Attachment H - Drawings 12 of 18 MECHANICAL.pdf

PDF 1 MB Posted

Attached to
P-332/P-334, Design-Bid-Build, Electrical Power Plant at Camp Lemonnier, Djibouti
Solicitation number
N6247023R0001
Issued by

About this file

This set of mechanical drawings and specifications is for the design and construction of HVAC systems to support the electrical power plant at Camp Lemonnier in Djibouti. The project includes one air handling unit with a split dehumidification unit, twelve fan powered VAV terminal units, two inline exhaust fans, ductwork, piping, controls, and other associated mechanical equipment. The specifications provide requirements for equipment, materials, testing, coordination between trades, submittals, start-up and commissioning. Control sequences are defined for the air handling unit and terminal boxes. Point lists, schedules and details are included to fully define the mechanical systems and ensure a code-compliant, functional design when installed as shown.

View the file

Other files

File Type Posted
N6247023R0001 Amendment 0009.pdf PDF
N6247023R0001 Amend 0008.pdf PDF
Attachment T - CE18 Electrical.pdf PDF
Attachment S - Electrical ES401 ES601.pdf PDF
N6247023R0001 Amend 0007.pdf PDF
Attachment R - P332 Elect Pwr Plnt FDA - MECH.pdf PDF
N6247023R0001 Amend 0006.pdf PDF
Revised Attachment E - Price Proposal Form_11OCT2023.pdf PDF
Attachment L - P332 Elect Pwr Plnt FDA - AE105 - ROOF PLAN.pdf PDF
Attachment K - P332 Elect Pwr Plnt FDA - AE103 - PARTIAL GROUND FLOOR PLAN - B.pdf PDF
N6247023R0001 Amend 0005.pdf PDF
Attachment N - P332 Elect Pwr Plnt FDA - AE402 - STAIR PLANS.pdf PDF
Attachment P - P332 Elect Pwr Plnt FDA - AF102 - GROUND LEVEL FINISH AND SIGNAGE PLAN - PARTIAL B.pdf PDF
Attachment Q - P332 Elect Pwr Plnt FDA - AG601 - SIGNAGE DETAILS AND SCHEDULE.pdf PDF
Attachment M - P332 Elect Pwr Plnt FDA - AE201 - EXTERIOR ELEVATIONS.pdf PDF
Attachment O - P332 Elect Pwr Plnt FDA - AF101 - GROUND LEVEL FINISH AND SIGNAGE PLAN - PARTIAL A.pdf PDF
N6247023R0001 Amend 0004.pdf PDF
N6247023R0001 Amend 0003.pdf PDF
N6247023R0001 Amend 0002.pdf PDF
Attachment J - Site Visit Log.pdf PDF
N6247023R0001 Amend 0001.pdf PDF
N6247023R0001.pdf PDF
Attachment A - Pre-Proposal Inquiry Form.xls XLS spreadsheet
Attachment H - Drawings 3 of 18 GEOTECH.pdf PDF
Attachment H - Drawings 10 of 18 FIRE PROTECTION.pdf PDF
Attachment H - Drawings 11 of 18 PLUMBING.pdf PDF
Attachment I Base Access Request Form.pdf PDF
Attachment H - Drawings 1 of 18 GENERAL.pdf PDF
Attachment B - SEC-NAV_5512_1_11787 Form.pdf PDF
Attachment H - Drawings 17 of 18 ELECTRICAL.pdf PDF
Attachment C - Construction Experience Project Data Sheet.pdf PDF
Attachment E - Price Proposal Form.pdf PDF
Attachment F - LRA Commercial Vehicle Inspection Procedures.pdf PDF
Attachment H - Specifications 1 of 3.pdf PDF
Attachment H - Drawings 7 of 18 STRUCTURAL.pdf PDF
Attachment H - Drawings 16 of 18 ELECTRICAL.pdf PDF
Attachment H - Drawings 14 of 18 MECHANICAL.pdf PDF
Attachment H - Drawings 2 of 18 LIFE SAFETY.pdf PDF
Attachment H - Drawings 18 of 18 TELECOM.pdf PDF
Attachment H - Specifications 3 of 3.pdf PDF
Attachment H - Specifications 2 of 3.pdf PDF
Attachment D - Past Performance Questionnaire (PPQ).pdf PDF
Attachment H - Drawings 9 of 18 INTERIORS.pdf PDF
Attachment H - Drawings 8 of 18 ARCHITECTURAL.pdf PDF
Attachment H - Drawings 6 of 18 CIVIL.pdf PDF
Attachment H - Drawings 5 of 18 CATHODIC PROTECTION.pdf PDF
Attachment H - Drawings 15 of 18 ELECTRICAL.pdf PDF
Attachment H - Drawings 13 of 18 MECHANICAL.pdf PDF
Attachment H - Drawings 4 of 18 CIVIL.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

# DEMOLITION NOTE IDENTIFICATION

INDICATES ITEM TO BE REMOVED

FLEXIBLE DUCT CONNECTION

VERTICAL FIRE DAMPER

VOLUME DAMPER

CEILING RETURN, EXHAUST OR TRANSFER REGISTER

CEILING SUPPLY DIFFUSER

MITERED ELBOW WITH TURNING VANES

RETURN DUCT TURNING UP

RETURN DUCT TURNING DOWN

EXHAUST DUCT TURNING UP

EXHAUST DUCT TURNING DOWN

SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)

SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)

200x200 SQUARE OR RECTANGULAR DUCTWORK

PIPE TURNING UP

PIPE TURNING DOWN

DUCT SMOKE DETECTOR

F10/6

(CFM)

EXHAUST GRILLE DESIGNATION

WITH CFM INDICATED

A6

(CFM)

