600-01, L’IBC VERRÀ APPLICATO PER I REQUISITI DI RESISTENZA AL FUOCO, LA SUPERFICIE AMMISSIBILE, I LIMITI DI ALTEZZA DEGLI EDIFICI, I REQUISITI DI DISTANZIAMENTO DELLE COSTRUZIONI, IL TIPO DI COSTRUZIONE E I REQUISITI IN TERMINI DI OCCUPAZIONE, SALVO MODIFICHE DA PARTE DEGLI UFC 3-600-01. LA NORMA NFPA 101 VERRÀ IMPIEGATA PER GLI ASPETTI COSTRUTTIVI RELATIVI ALLE VIE D’USCITA, ALLA SICUREZZA VITALE E AL LIVELLO DI RESISTENZA AL FUOCO DELLE PARETI NON PORTANTI. IN CASO DI INCONGRUENZE TRA NFPA 101 E IBC PER QUANTO CONCERNE IL LIVELLO DI RESISTENZA AL FUOCO, SI APPLICHERÀ QUANTO PREVISTO DALLA NFPA 101 E DAI CRITERI APPLICABILI DEGLI UFC 3-600-01. LE DEFINIZIONI PER L’OCCUPAZIONE PREVISTE DALLA NFPA 101 VERRANNO USATE PER DETERMINARE I REQUISITI IN TERMINI DI VIE D’USCITA, IN AGGIUNTA A QUANTO

EMENDATO DAGLI UFC 3-600-01.

3. CODICI E NORME APPLICABILI

UFC 1-200-01 - REQUISITI GENERALI PER L'EDILIZIA, 8 OTTOBRE 2019 CON MODIFICA 1, 1 OTTOBRE 2020 UFC 3-600-01 - PROGETTAZIONE DI SISTEMI DI PROTEZIONE ANTINCENDIO PER STRUTTURE, 8 AGOSTO 2016 CON MODIFICA 6, 6

MAGGIO 2021

UFC 4-010-01 - STANDARD EDILIZI MINIMI ANTITERRORISMO DEL DIPARTIMENTO DELLA DIFESA, 12 DICEMBRE 2018 CON MODIFICA 1, 19

AGOSTO 2020

UFC 4-021-01 - PROGETTAZIONE, ESERCIZIO E MANUTENZIONE: SISTEMI DI NOTIFICA DI MASSA, 9 APRILE 2008 CON MODIFICA 1, GENNAIO 2010 COME EMENDATO DALL’ENGINEERING AND CONSTRUCTION BULLETIN NO. 2018-17

IBC - EDIZIONE 2018 - CODICE INTERNAZIONALE PER L'EDILIZIA

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 1, NORMATIVA ANTINCENDIO, 2021 NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 10 - EDIZIONE 2022 - NORMA PER GLI ESTINTORI

PORTATILI

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 13 NORMA PER L’INSTALLAZIONE DEI SISTEMI

SPRINKLER, 2022

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 24 NORMA PER L’INSTALLAZIONE DEGLI IMPIANTI

ELETTRICI DI SERVIZIO ANTINCENDIO PRIVATI E SISTEMI CORRELATI, 2022

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 70, NORMATIVA NAZIONALE IN MATERIA DI ELETTRICITÀ, NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 72 NORMATIVA NAZIONALE IN MATERIA DI

SEGNALAZIONE E ALLARME ANTINCENDIO, 2020

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 80 NORMA PER LE FINESTRE E LE PORTE TAGLIAFUOCO, NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 90A NORMA PER L’INSTALLAZIONE DI IMPIANTI DI

CONDIZIONAMENTO DELL’ARIA E VENTILAZIONE, 2021

NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 101 NORMATIVA SULLA SICUREZZA VITALE, 2021 NFPA, ASSOCIAZIONE NAZIONALE AMERICANA DI PROTEZIONE ANTINCENDIO 291 PRASSI RACCOMANDATA PER I COLLAUDI

ANTINCENDIO E LA MARCATURA DEGLI IDRANTI, 2022

NORMATIVE DELLA NAZIONE OSPITANTE:

DM 10/03/1998 CRITERI GENERALI PER LA SICUREZZA ANTINCENDIO E LA GESTIONE DELLE EMERGENZE SUI LUOGHI DI LAVORO DM 22/02/2006 APPROVAZIONE DELLA REGOLAMENTAZIONE TECNICA DI PREVENZIONE ANTINCENDIO PER LA PROGETTAZIONE, LA

COSTRUZIONE E L’UTILIZZO DI EDIFICI E/O STRUTTURE AD USO UFFICIO

DM 22/12/2012 REGOLAMENTAZIONE TECNICA SULLA PREVENZIONE ANTINCENDIO PER I SISTEMI ANTINCENDIO ATTIVI INSTALLATI PER

ATTIVITÀ SOGGETTE A CONTROLLI ANTINCENDIO

DM 08/11/2019 APPROVAZIONE DELLA REGOLAMENTAZIONE TECNICA DI PREVENZIONE ANTINCENDIO PER LA PROGETTAZIONE, LA COSTRUZIONE E L’UTILIZZO DI IMPIANTI PER LA GENERAZIONE DI CALORE CHE IMPIEGANO COMBUSTIBILI GASSOSI

DM 03/08/2015 NORMATIVA DI PREVENZIONE ANTINCENDIO

DPR 151/2011 LISTA DELLE ATTIVITÀ SOGGETTE A CONTROLLI DA PARTE DEI VIGILI DEL FUOCO

REQUISITI DELLA NAZIONE OSPITANTE:

UNI 10779 SISTEMI ANTINCENDIO - RETI DI IDRANTI - PROGETTAZIONE, INSTALLAZIONE E UTILIZZO DEI SISTEMI ANTINCENDIO - RETI DI

