60040268.pdf

PDF 238 KB Posted

Attached to
BEQ Repair AS4212
Solicitation number
N4008525R2620
Issued by

About this file

This mechanical drawing (Sheet M-601) is part of a Naval Facilities Engineering Systems Command project for BEQ Repair AS4212 at Marine Corps Base Camp Lejeune, North Carolina. The detailed technical drawing provides comprehensive mechanical system specifications, including schedules for dedicated outside air systems (DOAS), air handling units (AHU), packaged terminal heat pumps (PTHP), ductless split system air handling units and condensing units, fans, louvers, air distribution systems, motorized dampers, and building air balance calculations.

The drawing includes extensive technical specifications such as design conditions, air flow rates, electrical requirements, cooling and heating capacities, and specific installation requirements. Notable technical details include indoor design conditions (cooling at 76°F, heating at 70°F), outdoor design conditions for winter and summer, and specific requirements for equipment like low leakage dampers, birdscreens, aluminum construction, and corrosion-resistant components suitable for a marine environment. The document is part of contract number N40085-23-B-0035 and is marked as sheet 132 of 179, indicating it is part of a larger set of construction documents.

View the file

Other files

File Type Posted
Amend 0021.pdf PDF
Amend 0020.pdf PDF
Amend 0019.pdf PDF
Amend 0018.pdf PDF
Amend 0017.pdf PDF
Amend 0016.pdf PDF
Amend 0015.pdf PDF
Amend 0013.pdf PDF
Amend 0014.pdf PDF
60040177.pdf PDF
60040178.pdf PDF
60040167.pdf PDF
Updated SUBMITTAL REGISTER.pdf PDF
60040172.pdf PDF
60040137.pdf PDF
Updated List of Drawings.pdf PDF
60040262.pdf PDF
60040179.pdf PDF
Updated PROJECT TABLE OF CONTENTS.pdf PDF
60040164.pdf PDF
11 81 00.pdf PDF
60040186.pdf PDF
60040187.pdf PDF
60040189.pdf PDF
60040299.pdf PDF
07 60 00.pdf PDF
07 61 15.00 20.pdf PDF
60040174A.pdf PDF
60040250.pdf PDF
60040188.pdf PDF
05 51 33.pdf PDF
Amend 12 and spec combined.pdf PDF
Amend 0012.pdf PDF
Amend 0011.pdf PDF
Amend 0010.pdf PDF
Amend 0009.pdf PDF
60040202_PPI.pdf PDF
60040196_PPI.pdf PDF
60040201_PPI.pdf PDF
PROJECT.pdf PDF
60040198_PPI.pdf PDF
60040197_PPI.pdf PDF
SECTION 33 61 14.pdf PDF
60040199_PPI.pdf PDF
60040210_PPI.pdf PDF
Amend and cont sheet combined.pdf PDF
60040195_PPI.pdf PDF
60040290_PPI.pdf PDF
REGISTER.pdf PDF
60040194_PPI.pdf PDF
Show 40 more

Latest 50 of 61 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYM. DESCRIPTION DATE APP.

REVISIONS

DR.

DES.

CHK.

SUBMITTED BY:

DESIGN DIR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

DATE

DATE

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND

CAMP LEJEUNE, NORTH CAROLINA

MARINE CORPS BASE

SIZE CODE IDENT. NO. NAVFAC DRAWING NO.

E1 80091

CONSTR. CONTR. NO.

AS NOTEDSCALE SHEET

M B

F A

N O

SPEC.

