This document is a detailed technical specification (Section 07 60 00) for flashing and sheet metal work for repairs at BEQ AS4212 at MCB Camp Lejeune, NC. The specification provides comprehensive requirements for sheet metal installation, including materials, fabrication, and installation methods for various components such as downspouts, gutters, flashings, copings, and sheet metal coverings.

Key technical requirements include using specific materials like aluminum, stainless steel, or copper with precise thickness specifications, mandating weathertight installations, and defining joint types and seam configurations. The document specifies detailed installation techniques, such as expansion and contraction joint spacing, counterflashing methods, and requirements for mechanical fastening. Contractors must submit shop drawings, samples, manufacturer's instructions, and maintain a quality control plan. The specification also includes tables detailing sheet metal weights, thicknesses, and joint types for different metal components, ensuring precise and standardized installation practices.

View the file

Other files

File Type Posted
Amend 0021.pdf PDF
Amend 0020.pdf PDF
Amend 0019.pdf PDF
Amend 0018.pdf PDF
Amend 0017.pdf PDF
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0013.pdf PDF
Amend 0014.pdf PDF
60040177.pdf PDF
60040178.pdf PDF
60040167.pdf PDF
Updated SUBMITTAL REGISTER.pdf PDF
60040172.pdf PDF
60040137.pdf PDF
Updated List of Drawings.pdf PDF
60040262.pdf PDF
60040179.pdf PDF
60040268.pdf PDF
Updated PROJECT TABLE OF CONTENTS.pdf PDF
60040164.pdf PDF
11 81 00.pdf PDF
60040186.pdf PDF
60040187.pdf PDF
60040189.pdf PDF
60040299.pdf PDF
07 61 15.00 20.pdf PDF
60040174A.pdf PDF
60040250.pdf PDF
60040188.pdf PDF
05 51 33.pdf PDF
Amend 12 and spec combined.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
60040202_PPI.pdf PDF
60040196_PPI.pdf PDF
60040201_PPI.pdf PDF
PROJECT.pdf PDF
60040198_PPI.pdf PDF
60040197_PPI.pdf PDF
SECTION 33 61 14.pdf PDF
60040199_PPI.pdf PDF
60040210_PPI.pdf PDF
Amend and cont sheet combined.pdf PDF
60040195_PPI.pdf PDF
60040290_PPI.pdf PDF
REGISTER.pdf PDF
60040194_PPI.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repairs BEQ AS4212 Project No. 23-0035 MCB Camp Lejeune, NC Roof Amendement - 25 July 2025

SECTION 07 60 00

FLASHING AND SHEET METAL

05/17, CHG 2: 11/18

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)

AAMA 2605 (2020) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels

ASTM INTERNATIONAL (ASTM)

ASTM A480/A480M (2020a) Standard Specification for General Requirements for Flat-Rolled Stainless and Heat-Resisting Steel Plate, Sheet, and Strip

ASTM B32 (2020) Standard Specification for Solder Metal

ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM B370 (2022) Standard Specification for Copper Sheet and Strip for Building Construction

SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION

(SMACNA)

SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition

1.2 GENERAL REQUIREMENTS

Finished sheet metal assemblies must form a weathertight enclosure without waves, warps, buckles, fastening stresses or distortion, while allowing for expansion and contraction without damage to the system. The sheet metal installer is responsible for cutting, fitting, drilling, and other operations in connection with sheet metal modifications required to accommodate the work of other trades. Coordinate installation of sheet metal items used in conjunction with roofing with roofing work to permit continuous, uninterrupted roofing operations.

SECTION 07 60 00 Page 1

1.3 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Exposed Sheet Metal Coverings; G

Gutters ; G

Downspouts ; G

Copings ; G

Recycled Content ; S

SD-04 Samples

Finish Samples ; G

SD-08 Manufacturer's Instructions

Instructions for Installation ; G

Quality Control Plan ; G

SD-10 Operation and Maintenance Data

Cleaning and Maintenance ; G

1.4 MISCELLANEOUS REQUIREMENTS

1.4.1 Product Data

Indicate thicknesses, dimensions, fastenings, anchoring methods, expansion joints, and other provisions necessary for thermal expansion and contraction. Scaled manufacturer's catalog data may be submitted for factory fabricated items.

