About this file

This document package includes technical specifications for water treatment and distribution services at Isa Air Base and supporting sites in Bahrain. The specifications describe the existing water infrastructure including two reverse osmosis water purification units that produce potable water. Details are provided on the non-potable water supply from the local utility, as well as storage tanks, pipelines and the high and low pressure water distribution zones. Inventories include potable and non-potable water delivery points, and backflow prevention devices. Relatedly, the pre-solicitation notice provides an opportunity for base operations support services including operation and maintenance of the water facilities under solicitation N6247018R3004 from the Naval Facilities Engineering Command. Responses are due based on the solicitation schedule.

The document package provides extensive technical specifications for contractors to operate and maintain the water infrastructure at Isa Air Base and surrounding sites in Bahrain under the base operations support services contract. Inventories and details of potable and non-potable water systems, tanks, delivery points and backflow devices inform response requirements.

View the file

Other files

File Type Posted
_ISA BOS Amendment 0020.pdf PDF
_J-1700000-03 Transportation Inventory (Amendment 0020).xlsx XLSX spreadsheet
_J-6 Section F Deliverables Amendment 0019.xlsx XLSX spreadsheet
_ISA BOS Amendment 0019.pdf PDF
_J-1502000-03 Facilities Property Inventory (Amendment 0019).xlsx XLSX spreadsheet
_J-1503020 Pest Control (Amendment 0019).pdf PDF
_J-0200000-10 FP IDIQ ELINS (Amendment 0019).xlsx XLSX spreadsheet
_J-0200000 Mgmt and Admin (Amendment 0019).pdf PDF
_J-1700000-03 Transportation Inventory (Amendment 0019).xlsx XLSX spreadsheet
_J-1502000-04 Facility Investment Sys & Equip Inv (Amendment 0019).xlsx XLSX spreadsheet
_J-0200000-09 DETISAABINST 5512.1 - ACCESS AND BADGE PROCEDURES (Amendment 0019).pdf PDF
_ISA BOS Amendment 0018.pdf PDF
_J-0401000 Force Protection (Amendment 0017).pdf PDF
_J-0200000-04, 05 GFF, GFE Inventory (Amendment 0017).xlsx XLSX spreadsheet
_J-1300000 Galley (Amendment 0017).pdf PDF
_J-1002000 Supply (Amendment 0017).pdf PDF
_J-0402000 Fire & Emergency Services (Amendment 0017).pdf PDF
_J-1503030-04 Container Location Collection Frequency (Amendment 0017).xlsx XLSX spreadsheet
_J-0200000-10 FP IDIQ ELINS (Amendment 0017).xlsx XLSX spreadsheet
_J-1602000 Electrical (Amendment 0017).pdf PDF
_J-1700000 Transportation (Amendment 0017).pdf PDF
_J-1503010-03, 04, 05 Custodial Inventory and Freq (Amendment 0017).xlsx XLSX spreadsheet
_J-0402000-05 F&ES GFE (Amendment 0017).xlsx XLSX spreadsheet
_J-5 Section B CLINS (Amendment 0017).docx DOCX document
_J-1604000-04 Tank Inv and Frequency (Amendment 0017).xlsx XLSX spreadsheet
_J-1604000 Wastewater (Amendment 0017).pdf PDF
_J-1502000-04 Facility Investment Sys & Equip Inv (Amendment 0017).xlsx XLSX spreadsheet
_J-1502000 Facility Investment (Amendment 0017).pdf PDF
_J-6 Section F Deliverables (Amendment 0017).xlsx XLSX spreadsheet
_J-1503020-05 Pest Control Frequencies (Amendment 0017).xlsx XLSX spreadsheet
_J-1402000 UH and Laundry Services (Amendment 0017).pdf PDF
_J-1502000-03 Facilities Property Inventory (Amendment 0017).xlsx XLSX spreadsheet
_J-1503030 Waste Management (Amendment 0017).pdf PDF
_J-1503050-03, 04 Container Inventory and Frequency (Amendment 0017).xlsx XLSX spreadsheet
_ISA BOS Amendment 0017.pdf PDF
_J-2 FTE Worksheet (Amendment 0017).xlsx XLSX spreadsheet
_J-1300000-07 Galley Mess Gear Inventory (Amendment 0017).xlsx XLSX spreadsheet
_ISA BOS Amendment 0016.pdf PDF
_ISA_BOS_Amendment_0015.pdf PDF
_J-10_03_NOV_Site_Visit_Presentation.pdf PDF
_J-11_03_NOV_Site_Visit_Sign_in_Sheet.pdf PDF
_J-0402000_Fire_&_Emergency_Services_(Amendment_0014).pdf PDF
_J-1606000-03.1_ISA_Bahrain_WTP_Schematics_20130610_(Amendment_0014).pdf PDF
_J-1602000-07_Power_Generation_Distribution_System_Flight_Line_(Amendment_0014).pdf PDF
_J-1503010_Custodial_(Amendment_0014).pdf PDF
_J-1503050_Grounds_(Amendment_0014).pdf PDF
_J-1606000-03.2_Existing_Water_System_Pressure_Zones_Map_(Amendment_0014).pdf PDF
_J-1606000_Water_(Amendment_0014).pdf PDF
_J-1501000-04_Meter_Group_Descriptions_Condition_Rating_(Amendment_0014).xlsx XLSX spreadsheet
_J-1503030-04_Container_Location_and_Collection_Frequencies_(Amendment_0014).xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 111 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Section J Documents, Exhibits, And Other Attachments