M-601

MAS

JDL

MORGAN HUNTER

LWM

REPAIR BEQ AS4212

MECHANICAL SCHEDULES

60040268 N40085-23-B-0035

COMM ROOM COOLING 68°F 68°F

HEATING 70°F 55°F

ALL

COOLING 76°F 84°F

SPACE TYPE SEASON OCCUPIED UNOCCUPIED

INDOOR DESIGN CONDITIONS

84 140

MCDB (°F) W (grains H2O/lbm dry air)

DEHUMDIFICATION CONDITIONS

WINTER 26.0 (99.0% ASHRAE)

SUMMER 91.0 / 77.0 (1% ASHRAE)

SEASON DB/WB (°F)

OUTDOOR DESIGN CONDITIONS

DESIGN CONDITIONS

6. VERIFY FINAL AIR VELOCITIES TO ENSURE THEY DO NOT EXCEED SCHEDULED VALUES.

5. EXISTING LOUVER IS SEMICIRCULAR SHAPE TO FIT IN GABLE ABOVE ROOF. SEE ARCHITECTURAL PLANS.

4. PROVIDE WITH CLASS 1A LOW LEAKAGE DAMPER INTEGRAL TO LOUVER.

3. PROVIDE WITH ALUMINUM BIRDSCREEN.

2. PROVIDE ALL ALUMINUM LOUVER WITH BAKED ENAMEL FINISH TO MATCH BUILDING EXTERIOR.

1. PROVIDE FULL SIZE PLENUM BEHIND LOUVER AND PAINT INSIDE OF PLENUM FLAT BLACK

REMARKS :

L-12,13,14 LAUNDRY EXHAUST 8X40 0.91 690 630 1,2,3

L-9,10,11 JANITOR INTAKE 14X12 0.20 500 75 1,2,3,4

L-8b DOAS EXH EXHAUST SEE PLANS 8.50 800 6800 1,2,3,5,6

L-8 DOAS 2,4,6 EXH EXHAUST SEE PLANS 2.50 800 2000 1,2,3,5,6

L-7 DOAS 1,3,5 EXH EXHAUST SEE PLANS 2.50 800 2000 1,2,3,5,6

L-6b DOAS 2,4,6 OA INTAKE SEE PLANS 4.76 500 2380 1,2,3,5,6

L-6a DOAS 2,4,6 OA INTAKE SEE PLANS 6.40 500 3200 1,2,3,5,6

L-5b DOAS 1,3,5 OA INTAKE SEE PLANS 5.80 500 2900 1,2,3,5,6

L-5a DOAS 1,3,5 OA INTAKE SEE PLANS 8.00 500 4000 1,2,3,5,6

L-2,3,4 LAUNDRY INTAKE 40X16 1.98 606 1200 1,2,3,4

L-1 MECH BLDG INTAKE 40X12 1.14 572 650 1,2,3,4

MARK SERVES FLOW SIZE WxH (in.)

FREE AREA

REQUIRED (s.f.)

MAX AIR VELOCITY

(fpm)

CFM REMARKS

LOUVER SCHEDULE

6. PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION.

5. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE REHEAT AND COOLING COILS.

4. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

3. PROVIDE UNIT WITH VERTICAL SUPPLY DISCHARGE AND HORIZONTAL RETURN INLET DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY FAN.

1. PROVIDE WITH 2" MERV 13 FINAL FILTER ON THE RETURN AIR INTAKE.

REMARKS:

AHU-1 550 0.75 19.5 / 13.7 78.0 / 67.0 55.0 / 55.0 44.0 / 54.0 5.0 2.9 6 3.9 25.7 55.0 / 95.0 140 / 110 5.0 5.0 1.7 208/3 0.5 3.0 / 15.0 250 1,2,3,4,5,6

EWT/LWT

CFM

E.S.P.

"WC

T.S.P.

"WC

TOTAL/

SENSIBLE MBH

EAT (DB/WB)

ºF

LAT

(DB/WB) ºF

WATER TEMP.

(ºF) WATER PD

FT. MAX.