IDRANTI - PROGETTAZIONE, INSTALLAZIONE E UTILIZZO

UNI 12845 IMPIANTI ANTINCENDIO FISSI - IMPIANTI SPRINKLER AUTOMATICI - PROGETTAZIONE, INSTALLAZIONE E MANUTENZIONE

UNI 11292 LOCALI PER L’INSTALLAZIONE DI POMPE PER GLI IMPIANTI ANTINCENDIO

UNI 11528 IMPIANTI A GAS CON APPORTO TERMICO SUPERIORE A 35 KW - PROGETTAZIONE, INSTALLAZIONE E MESSA IN SERVIZIO UNI 10435 APPARECCHIATURE A GAS CON APPORTO TERMICO NOMINALE SUPERIORE A 35 KW - ISPEZIONE E MANUTENZIONE UNI 9795 SISTEMI AUTOMATICI FISSI DI ALLARME E RILEVAMENTO ANTINCENDIO - PROGETTAZIONE, INSTALLAZIONE E UTILIZZO

UNI 9494 SISTEMI DI CONTROLLO TERMICO E DEL FUMO

4. CLASSIFICAZIONE DELL’OCCUPAZIONE

IBC SEZIONE 303: GRUPPO DI MONTAGGIO A-3 NFPA 101, CAPITOLO 13: OCCUPAZIONE ESISTENTE (NON PARTE DELL'AGGIUNTA) IBC SEZIONE 304: GRUPPO COMMERCIALE B NFPA 101, CAPITOLI 37 E 38: OCCUPAZIONE COMMERCIALE IBC SEZIONE 311: GRUPPO STOCCAGGIO S-1 NFPA 101, CAPITOLO 42: STOCCAGGIO - PERICOLO ORDINARIO

5. TIPO DI COSTRUZIONE (IBC 602.2 E TABELLA 601)

CONSTRUCTION TYPE IIB

6. LIMITI DI AREA E ALTEZZA (IBC, TABELLA 504 E IBC, TABELLA 506.2)

7. SEPARAZIONE DI OCCUPAZIONE E DESTINAZIONE MISTA (IBC, TABELLA 508.4)

LA STRUTTURA È CLASSIFICATA COME UNA DESTINAZIONE MISTA NON SEPARATA.

8. FIRE RESISTIVE REQUIREMENTS (IBC TABLE 601 AND 602)

ELEMENTO STRUTTURALE PRIMARIO RESISTENZA 0 ORE (DA PROTEGGERE COME PREVISTO DALLE

NORMATIVE DELLA NAZIONE OSPITANTE)

MURI PORTANI ESTERNI RESISTENZA 0 ORE *

MURI PORTANI INTERNI RESISTENZA 0 ORE (DA PROTEGGERE COME PREVISTO DALLE

NORMATIVE DELLA NAZIONE OSPITANTE)

PARETI E TRAMEZZI NON PORTANTI ESTERNI RESISTENZA 0 ORE

PARETI E TRAMEZZI NON PORTANTI INTERNI RESISTENZA 0 ORE (DA PROTEGGERE COME PREVISTO DALLE

NORMATIVE DELLA NAZIONE OSPITANTE)

STRUTTURA PAVIMENTALE E COMPENTI SECONDARI RESISTENZA 0 ORE (DA PROTEGGERE COME PREVISTO DALLE

NORMATIVE DELLA NAZIONE OSPITANTE)

STRUTTURA DEL TETTO E COMPENTI SECONDARI RESISTENZA 0 ORE (DA PROTEGGERE COME PREVISTO DALLE

NORMATIVE DELLA NAZIONE OSPITANTE)

* TIENE CONTO DEL REQUISITO DI DISTANZIAMENTO ANTINCENDIO DELLA TABELLA 602 IBC.

NOTA:

1. LA SEPARAZIONE DEI VANI DEVE RISPETTARE ANCHE LA NORMATIVE DELLA NAZIONE OSPITANTE. GLI ELEMENTI PORTANTI E STRUTTURALI VERRANNO PROTETTI DA VERNICE INTUMESCENTE AVENTE R E REI/EI RICHISTI, CONFORMEMENTE AL DM 22/02/2006.

MINIMO R/REI 30 PER TUTTI GLI UFFICI E R/REI 120 PER LOCALI MECCANICI, CALDAIE ED ELETTRICI.

9. PROTEZIONE DAI PERICOLI (NFPA 101 CAPITOLI 38 E 42)

PROTEZIONE DA AREE CON UN LIVELLO DI PERICOLO SUPERIORE AL NORMALE PER L’OCCUPAZIONE GENERALE DELL’EDIFICIO, COME AREE USATE PER LO STOCCAGGIO GENERALE, LOCALI CALDAIA OD OFFICINE DI MANUTENZIONE, CHE DEVONO ESSERE PROTETTI

COME PREVISTO DALLA NFPA 101 SEZIONE 8.7.

I LOCALI MECCANICI O CALDAIE DEVONO AVERE UNA RESISTENZA AL FUOCO DI 2 ORE, COME PREVISTO DAL DM 08/11/2019. I LOCALI ELETTRICI E TELECOMUNICAZIONI DEVONO AVERE UNA RESISTENZA AL FUOCO DI 2 ORE, COME PREVISTO DALLE NORMATIVE

INTERNE DI AVIANO.

10. REQUISITI DI PENETRAZIONE E PROTEZIONE DELLE APERTURE (NFPA 101 CAPITOLO 8)

LE PENETRAZIONI PER CAVI, CONDOTTE, TUBATURE E SIMILI UTILI PER GLI IMPIANTI ELETTRICI, MECCANICI, IDRAULICI E DI COMUNICAZIONE CHE ATTRAVERSANO LE BARRIERE ANTINCENDIO DEVONO ESSERE PROTETTE DA SISTEMI O DISPOSITIVI

APPROVATI E COLLAUDATI COME DA ASTM E 814 O ANSI / UL 1479.

LE CONDOTTE CHE PENETRANO NEI TRAMEZZI RESISTENTI AL FUOCO DEVONO DISPORRE DI SERRANDA TAGLIAFUOCO CON

RESISTENZA NON INFERIORE ALLA STRUTTURA ATTRAVERSO LA QUALE PASSA LA CONDOTTA.

