BEQ Repair AS4212
Solicitation number
N4008525R2620
Issued by

About this file

This document is an engineering drawing (E-111) for lightning protection system design for a Barracks Equipment Quarters (BEQ) repair project at Marine Corps Base Camp Lejeune. The roof plan drawing provides detailed specifications for lightning protection installation, including requirements for air terminals, conductors, and grounding components. Key technical specifications include:

Specific installation requirements mandate Class I air terminals (12 inches in height), using either copper or aluminum materials with 3/8 or 1/2 inch diameter. Conductors must be #17 AWG 29-strand copper or #14 AWG 14-strand aluminum, with copper preferred. The design requires down lead conductors connected to a ground loop, protected by PVC Schedule 40 conduit, and attached to a 3/4 inch by 10-foot copperclad ground rod. The lightning protection system must conform to NFPA 780 and UL 96A standards, with components requiring UL listing and Cal-OSHA approval. Conductors must be fastened at intervals not exceeding 36 inches on center, using matching metal roof fasteners compatible with the conductor material.

View the file

Other files

File Type Posted
Amend 0021.pdf PDF
Amend 0020.pdf PDF
Amend 0019.pdf PDF
Amend 0018.pdf PDF
Amend 0017.pdf PDF
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0013.pdf PDF
Amend 0014.pdf PDF
60040177.pdf PDF
60040178.pdf PDF
60040167.pdf PDF
Updated SUBMITTAL REGISTER.pdf PDF
60040172.pdf PDF
60040137.pdf PDF
Updated List of Drawings.pdf PDF
60040262.pdf PDF
60040179.pdf PDF
60040268.pdf PDF
Updated PROJECT TABLE OF CONTENTS.pdf PDF
60040164.pdf PDF
11 81 00.pdf PDF
60040186.pdf PDF
60040187.pdf PDF
60040189.pdf PDF
07 60 00.pdf PDF
07 61 15.00 20.pdf PDF
60040174A.pdf PDF
60040250.pdf PDF
60040188.pdf PDF
05 51 33.pdf PDF
Amend 12 and spec combined.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
60040202_PPI.pdf PDF
60040196_PPI.pdf PDF
60040201_PPI.pdf PDF
PROJECT.pdf PDF
60040198_PPI.pdf PDF
60040197_PPI.pdf PDF
SECTION 33 61 14.pdf PDF
60040199_PPI.pdf PDF
60040210_PPI.pdf PDF
Amend and cont sheet combined.pdf PDF
60040195_PPI.pdf PDF
60040290_PPI.pdf PDF
REGISTER.pdf PDF
60040194_PPI.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2

1 1 1

3 4

2'-0"

M

IN

1'

-0

MIN.

'-0

M

IN

GRADE

GROUND ROD

CONDUCTOR

DOWN

GROUND

ROD

CLAMP

AIR TERMINAL DETAIL

NTS

NOTES:

AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 & 96A REQUIREMENTS.

MATERIAL CLASS SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.

AIR TERMINALS SHALL BE UL LISTED & CAL-OSHA APPROVED.

LIGHTNING PROTECTION

CONDUCTORS:

FASTEN COPPER CONDUCTORS WITH COPPER STANDING SEAM

METAL ROOF FASTENER. FASTEN ALUMINUM CONDUCTORS WITH

ALUMINUM STANDING SEAM METAL ROOF FASTENER. LIGHTNING

PROTECTION CONDUCTORS SHALL BE FASTENED AT INTERVALS

NOT MORE THAN 36" ON CENTER.

EXTRUDED COPPER STANDING SEAM METAL

ROOF AIR TERMINAL BASE. FOR SURFACES NOT

COMPATIBLE WITH COPPER USE EXTRUDED

ALUMINUM STANDING SEAM METAL ROOF AIR

TERMINAL BASE.

AIR

TERMINAL

GROUNDING DETAILTHRU WALL ASSEMBLY DETAIL

THRU ROOF

CONDUCTOR

LIGHTNING

CONDUCTOR

LIGHTNING

CONDUCTOR

NTS NTSLRODTWL1 BLDGSG

A B

C D

E

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091 CONSTR. CONTR. NO.

AS NOTEDSCALE SHEETSPEC.

2 3 4 5 6

A B

C D

E

1 2 3 4 5 6

E-111

Approver

J. REED

REPAIR BEQ AS4212

ROOF PLAN - LIGHTNING PROTECTION

60040299 N40085-23-B-0035

3/32" = 1'-0"

B1 ROOF PLAN - LIGHTNING PROTECTION

PLAN NOTES

1 DOWN LEAD CONDUCTOR CONNECTED TO GROUND LOOP. PROVIDE PVC

SCHEDULE 40 TO PROTECT CONDUCTOR FROM PHYSICAL DAMAGE.

CONNECT DOWN LEAD CONDUCTOR TO #1/0 AWG COPPER GROUND LOOP

AND USE 3/4 INCH BY 10 FOOT COPPERCLAD GROUND ROD BY EXOTHERMIC

CONNECTION. SEE GROUNDING DETAIL. TYPICAL.

2 PROVIDE TEST WELL AT DOWNLEAD GROUND ROD LOCATION FOR FUTURE

TESTING AND MAINTENANCE AS REQUIRED.

3 CLASS I AIR TERMINAL, 12 INCHES IN HEIGHT/LENGTH. USE 3/8 INCH

DIAMETER FOR COPPER OR 1/2 INCH DIAMETER FOR ALUMINUM. AIR

TERMINAL MATERIAL MUST MATCH AND BE COMPATIBLE WITH MATERIAL

USED FOR CONDUCTORS. TYPICAL.

4 CLASS I CONDUCTORS MUST BE #17 AWG, 29 STRAND COPPER OR #14 AWG,

14 STRAND ALUMINUM. TYPICAL. COPPER MUST BE USED WHENEVER

POSSIBLE.

GRAPHIC SCALE: 3/32"=1'-0"

8' 0 8' 16' 24'

N

KELLY ROOT

FINAL

Sheets and Views
Layout1

File details come from the government source that posted it. Updated .