1.4.2 Finish Samples

Submit two color charts and two finish sample chips from manufacturer's standard color and finish options for each type of finish indicated.

1.4.3 Operation and Maintenance Data

Submit detailed instructions for installation and quality control during installation, cleaning and maintenance , for each type of assembly

SECTION 07 60 00 Page 2 indicated.

1.5 DELIVERY, HANDLING, AND STORAGE

Package and protect materials during shipment. Uncrate and inspect materials for damage, dampness, and wet-storage stains upon delivery to the job site. Remove from the site and replace damaged materials that cannot be restored to like-new condition. Handle sheet metal items to avoid damage to surfaces, edges, and ends. Store materials in dry, weather-tight, ventilated areas until installation.

PART 2 PRODUCTS

2.1 RECYCLED CONTENT

Provide products with recycled content. Provide data for each product with recycled content, identifying percentage of recycled content.

2.2 MATERIALS

Do not use lead, lead-coated metal, or galvanized steel. Provide materials, thicknesses, and configurations in accordance with SMACNA 1793 for each material. Different items need not be of the same metal, except that if copper is selected for any exposed item, all exposed items must be copper, and that contact between dissimilar metals must be avoided.

Furnish sheet metal items in 8 to 10 foot lengths. Single pieces less than 8 feet long may be used to connect to factory-fabricated inside and outside corners, and at ends of runs. Factory fabricate corner pieces with minimum 12 inch legs. Provide accessories and other items essential to complete the sheet metal installation. Provide accessories made of the same or compatible materials as the items to which they are applied.

Fabricate sheet metal items of the materials specified below and to the gage, thickness, or weight shown in Table I at the end of this section.

Where more than one material is listed for a particular item in Table I, each is acceptable and may be used, except as follows:

2.2.1 Exposed Sheet Metal Items

Must be of the same material. Consider the following as exposed sheet metal: gutters, including hangers; downspouts; cap, ste pped, base, and eave flashings and related accessories.

2.2.2 Drainage

Do not use copper for an exposed item if drainage from that item will pass over exposed masonry, stonework or other metal surfaces.

2.2.3 Copper, Sheet and Strip

Provide in accordance with ASTM B370, cold-rolled temper, H 00 (standard).

2.2.4 Stainless Steel

Provide in accordance with ASTM A480/A480M , Type 302 or 304, 2D Finish, fully annealed, dead-soft temper.

SECTION 07 60 00 Page 3

2.2.5 Aluminum Alloy Sheet and Plate

Provide in accordance with ASTM B209 form alloy, and temper appropriate for use. Provide material not less than 0.0 40-in in thickness.

Furnish aluminum with an organic coating treatment conforming to AAMA 2605 to obtain a 70% PVDF coating.

2.2.5.1 Alclad

When fabricated of aluminum, fabricate the following items with Alclad 3003, Alclad 3004, or Alclad 3005, clad on one side unless otherwise indicated.

a. Gutters, downspouts, and hangers

b. Gravel stops and fascia

c. Flashing

2.2.6 Prefinished Steel

Prefinished steel sheet coil is 0.024 inch, 24 gauge conforming to ASTM A 653, Class G90 and AAMA 621.

2.2.6.1 Organic Coating

Furnish prefinished steel with an organic coating treatment conforming to AAMA 2605 to obtain a 70% PVDF coating.

2.2.7 Finishes

Provide exposed exterior sheet metal and aluminum with a baked on, factory applied color coating of polyvinylidene fluoride (PVF2) or approved equal fluorocarbon coating. Dry film thickness of coatings must be 0.8 to 1.3 mils . Color is to match sheet metal roofing for newly constructed buildigs. Field applications of color coatings are prohibited and will be rejected.

2.2.8 Aluminum Alloy, Extruded Bars, Rods, Shapes, and Tubes

ASTM B221.