I SISTEMI DI TAGLIAFUOCO E TAGLIA ARIA NON SONO NECESSARI IN EDIFICI IGNIFUGHI (IBC 718.2, 718.3)

11. ELEMENTI STRUTTURALI A SUPPORTO DEI COMPONENTI PER L’USCITA E LA BARRIERA ANTINCENDIO (NFPA 101, 8.2) A. GLI ELEMENTI STRUTTURALI CHE SOSTENGONO LE BARRIERE ANTINCENDIO SONO AMMISSIBILI SOLO SE GARANTISCONO LA

RESISTENZA AL FUOCO RICHIESTA PER LA CLASSIFICAZIONE EDILIZIA DELL'EDIFICIO, A CONDIZIONE CHE VENGANO RISPETTATI I

SEGUENTI CRITERI:

1. TALI ELEMENTI STRUTTURALI SUPPORTANO I TRAMEZZI O LE PARETI NON PORTANTI AVENTI UNA RESISTENZA AL FUOCO DI

UN’ORA O MENO.

2. TALI ELEMENTI STRUTTURALI NON SERVONO COME COMPARTIMENTI DI USCITA O PROTEZIONE PER L’APERTURA VERTICALE.

B. GLI ELEMENTI STRUTTURALI CHE SUPPORTANO LE BARRIERE ANTINCENDIO DA UN’ORA PER USO OCCASIONALE (TABELLA 509

IBC) NON DEVONO NECESSARIAMENTE AVERE UNA RESISTENZA ANTINCENDIO.

12. IDENTIFICAZIONE DELLE BARRIERE ANTINCENDIO (IBC 703.7)

IDENTIFICARE TUTTE LE PARETI RESISTENTI AL FUOCO E AL FUMO, AD ECCEZIONE DELLE TROMBE DELLE SCALE O DELLE AREE PUBBLICHE INDICATE SOTTO, APPLICANDO ETICHETTE CON LA DICITURA “BARRIERA ANTINCENDIO E/O ANTIFUMO - PROTEGGERE TUTTE LE APERTURE”, COME PREVISTO DALL’IBC-2018 SEZIONE 703.7 E UFC 3-600-01 7-2. LE AREE PUBBLICHE COMPRENDONO UFFICI, ATRI, CORRIDOI, ECC. SENZA CONTROSOFFITTI. NELLE ZONE CON CONTROSOFFITTO, DIPINGERE UN’ETICHETTA DI NOTIFICA SULLA PARETE SOPRA AL CONTROSOFFITTO/FINITURA DEL SOFFITTO. NEI LOCALI MECCANICI, ELETTRICI E SIMILI, POSIZIONARE L’ETICHETTA A 2,4 M AL DI SOPRA DELLA QUOTA DEL PAVIMENTO FINITO. DISTANZIALE LE ETICHETTE DIPINTE ENTRO 4,6 METRI DALL'ESTREMITÀ DI CIASCUNA PARETE E A INTERVALLI DI MASSIMO 3 METRI. NEI LOCALI CON PAVIMENTAZIONE RIALZATA, POSIZIONARE LE ETICHETTE SULLE PARETI SOTTO IL PAVIMENTO, CON UNA DISTANZA RIDOTTA A UN INTERVALLO DI 4,6 METRI.

13. LIMITI DI CLASSIFICAZIONE DELLE FINITURE INTERNE (NFPA 101 10.2)

CONFORMEMENTE AL DM 22/02/2006, CORRIDOI, COMPARTIMENTI DI USCITA E CORRIDOI DI USCITA DEVONO PRESENTARE UN MASSIMO DEL 50% DI SUPERFICIE CON MATERIALI DI CLASSE 1 EUROPEA. TUTTE LE ALTRE SUPERFICI DEVONO PRESENTARE MATERIALI DI CLASSE 0. LA CLASSE 2 EUROPEA RISULTA AMMESSA PER I RIVESTIMENTI SE L’EDIFICIO È INTERAMENTE PROTETTO DA

UN SISTEMA AUTOMATICO A SPRINKLER.

14. REQUISITI DI ISOLAMENTO (UFC 3-600-01 SEZIONE 8-1)

DEV’ESSERE APPLICATO UN ISOLAMENTO TERMICO E ACUSTICO CON UN LIVELLO DI PROPAGAZIONE DELLE FIAMME (FS) NON SUPERIORE A 75 E UN LIVELLO DI FUMO SVILUPPATO (SD) NON SUPERIORE A 150 QUANDO IL COLLAUDO È STATO ESEGUITO

CONFORMEMENTE ALL’ASTM E84, AD ECCEZIONE DI QUANTO PREVISTO NELLA SEZIONE 8-1.

15. VIE DI USCITA (NFPA 101)

FARE RIFERIMENTO AI PIANI DI SICUREZZA PER IL CALCOLO DEL CARICO DEGLI OCCUPANTI E LE LIMITAZIONI DI USCITA. L’EDIFICIO P-242 VIENE CONSIDERATO COME UN’ESTENSIONE DELL’EDIFICIO ESISTENTE. È PRESENTE UN’ENTRATA PRINCIPALE O ACCESSO DIRETTO ALL’INTERNO DEL P-242, GLI OCCUPANTI POSSONO USCIRE ATTRAVERSO L’EDIFICIO P-242 O L’EDIFICIO ESISTENTE. LE VIE D’USCITA ESISTENTI, QUINDI, SONO CONSIDERATE SUPPLEMENTARI ALLE VIE D’USCITA DELL’EDIFICIO P-242. LA STRUTTURA INTERAMENTE DOTATA DI SPRINKLER (P-242) DEV’ESSERE COLLEGATA ALLA STRUTTURA ADIACENTE, INTERAMENTE DOTATA DI

SPRINKLER, CON UN CORRIDOIO COMUNE 065.

I CRITERI DELLA NAZIONE OSPITANTE SONO STATI DETERMINATI IN CONFORMITÀ ALLA RISPOSTA A RFI 35. IN CONFORMITÀ ALLA RFI 35, IL CARICO OCCUPANTE DELL'INTERO EDIFICIO È CONSIDERATO IN 72 PERSONE PIÙ IL 20 PERCENTUALE DI SICUREZZA PER UN TOTALE DI 87 PERSONE. LE MISURE MINIME RICHIESTE DAL DM 20/02/2006 PER UFFICI DI TIPO I SONO BASATE SU QUESTA

OCCUPAZIONE.