Table Of Contents Attachment

Number Attachment Title

J-1606000-01 Definitions and Acronyms J-1606000-02 References and Technical Documents J-1606000-03 Water Treatment Plant and Distribution System Description and Inventory J-1606000-04 Water Potable and Non-Potable Delivery Locations J-1606000-05 Bottled Water Delivery Locations J-1606000-06 Backflow Prevention Device Inventory

Attachment J-1606000-01 Definitions and Acronyms

Definition/Acronym Description ANSI American National Standards Institute Assistant Operator in Responsible Charge (AORC)e

Person designated to be responsible for the total operation and maintenance of a particular facility in the temporary absence of the operator in responsible charge...

AWWA American Water works Association CNIC Instruction

5090.1 A and CNIC M-

5090.1

Navy Overseas Drinking Water Program Ashore Manual

CNIC M-5090.2 Certificate To Operate Criteria And requirements For U.S Navy Overseas Drinking Water Systems.

CNIC M-5090.3 ORC and AORC Training and Certification Program for U.S. Navy Overseas Drinking Water Systems

DoD FGS Department of Defense Environmental Final Governing Standards NOCA Navy Operator Certification Authority NPDWR National Primary Drinking Water Regulations NSDWR National Secondary Drinking Water Regulations DoD OEBGD Department of Defense Overseas Environmental Baseline Guidance Document Operator in Responsible Charge

(ORC)

Person designated to be responsible for the total operation and maintenance of a particular facility.

OPNAVINST

5530.14E CH-2 0210

Navy Policies Instruction and Guidance

ROWPU Reverse Osmosis Water Purification Units UFC Unified Facilities Criteria USAPHC United States Army Preventive Health Command

Attachment J-1606000-01 Definitions and Acronyms

Definition/Acronym Description ANSI American National Standards Institute Assistant Operator in Responsible Charge (AORC)e

Person designated to be responsible for the total operation and maintenance of a particular facility in the temporary absence of the operator in responsible charge...

AWWA American Water works Association Certified Operator Ay holder of a certificate issued IAW the Operator and Facility Certification Program for U.S, Navy Overseas Drinking Water Systems CNIC Instruction

5090.1 A and CNIC M-

5090.1

Navy Overseas Drinking Water Program Ashore Manual

CNIC M-5090.2 Certificate To Operate Criteria And requirements For U.S Navy Overseas Drinking Water Systems.