VELOCITY

FPS, MAX

MIN. NUM. OF

ROWS

GPM

TOTAL

MBH

EAT/LAT ºF EWT/LWT ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM V/PH

SUPPLY

HP

MCA/MOP

MARK

SUPPLY FAN COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) ELECTRICAL

UNIT

WEIGHT

(LBS)

REMARKS

AIR HANDLING UNIT SCHEDULE

10. PROVIDE SUPPLY SIDE SMOKE DETECTOR AS REQUIRED BY NFPA 90A.

9. PROVIDE UNIT WITH RECIRCULATION PUMP AT PREHEAT COIL FOR FREEZE PROTECTION. ALSO PROVIDE 120/1 CIRCUIT FOR PUMP. PUMP IS TO BE SIZED FOR 110% OF PREHEAT COIL PRESSURE DROP AND DESIGN FLOW GPM. SEE HOT WATER PREHEAT COIL DETAIL AND CONTROLS FOR FURTHER INFORMATION.

8. PROVIDE UNIT WITH 3-POINT POWER CONNECTION. A SINGLE CONNECTION FOR THE SUPPLY FAN, A SINGLE CONNECTION FOR THE EXHAUST FAN AND A SINGLE CONNECTION FOR THE MARINE LIGHTS.

7. UNIT MUST HAVE CROSSFLOW FIXED PLATE TOTAL ENERGY HEAT EXCHANGER, PLENUM-TYPE SUPPLY/EXHAUST FANS, PREHEAT COIL, COOLING COIL, REHEAT COIL AND MARINE LIGHTS IN EACH FAN SECTIONS.

6. PROVIDE 6000 HR SALT SPRAY PROTECTIVE COATING ON THE PREHEAT, COOLING AND REHEAT COILS.

5. CONTRACTOR MUST VERIFY THAT UNIT CAN BE INSTALLED IN LOCATION SHOWN ON DRAWINGS PRIOR TO SUBMITTING FOR APPROVAL.

4. PROVIDE UNIT WITH VERTICAL SUPPLY DISCHARGE DUCT CONNECTION AND HORIZONTAL EXHAUST & OUTSIDE AIR DUCT CONNECTIONS. UNIT MUST HAVE 2" DOUBLE WALL CONSTRUCTION.

3. PROVIDE WITH CLASS 1A LOW LEAKAGE DAMPERS ON THE EXHAUST AND OUTSIDE AIR INTAKE UNIT CONNECTIONS.

2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR SUPPLY AND EXHAUST FANS, COMPATIBLE WITH VARIABLE FREQUENCY DRIVES.

1. PROVIDE WITH 2" MERV 8 FILTER ON THE EXHAUST AND 2" MERV 8 PREFILTERS & 2" MERV 13 FINAL FILTERS ON THE OUTSIDE AIR INTAKE.

REMARKS:

DOAS-6 1860 1.50 4.68 1600 1.50 2.83 62.6 22.0 / 52.0 140 / 110 5.00 5 4.2 175.2 / 66.08 84.0 / 78.6 51.5 / 51.2 44.0 / 54.0 5.0 5 6 35.0 66.0 52.0 / 85.0 140 / 110 5.0 5 4.5 93.0 78.0 76.0 50.0 82.3 71.6 22.0 70.0 35.0 51.4 41.2 61.9% 208/3 2.2 1.0 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-5 2300 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 50.0 140 / 110 5.0 5 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 5 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9,10

DOAS-4 1860 1.50 4.68 1600 1.50 2.83 62.6 22.0 / 52.0 140 / 110 5.00 5 4.2 175.2 / 66.08 84.0 / 78.6 51.5 / 51.2 44.0 / 54.0 5.0 5 6 35.0 66.0 52.0 / 85.0 140 / 110 5.0 5 4.5 93.0 78.0 76.0 50.0 82.3 71.6 22.0 70.0 35.0 51.4 41.2 61.9% 208/3 2.2 1.0 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-3 2300 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 52.0 140 / 110 5.0 5 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 5 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9,10

DOAS-2 1860 1.50 4.68 1600 1.50 2.83 62.6 22.0 / 52.0 140 / 110 5.00 5 4.2 175.2 / 66.08 84.0 / 78.6 51.5 / 51.2 44.0 / 54.0 5.0 5 6 35.0 66.0 52.0 / 85.0 140 / 110 5.0 5 4.5 93.0 78.0 76.0 50.0 82.3 71.6 22.0 70.0 35.0 51.4 41.2 61.9% 208/3 2.2 1.0 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9