IL DM 22/02/2006 PREVEDE UN MINIMO DI DUE USCITE IN DIREZIONI OPPOSTE. LA LARGHEZZA DI CIASCUNA VIA D’USCITA NON DEVE ESSERE INFERIORE A 2 MODULI. CIASCUN MODULO DEVE AVERE UNA LARGHEZZA MINIMA DI 600 MM. LA LARGHEZZA MINIMA DI CIASCUNA USCITA DEV'ESSERE DI ALMENO 1200 MM. LA PORTA DEVE APRIRSI NELLA DIREZIONE DELLA VIA D’USCITA.

LA CAPACITÀ DI USCITA DEV’ESSERE:

L (M) = (A / 50) * 0,60 LADDOVE A È L’OCCUPAZIONE TOTALE.

L (M) = (176 / 50) * 0,60 = 2,2 M DI CAPACITÀ DI USCITA RICHIESTA. VIENE FORNITA UNA CAPACITÀ DI USCITA

DI 3,6 M.

16. DEFLUSSO DALLE USCITE (NFPA 101)

IL DEFLUSSO DEV’ESSERE CONFORME ALLA NFPA 101 SEZIONE 7.7. LE USCITE DEVONO SBOCCARE DIRETTAMENTE SULLA PUBBLICA VIA O SU UN PERCORSO ESTERNO. LE USCITE POSSONO DARE SU CORTILI APERTI. LA LARGHEZZA DI USCITA DI CIASCUNA PORTA DEV’ESSERE DI 600 MM, COME PREVISTO DAL DM 22/02/2006. OGNI PORTA PER L'ESTERNO DEVE ESSERE UN MINIMO DI DUE MODULI.

17. ILLUMINAZIONE DELLE VIE D’USCITA (NFPA 101)

LE VIE D’USCITA DEVONO ESSERE ILLUMINATE COME PREVISTO DALLA NFPA 101 SEZIONE 7.8.1.2 A 7.8.1.5 NEI CORRIDOI DESIGNATI

CHE PORTANO A UN’USCITA E/O ALLA PUBBLICA VIA.

18. ILLUMINAZIONE D’EMERGENZA

L’ILLUMINAZIONE D’EMERGENZA DEV’ESSERE GARANTITA COME DA NFPA 101 SEZIONE 7.9.1.3 E 7.9.2 NEI CORRIDOI DESIGNATI CHE PORTANO A UN’USCITA E/O ALLA PUBBLICA VIA. LE VIE D’USCITA DEVONO FORNIRE UN MINIMO DI DUE ORE DI ILLUMINAZIONE E UN

MINIMO DI 5 LUX A 1 METRO DAL PAVIMENTO LUNGO LA VIA D’USCITA.

19. MARCATURA DELLE VIE D’USCITA (NFPA 101)

VIE D’USCITA, DIVERSE DALLE PORTE D’USCITA PRINCIPALI CHE SONO OVVIAMENTE E CHIARAMENTE IDENTIFICABILI COME USCITE, DEVONO PRESENTARE SEGNALI ALLE USCITE FACILMENTE VISIBILI DA TUTTE LE DIREZIONI DI PROVENIENZA, COME PREVISTO DALLA NFPA 101 SEZIONE 7.10. LA SEGNALETICA DEV'ESSERE PRESENTE ANCHE NEI COMPONENTI ORIZZONTALI DEL PERCORSO DI USCITA NEL COMPARTIMENTO D’USCITA IN CUI IL PROSEGUIMENTO DEL PERCORSO DI USCITA NON RISULTA EVIDENTE.

20. ACCESSO AL TETTO (UFC 3-600-01, SEZIONE 10-4)

L’ACCESSO AL TETTO PER I VIGILI DEL FUOCO NON È NECESSARIO DAL MOMENTO CHE L’EDIFICIO NON SUPERA I QUATTRO PIANI.

21. ESTINTORI PORTATILI (NFPA 10, 6.2.1.2.2)

METTERE A DISPOSIZIONE ESTINTORI COME PREVISTO DA NFPA 101 E UFC 3-600-01. IL DM 10/03/1998 CLASSIFICA L'EDIFICIO COME ATTIVITÀ AD ALTO RISCHIO E PERTANTO RICHIEDE UN ESTINTORE CON PORTATA MINIMA DI 34A-144B PER 100 MQ. GLI ESTINTORI SI TROVANO LUNGO LE VIE DI USCITA E LA DISTANZA MASSIMA DA UN ESTINTORE NON DEVE SUPERARE I 30 METRI.

22. SPRINKLER AUTOMATICI E ALTRE APPARECCHIATURE DI ESTINZIONE DEGLI INCENDI (NFPA 13 E UFC 3-600-01 CAPITOLO 9-7.2) I SISTEMI SPRINKLER CON TUBATURA A UMIDO AUTOMATICI, COMPLETI E CONTROLLATI VERRANNO INSTALLATI IN TUTTA LA PARTE AGGIUNTIVA, COME PREVISTO DALL’UFC 3-600-01 E NFPA 13. È NECESSARIA LA PROTEZIONE SISMICA DAL MOMENTO CHE IL SITO È CLASSIFICATO COME CATEGORIA DI PROGETTAZIONE SISMICA D. FARE RIFERIMENTO AI DISEGNI DI PROTEZIONE ANTINCENDIO PER MAGGIORI INFORMAZIONI. GLI ARMADIETTI DEI TUBI FLESSIBILI DEVONO ESSERE POSIZIONATI IN MODO CHE RISULTINO

RAGGIUNGIBILI ENTRO 20 METRI DA QUALSIASI PUNTO DELLA PARTE AGGIUNTIVA.