CEILING DIFFUSER DESIGNATION

WITH CFM INDICATED

G20/20 RETURN GRILLE DESIGNATION

GENERAL

DUCTWORK

MOTORIZED CONTROL DAMPER

INDICATES ROUND DUCTWORK

FLEXIBLE CONNECTION

RETURN, EXHAUST OR TRANSFER AIR FLOW

SUPPLY AIR FLOW

ACCESS DOORAD

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

ALUMINUMALUM

ARCHITECTURALARCH

DIAMETERDIA

DRAWINGDWG

EXISTINGEX

EXISTING TO REMAINEXR

GAUGEGA

GOVERNMENT FURNISHED

CONTRACTOR INSTALLED

GFCI

MISCELLANEOUSMISC

NOT IN CONTRACTNIC

TYPICALTYP

UNLESS OTHERWISE

NOTED

UON

GALVANIZEDGALV

RUN THRU JOISTSRBJ

REMOVE EXISTINGREX

AUTOMATIC AIR VENT

VALVES AND ACCESSORIES

AUTOMATIC FLOW CONTROL VALVE

BACKFLOW PREVENTER

BALL VALVE

BOTTOM CONNECTION

BUTTERFLY VALVE

CAPPED PIPE

CHECK VALVE

CLEAN OUT

DIRECTION OF FLOW

FLANGED CONNECTION

FLEXIBLE CONNECTION

FLOW METER

BALL VALVE FOR 2" & UNDER

BUTTERFLY FOR 2.5" AND LARGER

METERED BALANCING VALVE

W/PRESSURE TAPS

PRESSURE/TEMPERATURE TEST PLUG

PT

PIPE ANCHOR (W=WALL, C=CEILING, F=FLOOR)W,C,F

PIPE GUIDE

PIPE SLEEVE

PITCH

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

STRAINER

STRAINER W/BLOW DOWN VALVE

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

THERMOMETER

THERMOSTATIC RADIATOR VALVE

TOP CONNECTION

UNION

CONTROLS

CWR

CHS

CHR

CDWS

CDWR

HWS

RS

RL

D

CWS

RHG

CHILLED WATER RETURN

HOT WATER SUPPLY

HOT WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

DIRECTION OF FLOW

CONDENSATE DRAIN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CHILLED/HOT WATER SUPPLY

CHILLED/HOT WATER RETURN

CHILLED WATER SUPPLY

REFRIGERANT HOT GAS

PIPING

FLEXIBLE DUCT CONNECTION

LEGEND

M

200/200 OVAL DUCTWORK

# CONSTRUCTION NOTE IDENTIFICATION

INDICATES NEW ITEM

INDICATES EXISTING ITEM

REMOVE TO THIS POINT

CONNECT NEW TO EXISTING

ROOM NUMBER IDENTIFICATION

Ø

PUMP

PD PUMPED CONDENSATE

HWR

ANALOG INPUT (TO PANEL)

ANALOG OUTPUT (OUT OF PANEL)

DIGITAL INPUT (TO PANEL)

DIGITAL OUTPUT (OUT OF PANEL)

TWO WAY CONTROL VALVE

COMMON

CONTROL WIRING (SIGNAL PATH)

DATA TERMINAL CABINET

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE SENSOR

DUCT SMOKE DETECTOR

FAN VARIABLE SPEED SWITCH

AI

DI

DO

C

HIGH LIMIT TEMPERATURE SENSOR

HUMIDISTAT

LOCAL TEMPERATURE CONTROL PANEL

MOTOR

MOTORIZED CONTROL DAMPER

MOTOR STARTER

NORMALLY CLOSEDNC

NORMALLY OPENEDNO

POWER WIRINGEP

SENSOR

STATIC PRESSURE SENSOR

SWITCH

ZONE TEMPERATURE SENSOR

TEMPERATURE TRANSMITTER

CURRENT SENSING RELAY

NORMALLY OPEN CONTROLS

NORMALLY CLOSED CONTROLS

M

M

AO

S

P

T

TT

DTC

DPS

DSD

HL

TCP

MS

DP

VSF

H

S

CSR

DAMPER

FILTER

FAN ON-OFF SWITCHF

EMERGENCY SHUT-DOWN SWITCHE

METERM

HYDROGEN SENSOR AND PANELH

SPLIT DEHUMIDIFICATION UNITSDU

AIR HANDLING UNITAHU

CONTROL VALVE TAGV-1H

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N

DPS

/1 /2

:5

:0

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH001

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

M E

C H

A N

IC

A

L

LE

G E

N D

BAT

14124493

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL MECHANICAL

DRAWINGS WILL BE SHOWN ON THE RESPECTIVE MECHANICAL DRAWING.

2. PROVIDE A COMPLETE HVAC SYSTEM TO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT FOR A COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALL NECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOT SPECIFICALLY CALLED OUT.

3. CONFORM TO APPLICABLE ASHRAE, NFPA, AND SMACNA STANDARDS AND OTHER REGULATORY BODIES HAVING JURISDICTION OVER THE CLASS OF

WORK.

4. MATERIALS AND EQUIPMENT MUST HAVE STAMPS OR SEALS OF ARI, ASME, UL, AND ASTM.

5. MAKE TESTS FOR ACCEPTANCE AND APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS MUST BE PERFORMED IN THE PRESENCE OF THE CONTRACTING OFFICER UNLESS OTHERWISE WAIVED IN WRITING.

6. COORDINATE WORK WITH THE OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE

USE OF SPACE.

7. EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE SUBSTITUTED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICE, CIRCUIT BREAKERS AND CONDUIT SIZES ARE APPROPRIATELY MODIFIED AT NO COST TO THE OWNER.

8. RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING UNLESS OTHERWISE NOTED.

9. MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL DUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT ACCEPTABLE.

10. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES. FINISH AND COLOR TO BE

SELECTED BY CONTRACTING OFFICER FROM MANUFACTURER'S STANDARD PALETTE.

11. DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.

12. ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN, INSTALL DOUBLE WALL TURNING VANES. RADIUS ELBOWS SHALL HAVE A MINIMUM CENTERLINE RADIUS OF CURVATURE OF 1.5 TIMES DUCT WIDTH OR DIAMETER

13. PROVIDE DYNAMIC FIRE DAMPER IN ACCORDANCE WITH THEIR UL LISTING AND THE REQUIREMENTS OF NFPA 90A.

14. DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.

15. LAYOUT OF PIPING AND DUCTWORK IS DIAGRAMMATIC. RUN ALL EXPOSED PIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESS OTHERWISE NOTED.

ALLOW FOR RISES, DROPS AND OFFSETS AS REQUIRED.

16. EXTEND DRAIN LINES TO NEAREST DRAIN OR AS INDICATED. ALL CONDENSATE DRAIN PIPING MUST BE TRAPPED AND PITCHED DOWN IN DIRECTION OF

FLOW A MINIMUM OF 12.5%.

17. INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. PIPING MUST NOT INTERFERE WITH FILTER PULL. MAINTAIN EQUIPMENT MANUFACTURER'S RECOMMENDED MINIMUM SERVICE CLEARANCE.

18. MECHANICAL CONTRACTOR MUST PROVIDE AUTOMATIC CONTROL DEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE SWITCHES WHICH ARE ASSOCIATED WITH MECHANICAL EQUIPMENT AND ASSOCIATED CONTROL WIRING FROM STARTER TO THE CONTROL DEVICE. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM POWER SOURCE TO DISCONNECT SWITCH, FROM DISCONNECT SWITCH TO STARTER, AND

FROM STARTER TO THE EQUIPMENT.

19. ALL CONTROL WIRING EXCEPT IN EQUIPMENT ROOMS MUST BE RUN CONCEALED. WIRING IN WALLS MUST BE IN CONDUIT. ALL WIRING MUST BE PLENUM RATED. CONTROL WIRING IN EXPOSED AREAS SHALL BE BUNDLED AND SECURED OR RUN IN CONDUIT. NO WIRING SHALL BE SURFACE MOUNTED IN FINISHED SPACES. ALL ELECTRICAL WORK MUST BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE.

20. LOCATE THERMOSTATS 1220mm ABOVE FINISHED FLOOR OR AS NOTED ON THE PLANS.

21. ALL VALVES ARE FULL LINE SIZE EXCEPT CONTROL AND BALANCING VALVES. SIZE CONTROL VALVES TO OPERATE ACROSS THE FULL RANGE OF FLOW

AT THE COIL SERVED.