DOAS-1 2300 1.50 4.20 2000 1.50 2.82 84.2 22.0 / 52.0 140 / 110 5.0 5 5.7 220.2 / 83.14 84.0 / 78.6 52.0 / 51.0 44.0 / 54.0 5.0 5 6 43.9 86.3 52.0 / 85.0 140 / 110 5.0 5 5.8 93.0 78.0 76.0 50.0 84.6 74.5 22.0 70.0 35.0 48.6 40.5 50.0% 208/3 2.4 1.4 1.63 / 15.0 115/1 1400 1,2,3,4,5,6,7,8,9,10

EWT/LWT DB WB DB %RH DB WB DB DB %RH DB WB

OA RA SA OA RA SACFM

E.S.P.

"WC

T.S.P.

"WC

CFM

E.S.P.

"WC

T.S.P.

"WC

TOTAL

MBH

EAT/LAT ºF

EWT/LWT

ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM

TOTAL/

SENSIBLE MBH

EAT (DB/WB)

ºF

LAT

(DB/WB) ºF

WATER TEMP.

(ºF) WATER PD

FT. MAX.

VELOCITY

FPS, MAX

MIN. NUM.

OF ROWS

GPM

TOTAL

MBH

EAT/LAT

ºF

EWT/LWT

ºF

WATER PD

FT. MAX

VELOCITY

FPS, MAX

GPM

SUMMER WINTER

HX

EFFECT.

V/PH

SUPPLY

HP

EXHAUST

HP

MARINE

LIGHTS

MCA/MOP

MARINE

LIGHTS

V/PH

MARK

SUPPLY FAN EXHAUST FAN PREHEAT HEATING CAPACITY (HOT WATER) COOLING CAPACITY (CHILLED WATER) REHEAT HEATING CAPACITY (HOT WATER) TOTAL ENERGY HEAT EXCHANGER ELECTRICAL

UNIT

WEIGHT

(LBS)

REMARKS

DEDICATED OUTSIDE AIR SYSTEM SCHEDULE

DUCT LEAKAGE TEST MANUAL.

1. TEST IN ACCORDANCE WITH SPECIFICATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC, AND WITH THE PROCEDURES IN SMACNA HVAC AIR

REMARKS:

EXHAUST DUCT - - - - -1 - - - A 6 - - 1 1

- - - - - 1 - - - - A 6 1 1

- - - - -1 - - - - - A 6 1 1

- - - -1 - - - - A 6 - - 1 1DEDICATED OUTDOOR AIR

SYSTEM - DOAS

1 - - - - - A 3 A 6 - - 1 1

- - - -1 - - - - A 6 - - 1 1

AIR HANDLERS

1 - - - - - A 3 A 6 - - 1 1

SUPPLY DUCT

SUPPLY

DUCT(BETWEEN

AHU AND VAV

SUPPLY DUCT

(DOWNSTREAM OF

VAV BOXES)

RETURN

DUCT

EXHAUST/

RELIEF

DUCT

OUTSIDE AIR

DUCT

DUCT SEAL

CLASS

DUCT LEAK

CLASS

DUCT SEAL

CLASS

DUCT LEAK

CLASS

DUCT SEAL

CLASS

DUCT LEAK

CLASS

INCHES OF WATER ROUND / OVAL RECTANGULAR

LOCATION

DUCT PRESSURE CLASS SUPPLY / EXHAUST

RETURN/OUTSIDE AIR

DUCT TEST PRESSURE INCHES

OF WATER COLUMN

REMARKS

DUCT CONSTRUCTION AND LEAKAGE TESTING TABLE

4. PROVIDE BLANKET INSULATION ON THE BACK OF ALL DIFFUSERS.

3. ALL AIR DISTRIBUTION MUST BE 100% ALUMINUM CONSTRUCTION.

2. PROVIDE WITH SQUARE TO ROUND TRANSITION AS NECESSARY.

1. VERIFY ALL CEILING TYPES WITH ARCHITECTURAL PLANS TO DETERMINE MOUNTING DETAILS AND ACCESSORIES REQUIRED. COORDINATE COLOR WITH ARCHITECT.