CNIC M-5090.3 ORC and AORC Training and Certification Program for U.S. Navy Overseas Drinking Water Systems

DoD FGS Department of Defense Environmental Final Governing Standards Integrated Maintenance Program (IMP)

IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and minor repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, such as, reactive, preventive, predictive and proactive maintenance, into one optimal program. IMP also includes housekeeping, which is the care and servicing of property and equipment within facilities of a utility plant and distribution system, synonymous with janitorial and custodial services.

NFPA National Fire Protection Association NOCA Navy Operator Certification Authority NPDWR National Primary Drinking Water Regulations NSDWR National Secondary Drinking Water Regulations DoD OEBGD Department of Defense Overseas Environmental Baseline Guidance Document OMSI Operation And Maintenance Support Information Operator in Responsible Charge

(ORC)

Person designated to be responsible for the total operation and maintenance of a particular facility.

OPNAVINST

5530.14E CH-2 0210

Navy Policies Instruction and Guidance

ROWPU Reverse Osmosis Water Purification Units UFC Unified Facilities Criteria USAPHC United States Army Preventive Health Command USEPA US Environmental Protection Agency Water Distribution Facility

Facility or facilities used or available for use in the testing, storage, pumping, or distribution of water for a public water system. It specifically excludes treatment of any type.

Water Treatment Facility

Facility or facilities used or available for use in the collection, treatment, testing, storage, or pumping of water for a public water system. It specifically excludes distribution.

Attachment J-1606000-02

References and Technical Documents Reference Title UFC 3-440-02N Water Conservation Operation and Maintenance UFC 3-430-09 Exterior Mechanical Utility Distribution UFC 3-230-02 Water Supply Systems UG-2029-ENV Cross Connection Control and Backflow Prevention Program Implementation at Navy Shore Facilities OPNAVINST 5090.1 Environmental Readiness Program Manual

Attachment J-1606000-03 Water Treatment Plant and Distribution System Description and Inventory

Currently, non- potable water is supplied to the LSA by Bahrain Ministry of Electricity and Water via a 200 mm (8 inch) main that originates in the City of Sitra approximately 12 km (7.5 miles) to the north of Isa AB. The water is a mixture of desalinated sea water and untreated well water and is not deemed potable according to US standards.

Isa AB is located at the end of the transmission main; therefore, the water pressure fluctuates based on the demands of other water users closer to the water treatment plant at Sitra. The water pressure leaving the treatment plant is approximately 7 bars (103 pounds per square inch), but pressures at Isa AB can drop to as low as 2 bars.

This existing commercial water is only used for latrines, showers, and cleaning.

Two reverse osmosis water purification units (ROWPUs) capable of producing 360 kga/day total capacity of potable water, meeting US safe drinking water specifications, Description Make Model Number Serial Number Reverse Osmosis Unit Waterworks WWRO WWRO4700756 Reverse Osmosis Unit Waterworks HTDS WWR04300752

The ROWPU is containerized. The RO pump will feed the cartridge filters. Chlorination is done before the feed tank to prevent bacterial fouling in the filters. The RO container is automated and has built in protection for low pressure and high pressure shutdowns, as well as any electrical faults. An audible alarm and flashing light are provided to ensure operator attention. Acid and anti-scalant dosing is conducted prior to the micron filters to ensure adequate mixing and retention. The high pressure pump discharge is connected to the vessels with a 316L stainless steel manifold, complete with pump discharge stainless steel concentrate control valve.

Paddle wheel flow meters are incorporated in permeate line. Low pressure piping is with u-PVC Sch. 80 or Class E equivalent. The valves are in stainless steel on high pressure side and u-PVC for low pressure side. Sample valves, all in stainless steel, are provided at:

Feed pump discharge Inlet to micron filtration Outlet of micron filtration Permeate from each vessel And combined sample at permeate outlet

Post chlorination and caustic treatment for the final product water is also done.

