_J-1602000 Electrical (Amendment 0017).pdf
PDF 130 KB Posted
- Solicitation number
- N6247018R3004
About this file
This document package includes technical specifications for electrical power generation, transmission and distribution systems at various sites supported by Naval Facilities Engineering Command (NAVFAC) under Solicitation N62470-18-R-3004. Key requirements include operation and maintenance of electrical infrastructure at the Logistic Support Area, Fueling Assistance and Parking Service, Flight Line and Fuel Farm sites at Isa Air Base, Bahrain, as well as the Patriot Battery site in Riffa, Bahrain. The incumbent contractor is required to provide generators, fuel, switchgear, distribution panels, cables, lighting and grounding systems to support 115V, 230V and 415V power throughout the various sites. Preventative maintenance, testing, repair and replacement services must be delivered under an Integrated Maintenance Plan to ensure continuous system readiness over the base operations support contract period.
View the file
Other files
Show 40 more
Latest 50 of 111 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Section J Documents, Exhibits, and Other Attachments
Table of Contents
Attachment Number
Attachment Title
J-1602000-01 Definitions and Acronyms J-1602000-02 References and Technical Documents J-1602000-03 Electrical Power Generation and Transmission and Distribution System J-1602000-04 Electrical Power Generation and Transmission and Distribution System Inventory J-1602000-05 J-1602000-04
Flight Line Power Generation/ Distribution System
Attachment J-1602000-01 Definitions and Acronyms
Definition Description Equipment, Collateral Encompasses built-in and large substantially affixed equipment/property that is normally acquired and installed as part of a facility project.
Equipment, Installed Encompasses building-type equipment, built-in equipment, and large, substantially affixed equipment/property, and is normally acquired and installed as part of a facility project. Installed equipment is normally required to make a facility useful and operable. Removing such equipment would impair the usefulness, safety, or environment of the facility or the facility restoration work required after its removal, is substantial.
Equipment, Personal Property Personal property equipment includes all equipment other than collateral equipment. Such equipment, when acquired and used in a facility or a test apparatus, can be severed and removed after erection or installation without substantial loss of value or damage thereto or to the premises where installed.
Facilities Life Cycle A facilities life cycle is divided into four stages, requirements (planning and design), acquisition (construction and acceptance), stewardship (operations, maintenance and repair), and disposal.
Facilities Maintenance Management
The planning, prioritizing, organizing, controlling, reporting, evaluating, and adjusting of facilities maintenance operations to support the CNO/NAVFAC facilities policy and objectives and satisfy customers’ facility needs. Defined by the International Facility Management Association as “the practice of coordinating the physical workplace with the people and work of the organization.”
High Voltage Transmission Transmission of electrical loads greater than 69 kilovolts (KV).
Integrated Maintenance Plan IMP is a recurring state-of-the-art, reliability-centered inspection, testing, maintenance and repair program that determines best practices for managing the functions and consequences of failures of facilities equipment and system components. IMP encompasses accepted commercial practices, including reactive, preventive, predictive and proactive maintenance, into one optimal program. The IMP approach gives the Contractor full responsibility to maintain systems and equipment and perform repairs whenever necessary to ensure equipment and systems are operational and remain in a constant state of readiness.
Life-Cycle Costs A form of economic analysis that considers the total cost of owning, operating, and maintaining a building or system over its useful life.
Low Voltage Distribution Distribution of electrical loads less than or equal to 600 volts (V).
Medium Voltage Distribution Distribution of electrical loads ranging from greater than 600 V up to and including 69 KV.
Repair Repair is the restoration of facilities or equipment to such a condition that it may be effectively utilized for its designated purposes by overhaul, reconstruction, or replacement of constituent parts or materials which have deteriorated by action of the elements or usage, and which have not been corrected through maintenance. This term also applies to replacement of the entire unit or system if beyond economical repair. The intent of repair is to have the equipment at normal working condition.
Replacement Replacement, as a distinct work element, is confined to a program of planned replacement of a facility or its components. It may be further limited to major components such as air conditioning compressors, furnaces or hot water heaters. Replacement is performed when the equipment has reached the end of its useful life; when it no longer can perform due to degradation of its internal components and repair is no longer cost effective. Included under the replacement would be the major rebuilding of any component, since rebuilding also restores performance.
SCADA A version of telemetry commonly used in wide-area industrial applications, such as electrical power generation and distribution and water distribution, which includes supervisory control of remote stations as well as data
Attachment J-1602000-01 Definitions and Acronyms
Definition Description Acronym Title
AC Alternating Current (electricity)
ANSI American National Standards Institute
ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers
ASME American Society of Mechanical Engineers
BPVC Boiler and Pressure Vessel Code
IMP Integrated Maintenance Program NEC National Electrical Code NFPA National Fire Protection Association SCADA Supervisory Control and Data Acquisition SRM Sustainment, Restoration and Modernization
UFC Unified Facilities Criteria
UPV Unfired Pressure Vessel
Attachment J-1602000-02
References and Technical Documents
Reference Title MO-209 Engineering Criteria UFC 3-430-02FA Central Steam Boiler Plants UFC 3-430-07 Operations and Maintenance: Inspection and Certification of Boilers and
Unfired Pressure Vessels UFC 3-430-08N Central Heating Plants UFC 3-501-01 Electrical Engineering UFC 3-550-01 Exterior Electrical Power Distribution UFC 3-560-01 Electrical Safety. O&M NAVFAC P-307 Management of Weight Handling Equipment Department of the Army.