22. PROVIDE PRESSURE/TEMPERATURE (P/T) PLUGS, WITH CAPS UP AND DOWNSTREAM OF ALL EQUIPMENT, AT THE SUPPLY AND RETURN TAPS OF ALL PIPING BRANCHES AND WHERE INDICATED. PROVIDE EXTENDED PLUGS AND LABELS WHERE PIPING IS INSULATED. PROVIDE REMOVABLE INSULATION

PLUG.

23. PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS AND THE ENDS OF ALL PIPING LOOPS. PROVIDE 15mm DRAIN VALVES AT LOW POINTS IN PIPING.

PROVIDE MINIMUM PITCH SUFFICIENT TO ENSURE ADEQUATE VENTING AND DRAINING.

24. PROVIDE FLUSHING VALVES AND TEES AT BOTH SIDES OF ALL EQUIPMENT. TAPS MUST MATCH EQUIPMENT PIPING UP TO 25mm. FOR LARGER EQUIPMENT AND PIPE LOOPS PROVIDE 40mm TAPS AND VALVES.

25. LOCATE AND SIZE 100mm THICK CONCRETE HOUSEKEEPING PADS AND CURBS (PROVIDED BY GENERAL CONTRACTOR) IN ACCORDANCE WITH ACTUAL EQUIPMENT PURCHASED. EXTEND PAD BEYOND EQUIPMENT FOR 150mm IN ALL DIRECTIONS.

26. REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE AND PHASE REQUIREMENTS FOR ALL EQUIPMENT REQUIRING AN ELECTRICAL CONNECTION.

27. UNLESS OTHERWISE NOTED, FLEXIBLE CONNECTORS AND RIGID DUCT RUNOUTS SERVING A SINGLE GRILLE/REGISTER/DIFFUSER MUST BE THE SAME

SIZE AS THE GRILLE/REGISTER/DIFFUSER NECK. REFER TO SCHEDULES FOR NECK SIZES.

28. ALL REFRIGERANT PIPING MUST BE SIZED IN ACCORDANCE WITH THE MANUFACTURER’S WRITTEN INSTRUCTIONS.

29. PROVIDE ACCESS PANELS WHERE COMPONENTS REQUIREING ACCESS ARE INSTALLED BEHIND WALLS OR ABOVE INACCESSIBLE CEILINGS. REFER TO

ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

GENERAL NOTES

DESIGN CONDITIONS

SPACE/UNIT TYPE

WINTER INDOOR WINTER OUTDOOR SUMMER INDOOR SUMMER OUTDOOR

DB(°C) %RH DB(°C) %RH DB(°C) %RH DB(°C) %RH

VENTILATION 20 - 22 - 25.5 50 33 29

BATTERY ROOM 20 - 22 - 25.0 50 43 24

OFFICES, COMM/SCADA ROOMS 20 - 22 - 25.5 50 43 24

MECHANICAL/STORAGE ROOMS 20 - 22 - 29.4 50 43 24

ELECTRICAL ROOM 20 - 22 - 30.0 50 43 24

ENGINE HALL 20 - 22 - 37.8 50 43 24

DUCT CONSTRUCTION AND LEAKAGE SCHEDULE

SYSTEM SYSTEM DUCT TYPE

SMACNA

PRESSURE

CLASS

(Pa)

SEAL

CLASSIFICATION

(PER SMACNA)

ROUND LEAKAGE CLASS

(L/s PER M^2 AT 250 Pa)

RECTANGULAR LEAKAGE

CLASS

(L/s PER M^2 AT 250 Pa)

NOTES

SUPPLY AIR DUCTWORK FROM AIR HANDLING UNIT TO FPVAV +500 A 6 12 1,2

SUPPLY AIR DUCTWORK FROM FPVAV TO SUPPLY OUTLETS +250 A 6 12 1,3

RETURN AIR/OUTSIDE

AIR/EXHAUST AIR

DUCTWORK FROM GRILLES TO AIR HANDLING UNIT/FAN -250 A 6 12 1,3

NOTES:

1. DUCT CONSTRUCTION MUST BE IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS.

2. ALL SYSTEM DUCTWORK MUST BE LEAKAGE TESTED (DALT) IN ACCORDANCE WITH TESTING PROCEDURES IN SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL TO NO LESS

THAN THE INDICATED DUCT PRESSURE CLASS.

3. DUCT LEAKAGE TEST (DALT) NOT REQUIRED.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

GROUND LEVEL

2 31

A2

MH301

AHU-1H

0x

800x900

MECHANICAL

RISER

ROOM

700x900

450x450

SDU

40Ø D

50Ø CWS

50Ø CWR

GROUND LEVEL

BCD

B2

MH301

800x900

1150ø

FPVAV-1

MECHANICAL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:0

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH301

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

S E

C

TI

O N

S

BAT

14124494

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

1 : 50 B2

MECHANICAL SECTION

1 : 50 A2

MECHANICAL SECTION 2

1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5 1:50

0 5m1 2 3 40.5

GRAPHIC SCALE(S)

# KEY NOTES

GENERAL NOTES

1 FUEL OIL PIPING AND EQUIPMENT FOR REFERENCE ONLY.

2 RUN DUCTWORK AS CLOSE AS POSSIBLE TO BOTTOM OF STRUCTURE.

3 100mm CONCRETE PAD.

4 CWS/CWR FROM CHILLED WATER LOOP. SEE COIL DETAIL B5, SHEET

MH502.

5 SEE CONDENSATE DRAIN DETAIL, DETAIL A3, SHEET MH502.

6 SEE SUPPORT DETAIL C1, SHEET MH502.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

1. REFER TO HAZARDOUS AREA CLASSIFICATION PLANS IN ELECTRICAL

DRAWINGS: HVAC UP TO 1M ABOVE FLOOR NEEDS TO BE CLASS 1/DIVISION 2.

M

B C D

AHU-1H

FPVAV-1

0x

0x

0x

200x200 F300/300

F300/300 ø

B2

MH301

A2

MH301

F200/200 ø

WORKSHOP

MECHANICAL

MATCHLINE

MH402

507 L/S

200x200

F200/200

D S

D

450x450

200ø

(TYP)

(TYP)

SDU

50Ø CWR

50Ø CWS

40Ø D

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:0

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH401

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

M E

C H

A N

IC

A

L R

O O

M E

N

LA

R G

E D

P

LA

N

BAT

14124495

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

1 : 50 A2

MECHANICAL ROOM ENLARGED PLAN

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

GRAPHIC SCALE(S)

KEY PLAN

# KEY NOTES

GENERAL NOTES

A

B

1 600mm x 600mm INTAKE SAND LOUVER WITH FULL SIZE PLENUM, 300mm

DEEP. SEE ARCHITECTURAL DRAWINGS.

2 DDC CONTROL PANEL.

3 TERMINATE WITH 305mm x 305mm WIRE METAL MESH.

4 ROUTE CONDENSATE TO NEAREST FLOOR DRAIN.

5 SEE CONDENSATE DRAIN DETAIL, DETAIL A3, SHEET MH502.

6 SEE AHU COOLING COIL DETAIL B5, SHEET MH502.

7 SEE BRANCH CONNECTION DETAIL B3, SHEET MH502.

8 SEE FIRE DAMPER DETAIL A1, SHEET MH502. PROVIDE REMOVABLE

DUCT SECTION FOR ACCESS WHERE 305mm X 305mm ACCESS DOOR

CANNOT BE PROVIDED.