23. SISTEMI DI NOTIFICA DI MASSA E ALLARME ANTINCENDIO (UFC 3-600-01, UFC 4-021-01 E NFPA 72) LA PARTE AGGIUNTIVA VERRÀ DOTATA DI UN SISTEMA DI NOTIFICA DI MASSA E ALLARME ANTINCENDIO COMBINATO, INDIRIZZABILE, CONTROLLATO E COMPLETO. I NUOVI DISPOSITIVI DI NOTIFICA E DI AVVIO DELLA NOTIFICA DI MASSA E ALLARME ANTINCENDIO SARANNO COLLEGATE ALL’IMPIANTO ESISTENTE. L’IMPIANTO DEVE COMPRENDERE UN PANNELLO DI CONTROLLO DI NOTIFICA DI MASSA E ALLARME ANTINCENDIO COMBINATO E A DISTANZA, AVVISATORI A DISTANZA, CONSOLE DI UTILIZZO LOCALE, ALIMENTAZIONE ELETTRICA, SISTEMA SPRINKLER E MONITORAGGIO, MONITORAGGIO E CHIUSURA UNITÀ TRATTAMENTO ARIA, DISPOSITIVI DI AVVIO E AVVISATORI STROBOSCOPICI/ALTOPARLANTI. PER MAGGIORI INFORMAZIONI, FARE RIFERIMENTO AI DISEGNI DELL'ALLARME

ANTINCENDIO.

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

1684614

07/11/22

Richard Tyler, PE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

100 AIRSIDE DRIVE

MOON TOWNSHIP, PA 15108

A V

IA

N

O A

IR

B

A

IA

N

O

IT

A

L Y

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

SS

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

LMM / BTN

FIRE PROTECTION DPS

F

A

D A

L C

O M

B A

T R

E S

C U

E H

E L

IC

O P

T

U L A

T O

R F

A C

IL

IT

Y

P

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

N O

R F

O L

K V

A A

T L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

TE

M

S C

O M

M A

N D

A T

LA

N

TI

C

DRAWFORM REVISION: 12 APRIL 2018

ISSUED FOR CONSTRUCTION – 10 MAR 2023

AS NOTED

B

IM

/1

P

S im u la to r/

B L D

G P

-1

-F

.r v t

/7

/2

:0

:5

P M

L

IF

E S

A F

E T

Y

C O

D E

A N

A L

Y S

IS

C

O N

T

IN

U E

D

G-102

S

IC

U R

E Z

Z A

A

N A

L

IS

I D

E I

C O

D

IC

I C

O N

T

IN

U A

T O

14125385

KMC

LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL LIFE SAFETY/ACCESSIBILITY CODE SUBMITTAL

STOCCAGGIO, GRUPPO S-1 6.503

COMMERCIALE, GRUPPO B 6.410

MONTAGGIO, GRUPPO A-3 3.530

870 3.285

OCCUPAZIONE

SUPERFICIE AMMISSIBILE PER

EDIFICIO A UN PIANO DOTATO DI

IMPIANTO SPRINKLER (MQ)

AREA

AGGIUNTIVA (MQ)

AREA TOTALE DEL

PRIMO PIANO (MQ)

AREA EDIFICABILE PER IL TIPO DI COSTRUZIONE II-B, STRUTTURA A UN PIANO A DESTINAZIONE MISTA NON

SEPARATE E DOTATA DI SISTEMA SPRINKLER

FIRE BARRIERS 1 3/4

BARRIERE

ANTINCENDIO 2 1 1/2

COMPONENTI PARETI E DIVISORI (ORA)

ASSEMBLAGGI DI PORTE

TAGLIAFUOCO (ORA)

FINITURA DI SOFFITTI E PARETI INTERNE DI CLASSE A - INDICE DI PROPAGAZIONE DELLE FIAMME 0-25, FUMO SVILUPPATO 0-450 FINITURA DI SOFFITTI E PARETI INTERNE DI CLASSE B - INDICE DI PROPAGAZIONE DELLE FIAMME 26-75, FUMO SVILUPPATO 0-450 FINITURA DI SOFFITTI E PARETI INTERNE DI CLASSE C - INDICE DI PROPAGAZIONE DELLE FIAMME 76-200, FUMO SVILUPPATO 0-450 FINITURA PAVIMENTAZIONE INTERNA DI CLASSE I - FLUSSO RADIANTE CRITICO NON INFERIORE A 0,45 W/CM2 FINITURA PAVIMENTAZIONE INTERNA DI CLASSE II - FLUSSO RADIANTE CRITICO NON SUPERIORE A 0,22 W/CM2 MA INFERIORE A 0,45 W/CM2

CLASSE I O II CLASSE I O II N/A

STORAGE

CLASSE A, B O C CLASSE A, B O C CLASSE A, B O C

CLASSE I O II CLASSE I O II N/A

NUOVA ATTIVITÀ

CLASSE A, B O C CLASS A OR B CLASSE A, B O C

CAPIENZA

COMPARTIMENTI DI USCITA E

CORRIDOI DI USCITA

CORRIDOI SALE E SPAZI CHIUSI

CLASSIFICAZIONE DELLE FINITURE INTERNE (CON SPRINKLER): NFPA 101 A.10.2.2

IRE-3 600 855 71

IRE-2 600 1.948 71

IRE-1 600 1.948 71

USCITE SINGOLE DAI LOCALI

E-3 1.200 1.200 100

E-2 1.200 1.200 100

E-1 1.200 1.200 100

USCITE

LARGHEZZA LIBERA

MINIMA (MM)

LARGHEZZA LIBERA

EFFETTIVA (MM)

CAPIENZA DEGLI

OCCUPANTI

CAPIENZA DI USCITA NFPA 101, 7.2.1.2.3

DISTANZE DI USCITA

MASSIME IDENTIFICATE

6 15 46

DEPOSITO, PERICOLO

ORDINARIO

30 30 122

DEPOSITO 15 30 91

CAPIENZA SENZA USCITA (M) PERCORSO COMUNE (M) DISTANZA PERCORSO (M)

LIMITAZIONI DI USCITA, STRUTTURA DOTATA DI SPRINKLER

NFPA 101, TABELLA A.7.6

SONO DISPONIBILI USCITE SINGOLE DAI LOCALI.