REMARKS

R2 ALUMINUM FIXED VANE NA 12X6 8" 200 CFM 200 CFM 30 1,2,3,4

R1 SQUARE PLAQUE FACE DIFFUSER NA 24X24 12X12 550 CFM 600 CFM 30 1,2,3,4

E1 ALUMINUM FIXED VANE NA 6X4 6" 25 CFM 75 CFM 30 1,2,3,4

S3 ALUMINUM DOUBLE DEFLECTION 4 WAY 12X6 16X6 200 CFM 200 CFM 30 1,2,3,4

S2 SQUARE PLAQUE FACE DIFFUSER 4 WAY 24X24 8" 125 CFM 200 CFM 30 1,2,3,4

S1 ALUMINUM DOUBLE DEFLECTION 4 WAY 8X6 8" 75 CFM 75 CFM 30 1,2,3,4

MARK DESCRIPTION THROW FACE SIZE NECK SIZE MINIMUM CFM MAXIMUM CFM MAX. NC REMARKS

AIR DISTRIBUTION SCHEDULE

REMAIN ENERGIZED UNTIL SETPOINT IS REACHED

6. AUXILARY HEAT SHALL BE LOCKED OUT UNLESS THE HEATING SETPOINT IS UNABLE TO BE MAINTAINED WITH COMPRESSOR RUNNING CONTINUOUSLY IN HEATING MODE. AUXILARY HEAT WILL

5. PROVIDE TAMPER PROOF, FULL ENCLOSURE FOR UNIT. SEPARATE ENCLOSURE TO BE PROVIDED FOR CONDENSATE LINES, ELECTRICAL WIRING AND CONTROLS WITH ACCESS PANEL.

4. THE ROOM SHALL BE PROVIDED WITH A WALL MOUNTED BACnet MS/TP PROGRAMMABLE THERMOSTAT AND INTERFACED WITH THE DDC CONTROL SYSTEM.

3. PROVIDE UNIT WITH WALL SLEEVE, POLYCARBONATE OR STAINLESS STEEL DRAIN PAN, CENTER HOLE CONDENSATE DRAIN KIT AND OUTDOOR GRILLE.

2. PTHP SHOULD BE CORROSION RESISTANT AND FITTED WITH A METAL LIGATURE PROOF SECURITY COVER.

1. PROVIDE PACKAGED TERMINAL HEAT PUMP WITH AUXILIARY ELECTRIC HEAT, DISPOSABLE/REPLACEABLE FILTER AND POWER CORD.

REMARKS:

PTHP SLEEPING ROOMS HEAT PUMP 12.0 320 9.9 350 3.0 KW 3.1 11.8 208/1 100 1,2,3,4,5,6

TOTAL MBH CFM TOTAL MBH CFM AMPS V/PH

MARK AREA SERVED TYPE

COOLING HEATING AUXILARY

ELEC HEAT

DEHUMIDIFICATION

(PINTS/HR)

ELECTRICAL OPER.WEIGHT

(LBS)

REMARKS

PTHP SCHEDULE

1/30 HP, 120/1, & 1.5 FLA.

5. PROVIDE CONDENSATE PUMP FOR USE WITH UNIT, PROVIDE WITH BACNET MS/TP COMPATIBILITY, CAPABLE OF 10 GPH AT 20' HEAD,

4. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.