1. FOR OPEN DUCT IN OPEN CEILING TERMINATE WITH 12mmx12mm WIRE METAL

MESH.

2. REFER TO HAZARDOUS AREA CLASSIFICATION PLANS IN ELECTRICAL

DRAWINGS: HVAC UP TO 1M ABOVE FLOOR NEEDS TO BE CLASS 1/DIVISION 2.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

M

RISER

ROOM

STORAGE

COMM

SCADA

OFFICE

OFFICE

CONTROL

CORRIDOR

VESTIBULE

TOILET

TOILET

A200

A200

G550/550

A250

0x

0x

0x

G550/550

0x

0x

0x

A250

C D

106 L/S

47 L/S

G550/550

FPVAV-2

FPVAV-4

FPVAV-5

FPVAV-6

FPVAV-7

F250/250

0ø

F300/300

F300/300

0x

350x350

(TYP OF 2)

F200/150

FPVAV-3

200ø

350x300

200x200

250x200

0x

200ø

200x200

350x300

350x300

250x350

250x350

0x

0x

MATCHLINE

MH401

ø

250x250

250x200

300x250

200x200

G550/550

0x

0x

0x

350x300

EF-2H

0x

MATCHLINE

MH403

350x350

250x350

200x200

450x450

350x350

450x450

200ø

0ø

0ø

G550/550

G550/550

G550/550

(TYP)

(TYP)

5 (TYP)

150x200

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:0

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH402

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

M E

C H

A N

IC

A

L G

R O

U N

D F

LO

O

R P

LA

N

A

R E

A A

BAT

14124496

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

GRAPHIC SCALE(S)

KEY PLAN

# KEY NOTES

GENERAL NOTES

1 : 50 A2

MECHANICAL GROUND FLOOR PLAN - AREA A

A

B

1 SERVICE CLEARANCE. TYP FOR ALL FPVAV.

2 450mm x 450mm EXHAUST SAND LOUVER WITH 800mm PLENUM FULL SIZE

OF LOUVER. SEE ARCHITECTURAL DRAWINGS.

3 SEE SUPPORT DETAIL C1, SHEET MH502.

4 SEE BRANCH CONNECTION DETAIL B3, SHEET MH502.

5 SEE RETURN DIFFUSER DETAIL D5, SHEET MH502.

1. FOR OPEN DUCT IN OPEN CEILING TERMINATE WITH 12mmx12mm WIRE METAL

MESH.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

CORRIDOR

VESTIBULE

JANITOR

ELECTRICAL

VESTIBULE

DAY TANK

DAY TANK

250x250

200ø

G550/550

A250

B C D

A200

BATTERY

EF-1H

FPVAV-9

F300/300

FPVAV-8

250x250

0x

350x300

F300/300

400ø

0x

G550/550

F200/200

200x200 x6 x6

0x

MATCHLINE

MH402

MATCHLINE

MH403

0ø

0ø

3(TYP)

G550/550

DPS

(TYP)

F150/150

250x200

H

HYDROGEN

SENSOR

300x300

200x200

C D

DAY TANK

LUBE OIL

FPVAV-11

FPVAV-10

F300/300

F300/300

F300/300

F300/300

F300/300

0ø

400ø

350x300

0x

0x

350x300

ELECTRICAL

MH403

MATCHLINE

FPVAV-12

350x300

0x

0x

F300/300

F300/300

400ø

400ø

FPVAV-9

3 (TYP)

(TYP)

9(TYP)

350x300

300x300

300x300

300x300

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH403

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

M E

C H

A N

IC

A

L G

R O

U N

D F

LO

O

R P

LA

N

A

R E

A B

BAT

14124497

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

1:50 0 5m1 2 3 40.5

GRAPHIC SCALE(S)

KEY PLAN

# KEY NOTES

GENERAL NOTES

A

B

1 : 50 B3

MECHANICAL GROUND FLOOR PLAN - AREA B1

1 SERVICE CLEARANCE. TYP FOR ALL FPVAV.

2 HYDROGEN SENSOR IN DUCTWORK AND PANEL. PROVIDE SENSOR IN

EXHAUST AIR DUCT, PROVIDE ALARM FOR ROOM AND AUXILIARY

CONTACTS FOR CONNECTION TO DDC SYSTEM.

3 FPVAV MOUNTED 4700mm AFF.

4 EF-1H MOUNTED 3050mm AFF. SEE DETAIL D1, SHEET MH502.

5 RUN DUCTWORK AS CLOSE AS POSSIBLE TO BOTTOM OF STRUCTURE.

6 DOWNSTREAM DUCT STATIC PRESSURE SENSOR: INITAL SETPOINT AT

300 Pa.

7 SEE SUPPORT DETAIL C1, SHEET MH502.

8 SEE RETURN DIFFUSER DETAIL D5, SHEET MH502.

9 SEE BRANCH CONNECTION DETAIL B3, SHEET MH502.

10 SEE FIRE DAMPER DETAIL A1, SHEET MH502. PROVIDE REMOVABLE

DUCT SECTION FOR ACCESS WHERE 305mm X 305mm ACCESS DOOR

CANNOT BE PROVIDED.

11 150mm x 50mm DOWN TO 305mm ABOVE BATTERY RACK WITH VOLUME DAMPER, BALANCE FOR 132 L/s.

1 : 50 A1

MECHANICAL GROUND FLOOR PLAN - AREA B2

1. FOR OPEN DUCT IN OPEN CEILING TERMINATE WITH 12mmx12mm WIRE METAL

MESH.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

45°

30° TO 90°

ELEVATION

30° TO 90°

45°

PLAN VIEW

SUPPORT ANGLE

DOUBLE NUT (TYP)

SEE ATFP CABLE

ATTACHMENT TO

STRUCTURE DETAIL

SUPPORT ANGLE

DOUBLE NUT (TYP)

PLAN VIEW

TRANSVERSE AND

LONGITUDINAL

CABLE BRACE (TYP)

SUSPENDED

MECHANICAL

EQUIPMENT

CABLES INSTALLED

WITH 12mm SLACK

ON BOTH SIDES

HANGER

ROD (TYP)

VIBRATION

ISOLATION

(TYP.)

HANGER ROD. SEE HANGER

ROD ATTACHMENT DETAILS

SUSPENDED

MECHANICAL

EQUIPMENT

SUSPENDED

MECHANICAL

EQUIPMENT

SUPPORT

MEMBER

TRANSVERSE AND

LONGITUDINAL

CABLE BRACE (TYP.)

ELEVATION

HANGER ROD. SEE

HANGER ROD

ATTACHMENT DETAILS

SUSPENDED

MECHANICAL

EQUIPMENT

CABLES INSTALLED

WITH 12mm SLACK

ON BOTH SIDES

SEE ATFP CABLE

ASSEMBLY DETAIL

CABLES

INSTALLED

TIGHT (TYP)

SEE ATFP CABLE

ASSEMBLY DETAIL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH501

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

D E

TA

IL

S

BAT

14124498

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

NO SCALE

A2

ATFP EQUIPMENT BRACE W/ VIBRATION ISOLATORS

SUSPENDED EQUIPMENT:

1. ALL SUSPENDED MECHANICAL EQUIPMENT WEIGHING OVER 14kg MUST BE

INSTALLED TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY

DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.