USCITE NECESSARIE = 2 USCITE SINGOLE = 4 USCITE DISPONIBILI = 3

CARICO TOTALE DEGLI OCCUPANTI 109

ATTREZZATURE MECCANICHE, ELETTRICHE E

DI ALTRO TIPO E STOCCAGGIO

46.5 265 6

PIANIFICAZIONE DELLA MISSIONE/BIBLIOTECA 1.4 26 19

SALA MULTIFUNZIONE 1.4 70 50

BAIA SIMULATORE 14 296 22

DEPOSITO 14 160 12

UTILIZZO

FATTORE DI CARICO DEGLI

OCCUPANTI (MQ/ PERSONA)

AREA (MQ)

CARICO DEGLI

OCCUPANTI

CALCOLO DEL CARICO DEGLI OCCUPANTI AGGIUNTA PRIMO PIANO: NFPA 101, TABELLA 7.3.1.2 E UFC 3-600-01 TABELLA 10-1

DPS

DIESEL FUEL SFD

ENGINES

SDx SDx

SD

x

SD

x

SD

x

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

Cux

Cux

Cux

Cux Cux

Cux

Cux

Cux Cux Cux Cux Cux Cux Cux Cux Cux Cux Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

C ux

Cux

Cux

Cux

Cux

Cux

Cux

Cux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

C ux

Eux Eux Eux Eux Eux Eux

Eux Eux

Eux Eux

Eux Eux Eux Eux Eux Eux Eux

Eu x

Eu x

Eu x

Eu x

Eu x

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux

Eux Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux Eux

Eux Eux

Eux Eux

Eux

Eux Eux

Eux Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux Eux Eux Eux Eux Eux Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux

Eux Eux Eux Eux Eux Eux Eux Eux Eux Eux Eux

Eux Eux

Eux

Eux

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux Eux

Eux EuxEux

EuxEux

MH_30

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FWx FWx FWx FWx FWx FWx FWx FWx FWx FWx FWx FWx FWx FWx

FWx

FWx

FWx FWx

FWx FWx

FWx

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x

FW

x FWx

LOCALE POMPE

FIRE - PUMP ROOM

ATTACCO VIGILI DEL FUOCO

FIRE DEPT. CONNECTION

DN 150

FIRE W

ATER

DN 200

FIRE WATER

DN 200

FIRE WATER

DN 200

FIRE WATER

DN 200

FIRE WATER

DN 200

FIRE WATER

FIRE W

ATER DN 200

DN 200

FIRE WATER

DN 200

FIRE W

ATER

DN

FI

RE

W

AT

ER

FWxFIRE WATER DN 200 I.E.=800

MH_28

FWx

FWx

FWx

FWx

FWx

FWx

FWx

FWx

FWx FWx

FWx FWxI.E.=800

FIRE WATER DN 200

DN 250

FIRE WATER I.E.=1350

FWx

FWx

FWx

FWx

FWx

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

W x

Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx Wx

W x

W x

W x

UNITÀ LAVAVEICOLI

WATER

DN 32

W

AT

ER

D

N

W

ATER DN 100

W

AT

ER

D

N

W

AT

ER

DN

0 -

B

RO

KE

N

I.E

MH_25

DN 110

G G

G

CONTATTORE CABINA GAS

GAS METER CABINETG

CENTRALE TERMICA

BOILER ROOM

G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G

IDRANTE

HIDRANT

VEHICLE

WASHDOWN UNIT

IDRANTE

HIDRANT

DD

C

C

C

C

C

C

E

MH_26

E

E

MH_17

E

E

FFFFFFFFFF

F

F23 ADAL COMBAT RESCUE

HELICOPTER SIMULATOR FACILITY

(P242)

BUILDING / EDIFICIO 7300

BUILDING / EDIFICIO 73003

BUILDING /

EDIFICIO

73011

5.94

14.05 19.21

19.66

3.62

25.86

37.41

6.

25.79

.9

8.

2.

6.69

24.88

8.64 19.59 24.43 11.54

15.21

14.52

.2

STRUTTURA DEL SIMULATORE DI

ELICOTTERO DA RICERCA E SOCCORSO

IN COMBATTIMENTO ADAL F23

PM

BRANCH MANAGER

CHIEF ENG/ARCH

1684614

AS NOTED

KMC

AVIANO

AIR BASE

07/11/22

Richard Tyler, PE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y

SY

M

D

ES

C R

IP

TI

O N

D

AT

E

AP

PR

ACDBBRF

100 AIRSIDE DRIVE

MOON TOWNSHIP, PA 15108

AV

IA

N O

A

IR

B

AS

E

AV

IA

N

O , I

TA

LY

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

LMM / BTN

FIRE PROTECTION DPS

F2

AD

AL

C O

M

BA

T R

ES

C

U E

H

EL

IC

O

PT

ER

SI

M

U

LA

TO

R

F

AC

IL

IT

Y (P

2)

N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G

S

YS

TE

M

S C

O M

M

AN

D

VI

R

G

IN

IA

B

EA

C

H , V

A

AT

LA

N

TI

C

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M S

CO

M

M

AN

D

AT

LA

NT

IC

DRAWFORM REVISION: 12 APRIL 2018

ISSUE FOR CONSTRUCTION - 10 MAR 2023

NORTH

NORD

GRAPHIC SCALE

SCALA GRAFICA

PLAN

NORTH

NORTH

NORD

PL

OT

TE

D

BY

LI

FE

S

AF

ET

Y

- C O

D E

C O

M

PL

IA

N

C E

SI

TE

P

LA

N

G-110

SCALE: 1:200

15M0 5M 10M

I:\

P -2

A vi an o

AB

H el o Si m ul at or

\0 5_

D el iv er ab le s\ D ra w in gs

\0

D W

G _C

AD

\0

C

_C iv il\ Sh ee t F ile s\

Ar ch iv e\

.1 0.

\1

- 1

9- G

-1

.d w g 3/

7/

:2 4:

P

M H op ki ns , A us tin

GENERAL NOTES / NOTE GENERALI

1. REFER TO C-001 FOR ADDITIONAL NOTES. / FARE RIFERIMENTO A C-001 PER

ULTERIORI NOTE.