Pressure gauges are provided at all critical stages to read pressures at:

Pre-filter Post filter High pressure pump feed High pressure pump discharge Concentrate control

Temperature and pH indicators are provided at the RO inlet. A panel mounted conductivity meter is provided on the permeate line prior to chemical dosing to monitor membrane performance.

The system includes four 5040,000 gallon pretreatment holding tanks, two 20,000 gallon underground tanks and six eight 20,000 gallon treated holding tanks.

The not FFHC EWA water reaches the IAB LSA and splits into two lines in a series of two meter vaults, located on the south side of the LSA North Road (near Building 6400). One line feeds the source water tanks that supply water to WTP. The other line supplies the distribution network of the Low Pressure Zone (LPZ) that is no longer in use. The LPZ distribution line branch valve at this location is closed and the distribution line connected to the LPZ has been disconnected and terminated to avoid potential cross section on October 2015.

On the other side the source water is piped through the run of the side outlet tee into the treatment, storage and pumping facility that feeds the distribution system HPZ and tanker truck loading station. The HPZ water distribution system serves the southern portion of the IAB LSA in the area confined by North Road and the southern boundary of IAB LSA. The HPZ is controlled by the LSA WTP storage and pumping facility.

Attachment J-1606000-04

Water Potable and Non-Potable Delivery Locations

# Area Location Type Tank ID # Tanks Remarks

1, ISA Ice Plant Tank

– Isa LSA Potable N/A 2 N/A

3, ARMY Tank A – Ablution Units Isa LSA Potable 24062 2 NON potable water tank

5, ARMY Tank B- Ablution Units Isa LSA Potable 24279 2 NON potable water tank

Tank (South Road)– (4807 &

4808) Isa LSA Potable 28840 1 NON potable water tank

Bagel Shop Tank-

Direct Line Isa LSA Potable N/A 1 N/A

9 Main Galley Tank Isa LSA Potable N/A 1 N/A

Navy Medical –

Direct Line Isa LSA Potable N/A 1 N/A

Concession Trailer

Tank Isa LSA Potable N/A 1 N/A

Raptor Road Tank –

(3993 & 3994) Isa LSA Potable 28823 1 NON potable water tank

14 Marine Tank Isa LSA Potable Daily 1 NON potable water tank

Tank Beside Main DFAC (AB Unit) –

(7160 & 7260) Isa LSA Potable 26783 1 NON potable water tank

Marine Medic Tank

– (9913) Isa LSA Potable N/A 1 N/A

Main Laundry –

(7305) Isa LSA Potable N/A 1 NON potable water tank

Fire Department

(Oval) Tank Isa LSA Potable N/A 1 N/A

19 USN DJC2 ISA LSA Potable N/A 2 N/A

DFAC Fire Dept.

Water Tank ISA LSA Potable N/A 1 N/A 21 K9 Unit – (4801) ISA LSA Potable N/A 1 N/A 22 Vehicle Wash Rack ISA LSA Potable N/A 1 N/A