2. THESE DETAILS ARE PROVIDED AS GUIDANCE FOR THE SUPPORT OF SUSPENDED

MECHANICAL EQUIPMENT WEIGHING OVER 14 kg.

3. EQUIPMENT INSTALLED IN MECHANICAL EQUIPMENT ROOMS DO NOT HAVE TO MEET

THE ATFP STANDARDS FOR SUSPENDED EQUIPMENT.

4. THE MECHANICAL CONTRACTOR MUST PROVIDE ON THE SHOP DRAWINGS AN

ATFP BRACING FOR MECHANICAL EQUIPMENT SCHEDULE FOR

ALL SUSPENDED MECHANICAL EQUIPMENT WEIGHING 14 kg AND OVER.

5. THE DETAILS INDICATED REPRESENT THE MINIMUM REQUIREMENTS TO SATISFY

ATFP LOADING. PROVIDE SEISMIC BRACING DESIGN AS REQUIRED IN SPECIFICATION

13.48.73. THE MORE STRINGENT OF THESE TWO DESIGNS MUST BE USED FOR

BRACING EQUIPMENT.

ANTI-TERRORISM/FORCE PROTECTION (ATFP)

NOTES: EQUIPMENT

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

25mm Ø HANGER ROD

(TYPICAL): SUPPORT

FROM STRUCTURAL

STEEL ABOVE

FILTER

VIBRATION

ISOLATOR (TYPICAL)

FLEX

CONNECTION

PROVIDE SHEET METAL COLLAR WITH

FILTER CLIPS AND FLEX CONNECTION

WHERE DUCTWORK SHOWN

MAIN DUCT

MAIN DUCT

ROUND

RECTANGULAR

150mm

45°

BALANCING DAMPER

BRANCH DUCT

150mm

45°

THIS CONNECTION SHALL BE USED AT ALL BRANCHES FROM MAINS AND SUB-MAINS.

USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & THEN ONLY

WHERE ROUND RUNOUTS ARE INDICATED ON DRAWINGS

USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & THEN ONLY

WHERE RECTANGULAR RUNOUTS ARE INDICATED ON DRAWINGS

BALANCING DAMPER

BRANCH DUCT

METAL SLEEVE

DIFFUSER OR GRILLE CEILING

SHEET METAL SUPPLY PLENUM,

INSULATE SAME AS DUCT

FLEXIBLE DUCT SIZE AS

INDICATED ON FLOOR PLAN

0m m M

IN

IM

U M

FOR SIZE AND

CONTINUATION

SEE PLANS

PITCH DOWN

TOWARD

DRAIN

MINIMUM = 50mm

CLEANOUT

DRAIN LINE SHALL BE AT LEAST

THE SAME SIZE AS THE

CONNECTION ON THE

EQUIPMENT

EQUIPMENT

CASING

DEPTH OF SEAL SHALL BE A

MINIMUM = 50mm

(SECTION UNDER POSITIVE PRESSURE)

FOR SIZE AND

CONTINUATION

SEE PLANS

CLEANOUT

PITCH DOWN

TOWARD

DRAIN

MINIMUM = 150mm

CLEANOUT

DRAIN LINE SHALL BE AT

LEAST THE SAME SIZE AS THE

CONNECTION ON THE

EQUIPMENT

EQUIPMENT

CASING

DEPTH OF SEAL SHALL BE A

MINIMUM = 50mm

(SECTION UNDER NEGATIVE PRESSURE)

CLEANOUT

COIL

MANUAL

AIR VENT

DRAIN PAN

17mm∅ DRAIN VALVE

W/ HOSE

CONNECTION

NOTE:

1. ARRANGE PIPING TO PERMIT REMOVAL OF COIL.

2. THE METERED BALANCING VALVE SHALL BE INSTALLED BY THE

CONTRACTOR IN CONFORMANCE WITH VALVE MFR.'S RECOMMENDED

SPACING UP/DOWNSTREAM FROM PIPE CHANGES IN DIRECTION AND/OR

OTHER VALVES/COMPONENTS IN THE PIPING.

CWS

PRESSURE GAGE TAP W/

CAP & PET COCK (TYP)

DRAIN

CWR

CONTROL VALVE 2-WAY

SEE AHU VALVE

SCHEDULES

RETURN MAIN

SUPPLY MAIN

SEE NOTE 2

NOTE 5

SLEEVE, NOTE 2

NOTES:

1. PROVIDE 100% FREE AREA FIRE DAMPER. FOLLOW DAMPER MANUFACTURER INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION, NOT OUTSIDE THE

PENETRATION.

2. GALVANIZED SLEEVE GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND PERIMETER ANGLES.

3. PERIMETER ANGLES = GALVANIZED SLEEVE, NOT LESS THAN 32mm X 32mm 12 GAGE, TO PROVIDE 25mm OVERLAP OF OPENING

ON ALL 4 SIDES.

4. ACCESS DOOR = SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

5. PROVIDE HEIGHT AND WIDTH OPENING IN RATED ASSEMBLY WITH MINIMUM CLEARANCE OF 3mm LARGER THAN THE DAMPER/

SLEEVE ASSEMBLY. FOR FIRESTOP REQUIREMENTS REFER TO GENERAL NOTE THIS SHEET.

6. PROVIDE BREAKAWAY JOINT AT DUCT TO SLEEVE CONNECTION.

GENERAL NOTE FOR HORIZONTAL FIRE DAMPERS:

THIS TYPICAL FIRE DAMPER IS GENERIC GUIDANCE ONLY. INSTALL FIRE DAMPER IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION DETAILS. DO NOT VARY FROM THOSE INSTRUCTIONS IN ANY WAY. DO NOT FIRESTOP THE GAP BETWEEN THE FIRE DAMPER SLEEVE AND THE PENETRATION UNLESS SPECIFICALLY REQUIRED BY THE DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS USING MANUFACTURER'S RECOMMENDED FIRESTOP MATERIALS.

PERIMETER ANGLE,

NOTE 3 (NOT

FASTENED TO

PARTITION)

6mm

SHEET METAL

SCREW (TYP.)