2. REFER TO C-004 FOR CIVIL LEGEND AND ABBREVIATIONS. / FARE RIFERIMENTO

A C-004 PER LEGENDA CIVILE E ABBREVIAZIONI.

3. REFER TO G-101 FOR BUILDING LIFE SAFETY CODE ANALYSIS. / FARE

RIFERIMENTO A G-101 PER ANALISI DEL CODICE DI SICUREZZA VITALE

DELL'EDIFICIO.

BUILDING 7300 IS 17.3 METERS FROM BUILDING 73003. / L'EDIFICIO 7300

SI TROVA A 17,3 METRI DALL'EDIFICIO 73003.

LIMITS OF DISTURBANCE. / LIMITI DI DISTURBO.2

4 FIRE DEPARTMENT VEHICLE ACCESS. / ACCESSO DEI MEZZI DEI VIGILI

DEL FUOCO.

ADDITION FIRE DEPARTMENT BUILDING ACCESS. / ACCESSO ALL'EDIFICIO

DEI VIGILI DEL FUOCO PER PARTE AGGIUNTA.6

FIRE DEPARTMENT CONNECTION. / ATTACCO PER AUTOPOMPA.7

8 EXISTING FIRE HYDRANT. / IDRANTE ESISTENTE.

SHEET KEYNOTES / FOGLIO NOTE PRINCIPALI

FIRE DEPARTMENT ACCESS GATE. / VIA DI ACCESSO DEL VIGILI DEL

FUOCO

9 EXIT DISCHARGE PATH. / PERCORSO DI DEFLUSSO.

10 FIRE PUMP ROOM. / LOCALE POMPA ANTINCENDIO.

11 LOCATION OF BACKFLOW PREVENTER ASSEMBLY. /

PLACEHOLDER

INTENDED MAIN FIRE DEPARTMENT ENTRANCE TO ADDITION. / INGRESSO

PRINCIPALE ALLA PARTE AGGIUNTA PER I VIGILI DEL FUOCO.

14125386

DPS

DN

DN

DN

FE

C

FE

FEFE

FE

C

FE

FE

FEC

FE

FEC

H

R

2 HR 2 HR

H

R

H

R

H R

H

R

B

S-1

S-1 x4x3x2x1

SPARES STORAGE

ROOM / LOCALE

STOCCAGGIO RICAMBI

MISSION PLANNING /

LIBRARY /

PIANIFICAZIONE

MISSIONE /

BIBLIOTECA

UNISEX LATRINE /

SERVIZI IGIENICI

UNISEX081

ELECTRICAL /

ELETTRICA

MECHANICAL /

MECCANICA

MAINTENANCE OFFICE

/ UFFICIO

MANUTENZIONE

AVDTT / AVDTT

MULTI-PURPOSE

ROOM A / SALA

MULTIFUNZIONE A

MULTI-PURPOSE

ROOM B / SALA

MULTIFUNZIONE B

CORRIDOR /

CORRIDOIO

OFT SIMULATOR BAY /

BAIA SIMULATORE

OFT

SIMULATOR MX / TOOL

STORAGE / ICS

SUPPORT /

SIMULATORE MX /

MAGAZZINO

STRUMENTI /

SUPPORTO ICS

COMPUTER / IG /

COMPUTER /IG

BOILER / CALDAIA

TELECOM / TELECOM

H

R

2 HR 2 HR

H

R

JAN / SERVIZIO

2 HR

H

R

H R

2 HR

H R

H

R

S-1

1 HR

H

R

H

R

1 HR 1 HR

1 2 3 4 4' 5 6 7 8 9

I

H

G

F

D

C

B

A

[1/1.4]

[1/1.4]

M

M

9M

32M

M

M

SP

AC

E

DI

AG

ONA

L

LE

NG

TH

: 3 2.

M

EXIT SEPARATION DISTANCE: 17.5 M

SPACE DIAGONAL LENGTH: 26.1 M

EXIT SEPARATION DISTANCE: 11 M

R

FM

C P

DISTANZA TRA LE USCITE: 17,5 M

LU

NG

HE

ZZ

A

DI

AG

ONA

LE

D

EL

LO

S

PA

ZI

O: 3

2, M

LUNGHEZZA DIAGONALE DELLO SPAZIO: 26,1 M

DISTANZA TRA LE USCITE: 11 M

6M

M

IRE-1IRE-2IRE-3

5M

VESTIBULE /

VESTIBOLO

GENERAL NOTES / NOTE GENERALI

1. REFER TO SHEET G-101 FOR GENERAL NOTES. /

PER NOTE GENERALI, FARE RIFERIMENTO ALLA SCHEDA G-101.

2. AREAS ARE CONSIDERED BUSINESS UNLESS OTHERWISE NOTED. /

LE AREE VENGONO CONSIDERATE COME COMMERCIALI SE NON

DIVERSAMENTE DEFINITE.

3. EXIT SIGNS AND FIRE EXTINGUISHERS ARE SHOWN FOR INFORMATION

ONLY. REFER TO ELECTRICAL AND ARCHITECTURAL DRAWINGS FOR EXACT

LOCATIONS AND DETAILS. /

I SEGNALI DI USCITA E GLI ESTINTORI VENGONO MOSTRATI SOLO A TITOLO

INFORMATIVO. FARE RIFERIMENTO AI DISEGNI ELETTRICI E ARCHITETTONICI

PER DETTAGLI E POSIZIONI EFFETTIVE.

4. FIRE EXTINGUISHER CABINETS AND FIRE ALARM COMPONENTS IN THE

CORRIDOR MUST NOT PROTRUDE MORE THAN 4 INCHES INTO THE

CORRIDOR. /

GLI ARMADIETTI DEGLI ESTINTORI E I COMPONENTI DELL'ALLARME

ANTINCENDIO NEL CORRIDOIO POSSONO SPORGERE NEL CORRIDOIO PER

MASSIMO 4 POLLICI/10 CM.