2.2.9 Solder

Provide in accordance with ASTM B32, 95-5 tin-antimony.

2.2.10 Downspouts and Gutters

Downspouts, gutters, components and accessories are a matching material and finish.

Downspout tubing joints are tapered and telescope 1 inch. Metal brackets are fabrications 1 inch in width with a combination external strap and internal wall stand off. Fabricate seamless 45 degree offset and kickout elbows.

Fabricate offsets and terminations that telescope into downspout boot receivers.

SECTION 07 60 00 Page 4

Fabricate gutters in the longest lengths practical. Separate gutter end joints 0.375 of an inch and back with 6 inch wide exposed splice plates at gutter expansion joints. Create 0.375 inch expansion reveals to accommodate thermal movement with 6 inch wide concealed splice plates between joint lengths. Provide support brackets and interior spreaders.

Hem exposed edges. Construct corner fabrications using miter joints with button lock pockets in lieu of interlocked and mechanically fastened assemblies. Shop fabricate 1 foot, 6 inch inside corner, outside corner, tee and end terminations using butt joint and splice plate end conditions. Provide end caps, outlets and similar accessories.

Furnish bronze, copper, stainless steel or aluminum wire ball strainers at each outlet.

2.2.11 Copings

Provide copings in sheets, 8 or 10 feet long, joined by a 3/4 inch locked and soldered seam.

2.2.12 Fasteners

Use stainless steel fasteners to fasten. Confirm compatibility of fasteners and items to be fastened to avoid galvanic corrosion due to dissimilar materials.

Finish exposed rivets and fasteners to match substrate colors encountered.

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Metal Fascias and Soffits

3.1.2 Workmanship

Make lines and angles sharp and true. Free exposed surfaces from visible wave, warp, buckle, and tool marks. Fold back exposed edges neatly to form a 1/2 inch hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.

Make surfaces to receive sheet metal plumb and true, clean, even, smooth, dry, and free of defects and projections. For installation of items not shown in detail or not covered by specifications conform to the applicable requirements of SMACNA 1793, Architectural Sheet Metal Manual. Provide sheet metal flashing in the angles required to accommodate terminations, edges and wherever indicated and necessary to make the work watertight.

Join sheet metal items together as shown in Table II.

3.1.3 Nailing

Confine nailing of sheet metal generally to sheet metal having a maximum width of 18 inches . Confine nailing of flashing to one edge only. Space nails evenly not over 3 inch on center and approximately 1/2 inch from edge unless otherwise specified or indicated. Face nailing will not be permitted. Where sheet metal is applied to other than wood surfaces, include in shop drawings, the locations for sleepers and nailing strips required to secure the work. Secure flashing at one-half the normal

SECTION 07 60 00 Page 5 interval to ensure a wind-resistant installation.

3.1.4 Cleats

Provide cleats for sheet metal 18 inches and over in width. Cleats are continuous . Unless otherwise specified, provide cleats of 2 inches wide and of the same material and thickness as the sheet metal being installed. Secure one end of the cleat with two nails and the cleat folded back over the nailheads. Lock the other end into the seam.

Pre-tin cleats for soldered seams.

3.1.5 Bolts, Rivets, and Screws

Install bolts, rivets, and screws where indicated or required. Provide compatible washers where required to protect surface of sheet metal and to provide a watertight connection. Provide mechanically formed joints in aluminum sheets 0.040 inches or less in thickness.

3.1.6 Seams

Straight and uniform in width and height with no solder showing on the face.

3.1.6.1 Flat-lock Seams

Finish not less than 3/4 inch wide.

3.1.6.2 Lap Seams

Finish soldered seams not less than one inch wide. Overlap seams not soldered, not less than 3 inches .

3.1.6.3 Loose-Lock Expansion Seams

Not less than 3 inches wide; provide minimum one inch movement within the joint. Completely fill the joints with the specified sealant, applied at not less than 1/8 inch thick bed.

3.1.6.4 Standing Seams

Not less than one inch high, double locked without solder.

3.1.6.5 Flat Seams

Make seams in the direction of the flow.