3. AHU IS POWERED FROM CONDENSING UNIT.

2. PROVIDE UNIT WITH WALL MOUNTED CONDENSATE PUMP, WIRED TO MOTOR RATED SWITCH.

1. PROVIDE UNIT WITH WIRED WALL MOUNTED THERMOSTAT, AND CLEANABLE TYPE FILTERS.

REMARKS:

DAC-2 2ND FLR COMM AC 450 1.0 R-410A 35 1,2,3,4,5

DAC-1 1ST FLR ELEV AC 450 1.0 R-410A 35 1,2,3,4,5

MARK SERVES TYPE CFM MCA REFRIG. TYPE WEIGHT (LBS) REMARKS

DUCTLESS SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE

2. DUCTLESS SPLIT SYSTEM MUST BE CAPABLE OF HANDLING 100 FEET OF REFRIGERANT LINE BETWEEN AC AND CU.

QUANTITIES.

SALT-HOUR SEACOAST CONSTRUCTION. COATINGS MUST NOT REDUCE UNIT PERFORMANCE BELOW SCHEDULED

1. PROVIDE ALL ACCESSORIES REQUIRED FOR LOW AMBIENT OPERATION TO 0ºF. PROVIDE COIL GUARDS AND 6,000

REMARKS:

DCU-2 2ND FLR COMM 1 1/2 AC 19.8 208/1 11 28 100 1,2

DCU-1 1ST FLR ELEV 1 1/2 AC 19.8 208/1 11 28 100 1,2

MARK SERVES

NOMINAL

TONS

TYPE SEER VOLT/PH MCA MOCP

WEIGHT

(LBS)

REMARKS

DUCTLESS SPLIT SYSTEM CONDENSING UNIT SCHEDULE

MOUNTED CONTROL SWITCH NEAR ENTRANCE.

5. PROVIDE SIDEWALL MOUNTED FAN WITH TEFC MOTOR, MOTORSIDE GUARD, HANGING VIBRATION ISOLATION KIT, WALL SLEEVE AND BIRDSCREEN. PROVIDE WALL

4. PROVIDE FAN WITH TEFC MOTOR AND HANGING VIBRATION ISOLATION KIT.

3. FAN MUST OPERATE CONTINUOUSLY.

2. FAN MUST BE TIED TO THERMOSTAT AND HUMIDISTAT.

1. PROVIDE WITH HANGING VIBRATION ISOLATION KIT.

REMARKS:

EF-5 CORE JANITOR INLINE 225 0.75 DIRECT 1350 4.5 1/8 120/1 30 3,4

EF-2,3,4 LAUNDRY ROOMS PROPELLER 1,200 0.75 DIRECT 1725 18.0 1/2 120/1 25 1,2

EF-1 MECHANICAL BLDG PROPELLER 650 0.25 DIRECT 1050 4.4 1/20 120/1 30 5

HP V/PH

MARK AREA SERVED TYPE CFM

ESP

(IN H2O)

DRIVE RPM MAX. SONES

ELECTRICAL OPER.WEIGHT

(LBS)

REMARKS

FAN SCHEDULE

1. OVERALL BUILDING PRESSURIZATION IS POSITIVE.

REMARKS

DOAS-6 1860 1600 1

DOAS-5 2300 2000 1

DOAS-4 1860 1600 1

DOAS-3 2300 2000 1

DOAS-2 1860 1600 1

DOAS-1 2300 2000 1

AREA OUTSIDE AIR (CFM) EXHAUST AIR (CFM) REMARKS

BUILDING AIR BALANCE CALCULATION

1. CLASS 1A LOW LEAKAGE MOTORIZED DAMPER.

REMARKS :

MD-5 EF-5 EXHAUST 8X8 120/1 1

MD-4 DOAS-2,4,6 INTAKE 38X18 120/1 1

MD-3 DOAS-2,4,6 EXHAUST 38X16 120/1 1

MD-2 DOAS-1,3,5 INTAKE 38X18 120/1 1

MD-1 DOAS-1,3,5 EXHAUST 38X16 120/1 1

MARK SERVES FLOW SIZE WxH (in.) VOLT./PH REMARKS

DUCT-MOUNTED MOTORIZED DAMPER SCHEDULE

4 ROOFING AMENDMENT 07.25.25

File details come from the government source that posted it. Updated .