1 HOUR FIRE BARRIER /

BARRIERA ANTINCENDIO 1 ORA

LEGEND / LEGENDA

DESCRIPTION / DESCRIZIONE SYMBOL / SIMBOLO

SMOKE PARTITION /

PARATIA ANTIFUMO

FIRE EXTINGUISHER / ESTINTORE

FIRE EXTINGUISHER CABINET /

ARMADIETTO ESTINTORE

OCCUPANCY LOAD /

CARICO DEGLI CCUPANTI

EXIT NUMBER / NUMERO USCITA

EXIT SIGN / SEGNALETICA DI USCITA

TRAVEL DISTANCE /

DISTANZA PERCORSA

COMMON PATH OF TRAVEL /

PERCORSO COMUNE DI ESODO

DEAD END / SENZA USCITA

OCCUPANT LOAD FACTOR /

FATTORE DI CARICO DEGLI OCCUPANTI

[X/Y] PERSONS/ SQUARE METER

PERSONE/METRO QUADRO

2 HOUR FIRE BARRIER /

BARRIERA ANTINCENDIO 2 ORE

AREA NOT IN CONTRACT /

AREA FUORI CONTRATTO

0M

SP

1 HR

2 HR

E-0

0M

0M

IRE-0

0OCCUPANCY CLASSIFICATION /

CLASSIFICAZIONE DELL'OCCUPAZIONE

INDIVIDUAL ROOM EXIT /

USCITE SINGOLE DAI LOCALI

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

1684614

07/11/22

Richard Tyler, PE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

100 AIRSIDE DRIVE

MOON TOWNSHIP, PA 15108

A V

IA

N

O A

IR

B

A

IA

N

O

IT

A

L Y

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

SS

IF

IE

D

F

IL

E N

A M

E

P

LO

T T

E D

LMM / BTN

FIRE PROTECTION DPS

F

A

D A

L C

O M

B A

T R

E S

C U

E H

E L

IC

O P

T

U L A

T O

R F

A C

IL

IT

Y

P

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

N O

R F

O L

K V

A A

T L A

N T

IC

D

E S

IG

N

A N

D C

O N

S T

R U

C T

IO

N

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

TE

M

S C

O M

M A

N D

A T

LA

N

TI

C

DRAWFORM REVISION: 12 APRIL 2018

ISSUED FOR CONSTRUCTION – 10 MAR 2023

AS NOTED

B

IM

/1

P

S im u la to r/

B L D

G P

-1

-F

.r v t

/7

/2

:1

:0

P M

L

IF

E S

A F

E T

Y

F

IR

S T

F L

O O

R P

L A

N

G-111

S

IC

U R

E Z

Z A

P

L A

N

IM

E T

R

IA

P R

IM

O

P

IA

N O

14125387

KMC

SCALE / SCALA: 1 : 100

LIFE SAFETY - FIRST FLOOR PLAN / SICUREZZA VITALE - PLANIMETRIA PRIMO PIANO

A1

MAXIMUM IDENTIFIED

EGRESS DISTANCES

6 15 46

STORAGE, ORDINARY

HAZARD

30 30 122

BUSINESS 15 30 91

OCCUPANCY DEAD END (M) COMMON PATH (M) TRAVEL DISTANCE (M)

EGRESS LIMITATIONS, SPRINKLERED FACILITY

NFPA 101, TABLE A.7.6

KEYNOTES / NOTE PRINCIPALI

1 FIRE ALARM/MASS NOTIFICATION SYSTEM CONTROL PANEL. / PANNELLO DI

CONTROLLO DEL SISTEMA DI NOTIFICA DI MASSA/ALLARME ANTINCENDIO.

2 REVERSE EXISTING EXIT SIGN TO REFLECT NEW EGRESS ROUTE. /

INVERTIRE IL SEGNALE DI USCITA ESISTENTE PER RIFLETTERE IL NUOVO

PERCORSO DI USCITA.

DISTANZE DI USCITA

MASSIME IDENTIFICATE

6 15 46

DEPOSITO, PERICOLO

ORDINARIO

30 30 122

DEPOSITO 15 30 91

CAPIENZA SENZA USCITA (M) PERCORSO COMUNE (M) DISTANZA PERCORSO (M)

LIMITAZIONI DI USCITA, STRUTTURA DOTATA DI SPRINKLER

NFPA 101, TABELLA A.7.6

MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER /

MASSIMA PERCORSO DALL'ESTINTORE 20 M

MAXIMUM FLOOR AREA PER EXTINGUISHER /

SUPERFICIE MASSIMA PER ESTINTORE

550 MQ

MAXIMUM FLOOR AREA PER UNIT OF A / SUPERFICIE

MASSIMA PER UNITA' DI A

139 MQ

PROVIDED EXTINGUISHER RATING / VALUTAZIONE

DELL'ESTINTORE FORNITO

4-A:80B:C (34A:144B)

NFPA 10 (2018) TABLE 6.2.1.1 / NFPA 10 (2018) TABELLA 6.2.1.1

DIMENSIONE E POSIZIONAMENTO DELL'ESTINTORE PER RISCHI ORDINARI DI CLASSE A

FIRE EXTINGUISHER SIZE AND PLACEMENT FOR ORDINARY CLASS A HAZARDS

E-1

E-2

E-3

DPS

G-101-LIFE SAFETY -CODE ANALYSIS / SICUREZZA -ANALISI DEI CODICI
G-102-LIFE SAFETY -CODE ANALYSIS CONTINUED / SICUREZZA -ANALISI DEI CODICI CONTINUATO
G-110-LIFE SAFETY - CODE COMPLIANCE SITE PLAN
G-111-LIFE SAFETY -FIRST FLOOR PLAN / SICUREZZA -PLANIMETRIA PRIMO PIANO
2023-03-14T13:18:47-0400
Amanda Silva
2023-03-14T13:22:48-0400
Amanda Silva
2023-03-14T13:23:29-0400
Brandon Fombelle
2023-03-14T13:24:11-0400
Amanda Silva
2023-03-15T14:17:46-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-03-15T14:18:15-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-03-15T14:18:15-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-03-15T14:18:16-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.

File details come from the government source that posted it. Updated .