This document includes an architectural drawing and details for a partial ground floor plan for an electrical power plant project at Camp Lemonnier, Djibouti. The drawing provides specifications for partition types, notes on dimensions and finishes, and identifies various mechanical, electrical, and plumbing elements to be included. It also lists Solicitation Number N6247023R0001 for the design-bid-build project P-332/P-334 Electrical Power Plant at Camp Lemonnier, to be awarded by the Department of the Navy Naval Facilities Engineering Command. The solicitation is for the design and construction of the electrical power plant to include day tanks for fuel oil, lube oil tanks, switchgear, transformers, ventilation systems, and other utilities as depicted on the architectural drawing.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL
JANITOR
CORRIDOR
VESTIBULE
DAY TANK
DAY TANK
DAY TANK
LUBE OIL
VESTIBULE
101A101B
103A
124A
116B123A
123C 123D
125A
126A
127A
114A
114B114C
C300R3
C300R3
C300R3
C250S100 C250S100
C300R3
S150N
C300R3 C300R3
S150N
C300S100
C300R3
C300R3
S150N S150N
106A105A104A
102A
C300S100
C300S100
C300S100
BATTERY
TYP
TYP
TYP
CA B D
123B
TYP.
ENGINE
HALL
123E
123F
115A
63 63
E
FUEL PUMP
ROOM
128A
C250
C250
C250R2
PARTITION TYPES
TAG SYMBOL TYPE DESCRIPTION
GENERAL PARTITION NOTES:
1. METAL STUD GAUGE AND SPACING TO BE DETERMINED BY METAL STUD MANUFACTURER GUIDELINES AND TEST REPORTS IN ORDER TO MEET THE FOLLOWING PERFORMANCE REQUIREMENTS FOR HORIZONTAL DEFLECTION, UON IN THE SPECIFICATIONS.
A. TYPICAL PARTITION STUD GAUGE SHALL BE DESIGNED TO AN L/120 DEFLECTION OR LESS AS REQUIRED BY CODE, UON.
2. PARTITION DIMENSIONING AND PARTITION TYPE DESIGNATIONS ARE INDEPENDENT OF APPLIED FINISHES. REFER TO FINISH SCHEDULE FOR
INFORMATION REGARDING APPLIED FINISHES.
3. ALL PARTITIONS TO RUN FROM FINISH FLOOR TO UNDERSIDE OF DECK, UON.
4. PROVIDE WATER RESISTANT GWB FULL LENGTH OF TOILET / URINAL WALLS AND WITHIN 2 FEET HORIZONTALLY AND 4 FEET VERTICALLY OF SINKS, LAVATORIES AND JANITORS CLOSETS AND ARE NOT SCHEDULED TO RECEIVE TILE.
5. REFER TO LIFE SAFETY PLAN FOR LOCATIONS OF WALLS WITH HOURLY RATINGS.
6. INSTALL ALL FIRE RATED WALL ASSEMBLIES IN STRICT ACCORDANCE WITH APPLICABLE CODES, ORDINANCE, OR LAWS AND UL DESIGN.
7. ALL PENETRATIONS IN RATED WALL ASSEMBLIES SHALL BE BY UL APPROVED FIRE RATED ASSEMBLIES.
8. ALL FIRE RATED AND SMOKE BARRIER PARTITIONS SHALL BE LABELED ABOVE CEILING WITH 2" TALL (MIN) LETTERS AT NOT MORE THAN 8'-0" OC.
AN EXAMPLE LABEL IS AS FOLLOWS: "ONE HOUR FIRE PARTITION"
S100N
S150N
100 STL STUDS WITH 13 GWB (EACH SIDE) AND 89 SOUND ATTENUATION BLANKETS
150 STL STUDS WITH 13 GWB (EACH SIDE) AND 89 SOUND ATTENUATION BLANKETS
SN
- STL STUD
- INSULATED
CS
- CONCRETE
- STL STUD
ENCLOSURE
- INSULATED
C250S100
C300S100
250 CONCRETE (3 HR RATING), 100 STL STUDS @ 400 OC WITH 13 GWB (ONE SIDE) AND 89 SOUND
ATTENUATION BLANKETS
300 CONCRETE (3 HR RATING), 100 STL STUDS @ 400 OC WITH 13 GWB (ONE SIDE) AND 89 SOUND
ATTENUATION BLANKETS
C250 250 CONCRETE
C
- CONCRETE
C250R3
C300R3
250 CONCRETE, 3 HR RATING
300 CONCRETE, 3 HR RATING
CR
- CONCRETE
- RATED
C300 300 CONCRETE
1. PLAN DIMENSIONS SHOWN ARE TO FACE OF FRAMING MEMBERS, FACE OF
CONCRETE, FACE OF EXISTING WALL, AND TO CENTER LINE OF COLUMNS,
EXCLUSIVE OF INTERIOR WALLS.