3.1.7 Soldering

Where soldering is specified, apply to copper and stainless steel items.

Pre-tin edges of sheet metal before soldering is begun. Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.

3.1.8 Mechanical Fastening

Aluminum 0.040 inch or less in thickness must be butted and the space backed with formed flashing plate; or lock joined, mechanically fastened, and filled with sealant as recommended by the aluminum manufacturer.

SECTION 07 60 00 Page 6

3.1.8.1 Mechanical Fastening of Aluminum

Use No. 12, aluminum alloy, sheet metal screws or other suitable aluminum alloy or stainless steel fasteners. Drive fasteners in holes made with a No. 26 drill in securing side laps, end laps, and flashings. Space fasteners 12 inches maximum on center. Where end lap fasteners are required to improve closure, locate the end lap fasteners not more than 2 inches from the end of the overlapping sheet.

3.1.9 Protection from Contact with Dissimilar Materials

3.1.9.1 Copper or Copper-bearing Alloys

Paint with heavy-bodied bituminous paint surfaces in contact with dissimilar metal, or separate the surfaces by means of moistureproof building felts.

3.1.9.2 Aluminum

Do not allow aluminum surfaces in direct contact with other metals except stainless steel, zinc, or zinc coating. Where aluminum contacts another metal, paint the dissimilar metal with a primer followed by two coats of aluminum paint. Where drainage from a dissimilar metal passes over aluminum, paint the dissimilar metal with a non-lead pigmented paint.

3.1.9.3 Metal Surfaces

Paint surfaces in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.

3.1.10 Expansion and Contraction

Provide expansion and contraction joints at not more than 32 foot intervals for aluminum and at not more than 40 foot intervals for other metals. Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval. Space joints evenly. Join extruded aluminum gravel stops and fascia by expansion and contraction joints spaced not more than 12 feet apart.

3.1.11 Counterflashing

Except where indicated or specified otherwise, insert counterflashing above roof decks, extend down vertical surfaces over upturned vertical leg of base flashings not less than 3 inches . Fold the exposed edges of counterflashings 1/2 inch . Where stepped counterflashings are required, they may be installed in short lengths a minimum of 8 inches by 8 inches or may be of the preformed single piece type. Provide end laps in counterflashings not less than 3 inches and make it weathertight with plastic cement. Do not make lengths of metal counterflashings exceed 10 feet . Form flashings to the required shapes before installation. Factory form corners not less than 12 inches from the angle. Secure the flashings in the reglets with lead wedges and space not more than 18 inches apart; on short runs, place wedges closer together. Fill caulked-type reglets or raked joints which receive counterflashing with caulking compound. Turn up the concealed edge of counterflashings built into masonry or concrete walls not less than 1/4 inch and extend not less than 2 inches into the walls. Install counterflashing to provide a spring action against base

SECTION 07 60 00 Page 7 flashing.

3.1.12 Gutters

The hung type of shape indicated and supported on underside by brackets that permit free thermal movement of the gutter. Provide gutters in sizes indicated complete with mitered corners, end caps, outlets, brackets, and other accessories necessary for installation. Bead with hemmed edge or reinforce the outer edge of gutter with a stiffening bar not less than 3/4 by 3/16 inch of material compatible with gutter. Fabricate gutters in sections not less than 8 feet . Lap the sections a minimum of one inch in the direction of flow or provide with concealed splice plate 6 inches minimum. Join the gutters, other than aluminum, by riveted and soldered joints. Join aluminum gutters with riveted sealed joints. Provide expansion-type slip joints midway between outlets. Install gutters below slope line of the roof so that snow and ice can slide clear. Support gutters on adjustable hangers spaced not more than 30 inches on center or with continuous cleats and counterflashing . Adjust gutters to slope uniformly to outlets, with high points occurring midway between outlets.

Fabricate hangers and fastenings from compatible metals.

3.1.13 Downspouts

Space supports for downspouts . Types, shapes and sizes are indicated.