Fuel Point Water

Tank ISA LSA Potable N/A 1 N/A

AB Units Tank – (2004,2005,2020) Isa PAT Potable 24581 1 N/A

Galley Tank –

(2001) Isa PAT Potable 26176 1 N/A

26 Laundry Unit Tank ISA PAT Potable N/A 1 N/A

# Area Location Type Tank ID # Tanks Remarks

AB Unit Tank –

(3004,3005) Riffa PAT Potable 24801 1 N/A

DFAC Tank –

(3001) Riffa PAT Potable 26177 1 N/A

Male AB Unit Tank

– (5029) Flight line Potable N/A 1 NON potable water tank

Female AB Unit

Tank- (5030) Flight line Potable N/A 1 NON potable water tank

31, Marine AB Unit Tank – (5201 to

5206) Flight line Potable 28936937 2 NON potable water tank

Galley Tank –

(5003) Flight line Potable 28938 1 N/A

AB Unit Tank –

(5605) Fuel Farm Potable 23242 1 N/A

# Area Location Type Tank ID # Tanks Remarks

1, ISA Ice Plant Tank

– Direct Line Isa LSA Potable N/A 2 N/A

3, ARMY Tank A – Ablution Units Isa LSA Potable 24062 2

5, ARMY Tank B- Ablution Units Isa LSA Potable 24279 2

Tank (4807 &

4808) Isa LSA Potable 28840 1

Bagel Shop Tank-

Direct Line Isa LSA Potable N/A 1 N/A

9 Main Galley Tank Isa LSA Potable N/A 1 N/A

Navy Medical Tank

– Direct Line Isa LSA Potable N/A 1 N/A

Concession Trailer

Tank Isa LSA Potable N/A 1 N/A

Raptor Road Tank –

(3993 & 3994) Isa LSA Potable 28823 1

14 Marine Tank Isa LSA Potable Daily 1

Tank Beside Main DFAC (AB Unit) –

(7160 & 7260) Isa LSA Potable 26783 1 N/A

Marine Medic Tank

– (9913) Isa LSA Potable N/A 1 N/A

Main Laundry –

(7305) Isa LSA Potable N/A 1 N/A

# Area Location Type Tank ID # Tanks Remarks

Fire Department

(Oval) Tank Isa LSA Potable N/A 1 N/A

19 USN DJC2 ISA LSA Potable N/A 2 N/A

DFAC Fire Dept.

Water Tank ISA LSA Potable N/A 1 N/A

21 K9 Unit – (4801) ISA LSA Potable N/A 1 N/A 22 Vehicle Wash Rack ISA LSA Potable N/A 1 N/A

Fuel Point Water

Tank ISA LSA Potable N/A 1 N/A

AB Units Tank – (2004,2005,2020) Isa PAT Potable 24581 1 N/A

Galley Tank –

(2001) Isa PAT Potable 26176 1 N/A

26 Laundry Unit Tank ISA PAT Potable N/A 1 N/A

AB Unit Tank –

(3004,3005) Riffa PAT Potable 24801 1 N/A

DFAC Tank –

(3001) Riffa PAT Potable 26177 1 N/A

Male AB Unit Tank

– (5029) Flight line Potable N/A 1 N/A

Female AB Unit

Tank- (5030) Flight line Potable N/A 1 N/A

31, Marine AB Unit Tank – (5201 to

5206) Flight line Potable 28936937 2 N/A

Galley Tank –

(5003) Flight line Potable 28938 1 N/A

Apron Tank 1

(5000 gal) Flight line Potable N/A 1 N/A

Apron Tank 2

(5000 gal) Flight line Potable N/A 1 N/A

AB Unit Tank –

(5605) Fuel Farm Potable 23242 1 N/A

Inside Marines

DKET Isa LSA Non -Potable N/A 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank A 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank B 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank C 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank D 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank E 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank F 1 N/A

# Area Location Type Tank ID # Tanks Remarks

ROWPU Product

Tank Isa LSA Potable Tank G 1 N/A

ROWPU Product

Tank Isa LSA Potable Tank H 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Tank 1 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Tank 2 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Tank 3 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Tank 4 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Underground 1 N/A

ROWPU Raw Water Tank Isa LSA Non-Potable Underground 1 N/A

Sl.

N0

Area Location Type Tank ID No. of Tanks

Remarks

1 ARMY Tank A – Ablution Units Isa LSA Potable 24062 2 N/A

2 ARMY Tank B- Ablution Units Isa LSA Potable 24279 2 N/A

3 Tank (South Road)– (4807 & 4808) Isa LSA Potable 28840 1 N/A

4 Main Galley Tank Isa LSA Potable N/A 1 N/A

5 Concession Trailer Tank Isa LSA Potable N/A 1 N/A

6 Raptor Road Tank – (3993 & 3994) Isa LSA Potable 28823 1 N/A

7 Marine Tank Isa LSA Potable N/A 1 N/A

Tank Beside Main DFAC (AB Unit) – (7160 & 7260)