2. ALL INTERIOR DIMENSIONS ARE TO FACE OF PARTITION ASSEMBLY AS DEFINED
BY THE PARTITION SCHEDULE AND ARE EXCLUSIVE OF ANY APPLIED FINISH.
3. ALL DIMENSIONS TO BE FIELD VERIFIED PRIOR TO INSTALLATION OF EQUIPMENT
/ SHELVING / CASEWORK.
4. ANY CONFLICTING INFORMATION BETWEEN THE ARCHITECTURAL DRAWINGS
AND OTHER DRAWINGS OR SPECIFICATIONS IN THIS SET SHALL BE NOTED IN
WRITING TO THE ARCHITECT FOR REVIEW AND MUST BE CLARIFIED PRIOR TO
COMMENCING THE CONSTRUCTION IN QUESTION.
5. PROVIDE FIRE RETARDANT TREATED WOOD BLOCKING IN METAL STUD
PARTITIONS FOR MOUNTING FIXTURES, MILLWORK, SHELVING, HARDWARE,
DOOR STOPS AND OTHER EQUIPMENT.
6. VERIFY AND COORDINATE PENETRATIONS THROUGH FOUNDATION, FLOOR
SLAB, ROOF ASSEMBLIES, AND PARTITIONS WITH APPROPRIATE ENGINEERING
DRAWINGS.
7. VERIFY AND COORDINATE FINISH FLOOR ELEVATIONS WITH CIVIL AND
STRUCTURAL PRIOR TO COMMENCING CONSTRUCTION. NOTIFY ARCHITECT IN
WRITING BEFORE CONSTRUCTION OF ANY CONFLICTS.
8. REFER TO SHEET AE601 FOR DOOR SCHEDULE.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
DESIGN DIRECTOR
FIRE PROTECTION
N A V A L F A C
IL
IT
IE
S E N G
IN
E E R
IN
G S Y S T E M S C O M M A N D A T L A N T
IC
N O
R F
O L
K V
A
AS NOTED
1643338
A T
LA
N
T
IC
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N
DPS
/2
/2
:0 :4
A
M B
IM
/P
E le c tr ic a l P o w e r
P la n t F
D A
/8
P
E le c t P w r
P ln t F
D A
A
.r v t
AE103
P -3 /P -3 E L E C T R
IC
A L P O W E R P L A N T
P A R
TI
A L G R O U N D F
LO
O R P
LA
N B
RAM
14124452
SEB SEB
JWH/SCN
D
JI
B O
U T
I, D
JI
B
O U
T I
C A
M P
L E
M O
N N
IE
R
RICHARD STEPHENS
DER
1 : 100A1
GROUND LEVEL - PARTIAL B
SEE SHEET AE102
1:100 0 9 10m87654321
GRAPHIC SCALE(S)
GENERAL NOTES
KEY PLAN
# KEY NOTES
A
B
1 METAL GRATING OVER UTILITY TRENCH
8 ELECTRICAL PANEL. SEE ELECTRICAL.
12 FUEL OIL DAY TANK. SEE MECHANICAL.
13 FUEL OIL OVERFLOW TANK. SEE MECHANICAL.
14 FUEL OIL OVERFLOW PUMP. SEE MECHANICAL.
15 EMERGENCY EYEWASH / SHOWER. SEE PLUMBING.
16 PREFINISHED METAL DOWNSPOUT WITH SPLASH BLOCK.
27 SWITCHGEAR. SEE ELECTRICAL.
45 EXHAUST STACK. SEE MECHANICAL.
46 LUBE OIL TANK. SEE MECHANICAL.
47 LUBE OIL PUMP. SEE MECHANICAL.
48 PREFINISHED METAL DOWNSPOUT. CONNECT TO UNDERGROUND PIPING. SEE
CIVIL.
51 EXHAUST STACK SUPPORT. SEE STRUCTURAL.
52 PREFINISHED METAL STAIR WITH METAL GRATING TREADS.
53 VENTILATION LOUVER. SEE MECHANICAL.
54 ELECTRIC WATER COOLER. SEE PLUMBING.
55 STEEL BOLLARD, CONCRETE-FILLED. SEE CIVIL.
61 TRANSFORMER. SEE ELECTRICAL.
62 CONCRETE EQUIPMENT PAD. SEE STRUCTURAL.
63 CONCRETE CONTAINMENT DIKE. SEE STRUCTURAL.
64 METAL BAR GRATING OVER CONTAINMENT DIKE
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
E V
IS
IO
N
D A
T E
| Sheets |
| AE103 - PARTIAL GROUND FLOOR PLAN - B |