Provide complete including elbows and offsets. Provide downspouts in approximately 10 foot lengths. Provide end joints to telescope not less than 1/2 inch and lock longitudinal joints. Provide gutter outlets with wire ball strainers for each outlet. Provide strainers to fit tightly into outlets and be of the same material used for gutters. Keep downspouts not less than one inch away from walls. Fasten to the walls at top, bottom, offsets and intermediate point s not to exceed 5 feet on center with leader straps or concealed rack-and-pin type fasteners. Form straps and fasteners of metal compatible with the downspouts.

3.1.13.1 Terminations

Neatly fit into the drainage connection the downspouts terminating in drainage lines and fill the joints with a portland cement mortar cap sloped away from the downspout. Provide downspouts terminating in splash blocks with elbow-type fittings. Provide splash pans as specified.

3.1.14 Sheet Metal Covering on Flat, Sloped, or Curved Surfaces

Except as specified or indicated otherwise, cover and flash all minor flat, sloped, or curved surfaces such as crickets, bulkheads, dormers and small decks with metal sheets of the material used for flashing; maximum size of sheets, 16 by 18 inches . Fasten sheets to sheathing with metal cleats. Lock seams and solder. Lock aluminum seams as recommended by aluminum manufacturer. Provide an underlayment of roofing felt for all sheet metal covering.

3.1.15 Copings

Provide coping with locked and soldered seam. Terminate outer edges in edge strips. Install with sealed cover plate joints.

3.2 PAINTING

Touch ups in the field may be applied only after metal substrates have

SECTION 07 60 00 Page 8 been cleaned and pretreated in accordance with manufacturer's written instructions and products.

Field-paint sheet metal for separation of dissimilar materials.

3.3 CLEANING

Clean exposed sheet metal work at completion of installation. Remove grease and oil films, handling marks, contamination from steel wool, fittings and drilling debris, and scrub-clean. Free the exposed metal surfaces of dents, creases, waves, scratch marks, and solder or weld marks.

3.4 REPAIRS TO FINISH

Scratches, abrasions, and minor surface defects of finish may be repaired in accordance with the manufacturer's printed instructions and as approved. Repair damaged surfaces caused by scratches, blemishes, and variations of color and surface texture. Replace items which cannot be repaired.

3.5 FIELD QUALITY CONTROL

Establish and maintain a Quality Control Plan for sheet metal used in conjunction with roofing to assure compliance of the installed sheet metalwork with the contract requirements. Remove work that is not in compliance with the contract and replace or correct. Include quality control, but not be limited to, the following:

a. Observation of environmental conditions; number and skill level of sheet metal workers; condition of substrate.

b. Verification that specified material is provided and installed.

c. Inspection of sheet metalwork, for proper size(s) and thickness(es), fastening and joining, and proper installation.

3.5.1 Procedure

Submit for approval prior to start of roofing work. Include a checklist of points to be observed. Document the actual quality control observations and inspections. Furnish a copy of the documentation to the Contracting Officer at the end of each day.

TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES

Sheet Metal Items Copper kilograms per square foot

Aluminum, inch

Stainless Steel, inch

SECTION 07 60 00 Page 9

TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES

Sheet Metal Items Copper kilograms per square foot

Aluminum, inch

Stainless Steel, inch

Downspouts and leaders

16 .032 .015

Downspout clips and anchors

- .040 clip .125 anchor

Downspout straps, 2-inch

48 (a) .060 .050

Conductor heads 16 .032 .015

Scupper lining 20 .032 .015

Strainers, wire diameter or gage

No. 9 gage .144 diameter

.109 diameter

Flashings:

Base 20 .040 .018

Counter-flashing 16 .032 .015

Eave 16 - .015

Stepped 16 .032 .015

Pipe vent sleave

SECTION 07 60 00 Page 10

TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES

Sheet Metal Items Copper kilograms per square foot

Aluminum, inch

Stainless Steel, inch

Coping 16 .040

Extrusions - .075 -

Sheets, smooth 20 .050 .018

Edge strip 24 .050 .025

Gutters:

Gutter section 16 .032 .015

Continuous cleat 16 .032 .015

Hangers, dimensions 1 inch by 1/8 inch (a)

1 inch by .080 inch

1 inch by .037 inch

Joint Cover plates (See Table II)

16 .032 .015

(a) Brass.