FIRE

PARTITION

OR WALL

BREAKAWAY

JOINT NOTE 6

TYPICAL DUCT

INSULATION

ACCESS DOOR

NOTE 4

SUPPORT

VIBRATION

ISOLATORS

(TYP)

FLEXIBLE

CONNECTION (TYP)

CEILING SUSPENSION BRACKETS

PROVIDED BY MANUFACTURER (TYP)

SUPPLY OR

EXHAUST FAN

MOTOR

HANGER

ROD (TYP)

RECTANGULAR

DUCT

LAG TO CURB

WALL MOUNTED

EXHAUST FAN

PREFABRICATED

CURB

LAG TO WALL WITH 15Ø

WOOD SCREWS 100mm ON

CENTER ALL FOUR SIDES

GRAVITY

BACKDRAFT DAMPER

MOTOR SAFETY

DISCONNECT SWITCH

INTEGRAL W/ FAN

CONDUIT

CHASE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH502

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

D E

TA

IL

S

BAT

14124499

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

NO SCALE

C1

FAN POWERED VAV UNIT SUPPORT DETAIL

NO SCALE

B3

BRANCH CONNECTION DETAILS

NO SCALE

D5

DIFFUSER GRILLE PLENUM DETAIL

NO SCALE

A3

TYPICAL CONDENSATION DRAIN TRAP DETAIL

NO SCALE

B5

AHU COIL PIPING

MH301, MH401, MH402, MH403

MH401, MH402, MH403

MH401, MH402, MH403

MH301, MH401

MH301, MH401

NO SCALE

A1

HORIZONTAL FIRE DAMPER

MH401

NO SCALE

D3

INLINE CENTRIFUGAL FAN MOUNTING DETAIL

NO SCALE

D1

SIDEWALL EXHAUST FAN DETAIL

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH601

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

S C

H E

D U

LE

BAT

14124500

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

8. UNITS MUST BE SUSPENDED WITH 25mm DEFLECTION SPRING ISOLATORS.

7. ESP INCLUDES SUPPLY DUCTWORK, DIFFUSERS, DAMPERS, AND FILTER.

5. SOUND NC LEVEL CALCULATED IN ACCORDANCE WITH ARI 855-1998. PROVIDE 25mm MATTE FACED INSULATION.

4. RADIATED NC IS BASED ON FAN PLUS AIR VALVE AT 0.25 kPa INLET STATIC PRESSURE.

3. PROVIDE SINGLE POINT ELECTRICAL CONNECTION WITH INTEGRAL DISCONNECT.

2. PROVIDE CONTROL TRANSFORMER, FAN RELAY, DAMPER ACTUATOR, AND WIRING TO CONTROLLER.

1. COORDINATE WITH CONTROLS CONTRACTOR: INSTALL CONTROLLER AT FACTORY.

NOTES

FPVAV-12 406 0.25 38 870 272 904 0.10 0.56 0.1

FPVAV-11 406 0.25 38 904 272 904 0.10 0.56 0.1

FPVAV-10 406 0.25 38 904 272 904 0.10 0.56 0.1

FPVAV-09 406 0.25 38 904 272 904 0.10 0.56 0.1

FPVAV-08 203 0.25 32 359 272 359 0.10 0.13 0.1

FPVAV-07 203 0.25 33 354 106 354 0.10 0.13 0.1

FPVAV-06 203 0.25 29 170 51 170 0.10 0.13 0.1

FPVAV-05 203 0.25 26 283 85 283 0.10 0.13 0.1

FPVAV-04 203 0.25 26 175 53 175 0.10 0.13 0.1

FPVAV-03 254 0.25 33 324 144 481 0.10 0.13 0.1

FPVAV-02 152 0.25 29 106 32 1036 0.10 0.13 0.1

FPVAV-01 305 0.25 34 601 152 507 0.10 0.25 0.1

MAX. MIN. L/s ESP (kPa) FAN MOTOR (kW)

MARK MIN INLET DIA (mm)

MIN INLET SP

(kPa)

MAX RADIATED

NOISE (NC)

VOL. REG. (L/s) FAN CAPACITY

CLEAN AIR

FILTER PD

(kPa)

SERIES FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE

DIFFUSERS, REGISTERS AND GRILLES SCHEDULE

MARK

NECK/COLLAR

SIZE (mm)

MODULE

SIZE (mm)

SERVICE MOUNTING TYPE MATERIAL MAX L/s

MAX PRESSURE

DROP (Pa)

MAX NC

ISOTHERMAL THROW

AT 50 FPM (mm)

BASIS OF DESIGN

NOTES

MANUFACTURER MODEL

A200 200 600 X 600 SUPPLY LAY-IN LOUVERED FACE ALUMINUM 210 17.4 15 4260 TITUS TDC-AA 1

A250 250 600 X 600 SUPPLY LAY-IN LOUVERED FACE ALUMINUM 375 24.8 20 6100 TITUS TDC-AA 1

F200/150 NECK + 30 SUPPLY SURFACE MOUNT 45° ADJUSTABLE BLADES ALUMINUM 24.8 25 TITUS 300FL 1,2

F200/200 NECK + 30 SUPPLY/RETURN SURFACE MOUNT 45° ADJUSTABLE BLADES ALUMINUM 24.8 25 TITUS 300FL 1,2

F250/250 NECK + 30 SUPPLY SURFACE MOUNT 45° ADJUSTABLE BLADES ALUMINUM 24.8 25 TITUS 300FL 1,2

F300/300 NECK + 30 SUPPLY SURFACE MOUNT 45° ADJUSTABLE BLADES ALUMINUM 24.8 25 TITUS 300FL 1,2

G550/550 600 X 600 RETURN/EXHAUST LAY-IN 12X12X12 EGGCRATE ALUMINUM 24.8 25 TITUS 50F 1,2

SDU 102 HIGH EFFICIENCY 13 0.16 33.0 28.6 12.6 696 13.5 24.5 7.2 17.2 68.7 5.7 0.21 V-SDU 9.1 TRANE - CSAA

ENT. DB ENT. WB LVG. DB ENT. LVG.

THICKNESS (mm) TYPE MERV

MID-LIFE P.D

(kPa)

AIR TEMP (°C)

AIRFLOW (L/s)

SENSIBLE

CAPACITY (kW)

TOTAL CAPACITY

(kW)

WATER TEMP (°C)

MAX LPM

MAX FLUID PD

(kPa)

MAX AIR PD (kPa)

CONTROL VALVE

TAG

CONTROL VALVE

Kv

MARK

SDU FILTER SECTION COOLING COIL (SDU)

BASIS OF DESIGN

SPLIT DEHUMIDIFICATION UNIT SCHEDULE

NOTES:

1. PROVIDE WITH OPPOSED BLADE VOLUME DAMPER.

2. PROVIDE WITH FRAME FOR CEILING INSTALLATION.

AHU-1H

MECHANICAL

6,145 696 0.5 11.19 1.0

DIRECT DRIVE

PLENUM

102 PLEATED 13 0.16 28.6 22.3 12.8 12.7 5449.0 107.3 197.2 7.2 17.2 277.3 43.9 0.1 V-1H 30.0 TRANE - CSAA

ENT. DB ENT. WB LVG. DB LVG. WB ENT. LVG.

MAX

SUPPLY

AIR (L/s)

OA (L/s)

ESP

(kPa)

MAX

kW

FAN

QTY

TYPE

THICKNESS

(mm)

TYPE MERV

MID-LIFE

P.D (kPa)

AIR TEMP (°C)

AIRFLOW

(L/s)

SENSIBLE

CAPACITY

(kW)

TOTAL

CAPACIT

Y (kW)

WATER TEMP (°C)

MAX

LPM

MAX FLUID

PD (kPa)

MAX AIR PD

(kPa)

CONTROL

VALVE TAG

CONTROL

VALVE Kv

MARK LOCATION

SUPPLY FAN RETURN AIR FILTER SECTION (AHU) RETURN AIR CHILLED WATER COIL (AHU)

BASIS OF DESIGN

AIR HANDLING UNIT SCHEDULE

3. PROVIDE WITH LOW LEAKAGE MOTORIZED DAMPER (SEE CONTROLS).

2. NON-SPARKING TYPE A FAN CONSTRUCTION WITH EXPLOSION-PROOF MOTOR.

NOTES:

1. PROVIDE WITH PRE-WIRED SPEED CONTROLLER, ISOLATION HANGERS (SUSPENDED UNIT ONLY) & INTEGRAL

DISCONNECT SWITCH.