AR 420-49 Heating, Energy Selection and Fuel Storage, Distribution, and Dispensing Systems TM 5-811-6 Electric Power Plant Design TM 5-815-1 Air Pollution Control Systems Boilers and Incinerators
Non-Government Publications.
American Association of State Highway and Transportation Officials, (AASHTO) 444 North Capital Street, N.W., Suite 249, Washington, DC 20001
American Boiler Manufacturers Association (ABMA) 950 N. Glebe Road, Suite 160, Arlington, VA 22203
American Concrete Institute (ACI) P.O. Box 19150, Redford Station, Detroit, MI 48219-0150
American Gear Manufacturers Association (AGMA) 1500 King Street, Suite 201, Alexandria, VA 22314
American National Standards Institute, Inc. (ANSI) 11 West 42nd Street, New York, NY 10036
American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Publication Dept. 1791 Tullie Circle, N.E., Atlanta, GA 30329
ASHRAE (1991) Handbook, HVAC Applications ASHRAE (1992) Handbook, HVAC Systems and Equipment ASHRAE (1993) Handbook, Fundamentals ASHRAE (1990) Handbook, Refrigeration Systems and Applications
Attachment J-1602000-03 Electrical Power Generation and Transmission and Distribution System Description
Logistic Support Area (LSA), Isa Air Base
The LSA electrical source is provided by portable generators and permanent power supplied by the Kingdom of Bahrain Electric and Water Authority (EWA).
The RAS Grain Intake 11-kV is the utility substation that supplies power to the LSA. The substation is outside the perimeter of the LSA to the east.
The LSA is supplied by redundant feeders from the (EWA) RAS Grain Intake 11-kV utility substation, one feeder connected to 1USS and the other feeder connected to 7USS.
The 11-kV ring is routed through the site and the loop disconnect at 3USS RMU (Ring Main Unit) is open. One feeder supplies 1USS and 2USS while the other feeder supplies 7USS, 6USS, 5USS, 4USS, and 3USS. The Site 1 – LSA, 11-kV utility distribution is maintained by EWA.
The 415Y/240 VAC electrical distribution has been installed in a workmanlike manner.
Final distribution panels were located outdoors and supplied multiple branch panel boards located inside the buildings.
LSA Isa Air Base electrical distribution utilized a mixture of SWA (Steel Wire Armored) direct-buried cable, or multi conductors in a raceway system.
These distribution systems have a properly sized bonding jumper from neutral-ground installed at the supply source. Separate neutral and equipment grounding conductors should be routed throughout the distribution system per NEC 250.32.
The electrical distribution was primarily direct buried; however, there were a few electrical hand-holes at the LSA site.
A considerable amount of abandoned cable and electrical equipment present at the LSA.
Solar street lighting manufactured by Solar Illuminations is primarily utilized at the LSA. The solar street lights consist of a 20 foot pole with two solar panels, a light fixture at the top of the pole and a control cabinet at the base of each pole to house two, 12-volt batteries and a charging controller.
Portable generator light towers are also utilized and consideration should be given to replacing these units with either portable solar light towers or permanent pole solar lights.
FASP, Isa Air Base
The electrical distribution at the FASP was supplied by portable military generators and the electrical distribution consisted of armored electrical cables routed on the ground.
Portable generator light towers are utilized at the FASP.
Flight Line, Isa Air Base Bahrain
The Flight Line electrical source is provided by portable 415Y/240 Aggreko generators and by military portable generators.
The electrical distribution is installed above grade; cables are routed above grade and randomly routed over hand - hole covers and in front of electrical cabinets.
Final distribution panels were located outdoors and supplied multiple branch panelboards located inside the buildings.
The electrical distribution was primarily direct-buried; however, there were a few electrical hand-holes at the Flight Line site.
Portable generator light towers are utilized at the Flight Line Site.
Fuel Farm, Isa Air Base Bahrain
The electrical distribution at the Fuel Farm was primarily expeditionary and supplied by portable generators. There were no electrical hand-holes on the Fuel Farm Site.
Portable generator light towers are utilized at the Fuel Farm.
Attachment J-1602000-04 Generator Inventory
Insert file J-1602000-04 Generator Inventory
Attachment J-1602000-05 Attachment J-1602000-04
Flight Line Power Generation/ Distribution System
Current power generation & distribution electrical power system at flight line
1) 60HZ U.S. Standard 110V/208V
a) 3 X 350kVA generators
b) 1 X 20000 liter fuel tank
c) 1 X 4000A sync panel
d) 1 X 2500A panel
e) 2 X 2000A panel
f) 3 X 1000A panel
g) Direct buried Electrical cables
h) Grounding system
2) 50Hz Local Standard 230V/415V
a) 4 X 350kVA generators
b) 1 X 20000 liter Fuel tank
c) 1 X 8000A Sync panel
d) 1 X 2500A panel
e) 3 X 3000A Panel
f) 4 X 1000A panel
g) Direct buried Electrical cables
h) Grounding system
File details come from the government source that posted it. Updated .