Isa LSA Potable 26783 1 N/A

9 Marine Medic Tank – (9913) Isa LSA Potable N/A 1 N/A

10 Fire Department (Oval) Tank Isa LSA Potable N/A 1 N/A

11 USN DJC2 Isa LSA Potable N/A 2 N/A

12 DFAC Fire Dept. Water Tank Isa LSA Potable N/A 1 N/A

13 K9 Unit – (4801) Isa LSA Potable N/A 1 N/A

14 Vehicle Wash Rack Isa LSA Potable N/A 1 N/A

15 Fuel Point Water Tank Isa LSA Potable N/A 1 N/A

16 Inside Marines DKET Isa LSA Non -

Potable N/A 1 N/A

17 ROWPU Product Tank Isa LSA Potable Tank A 1 N/A

18 ROWPU Product Tank Isa LSA Potable Tank B 1 N/A

Sl.

N0

Area Location Type Tank ID No. of Tanks

Remarks

19 ROWPU Product Tank Isa LSA Potable Tank C 1 N/A

20 ROWPU Product Tank Isa LSA Potable Tank D 1 N/A

21 ROWPU Product Tank Isa LSA Potable Tank E 1 N/A

22 ROWPU Product Tank Isa LSA Potable Tank F 1 N/A

23 ROWPU Product Tank Isa LSA Potable Tank G 1 N/A

24 ROWPU Product Tank Isa LSA Potable Tank H 1 N/A

25 ROWPU Raw Water Tank Isa LSA Non-

Potable Tank 1 1 N/A

26 ROWPU Raw Water Tank Isa LSA Non-

Potable Tank 2 1 N/A

27 ROWPU Raw Water Tank Isa LSA Non-

Potable Tank 3 1 N/A

28 ROWPU Raw Water Tank Isa LSA Non-

Potable Tank 4 1 N/A

29 ROWPU Raw Water Tank Isa LSA Non-

Potable Underground 1 N/A

30 ROWPU Raw Water Tank Isa LSA Non-

Potable Underground 1 N/A

31 AB Units Tank – (2004,2005,2020) Isa PAT Potable 24581 1 N/A

32 Galley Tank – (2001) Isa PAT Potable 26176 1 N/A

33 Laundry Unit Tank ISA PAT Potable N/A 1 N/A

34 AB Unit Tank –(3004,3005) Riffa

PAT

Potable 24801 1 N/A

35 DFAC Tank – (3001) Riffa

PAT

Potable 26177 1 N/A

36 Male AB Unit Tank – (5029) Flight line

Potable N/A 1 N/A

37 Female AB Unit Tank- (5030) Flight line

Potable N/A 1 N/A

38 Marine AB Unit Tank – (5201 to 5206) Flight line

Potable 28936937 2 N/A

39 Galley Tank – (5003) Flight line

Potable 28938 1 N/A

40 Apron Tank 1 (5000 gal) Flight line

Potable N/A 1 N/A

41 Apron Tank 2 (5000 gal) Flight line

Potable N/A 1 N/A

42 P8 Hangar Flight line

Non- Potable

N/A 2 Fire

Suppression water tank

43 AB Unit Tank – (5605) Fuel Farm

Potable 23242 1 N/A

Total Tanks 48

Attachment J-1606000-05 Bottled Water Delivery Locations

DFAC

Gym MWR K-Span Chapel Marine area (2 points in this area) LSA Downtown area Post Office Bus Stop Manhattan Beach SEC FOR TOC (LSA at lower end of camp) Flight Line

On average three pallets of bottled water is delivered to each water point. Note that during the summer months an additional pallet may be required to keep up with demand.

Note:

24 bottles = 1 case

50 cases = 1 pallet

ATTACHMENT J-1606000-06

Backflow Prevention Device Inventory

Attachment J-1606000-06 Backflow Prevention Device Inventory

Item No:

Description Model Serial No Location

1 Backflow Preventer - 4" TYPE RP WATTS LF

909 M2 QT

16184 2040 Water Storage tanks near RO Facility