EF-2H TOILET AIR EXHAUST IN-LINE FAN 72 0.3 1725 15.6 DIRECT 450 1,3

EF-1H BATTERY ROOM SIDEWALL CENTRIFUGAL 396 0.1 970 6.1 BELT 94 1,2,3

MARK SERVICE TYPE L/s

ESP

(kPa)

RPM SONES DRIVE MAX W NOTES

FAN SCHEDULE

NOTES:

1. ESP DOES NOT INCLUDE PRESSURE DROP OF FILTERS OR COILS IN AHU.

2. PROVIDE SUPPLY FANS WITH TEFC EXPLOSION - PROOF MOTORS.

3. CHILLED WATER COIL FOULING FACTOR: 0.017610 M2°C/KW.

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

CSR

DO2

MS

DI1

DO1

DI2

ES

M

NO

EA

UPON A COMMAND FROM THE DDC SYSTEM FOR THE FAN TO RUN, THE

OUTSIDE AIR DAMPER SHALL FULLY OPEN. UPON PROOF OF DAMPER

OPENING, THE FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY.

UPON COMMAND FROM THE DDC SYSTEM FOR THE FAN TO TURN OFF,

THE REVERSE SHALL OCCUR. THE DDC SYSTEM SHALL MONITOR FAN

STATUS AND PROVIDE ALARMS FOR THE FOLLOWING CONDITIONS:

-FAN COMMANDED OFF, DAMPER OPEN

-FAN ON, DAMPER CLOSED

-BATTERY ROOM HYDROGEN SENSOR.(SET AT 1%)

SEQUENCE OF OPERATION (RUNS CONTINUOUSLY)

FAN DDC POINTS LIST

INPUT

GRAPHICTREND ALARM

OUTPUT

POINT # POINT DESCRIPTION

DI1

DI2

DO1

DO2

DAMPER STATUS

FAN STATUS (ON/OFF)

DAMPER OPEN/CLOSE

FAN SIGNAL (START/STOP)

M

X X X

X

X X X

X

DI3 HYDROGEN ALARM XX

THE VAV TERMINAL UNIT SHALL BE ENABLED OR DISABLED THROUGH THE BUILDING DDC SYSTEM WITH ASSOCIATED AHU-1H.

UNIT FAN SHALL OPERATE CONTINUOUSLY.

THE SPACE TEMPERATURE SET POINT SHALL BE ADJUSTED EITHER BY A DDC GLOBAL COMMAND OR LOCAL ROOM SENSOR.

UPON A RISE SPACE TEMPERATURE ABOVE OCCUPIED SET POINT THE AIR DAMPER SHALL BE MODULATED OPEN TOWARD MAXIMUM COOLING POSITION. UPON A DROP SPACE TEMPERATURE BELOW SET POINT THE AIR DAMPER SHALL BE MODULATED

CLOSED TO MINIMUM POSITION.

SEQUENCE OF OPERATION

FOR ROOM SENSOR LOCATION,

SEE FLOOR PLAN

SET POINT VARIES: SEE

DESIGN CONDITIONS,

SHEET MH001

T AI3

AI4

AO2

AI1 AO1

DDC POINTS LIST

INPUT

POINT # POINT DESCRIPTION TREND ALARM GRAPHIC

OUTPUT

ANALOG SPACE AIR TEMPERATURE

FPVAV BOX AIRFLOW

SUPPLY AIR TEMPERATURE

AI1

AI2

AI3

LOCAL TEMPERATURE SETPOINT ADJUSTMENTAI4

POINT # POINT DESCRIPTION TREND ALARM GRAPHIC

AIR VALVE POSITIONAO1

SPACE TEMPERATURE SETPOINTAO2ANALOG

DIGITAL

FAN START/STOP DO1

RA

SA

DO1AO2

PRIMARY AIR

UNIT CONTROL

PANEL

M

X

X

X

X X

X

X

X

X

X

X

X X

TAI2

FP VAV BOX & EF CONTROLLER

AHU-1H & SDU CONTROLLER

DDC WORKSTATION RM 107 (SEE

SPECIFICATIONS)

SWITCH/ROUTER

COMM BUS (TYP)

FUTURE CONN TO

HUB/SWITCH AND

SERVER (NIC)

DDC

CONTROL

PANEL IN

MECH RM 113

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH801

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

C O

N

TR

O

LS

BAT

14124501

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

NO SCALE

FAN CONTROL DIAGRAM (EF-1H SHOWN TYPICAL FOR EF-2H)

NO SCALE

FAN POWERED VAV TERMINAL UNIT CONTROL DIAGRAM

NO SCALE

DDC SYSTEM ARCHITECTURE DIAGRAM

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

EF-2

EA

VAV AIR-HANDLING UNIT (AHU-1H) WITH SPLIT

DEHUMIDIFICATION UNIT (SDU) SEQUENCE OF OPERATION

NO

THE AIR-HANDLING UNIT AND COORDINATED CONTROLS OPERATE CONTINUOUSLY. THE OUTSIDE AND RETURN AIR DAMPERS OPEN AND PROVEN, AND THE EXHAUST AIR DAMPER OPEN AND PROVEN BEFORE THE AHU AND INTERLOCKED EXHAUST FAN ARE ENABLED. THE VARIABLE SPEED DRIVE MUST MODULATE THE SUPPLY FAN SPEED TO MAINTAIN DUCT STATIC PRESSURE IN THE DUCT AT A POINT 2/3 FROM FAN OUTLET TO END OF THE DUCT. DUCT STATIC PRESSURE MUST BE RESET BASED ON THE ZONE REQUIRING THE MOST PRESSURE (I.E., THE SET POINT IS RESET TO A LOWER VALUE UNTIL ONE ZONE DAMPER IS AT 90% OPEN. UPON ANY ZONE DAMPER MOVING TO 100% OPEN, STATIC PRESSURE MUST BE RESET TO A HIGHER VALUE). UPON FAILURE OF ZONE TERMINAL CONTROL LOOP, FAN SPEED MUST BE MODULATED BASED UPON THE DUCT STATIC PRESSURE. OUTSIDE AIRFLOW WILL BE MONITORED BY AN AIRFLOW MEASURING STATION: OUTSIDE AIR DAMPER WILL MODULATE TO MAINTAIN THE SCHEDULED VENTILATION AIRFLOW WHILE THE UNIT SUPPLY AIRFLOW IS VARIABLE.

COOLING (RETURN AIR):

WITH THE RETURN AIR DAMPER OPEN, THE UNIT CHILLED WATER CONTROL VALVE MUST BE MODULATED TO MAINTAIN UNIT DISCHARGE AIR TEMPERATURE SET POINT (12.8°C). ON A RISE IN UNIT DISCHARGE AIR TEMPERATURE THE VALVE MUST MODULATE OPEN: ON A FALL IN TEMPERATURE THE REVERSE MUST OCCUR.