SECTION 07 60 00 Page 11

TABLE II. SHEET METAL JOINTS

TYPE OF JOINT

Item Designation Copperl and Stainless Steel

Aluminum Remarks

Flashings

Base One inch 3 inch lap for expansion joint

One inch flat locked, soldered;

sealed; 3 inch lap for expansion joint

Aluminum manufacturer's recommended hard setting sealant for locked aluminum joints. Fill each metal expansion joint with a joint sealing compound.

Eave One inch flat locked, cleated. One inch loose locked, sealed expansion joint, cleated.

One inch flat locked, locked, cleated one inch loose locked, sealed expansion joints, cleated

Same as base flashing.

Stepped 3 inch lap 3 inch lap --

Edge strip Butt Butt --

Gravel stops:

SECTION 07 60 00 Page 12

TABLE II. SHEET METAL JOINTS

TYPE OF JOINT

Item Designation Copperl and Stainless Steel

Aluminum Remarks

Extrusions -- Butt with 1/2 inch space

Use sheet flashing beneath and a cover plate

Sheet, smooth Butt with 1/4 inch space

Butt with 1/4 inch space

Use sheet flashing backup plate.

Gutters 1.5 inch lap, riveted and soldered

One inch flat locked riveted and sealed

Aluminum producers recommended hard setting sealant for locked aluminum joints.

-- End of Section --

SECTION 07 60 00 Page 13

THIS PAGE INTENTIONALLY LEFT BLANK

SECTION 07 60 00 Page 14

07 60 00 - FLASHING AND SHEET METAL
PART 1 GENERAL
1.1 REFERENCES
1.2 GENERAL REQUIREMENTS
1.3 SUBMITTALS
1.4 MISCELLANEOUS REQUIREMENTS
1.4.1 Product Data
1.4.2 Finish Samples
1.4.3 Operation and Maintenance Data

1.5 DELIVERY, HANDLING, AND STORAGE

PART 2 PRODUCTS
2.1 RECYCLED CONTENT
2.2 MATERIALS
2.2.1 Exposed Sheet Metal Items
2.2.2 Drainage
2.2.3 Copper, Sheet and Strip
2.2.4 Stainless Steel
2.2.5 Aluminum Alloy Sheet and Plate
2.2.5.1 Alclad
2.2.6 Prefinished Steel
2.2.6.1 Organic Coating
2.2.7 Finishes
2.2.8 Aluminum Alloy, Extruded Bars, Rods, Shapes, and Tubes
2.2.9 Solder
2.2.10 Downspouts and Gutters
2.2.11 Copings
2.2.12 Fasteners
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Metal Fascias and Soffits
3.1.2 Workmanship
3.1.3 Nailing
3.1.4 Cleats
3.1.5 Bolts, Rivets, and Screws
3.1.6 Seams
3.1.6.1 Flat-lock Seams
3.1.6.2 Lap Seams
3.1.6.3 Loose-Lock Expansion Seams
3.1.6.4 Standing Seams
3.1.6.5 Flat Seams
3.1.7 Soldering
3.1.8 Mechanical Fastening
3.1.8.1 Mechanical Fastening of Aluminum
3.1.9 Protection from Contact with Dissimilar Materials
3.1.9.1 Copper or Copper-bearing Alloys
3.1.9.2 Aluminum
3.1.9.3 Metal Surfaces
3.1.10 Expansion and Contraction
3.1.11 Counterflashing
3.1.12 Gutters
3.1.13 Downspouts
3.1.13.1 Terminations
3.1.14 Sheet Metal Covering on Flat, Sloped, or Curved Surfaces
3.1.15 Copings
3.2 PAINTING
3.3 CLEANING
3.4 REPAIRS TO FINISH
3.5 FIELD QUALITY CONTROL
3.5.1 Procedure

File details come from the government source that posted it. Updated .