COOLING (OUTSIDE AIR):

WITH THE OUTSIDE AIR DAMPER OPEN, THE SPLIT DEHUMIDIFICATION CHILLED WATER CONTROL VALVE MUST BE MODULATED TO MAINTAIN COOLING COIL DISCHARGE AIR TEMPERATURE SET POINT (11.1°C) FOR DEHUMIDIFICATION. ON A RISE IN COIL DISCHARGE AIR TEMPERATURE THE VALVE MUST MODULATE OPEN:

ON A FALL IN TEMPERATURE THE REVERSE MUST OCCUR.

SAFETIES AND ALARMS:

UPON SENSING PRESSURE ABOVE ITS SET POINT (ADJUSTABLE), THE HIGH LIMIT PRESSURE SENSOR MUST SHUT DOWN THE SYSTEM AND INITIATE AN ALARM ON THE DDC SYSTEM: THE ALARM MUST REQUIRE MANUAL RESET EITHER AT THE UNIT OR THE CENTRAL BUILDING CONTROLS. ONCE CLEARED THE STATIC PRESSURE MUST RETURN TO NORMAL CONTROL. UPON SENSING PRODUCTS OF COMBUSTION BY THE SUPPLY AIR DUCT SMOKE DETECTOR, THE ASSOCIATED SUPPLY FAN AND EXHAUST FAN EF-1 MUST BE DE-ENERGIZED, ALL DAMPERS MUST BE PLACED IN THEIR CLOSED POSITIONS, AND A SIGNAL MUST BE SENT TO THE FIRE ALARM PANEL. DIFFERENTIAL PRESSURE SENSORS (ADJUSTABLE) MUST MONITOR THE PRESSURE ACROSS THE UNIT FILTERS (BOTH RETURN AND OUTSIDE AIR). UPON SENSING PRESSURE AT ITS “DIRTY” SET POINT (62 Pa) A TROUBLE SIGNAL MUST BE INITIATED FOR DIRTY FILTER STATUS. THE SYSTEM MUST MONITOR ALL VFD SAFETIES. THE SYSTEM MUST MONITOR RETURN AIR, SUPPLY AIR, AND OUTSIDE AIR TEMPERATURES. THE SYSTEM MUST MONITOR THE RETURN AIR AND OUTSIDE AIR RELATIVE HUMIDITY. THE SYSTEM MUST MONITOR THE OUTDOOR AIR AND EXHAUST FANS MOTOR STATUS.

DI6 CSR

DI7

DO2

DO3

M

M

ES

MS

DDC POINTS LIST

INPUT

POINT # POINT DESCRIPTION TREND ALARM GRAPHIC

OUTPUT

ANALOG

OUTSIDE AIR TEMPERATURE

SUPPLY AIR TEMPERATURE

RETURN AIR TEMPERATURE

AI1

AI2

AI3

OUTSIDE AIR COIL LATAI4

RETURN AIR COIL LATAI5

DOWN DUCT STATIC PRESSUREAI6

OUTSIDE AIR FILTER PRESSURE DROPAI7

POINT # POINT DESCRIPTION TREND ALARM GRAPHIC

SAF VFD STATUSDI1

OUTSIDE AIR DAMPER STATUSDI2

RETURN AIR DAMPER STATUSDI3

DI4 SUPPLY AIR DUCT SMOKE DETECTOR

DI5

SUPPLY FAN VFD SPEED %AO1

OUTSIDE AIR DAMPER POSITION%AO2

AO4

SUPPLY AIR FAN START/STOP DO1

DO2

EXHAUST AIR DAMPER POSITION

DIGITAL

ANALOG

DIGITAL

DI6

DI7

SUPPLY DUCT HIGH PRESSURE SWITCH

EXHAUST FAN STATUS

EXHAUST DAMPER STATUS

RETURN AIR CHILLED WATER VALVE POSITION%

AO5 OUTSIDE AIR CHILLED WATER VALVE POSITION%

EXHAUST FAN START/STOP

DO3

RA

OA

DPS

AI6

VFDDI1

DO1

AO1

T

AI4

C

C

C

C

AI5

AO4

AO5

DPS

AI8

M

AO2

M

AO3

T

AI2

AI11

RH

AI9

RH

AI10

AFMS

DPS

AI7

T

AI3

RETURN AIR FILTER PRESSURE DROPAI8

OUTSIDE AIR RELATIVE HUMIDITYAI9

RETURN AIR RELATIVE HUMIDITYAI10

OUTSIDE AIR AIRFLOWAI11

X X

X X

X X

X

X XX

X

X

X

X

X

X X

X X

X X

X

X

X

X

DI2

T

AI1

H

DI5

DI3

DI4

X X

X X

X X

X X

X X

X X

X

X

X

X

AO3 RETURN AIR DAMPER POSITION % X

T

HL

DSD

PROVIDED BY FIRE

ALARM SYSTEM

PROVIDER

SA

V-SDU

NO

V-1H

NO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S T

E M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A T

L A

N T

IC

N

O R

F O

L K

V

A

AS NOTED

1643338

A T

LA

N

T

IC

D E

S

IG

N A

N D

C O

N S

T R

U C

T

/1 /2

:5

:1

A

M B

IM

/P

E le c tr ic a l P o w e r

P la n t F

D A

/8

P

E le c t P w r

P ln t F

D A

C M

.r v t

MH802

P -3

/P

-3 E

L E

C T

R

IC

A L P

O W

E R

P L A

N T

C O

N

TR

O

LS

BAT

14124502

MRK MLJ

MWS/SCN

D

JI

B O

U T

I, D

JI

B

O U

T I

C A

M P

L E

M O

N N

IE

R

RICHARD STEPHENS

SCE

NO SCALE

VAV AIR HANDLING UNIT CONTROL DIAGRAM

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P

Sheets
MH001 - MECHANICAL LEGEND
MH301 - SECTIONS
MH401 - MECHANICAL ROOM ENLARGED PLAN
MH402 - MECHANICAL GROUND FLOOR PLAN - AREA A
MH403 - MECHANICAL GROUND FLOOR PLAN - AREA B
MH501 - DETAILS
MH502 - DETAILS
MH601 - SCHEDULE
MH801 - CONTROLS
MH802 - CONTROLS
2022-12-15T09:56:08-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:27-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:27-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:27-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:28-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:28-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:28-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:29-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:29-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:56:29-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:12-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:30-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:30-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:31-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:31-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:32-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:32-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:32-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:33-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2022-12-15T09:57:33-0500
Virginia Beach
Michael R. Karcher
I, Michael R. Karcher, am signing to approve this document.
2023-06-08T14:12:05-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:10-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:10-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:11-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:11-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:12-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:13-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:13-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:14-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:14-0400
CDR Sandranell Moerbe, PWO CLDJ
by memo dated 7 June 2023
2023-06-08T14:12:45-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:12-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:13-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:14-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:14-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:15-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:16-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:16-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:17-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.
2023-06-08T14:13:18-0400
Rick Stephens
I, Rick Stephens, am signing to approve this document.

File details come from the government source that posted it. Updated .